Foam 880 a August 18, 1999 DESIGN DATA The Viking Corporation 201 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (616) 945-9501 (877) 384-5464 Fax: (616) 945-9599 e-mail: techsvcs@vikingcorp.com 3. PRODUCT DESCRIPTION The Viking Model VFS-100 Foam Hose Station is a self-inducting, continuous flow hose reel station with a foam concentrate supply tank built into the unit. The Model VFS-100 is designed for use in flammable liquid storage areas, aircraft hangars, heli-pads, and any other areas where foam solution handlines are required. 4. TECHNICAL DATA 8. OPERATION (Refer to Figure 1.) An automatic water supply is required to be connected to the 1-1/2“ (40 mm) inlet. The foam solution control valve (2) must be open and the water supply bypass control valve (1) must be closed to proportion foam. The eductor (3) in the supply loop to the hose reel (7) is connected to the foam concentrate supply tank (4). When the hose reel nozzle (purchased separately) is opened, water passing through the eductor (3) will cause a strong venturi effect in the low-pressure area of the eductor (3). This causes foam concentrate to be proportioned into the water stream. After foam concentrate is proportioned into the water stream, the mixture becomes foam water solution. Foam water solution is then discharged through the hose, out of the nozzle, and onto the hazard. If only water is desired to be discharged, or if flushing of the hose line is required, close foam solution control valve (2), open water supply bypass control valve (1), and open hose nozzle to discharge system supply water. BS Listings and Approvals: None Minimum Recommended Ambient Temperature: 40 °F (4 °C) Rated discharge flow: 60 gpm (227 L/min) Maximum Hose Length: 100 ft. (30,47 m) Concentrate Storage Tank Capacity: 55 gallons (208 L) 5. AVAILABILITY AND SERVICE O The Viking Foam Hose Station is available through a network of domestic, Canadian, and international distributors. See the Yellow Pages of the telephone directory for a local distributor (listed under “Sprinklers- Automatic-Fire”), or contact The Viking Corporation. Viking technical data may be found on The Viking Corporation’s Web site at http://www.vikingcorp.com. The Web site may include a more recent edition of this technical data page. 6. GUARANTEES For details of warranty, refer to Viking’s current list price schedule or contact The Viking Corporation directly. 7. APPLICATION The Viking Model VFS-100 Foam Hose Station is used wherever Class B fires Form No. F_090198 curely mount the device to a horizontal surface that the unit will rest on. Foam concentrate is placed in the Foam Concentrate Supply Tank (4) by opening the foam concentrate fill connection and filling to the appropriate level. The capacity of the tank is 55 gallons. A sealing oil should be placed over the surface of the foam concentrate to avoid exposing the concentrate to air. Note: Foam concentrate will solidify if it is exposed to atmospheric air for extended periods of time. After the unit has been secured and the concentrate storage tank supplied, the water supply can connect to the inlet connection of the unit. The hose nozzle is normally closed, the foam solution control valve is normally open, and the water supply bypass control valve is normally closed. TE 2. MANUFACTURED FOR: (flammable and combustible liquids) are stored, transferred, or are used in process operations. The Viking Model VFS-100 continuous flow foam hose reel is designed for use in airplane hangars as required by NFPA 409, heli-decks or heli-pads as required by NFPA 418, and other areas where flammable liquids are handled. The Model VFS-100 is a stand-alone foam hose reel that is not dependent on its supply piping to be fed from a foam proportioning supply. The VFS-100 is ideal to add to an existing facility that may or may not have a foam system in place. If a foam system is in place and the addition of hose stations is required, the VFS-100 would not tax the existing foam concentrate supply. If a water system is in place and the addition of foam hose stations is required, the expense of a bladder tank type hose reel can be avoided. LE Viking Foam Hose Station Model VFS-100 O 1. PRODUCT NAME FOAM HOSE STATION 9. INSTALLATION (Refer to Figures 1 and 2.) The Viking Model VFS-100 Foam Hose Station is a pre-assembled unit. Outlets at the base of the unit are provided to se- 10. MAINTENANCE (Refer to Figures 1 and 2.) 1. If the hose reel unit was discharged, the foam concentrate level should be checked. If foam concentrate has been used, fill the concentrate to the appropriate level. 2. If the Foam Eductor (3) requires removal, close the Foam Concentrate Solution Valve (2). Relieve pressure from the downstream piping by opening the hose reel discharge nozzle. After the water pressure has been eliminated, remove the 1-1/2” Pipe Union (5), remove mounting bolts, and unthread the foam eductor from the inlet piping. 3. If foam concentrate requires removal, close the Foam Solution Control Valve (2), place a hose on Foam Concentrate Drain Valve (17), and place foam concentrate into a suitable container. Foam concentrate should be disposed of in a manner conforming to local requirements. 4. If the hose is distributed from the Supply Loop to the Hose Reel (7), the hose can be retrieved and re-spooled by winding the Hose Retrieval Handle (6) clockwise until hose and nozzle are adequately replaced on the spool. 11. INSPECTIONS AND TESTS Inspections and tests should be conducted at the frequency required by NFPA 25 and the Authority Having Jurisdiction. New issue , dated August 18, 1999. Foam 880 b August 18, 1999 FOAM HOSE STATION O BS O LE TE DESIGN DATA Figure 1 Foam 880 c August 18, 1999 FOAM HOSE STATION DESIGN DATA COMPONENTS OF FOAM HOSE STATION ITEM NO. DESCRIPTION REPLACEMENT PARTS FOR 1 Water Supply By-Pass Control Valve FOAM HOSE STATION 2 Foam Solution Control Valve 3 Eductor 4 Foam Concentrate Supply Tank 5 1-1/2" Pipe Union 6 Hose Retrieval Handle 7 Hose Reel VIKING F01811 Hose Assembly F01705 Tank Assembly LE O BS O Figure 2 DESCRIPTION TE PART NUMBER