Design consideration of the active

advertisement
958
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 18, NO. 4, JULY 2003
Design Consideration of the Active-Clamp
Forward Converter With Current Mode
Control During Large-Signal Transient
Qiong M. Li, Member, IEEE, and Fred C. Lee, Fellow, IEEE
Abstract—The design issues of the active-clamp forward converter circuit with peak current mode control in small signal stability and large-signal transients are discussed. A design procedure is provided to solve circuit issues under these conditions. It
is the first time that with the aid of simulation, we are able to optimize the circuit design of the active-clamp forward converter for
large-signal transient behaviors.
Index Terms—Active-clamp, forward converter, large-signal
transient.
I. INTRODUCTION
T
HE forward converter with the active-clamp reset offers
many advantages over the forward converter with other
transformer reset methods [1]. However, during the large-signal
transients, the maximum magnetizing current of the transformer
and the peak voltage of the primary switch are strongly affected
by the active-clamp circuit dynamics. Although some design
issues have been discussed [2]–[6], the design of active-clamp
forward converter is still based on steady state performance. The
voltage and current stresses of the circuit are very hard to predict
during the large-signal transient and under abnormal conditions
due to the nonlinearity of the circuit, and the conflict effect of the
different parameters makes it even harder to generate a design
procedure [6], [7].
This paper focuses on design issues related to the active-clamp reset circuit. The design procedures of the forward
converter, such as L, C output filter design and current control
loop design have been discussed in many literatures such as
in [8]–[10]. A design procedure for the active-clamp forward
circuit is proposed by using design curves that are generated by
running a large amount of simulations. The design procedure
will cover the problems related to the large-signal transient as
well as to the small-signal stability. It shows that the dynamic
performance and the robustness of the circuit can be improved
by using this approach. It is the first time that with the aid of
simulation, we are able to optimize the circuit design of the
active-clamp forward converter for the large-signal transient
behaviors. An active-clamp forward converter circuit with peak
current mode control is used as an example.
Fig. 1. Active-clamp forward converter circuit diagram.
Fig. 2.
Active-clamp circuit problems during large-signal transient.
Fig. 3. Stability problem due to the resonant network of the active-clamp reset
circuit.
Manuscript received October 6, 2000; revised February 14, 2003. Recommended by Associate Editor K. Smedley.
Q. M. Li is with the Philips Research USA, Briarcliff Manor, NY 10510 USA.
F. C. Lee is with the Center for Power Electronics Systems, Virginia Polytechnic Institute and State University, Blacksburg, VA 24061 USA.
Digital Object Identifier 10.1109/TPEL.2003.813760
II. DESIGN ISSUES OF THE ACTIVE-CLAMP CIRCUIT
The active-clamp forward converter circuit diagram is shown
in Fig. 1. Fig. 2 shows the load transient waveforms of the ac-
0885-8993/03$17.00 © 2003 IEEE
LI AND LEE: DESIGN CONSIDERATION OF THE ACTIVE-CLAMP FORWARD CONVERTER
959
Fig. 4. Large-signal response waveform at Vin = 36 V, Io from no load to full load then to no load transient. Load step slew rate is 1 A/us: (a) measurement
and (b) simulation.
tive-clamp circuit, where
is the output voltage,
is
is the magnetizing
the voltage across the main switch, and
current of the transformer. From Fig. 2 we can see that the maximum voltage of the main switch and the maximum magnetizing
current of the transformer during transient are much larger than
that at the steady state. These can cause circuit problems such
as voltage stresses, transformer saturation, and the diode reverse
recovery problem [2], [3], [6], which are marked as dotted circles in Fig. 2.
Besides the large-signal transient problems, circuit can have
stability problem due to the interaction of the resonant network
of the active-clamp-reset circuit [4]. Fig. 3 shows small-signal
V. The phase
transfer function of the loop gain at
margin of the loop gain at crossover frequency is negative due
to the additional pole in the active-clamp-reset circuit near the
resonant frequency. This paper is going to demonstrate how to
design the circuit to solve these problems.
