General
The ZGGH15-24 Modular Power Supply SPD consists of a ZGGH15-24MK power supply module and a
ZGGH20-DZ1 base, used for secondary and tertiary protection of the DC system + — - and - — PE. It is
connected between DC power supply and system equipment in series or in parallel. It can prevent equipment
from the impulse surge and transient overvoltage caused by the outside environment (such as lightning, EMI,
etc.) or by the system (such as switching effects of the system, startup or shutoff of the inductance and
capacitance load, etc.).
Features
1 Anti-reverse slot design;
2 Low residual voltage;
3 Overtemperature protection;
4 Failure indication and central remote signalling alarm dry contact;
5 IP20, UL94 V0
Technical Data
Operating Environment
Sichuan Zhongguang Lightning Protection Technologies Co., Ltd.
Website: www.zhongguang.com
Page 1 of 6
ZGGH15-24 Modular Power Supply SPD
Product Specification
Version: V1.0
Temperature
-40℃~80℃
Relative humidity
≤95% (25℃)
≤3000m
Altitude
Technical Parameters
Model
ZGGH15-24
SPD according to IEC 61643-1
Class Ⅱ, Class Ⅲ
SPD according to EN 61643-11
Type 2, Type 3
Nominal operating voltage UO
Maximum continuous operating voltage Uc
24V DC
+— -: 45V DC; -—PE: 0V
Current
DC
Nominal discharge current In (8/20μs)
8kA
Maximum discharge current Imax (8/20μs)
15kA
Class Ⅱ voltage protection level Up
+ — -: 280 V; - — PE: 800 V
Complex wave Uoc
16kV
Limiting voltage (2kV 1.2/50μs, 1kA 8/20μs)
+ — -: 150 V; - — PE: 150 V
Class Ⅲ voltage protection level Up
+ — -: 280 V; - — PE: 280 V
Rated load current
25A
Actuation time of degradation indicating
device (320mA)
≤1min
≤25A gL/gG
Preposed fuse
Connection mode
In series, in parallel
Protection mode
+ - -; - - PE
Response time T
+ - -: ≤25ns; - - PE: ≤100ns
Cross-sectional area of connecting terminals
2
Multi-core: 0.2~2.5mm ; single-core: 0.2~4mm
Max. connection area of remote signalling
terminals
Intensity of remote signalling alarm contact
Isolation between the alarm circuit and main
circuit
2
2.5mm
AC: 250V/0.75A 125V/3A
DC: 30V/2A
Reinforced insulation is applied between the alarm circuit and main circuit.
(With U0 not exceeding 230V according to EN 60950-1:2006, it can withstand
insulation voltage of 3000Vrms.)
Torque: connecting terminal
1.0Nm
Material of enclosure
PBT V-0
Degree protection provided by enclosure (IP
code)
Installation method
2
IP20
35mm standard guide rail
Weight
90±5g
Sichuan Zhongguang Lightning Protection Technologies Co., Ltd.
Website: www.zhongguang.com
Page 2 of 6
ZGGH15-24 Modular Power Supply SPD
Product Specification
Version: V1.0
Circuit Diagram
+
5
6 +
U
11
OUT
U
IN
12
-
1
2 -
PE
3
4 PE
Fig. 1 Circuit diagram
Configuration
Dimensions: 90×18×69 (Fig. 2)
For mounting on: DIN 35mm standard guide rail
Flammability: UL94 V0
Degree of protection: IEC 60529 IP20
Sichuan Zhongguang Lightning Protection Technologies Co., Ltd.
Website: www.zhongguang.com
Page 3 of 6
ZGGH15-24 Modular Power Supply SPD
Product Specification
Version: V1.0
+/6
/4
-/2
12
11
OUT
RoHS
5/+
3/
1/-
IN
Fig.2 Dimensions drawing
Standards Complied
IEC 61643-1:2005
UL 1449 ed3
Approval/Certifications
Installation, Usage and Maintenance
Installation
1 This product can only be installed and maintained by qualified professionals. The installation position cannot
be touched by hands. Ensure that it is unpowered before installation.
2 The SPD should be installed behind the fuse (FU1) of the power supply circuit, with the capacity of the fuse
not exceeding 25A gL/gG; otherwise another fuse (FU2) should be provided in the surge protection branch
circuit.
3 Refer to Fig. 1, Fig. 2 and Fig. 3 for connection according to the marks on the SPD, with “Positive” to “+” of
SPD, “Negative” to “-” of SPD, and “ ” to PE. There are “IN” and “OUT” markings on the SPD, and the input
and output connections must be reliable.
4 Connection of remote signalling alarm: the SPD is provided with remote signalling alarm interfaces 11 and 12
(normally short-circuited; abnormally open), applicable for remote centralized monitoring or alarm.
5 After the connection, check if the module is fitted in before powered on. If normal, the “Green” indicator is on.
Sichuan Zhongguang Lightning Protection Technologies Co., Ltd.
Website: www.zhongguang.com
Page 4 of 6
ZGGH15-24 Modular Power Supply SPD
Product Specification
Version: V1.0
Wiring Diagram
2
FM
FM
4
PE
+
4
6
6
12
11
OUT
11 12
2
FM
12
11
OUT
Modular Power
Supply SPD
IN
1
3
5
FU1>25A gL =>FU2≤25A gL
FU1≤25 gL=>FU2
+
FU2
IN
1
3
5
FU1
PE
FU1
FU1≤25 A gL
-
-
PE
+
Fig. 3 Wiring diagram
Usage and Maintenance
1 After failure, the ZGGH15-24 Modular Power Supply SPD shall be automatically disconnected with the power
supply circuit through the internal thermal fuse system, the working indicator in the display window is off, and
remote signalling interfaces 11 and 12 are closed. When the “Green” indicator is off or there’s a remote alarm
signal, the SPD should be changed immediately.
2 The
display
window
of..
the
SPD
must
checked
after
the
lightning
storm.
....
.
..
.
...
.
.....
...
...
..
.b
.e..
.......
.
.
.
..
...
.
..
.
.
.
...
.
....
Package, Transportation and Storage
Package
A package consists of four pcs of SPDs with a copy of users’ manual.
Transportation
There should be covering during transportation. No strong shocks and impacts are allowed.
Storage
The storage temperature is -40℃~80℃ and relative humidity 95% or less. Good ventilation, dry ground and no
corrosive gas are in the warehouse. Products whose shelf lives are over one year could only be used after
passing the re-check.
Sichuan Zhongguang Lightning Protection Technologies Co., Ltd.
Website: www.zhongguang.com
Page 5 of 6
ZGGH15-24 Modular Power Supply SPD
Product Specification
Version: V1.0
Contact
Sichuan Zhongguang Lightning Protection Technologies Co., Ltd.
No. 19 Tianyu Rd., West Park, Chengdu Hi-Tech Zone, Chengdu, Sichuan 611731 China
Fax: +86 28 87843532
Tel.: +86 28 66755400/ 86082899, 86083899 (Direct) 2051 (Ext.)
E-mail: support@zhongguang.com
Sichuan Zhongguang Lightning Protection Technologies Co., Ltd.
Website: www.zhongguang.com