Connector Options: MODEL LPD100 INSTALLATION AND OPERATING MANUAL for 4/20 mA LOOP INDICATOR in mm Figure 2 Ordering Information: Model: LPD100 Connector Option Calibration Range (A,B,C,D,E) Zero/Full Scale Units of Measure example: LPD100A -14.7/100 psig Description: LPD100 loop indicator with “A” connector option (see above) calibrated so that the display reads -14.7 psig @ 4 mA and 100 psig @ 20 mA. If the calibrated range is greater than 1999 counts, add a “K” to the end of the model number. Exanple: LPD100AK -14.7/2500 psig Same as above except calibrated to display 2500 psig @ 20 mA. K796418 Rev B The model LPD100 loop indicator is a digital display designed to connect directly to the Ametek HPT100 series transducer. Its purpose is to produce a local indication of the process in either pressure, current or percent of full scale. The display span settings and decimal positions are factory set. The unit span and zero may be adjusted in the field with externally accessible potentiometers. The LPD100 is connected in series with the transducer and is powered by the same 2 wire 4-20 mA current loop of the transducer A typical installation attached to a transducer is shown in Figure 1. Electrical Connections: Typical Electrical Connections : + Pressure Transducer (HPT 100) (+) 4-20 mA 4 to 20 mA + (+) 4-20 mA 100.0 A LPD100 (-) 4-20 mA - Load Resistor 24 V Power Supply (-) 4-20 mA Connector Designations: Transducer Connection Options A-B-C-D Power Connection Options A-B Pigtail Designations: Transducer Connection Option E only Power Connection Options C-D-E RED- (+) 4-20 mA RED- (+) 4-20 mA BLK- (-) 4-20 mA BLK- (-) 4-20 mA 100.0 Figure 1 The available options allow for connector to connector connections, connector to pigtail connections or pigtail to pigtail connections. The options are illustrated in Figure 2. Display Position: The LPD100 options A through D can swivel on the Bendix type connector up to 320° of rotation. This is accomplished by loosing the swivel locking nut , turning the housing to the correct orientation, and tighten the swivel locking nut. The swivel locking nut need only be hand tightened to prevent rotation. Zero and Span Adjustments: The ZERO and SPAN adjustments are marked on the top side of the indicator. With 4 mA applied to the loop, adjust the ZERO for the correct zero reading on the display. With 20 mA applied to the loop, adjust the SPAN for the correct full scale reading on the display. This procedure may need to be repeated until the zero and full scale readings are correctly set. Note: The LPD100 is a indicator of the transducer output. It is not intended to be a calibration device and should not be used to set the transducer output. GRN - CHASSIS GND Note: Shield wire connected to chassis. A LPD100 GRN - CHASSIS GND Specifications: SIGNAL CURRENT:............................... 4 to 20 mA, DC OVERLOAD............................................ 60 mA forward, 75 mA reverse VOLTAGE DROP @ 20 mA................... 3.5 Volts, Max. DISPLAY................................................. 0.3” H, 3 ½ Digits LPD100, 4-½ Digits LPD100_K LEAST SIGNIFICANT DIGIT ................Fixed Zero @ Least Significant Digit for LPD100_K ZERO RANGE......................................... 20% of selected range SPAN ....................................................... -100 to 1999 counts LPD100/-1000 to 19990 LPD100_K OVERRANGE INDICATION ................. “1” in most significant digit, rest of digits blank WEIGHT.................................................. 2.5 oz. max. w/o cable MATERIAL & FINISH ........................... Clear anodized aluminum HOUSING................................................ Face 2.08” H, 2.08” W; 1.48”min/2.75” max. D ................................................................. Face 52,8mm” x52.,8mm x; 37,6/69,9 mm D ROTATION ............................................. 320° ACCURACY, INCLUDING LINEARITY...............±(0.1 % F.S. + 1 count), @ 25°C TEMPERATURE COEFFICIENT ...........................±200 PPM/°C OPERATING TEMPERATURE ..............................-20 to +70 degree C STORAGE TEMPERATURE...................................-40 to +85 degree C READING RATE......................................................2.5 Readings/second