III. CIRCUIT UNDER WORST CASE CONDITION
The fist step before we start the design is to find the worst case
condition during the large-signal transient, so we can design the
circuit under the worst case condition. In a current-mode-controlled circuit, the output voltage is not sensitive to the line
change because of the feed-forward effect in the control [7],
[8]. The same is true for the stresses of voltage and current in
the active-clamp circuit. Simulation results also verified that the
voltage and current stresses in the active-clamp circuit is not a
problem during line step changes in a current-mode-controlled
circuit [7]. While in a load transient, the worst condition happens from no load to full load change at low line condition [6],
[7]. The main reason is that the clamp capacitor voltage is a
function of the duty cycle
(1)
where n is the transformer turns ratio. At low line, circuit has the
largest duty cycle in steady state. While a no load to full load
change drives the duty cycle even larger during the transient,
most of the time to the maximum duty cycle, which is limited
by the controller chip.
A virtual prototype test procedure is used to detect the circuit
worst case condition by simulating the circuit dynamic performance under different lines, loads, and the abnormal conditions
[7]. From the simulation, it shows that the worst condition occurs when the circuit has a large load transient from no load to
full load at low line.
In order to verify the accuracy of simulation, a circuit prototype was built to compare the circuit dynamic performance. An
active-clamp forward converter circuit with peak current mode
control is used as an example to demonstrate the design process.
The circuit has input voltage 36–72 V and full load 30 A. The
switching frequency is 500 kHz and the duty cycle limit of the
controller chip is 0.75. The control bandwidth of the circuit is
14 kHz, the transformer turns ratio is 4, the active clamp circuit
is 80 uH, and
is 0.01 uF.
Fig. 4 shows the measured and simulated large-signal
V, Io from no load to full load to no
responses at
load transient. The full load is 30 A and the load step slew
rate is 1 A/us. Fig. 4(a) is the measurement and Fig. 4(b) is
the simulation result. Fig. 5 is the zoomed-in waveforms of
Fig. 4. Fig. 5(a) is the measured waveform from no load to full
load transient. Fig. 5(b) is the simulated waveform from no
load to full load transient. Fig. 5(c) is the measured waveform
from full load to no load transient. Fig. 5(d) is the simulated
waveform from full load to no load transient. Comparing the
measurement and simulation, it shows that the simulation is
accurate enough to provide the design information and predict
the dynamic behavior of the system.
IV. DESIGN PROCEDURE OF THE ACTIVE-CLAMP CIRCUIT
Although it is possible to adjust the circuit parameters by
trials and errors to fix the problems, the problem’s solution is
not straightforward. It may require a lot of time and effort but
still not come out a robust design, since these parameters are
not independent parameters and involve different circuit design
issues.
960
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 18, NO. 4, JULY 2003
Fig. 5. Zoomed-in waveforms of Fig. 4 from no load to full and then full load to no load transient. (a) Measured waveform of no load to full load transient.
(b) Simulated waveform of no load to full load transient. (c) Measured waveform of full load to no load transient. (d) Simulated waveform of full load to no load
transient.
This section will demonstrate how to generate design
information and optimize the design parameters related to
these design issues. The design parameters discussed here are
, the clamp
the magnetizing inductance of the transformer
, the control bandwidth , and the maximum
capacitance
duty cycle limit Dmax. It is recommended to have an initial
design of the circuit as a conventional forward converter
before the active-clamp reset circuit design, then to follow the
design procedure proposed here to prevent problems related
to active-clamp circuit. The design process focuses on solving
the potential problems in the circuit: voltage stress of the main
switch, transformer core saturation, diode reverse recovery
of the active-clamp switch, small-signal instability due to the
active-clamp resonant network.
A. Normalization
The normalized peak voltage and peak current values will
be used in the design curve. The normalized switch voltage
and the normalized magnetizing current is
is
onant frequency,
impedance
. The x-axis of the design curve uses res, as a parameter, and
is the characteristic
(2)
(3)
B. Design Constraints
There are four design criteria: the voltage stress of the main
switch, the transformer saturation, the reverse recovery problem
of the body diode of the active clamp switch, and the smallsignal stability problem.
