BIDDING & CONTRACT REQUIREMENTS Document 00901 – Addendum No. 1 DATE: April 30, 2015 Parkland College IGW Architecture 114 West Main Street / Urbana, Illinois 61801 Tel 217-328-1391 Fax 217-328-1401 TO: PROSPECTIVE BIDDERS SUBJECT: ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS FOR Marketing & Public Relations Relocation Remodeling 2400 West Bradley Champaign, Illinois This addendum forms a part of the bidding and contract documents and modifies the original bidding documents, dated April 15, 2015. Acknowledge receipt of this addendum in space provided on Bid Form. FAILURE TO DO SO MAY SUBJECT BIDDER TO DISQUALIFICATION. PROJECT MANUAL 1. Section 01 50 00 – Temporary Facilities and Controls A. Paragraph 3.2, F, Note requirements for dust control and isolation of HVAC system. Provide filters on all returns. Provide dust partitions to separate work area from other occupied space, dust partitions of 2x4 framing, poly sheet and plywood on exterior. 2. Section 10 11 00 – Visual Display Surfaces A. Paragraph 2.2, A, Basis of Design is Claridge Tack Wall series with perimeter fabric covered trim and butt joint fabric wrapped panels at intermediate vertical joints. DRAWINGS 1. Sheet A0.2 – Partial Demolition Reflected Ceiling Plan A. Keyed Note D1; To clarify most of the ceiling areas labeled as D1 will need to be removed where new acoustical tile ceilings are installed at near the same elevations. Where gypsum wall board ceilings and soffits are installed at the same or lower elevation the existing ceiling may just be removed as required for new work. 2. Sheet A1.1 – Partial First Floor Plan A. Add general note to provide blocking in new and existing walls for attachment of casework. B. Door and sidelights X158B, Sand, touch-up stain and varnish existing door, frame and sidelights to remain. 3. Sheet A4.1 – Door Hardware and Room Finish Schedule A. Wall Types, All walls shall extend up to existing gypsum ceiling where it remains or 6” above new ceilings. Brace new partitions up to structure at 32” o.c. Parkland College – Marketing & Public Relations Relocation Remodeling IGW File #1432 – 04-30-15 ADDENDUM NO. 1 00901-1 4. SHEET M0.1: A. Mechanical Contractor temporarily block off return air openings into shaft (above GWB ceiling) to prevent migration of construction dust into return air plenum. Remove at end of construction. 5. SHEET M1.1: A. See revised RETROFIT VAV TERMINAL UNIT INSERT SCHEDULE and HOT WATER CONTROL VALVE SCHEDULE on Drawing MD1 included as an attachment to this addendum. 6. SHEET E0.0: A. Light Fixture Schedule; change type F3 as follows: “Corelite Class A D/I Series, white finish, 3-28watt, F28T5, SP35 fluorescent lamps cross-sectional. Refer to plans for lengths required, adjustable air-craft cable supports, acrylic dust cover. 7. SHEET E0.1 : A. Remove existing Panel 3F. Existing feeder and branch circuits (conduit & wire) to remain shall be disconnected and reconnected to new Panel 3F. 8. SHEET E1.1 : A. Clarification: Low-voltage cable associated with the occupancy sensors and room controllers can be installed “free-air” above accessible ceilings. 9. SHEET E2.1 : A. Delete reference to Panel 3FA in its entirety. Replace existing Panel 3F with new Panel 3F. Reconnect existing feeder and remaining branch circuits (conduit & wire) to new Panelboard. 10. SHEET E4.1 : A. Delete Detail 1 – “One-Line Power Diagram” in its entirety. B. Delete Detail 2 – “One-Line Power Diagram” in its entirety. C. Panel Schedule 3F shall be as follows: 72 poles in single 20” wide x 44.0” high panel section, 225 amp, main lug only, bottom fed, bolt-on circuit breakers, 22 KAIC, surface mounted in NEMA 1 enclosure. Provide seventy-two (72), 20A/1P circuit breakers. Bids are due on Tuesday May 5, 2015 at 3:00 P.M. prevailing time. Bids are due at: Parkland College, Room X150 Attachments: Specification Sections: None Drawings: MD1 Respectfully submitted, IGW Architecture This addendum consists of 2 pages. Parkland College – Marketing & Public Relations Relocation Remodeling IGW File #1432 – 04-30-15 ADDENDUM NO. 1 00901-2