T7147A,G Remote Space Sensors and Override Modules INSTALLATION INSTRUCTIONS APPLICATION 2000 SPECIFICATIONS Temperature Sensor: Thermistor-resistor (NTC) element. 7A 1800 1700 1420 OHMS AT 75°F (24°C) 1600 1500 1400 1300 1200 1100 T71 47G 1000 900 710 OHMS AT 75°F (24°C) 800 700 600 500 10 20 30 40 50 60 70 90 80 °F 100 °C -10 0 10 20 30 40 TEMPERATURE (DEGREES) Mounting: Mounts on wall or 2 x 4 in. vertical outlet box with screws provided. 1-13/16 (46) 14 1800 Sensor Resistance: Resistance decreases as temperature increases (Fig. 2). T7147A: 1420 ohms nominal at 75°F (24°C); resistance changes 15 ohms for each 1°F (0.6°C) temperature change. T7147G: 710 ohms nominal at 75°F (24°C); resistance changes 7.5 ohms for each 1°F (0.6°C) temperature change. Dimensions: See Fig. 1. T7 1900 RESISTANCE (OHMS) The T7147A,G Remote Space Sensors and Override Modules are used with T7300/Q7300 Thermostat/ Subbase to provide space temperature control, switch initiation and override indication from a remote location. M17730 Fig. 2. T7147 Remote Sensor resistance change with change in temperature. INSTALLATION When Installing this Product... 3-1/4 (83) 4-5/8 (117) COOLER TEMPORARY OCCUPIED WARMER 1. 2. 1 3-13/16 (97) 3. 4. 7/8 (22) 1-1/16 (27) 3/8 (10) 2-7/8 (73) 3-5/8 (92) 1 NOT ALL MODELS HAVE WARMER/COOLER FUNCTION. M11186A Fig. 1. T7147 dimensions in in. (mm). ® U.S. Registered Trademark Copyright © 2001 Honeywell • All Rights Reserved Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. Installer must be a trained, experienced service technician. After installation is complete, check out product operation as provided in these instructions. CAUTION Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry. Disconnect power supply before installation. 62-3049-2 T7147A,G REMOTE SPACE SENSORS AND OVERRIDE MODULES Location Connect the correct Q7300 control wires to the T7147 as shown in Fig. 4 through 9. Be sure all connections are tight. Loose or intermittent wire connections cause inconsistent system operation. Locate the T7147 or remote sensor about 5 ft (1.5m) above the floor on an inside wall where it is affected by freely circulating air at average room temperatures. IMPORTANT The T7147 ground (GND) connection is required. Use the junction box or conduit for a grounding location. Mounting 1. 2. 3. 4. 5. 6. Loosen the cover locking screw and remove the thermostat cover. Run wire to selected location; thread wire through semicircular hole in base; and make connections to the T7147 (see the Wiring section). Four mounting screws are provided: two selftapping for wall mounting, and two for outlet box mounting. Select proper screws for the application. If air drafts occur through the wall opening, eliminate with suitable material. Fasten the T7147 on the wall or outlet box with screws through the thermostat mounting holes. See Fig. 3. Replace cover and tighten the cover locking screw. WALLPLATE CA5 CA4 CA3 CA2 CA1 GND 2 CA5 CA4 CA3 OUTLET BOX CA2 CA1 GND 1 MOUNTING SCREW (2) T T MOUNTING TAB (2 INSIDE COVER) 1 ROUTE EXCESS WIRING AWAY FROM SENSOR ELEMENT FOR OPTIMUM PERFORMANCE. CO OLE R TE MPO OCC RA UP RY IED WAR MER 2 CONNECTIONS TO CA3 AND CA4 NOT REQUIRED M17717 ON T7147A2000. MOUNTING TAB SLOT (2) Fig. 4. Connecting wires to T7147. THERMOSTAT COVER LOCKING SCREW OPERATION AND CHECKOUT M10869B Fig. 3. Mounting the T7147. Operation The remote sensor control element is a negative temperature coefficient (NTC) thermistor. As the room temperature increases, thermistor resistance decreases. Wiring CAUTION The thermistor resistance change causes the motor, system logic panel or system transmitter bridge circuit to become unbalanced. As the electronic motor, system logic panel or system transmitter circuits react to rebalance the circuit, damper or valve movement, or heating and/or cooling equipment sequential staging occurs. Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry. Disconnect power supply before installation. IMPORTANT All wiring must agree with applicable codes, ordinances and regulations. Overrides Keys on the face of the T7147 can enact override functions programmed at the T7300/Q7300. IMPORTANT • To avoid electrical interference, which can cause erratic performance, keep wiring runs as short as possible and do not run thermostat wires adjacent to the line voltage electrical distribution systems. • Use shielded cable (Belden type 8762 or equivalent for 2-wire and Belden type 8772 or equivalent for 3-wire). • The cable shield must be grounded only at the controlled equipment case. NOTE: All overrides must be programmed at the T7300/Q7300. The T7147 cannot change these programmed settings. Temporary Occupied Pressing the Temporary Occupied key sends a signal from the T7147 to the T7300/Q7300. The T7300 proceeds into an occupied override and sends a signal to the T7147 that turns on the Temporary Occupied LED. The LED remains on for the duration of the override. Refer to instructions supplied with other system components. 62-3049—2 2 T7147A,G REMOTE SPACE SENSORS AND OVERRIDE MODULES T7300/Q7300 T7147 C1 CA1 C2 CA2 C3 CA3 C4 CA4 C5 CA5 T T T T COOLER WARMER 3 HR OCCUPIED 1 T 2 1 WARMER/COOLER FUNCTIONS ARE NOT AVAILABLE WITH THE T7147A1002. 2 SHIELDED CABLE CAN BE REQUIRED IN SOME INSTALLATIONS. 3 THE GROUND (GND) CONNECTION TO THE T7147 IS REQUIRED. USE THE JUNCTION BOX OR CONDUIT FOR A CONVENIENT GROUNDING LOCATION. GND M10193 3 Fig. 5. Typical wiring diagram for T7147 used with T7300/Q7300 Thermostat/Subbase. T7300/Q7300 T T7047C2007 T7047C2007 T T T T T T T 2 C1 T7147A C2 T C3 T T T 1 A MAXIMUM OF FOUR T7147 ALLOWED PER SYSTEM. T7047C2007 T T 2 SHIELDED CABLE CAN BE REQUIRED IN SOME INSTALLATIONS. CA1 CA2 CA3 CA4 CA5 GND 3 THE GROUND (GND) CONNECTION TO THE T7147 IS REQUIRED. USE THE JUNCTION BOX OR CONDUIT FOR A CONVENIENT GROUNDING LOCATION. 1 C4 3 C5 M10194BB Fig. 6. T7147 used in a four-temperature sensor averaging application with T7300/Q7300 Thermostat/Subbase. T7047C2007 T7300/ Q7300 T T T T T7047C2007 T T T T T 1 A MAXIMUM OF FOUR T7147 ALLOWED PER SYSTEM. T7047C2007 T T T T T T 2 SHIELDED CABLE CAN BE REQUIRED IN SOME INSTALLATIONS. T T7047C2007 T 2 T7047C2007 T 3 THE GROUND (GND) CONNECTION TO THE T7147 IS REQUIRED. USE THE JUNCTION BOX OR CONDUIT FOR A CONVENIENT GROUNDING LOCATION. T7047C2007 T T C1 C2 C3 C4 T7047C2007 T7147A T T T T T T T7047C2007 T T T CA1 CA2 CA3 CA4 CA5 GND 1 C5 M10195BB 3 Fig. 7. T7147 used in a nine-temperature sensor averaging application with T7300/Q7300 Thermostat/Subbase. Temporary Setpoint Adjust NOTES: — Pressing the Temporary Occupied key followed by the Warmer or Cooler key sends a signal from the T7147 to the T7300/Q7300. The T7300 proceeds into the programmed setpoint override. and sends a signal to the T7147 turning on the Temporary Occupied LED with appropriate Warmer or Cooler LED. The LED remains on for the override duration. — — 3 This override is a 0 to 5 degree offset from the occupied control point. The override can be performed at any time regardless of the mode in which the T7300 is operating. Press the override key again to exit the override feature and return to normal T7300 operation. 