1) Design constraint 1: switch voltage stress
The design constraint for the switch voltage stress is
peak
rating
(4)
LI AND LEE: DESIGN CONSIDERATION OF THE ACTIVE-CLAMP FORWARD CONVERTER
961
Fig. 7. Transformer saturation area.
Fig. 6.
Relation of the saturation flux to the saturation magnetizing current.
Where,
peak is the peak voltage during the tranrating is the device voltage rating of the main
sient,
switch. If the voltage stress is unknown, which is the
case in the design sometime, we can eliminate the voltage
overstress restriction.
2) Design constraint 2: small signal stability
Studies show that the active-clamp reset circuit introduces an additional pair of moving pole and zero in the
loop gain [5], [11]. The frequency, , of the moving pole
is a function of the resonant frequency
(5)
In order to guarantee a stable operation in the circuit,
the moving frequency, , has to be designed away from
the crossover frequency (e.g., two times larger). The
smallest happens at the maximum duty cycle, so the resonant frequency of the active-clamp circuit should meet
the following equation in order to have a stable system
and not affect the phase margin
Fig. 8. Diode reverse recovery problem area.
4) Design constraint 4: diode reverse recovery problem
The magnetizing current to prevent the diode from reverse recovery problem is
(10)
where,
(11)
(6)
is the duty cycle limit value of the controller
where
chip, is the control bandwidth.
3) Design constraint 3: transformer saturation
Fig. 6 shows the relation between the flux and the magis the effective cross sectional
netizing current, where,
is the magnetizing current. From
area of the core,
Fig. 6, we can get
(7)
We can rewrite the saturating magnetizing current into
(8)
The design constraint for the transformer saturation is
(9)
The design constraint for the transformer saturation is
shown as the shaded area in Fig. 7. It is a straight line in
the normalized design curve.
The ripple current can be written as
(12)
The diode reverse recovery problem area is shown as in
Fig. 8. It is a straight line in the normalized design curve.
According to four design constraints, we can draw the feasible operating regions for voltage and magnetizing current as
shown in Fig. 9. If the voltage stress is unknown, which is the
case in the design sometime, we can ignore the voltage overstress area in Fig. 9(a) to get an easier start. After defining the
design regions to meet other constraints, the circuit parameters
with smallest voltage stress value can be selected from the design curve.
C. Generating Design Curves
The worst case happens at low line and load from low to high
transient. In this example, Vin is 36 V, and Io changes from
0 A to 30 A. A set of design curves is generated by varying
and
values with a fixed control bandwidth, 14 kHz, and
962
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 18, NO. 4, JULY 2003
(a)
Fig. 10.
Design curve of the normalized peak switch voltage versus f .
Fig. 11.
Design curve of normalized peak magnetizing current versus f .
(b)
Fig. 9. Feasible operating regions for voltage and magnetizing current.
(a) Design area for normalized switch voltage curve. (b) Design area for
normalized magnetizing current curve.
maximum duty cycle limit, 0.75. Each single simulation generates one point in the voltage design curve and one point in
the magnetizing current curve. The normalized design curve for
peak voltage and magnetizing current are shown in Fig. 10 and
Fig. 11, respectively. The shaded areas are the design prohibited
area. The total simulation CPU time is only 9 minutes by using
an adequate simulation and modeling approach [7].
D. Feasible
and
to Meet the Design Constraints
After we generate the design curves with design constraints,
and
to meet all the design criteria can be
the feasible
easily determined.
Assuming the device rating of the main switch is 180 V,
so the normalized boundary of the voltage stress is 5 when
V. When the control bandwidth,
kHz,
, the boundary of
and maximum duty cycle limit,
the resonant frequency for small-signal stability is 112 kHz.
and
can be determined by three steps.
The feasible
in peak1) Find the desired parameter ranges for and
voltage design curves.
Fig. 10 is the peak-voltage design curves with 14 kHz
0.75. These is a big dot in Fig. 10, which correand
uH and
sponds to the original design,
uF. The maximum voltage is about 200 V, so the
original design exceeds the 180 V voltage rating of the
switch under worst case condition.
