ZGG40-275 Modular Power Supply SPD Product Specification

advertisement
ZGG40-275 Modular Power Supply SPD
Product Specification
General
The ZGG40-275 Modular Power Supply SPD can be used for protection of L-N and L/N-PE. It is applied in the
low voltage AC power distribution system, and connected between AC power supply and system equipment in
parallel. It can prevent equipment from the impulse surge and transient overvoltage caused by the outside
environment (such as lightning, EMI, etc.) or by the system (such as switching effects of the system, startup or
shutoff of the inductance and capacitance load, etc.).
Features
1
Anti-reverse slot design;
2
High discharge capacity and low residual voltage;
3
Overtemperature protection;
4
Failure indication and remote signalling alarm dry contacts.
5
IP20, UL94 V0
Sichuan Zhongguang Lightning Protection Technologies Co., Ltd.
Website: www.zhongguang.com
Page 1 of 6
ZGG40-275 Modular Power Supply SPD
Product Specification
Version: P1.1
Standards Complied
IEC 61643-1:2005
Surge protective devices connected to low-voltage distribution systems - Part 1:
Technical requirements and testing methods
EN 61643-11/A11:2007 Low-voltage surge protective devices - Part 11: Surge protective devices connected
to low-voltage power distribution systems
UL 1449 ed3
UL 1449 Third Edition
EN 60950-1:2006
Information technology equipment - Safety - Part 1: General requirements
YD/T 1235.2-2002
Testing methods for surge protective devices connected to low-voltage distribution
systems of telecommunication stations / sites
Approval/Certifications
Technical Data
Operating Environment
Temperature
-40℃~80℃
Relative humidity
≤95% (25℃)
Altitude
≤3000m
Technical Parameters
Model
ZGG40-275
SPD according to IEC 61643-1
Class Ⅱ
SPD according to EN 61643-11
Type 2
Nominal operating voltage UO
230V AC
Maximum continuous operating voltage Uc
275V AC
Operating frequency
50/60Hz
Nominal discharge current In (8/20μs)
20kA
Maximum discharge current Imax (8/20μs)
40kA
Voltage protection level Up
Mains-side overcurrent protection
Leakage current
Connection mode
≤1.35kV
125A gL/gG
≤20μA
In parallel
Sichuan Zhongguang Lightning Protection Technologies Co., Ltd.
Website: www.zhongguang.com
Page 2 of 6
ZGG40-275 Modular Power Supply SPD
Product Specification
Version: P1.1
Protection mode
L-N, L/N-PE
Response time T
≤25ns
Cross-sectional area of connecting terminals
Multi-core: 4~25mm2; single-core: 4~35mm2
1.5mm2
Max. connection area of remote signalling terminals
Intensity of remote signalling alarm contact
AC: 250V/0.75A 125V/3A
Isolation between the alarm circuit and main circuit
DC: 30V/2A
Reinforced insulation is applied between the
alarm circuit and main circuit.
(With U0 not exceeding 230V according to EN
60950-1:2006, it can withstand insulation
voltage of 3000Vrms.)
Torque: connecting terminal/remote signalling interface
Material of enclosure
4.5/0.25Nm
PBT V-0
Degree protection provided by enclosure (IP code)
Installing form
IP20
35mm standard guide rail
Application system
TT, TN, IT
Weight
(130±5)g
Circuit diagram
Fig. 1 Circuit diagram
Sichuan Zhongguang Lightning Protection Technologies Co., Ltd.
Website: www.zhongguang.com
Page 3 of 6
ZGG40-275 Modular Power Supply SPD
Product Specification
Version: P1.1
Configuration
Overall dimensions: 90mm×18mm×67mm (excluding remote signalling terminals)
Fig. 2 Overall dimensions
Installation, Usage and Maintenance
Installation
1
This product can only be installed and maintained by qualified professionals. The installation position
cannot be touched by hands. Ensure that it is uncharged and check whether the SPD is all right before
installation. If there’s damage or the display window is red, the SPD can not be used any more; if the
window is green, the SPD is normal.
2
The SPD should be installed behind the fuse (FU1) of the power supply circuit, with the capacity of the
fuse not exceeding 125A gL/gG; otherwise an 80A gL/gG fuse (FU2) should be provided in the surge
protection branch circuit.
3
Refer to Fig. 3 for connection, according to the marks on the SPD. The sectional area of the connecting
wire must be more than 4mm2, as short as possible.
4
Connection of remote signalling alarm: the SPD is provided with remote signalling interfaces (1 and 2
normally closed, and 2 and 3 normally open), applicable for remote monitoring or alarm.
5
After the connection, check if the module is fitted in. If so, 1 and 2 are closed, and 2 and 3 are open; if not,
repress the module.
Sichuan Zhongguang Lightning Protection Technologies Co., Ltd.
Website: www.zhongguang.com
Page 4 of 6
ZGG40-275 Modular Power Supply SPD
Product Specification
Version: P1.1
Wiring diagram
TN-C/IT System
TN-S System
TT System “3+1” Circuit
Fig. 3 Wiring diagram
Usage and Maintenance
1
After failure, the ZGG40-275 Modular Power Supply SPD shall be automatically disconnected with the
power supply circuit through the internal thermal fuse system, the display window changes to “Red” from
“Green”, and remote signalling interfaces 1 and 2 are open and 2 and 3 are closed. When the degradation
display window is “Red” or there’s a remote alarm signal, the SPD should be changed immediately.
2. The
display
window
o.
f.
the
SPD
must
checked
after
the
lightning
storm.
....
.
..
.
...
.
.....
...
...
..
.be
...
.......
.
.
.
..
...
.
..
.
.
.
...
.
.
...
Package, Transportation and Storage
Package
A package consists of 4 SPDs with a Users’ Manual.
Transportation
There should be covering during transportation. No strong shocks and impacts are allowed.
Storage
The storage temperature is -40℃~80℃, and relative humidity 95% or less. Good ventilation, dry ground and
no corrosive gas are in the warehouse. Products whose shelf life is over one year could only be used after
passing the re-check.
Sichuan Zhongguang Lightning Protection Technologies Co., Ltd.
Website: www.zhongguang.com
Page 5 of 6
ZGG40-275 Modular Power Supply SPD
Product Specification
Version: P1.1
Manufacturer Information
Company Name: Sichuan Zhongguang Lightning Protection Technologies Co., Ltd.
Manufacturing Base: No. 19, Tianyu Rd., West Park, Chengdu Hi-Tech Zone, Sichuan, China
Postcode: 611731
Global Service Hotline: +86 400 682 1987
Service Tel.: +86 28 86082899 / 86083899 (Direct) 8090 (Ext.)
Fax: +86 28 87843532
Website: www.zhongguang.com
E-mail: support@zhongguang.com
Sichuan Zhongguang Lightning Protection Technologies Co., Ltd.
Website: www.zhongguang.com
Page 6 of 6
Download