62-3049—2 T7147A,G REMOTE SPACE SENSORS AND OVERRIDE MODULES T7300/ Q7300 T7147G T7147G 1 THE GROUND (GND) CONNECTION TO THE T7147 IS REQUIRED. USE THE JUNCTION BOX OR CONDUIT FOR A CONVENIENT GROUNDING LOCATION. 2 SHIELDED CABLE CAN BE REQUIRED IN SOME APPLICATIONS. 2 T T T T 3 C1 T T 3 1 CA1 CA2 CA3 CA4 CA5 GND 1 CA1 CA2 CA3 CA4 CA5 GND C2 3 WARMER/COOLER FUNCTIONS ARE NOT AVAILABLE WITH THE T7147G2007, G2015. C3 C4 M10865A C5 Fig. 8. T7147G in 2-temperature sensor averaging application with T7300/Q7300 Series 2000 Thermostat/Subbase. T7300/ Q7300 T T7147G 3 1 1 T T7147A T T7147A T T T 2 C1 CA1 CA2 CA3 CA4 CA5 GND C2 T T 4 2 CA1 CA2 CA3 CA4 CA5 GND 2 CA1 CA2 CA3 CA4 CA5 GND C3 C4 C5 1 T7047C1025 CAN BE SUBSTITUTED FOR T7147A IF REMOTE OVERRIDE IS NOT REQUIRED. 2 THE GROUND (GND) CONNECTION TO THE T7147 IS REQUIRED. USE THE JUNCTION BOX OR CONDUIT FOR A CONVENIENT GROUNDING LOCATION. 3 SHIELDED CABLE CAN BE REQUIRED IN SOME INSTALLATIONS. 4 WARMER/COOLER FUNCTIONS ARE NOT AVAILABLE WITH THE T7147G2007, G2015. M10866BB Fig. 9. T7147 in 3-temperature sensor averaging application with T7300/Q7300 Series 2000 Thermostat/Subbase. Averaging Sensors 3. For large zone temperature control, use a T7300 with several remote temperature sensors. The T7300 averages the temperature signals from all the remote temperature sensors for more comfortable control. 4. NOTE: Up to four sensors can be used with one T7300/Q7300 Series 2000 Thermostat. 5. Calibration The T7147 Electronic Thermostat or Remote Space Sensor is accurately calibrated at the factory. It cannot be field calibrated. NOTE: If the T7147 does not check out, review the wiring and connections between the Q7300 and T7147. Replace the T7147 if wiring continuity checks out. If the new T7147 does not check out, replace the Q7300. Checkout Allow the T7147 Remote Sensor and Override Module to stabilize to ambient conditions before measuring the resistance: 1. Measure nominal resistance according to the values described in the Specifications section. 2. Measure the T7147 resistance in accordance with the temperature curves. See Fig. 2. Press the Temporary Occupied key once. The LED turns on. Check that the T7300 displays Temporary Occupied. For models with Warmer and Cooler keys, press the Warmer key once. The Warmer LED turns on. Press the Cooler key and the Warmer LED turns off. Press the Cooler key again and the Cooler LED turns on. Press the Temporary Occupied key once. All LED turn off. T7300 Temporary Occupied display turns off and returns to normal operation. 6. Check the complete control systems operation as directed in the associated technical publications. Home and Building Control Home and Building Control Honeywell 1985 Douglas Drive North Golden Valley, MN 55422 62-3049—2 B.B. 2-01 Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Scarborough, Ontario M1V 4Z9 Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers. www.honeywell.com/building/components