The dotted lines covered area is the desired design area
to meet voltage stress limitation and small signal stable
criterion in the normalized peak switch voltage versus
curves. We can see that only the curve at
uH
meets the constraints when is at 100 kHz to 480 kHz
range.
in step 1, we can
2) Within the defined ranges for and
that also meet the
find the desired ranges for and
magnetizing current constraints.
Fig. 11 is the peak magnetizing-current design curves
0.75. These is a big dot in Fig. 11,
with 14 kHz and
uH
which corresponds to the original design,
uF. It shows that the original design has
and
diode reverse recovery problem and is at the boundary of
the transformer saturation.
From the design curves, we can see that has to be
larger than 530 kHz in order to meet magnetizing current
constrains. So there are no feasible parameters available
within the desired areas from step1. It also means that
and
can meet all the design
there is no feasible
constraints in the previous circuit condition.
LI AND LEE: DESIGN CONSIDERATION OF THE ACTIVE-CLAMP FORWARD CONVERTER
Fig. 12. Normalized voltage design curve reduced maximum duty cycle limit.
The Dlim is reduced from 0.75 to 0.7. The design area to meet voltage stress
limitation and small signal stable criteria is shown in the dotted area.
3) If we find the desired ranges for
can be calculated by
and 2,
and
963
Fig. 13. Normalized magnetizing current design curve with reduced maximum
duty cycle limit. The Dlim is reduced from 0.75 to 0.7. The design area without
transformer saturation and diode reverse recovery problem shows in the dotted
line.
from step 1
(13)
Within the desired parameter range, a smaller , thus
is preferred to reduce the voltage and current
a larger
stresses.
V. DESIGN TRADE-OFF
Previous example shows that there is no adequate
and
to meet all the design criteria. The design curve of normalkHz
ized peak switch voltage versus (Fig. 10) requires
kHz, while the design curve of normalized peak magkHz with
netizing current versus (Fig. 11) requires
uH. There is not any to meet both conditions. There
are several design trade-off and solutions to solve the problem.
A. Design Trade-Off 1: Increasing Device Rating
From Fig. 10 and Fig. 11, we see that if we do not restrict
the device voltage rating to 180 V, voltage constrain becomes:
kHz, so there is a small area in Fig. 11 which can
kHz. The design result
meet all the design criteria:
uH and
kHz,
with this trade-off will be
smaller than 4.5 nF to meet the requirement.
which gives any
The disadvantages of this solution are the higher voltage rating
device and the high ripple current of the magnetizing current
.
due to a much smaller
It is worth of mentioning that a very small magnetizing inductance could have a high ripple of the magnetizing current which
will increase the loss of the circuit and may affect the main converter operation if the ripple of the magnetizing current is not
negligible to the reflected load.
B. Design Trade-Off 2: Getting Rid of the Constraint of the
Body Diode Reverse Recovery
From Fig. 11, we see that the diode reverse recovery constraint is the hardest one to meet in the parameter design. The de-
sign is more flexible without this constraint. This can be done by
connecting a Schottky diode in series with the auxiliary switch
to block the conduction of the body diode, and then to connect a fast-recovery anti-parallel diode around the series connection of the Schottky and the auxiliary switch [2]. The disadvantage is the additional components to increase the cost of
the circuit. With this trade-off, we relaxed the second condition
uH,
(magnetizing current). For example, if we select
kHz from Fig. 11. The final solution will be
we get
kHz
kHz, thus
nF
nF.
C. Design Trade-Off 3: Decreasing Control Bandwidth
A smaller bandwidth in the design can reduce the peak
voltage and magnetizing current during load transients. The
disadvantage is a slower recovery from the transient in the
output voltage of the main converter. For example, if we
reduced the bandwidth from 14 kHz to 8 kHz, one of the design
uH and
nF.
result can be
D. Design Trade-Off 4: Reducing Maximum Duty Cycle Limit
Value
The voltage and current stresses can also be reduced by reducing the maximum duty cycle limit value. Similar to solution
3, the disadvantage is a slower recovery from transient in the
output voltage of the main converter. One of the design result is
uH and
nF. The next section will show the
design curves and result using this trade-off as an example.
E. Circuit Redesign by Using Trade-Off 4
Fig. 12 and Fig. 13 shows the normalized voltage design
curve with reduced maximum duty cycle limit. The maximum
duty cycle limit is reduced from 0.75 to 0.7. The design curve
of normalized peak switch voltage versus (Fig. 12) requires
kHz, while the design curve of normalized peak magnekHz when we
tizing current versus (Fig. 13) requires
uH. So one of the design result is
uH,
select
is less than 5.2 nF. A smaller
has a larger voltage stress,
964
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 18, NO. 4, JULY 2003
(a)
Fig. 14. Design verification of dc bias of magnetizing current of transformer
at steady state.
(b)
Fig. 16. Design verification of the large-signal transient analysis with worst
case: Vin = 36 V, Io = 0 to 30 A. (a) Waveforms with original design and
(b) waveforms after design modification.
Fig. 15.
Design verification of the small signal analysis.
VII. CONCLUSION
but more design margin without saturation and diode reverse recovery problem.
VI. VALIDATION OF THE DESIGN
VIRTUAL PROTOTYPE TEST
BY
This section shows the comparisons between the original circuit problems and the circuit behavior after the final design modification. The circuit parameters are modified by reducing the
maximum duty cycle limit from 0.75 to 0.7 and magnetizing inductance from 80 uH to 40 uH. The clamp capacitance is 5 nF.
Fig. 14 shows design verification of dc bias of magnetizing
current of transformer. The dc bias of the magnetizing current
does not shown any problems since the magnetizing current
ripple is about 800 mA. Fig. 15 shows the design verification
of the small signal analysis under worst case condition. The
resonant frequency of the active-clamp circuit has been pushed
high enough and does not interfere with the crossover frequency
of the loop gain. Fig. 16 shows the design verification of the
V,
large-signal transient analysis under worst case:
to 30 A. Fig. 16(a) shows the waveforms with original
design. Fig. 16(b) shows the waveforms after design modification. The original circuit problems during large-signal transient
are solved.
The design issues of the active-clamp forward converter circuit with peak current mode control in small signal stability and
large-signal transients are discussed. A design procedure is proposed to solve design issues. The circuit performances of the
power supply system design are improved by redesign the active-clamp reset circuit. It is the first time that with the aid of
the virtual prototype, we are able to optimize the circuit design
of the active-clamp forward converter for large-signal transient
behaviors.
REFERENCES
[1] P. Vinciarelli, “Optimal resetting of the transformer’s core in single
ended forward converters,” U.S. Patent 4 441 146, Apr. 1984.
[2] B. Carsten, “Design techniques for transformer active reset circuits at
high frequencies and power levels,” in Proc. Conf. High Freq. Power
Conv., 1990, pp. 235–246.
[3] D. Dalal and L. Wofford, “Novel control IC for single-ended active
clamp converters,” in Proc. Conf. High Freq. Power Conv., 1995, pp.
136–146.
[4] Q. Li, F. C. Lee, and M. M. Jovanovic, “Design considerations of transformer DC bias of forward converter with active-clamp reset,” in Proc.
IEEE APEC, 1999, pp. 553–559.
[5] A. Fontan, S. Ollero, E. de la Cruz, and J. Sebastian, “Peak current mode
control applied to the forward converter with active clamp,” in IEEE
PESC Rec., 1998, pp. 45–51.
[6] Q. Li, F. C. Lee, and M. M. Jovanovic, “Large-signal transient analysis
of forward converter with active-clamp reset,” IEEE Trans. Power Electron., vol. 17, pp. 15–24, Jan. 2002.
LI AND LEE: DESIGN CONSIDERATION OF THE ACTIVE-CLAMP FORWARD CONVERTER
[7] Q. Li, “Developing modeling and simulation methodology for virtual
prototype power supply system,” Ph.D. dissertation, VPI&SU, Blacksburg, VA, Mar. 1999.
[8] R. W.Robert W. Erickson and D.Dragan Maksimovic, Fundamentals of
Power Electronics, 2nd ed. Boston, MA: Kluwer, 2000.
[9] R. B. Ridley, “Secondary LC filter analysis and design techniques for
current-mode-controlled converters,” IEEE Trans. Power Electron., vol.
PE-3, pp. 499–507, Oct. 1988.
[10] F. C. Lee, Y. Yu, and M. F. Mahmoud, “A unified analysis and design
procedure for the standardized control module for DC-DC switching
regulators,” in IEEE PESC Rec., 1980, pp. 284–301.
[11] G. Stojcic, F. C. Lee, and S. Hiti, “Small-signal characterization of active-clamp PWM converters,” in Proc. Conf. High Freq. Power Conv.,
1996, pp. 52–62.
Qiong M. Li (S’93–M’99) received the B.S. and
M.S. degrees in electrical engineering from Xian
Jiaotong University, Xian, China, in 1988 and 1991,
respectively, and the Ph.D. degree in electrical and
computer engineering from the Center for Power
Electronics Systems (CPES), Virginia Polytechnic
Institute and State University, Blacksburg, in 1999.
She is a Senior Member of Research Staff at
Philips Research USA, Briarcliff Manor, NY, where
she is mainly responsible for the research and technology development of digital control systems for
power supplies and lighting applications. Her main research interests include
power converter analysis and design, digital control system implementation,
DSP control algorithms, modeling, and simulation of power converters.
Dr. Li is a member of the IEEE Power Electronics Society, Phi Kappa Phi,
and Eta Kappa Nu.
965
Fred C. Lee (S’72–M’74–SM’87–F’90) received
the B.S. degree in electrical engineering from the
National Cheng Kung University, Taiwan, R.O.C.,
in 1968 and the M.S. and Ph.D. degrees in electrical
engineering from Duke University, Durham, NC, in
1971 and 1974, respectively
He is a University Distinguished Professor with
Virginia Polytechnic Institute and State University
(Virginia Tech), Blacksburg, and prior to that he was
the Lewis A. Hester Chair of Engineering at Virginia
Tech. He directs the Center for Power Electronics
Systems (CPES), a National Science Foundation engineering research center
whose participants include five universities and over 100 corporations. In
addition to Virginia Tech, participating CPES universities are the University
of Wisconsin-Madison, Rensselaer Polytechnic Institute, North Carolina A&T
State University, and the University of Puerto Rico-Mayaguez. He is also
the Founder and Director of the Virginia Power Electronics Center (VPEC),
one of the largest university-based power electronics research centers in
the country. VPEC’s Industry-University Partnership Program provides an
effective mechanism for technology transfer, and an opportunity for industries
to profit from VPEC’s research results. VPEC’s programs have been able to
attract world-renowned faculty and visiting professors to Virginia Tech who,
in turn, attract an excellent cadre of undergraduate and graduate students.
Total sponsored research funding secured by him over the last 20 years
exceeds $35 million. His research interests include high-frequency power
conversion, distributed power systems, space power systems, power factor
correction techniques, electronics packaging, high-frequency magnetics, device
characterization, and modeling and control of converters. He holds 19 U.S.
patents, and has published over 120 journal articles in refereed journals and
more than 300 technical papers in conference proceedings.
Dr. Lee received the Society of Automotive Engineering’s Ralph R. Teeter
Education Award (1985), Virginia Tech’s Alumni Award for Research Excellence (1990), and its College of Engineering Dean’s Award for Excellence in
Research (1997), in 1989, the William E. Newell Power Electronics Award, the
highest award presented by the IEEE Power Electronics Society for outstanding
achievement in the power electronics discipline, the Power Conversion and Intelligent Motion Award for Leadership in Power Electronics Education (1990),
the Arthur E. Fury Award for Leadership and Innovation in Advancing Power
Electronic Systems Technology (1998), the IEEE Millennium Medal, and
honorary professorships from Shanghai University of Technology, Shanghai
Railroad and Technology Institute, Nanjing Aeronautical Institute, Zhejiang
University, and Tsinghua University. He is an active member in the professional
community of power electronics engineers. He chaired the 1995 International
Conference on Power Electronics and Drives Systems, which took place in
Singapore, and co-chaired the 1994 International Power Electronics and Motion
Control Conference, held in Beijing. During 1993-1994, he served as President
of the IEEE Power Electronics Society and, before that, as Program Chair
and then Conference Chair of IEEE-sponsored power electronics specialist
conferences.
Download