F/CATALOGUE / LIGHT-FITTINGS
PAGE
1 OF 6
CATEGORY-HY
SPECIFICATION & QUOTATION FOR FLAMEPROOF/W.PROOF LIGHT FITTINGS
Supply of Cast Aluminium LIGHT FITTINGS dust, vermain and Flameproof & Weatherproof suitable for Structure mounting.
All the enclosures are cast out of superior quality aluminium alloy. All the surfaces are carefully cleaned and levelled so as
to give very smooth surface. All the enclosures are chromatised and finally epoxy powder coated by static charge spray
method by light grey shade 631 as per IS5. Powder coating gives very tough durable and extremely smooth surface. All the
mating surfaces are provided with round rubber gasket in the groove so as to make it effectively dust and vermain proof.
Prototype LIGHT FITTINGS with control gear fitted is tested by C.M.R.I for Explosion proof-ness and for IP65 Class of
protection. MOUNTING: M.S.Strip is provided for fixing. CABLE ENTRIES: Threaded cable entries are provided. Unless
otherwise specified no gland will be provided. EARTHING: Earthing is provided on both sides of enclosures by 5mm screw
with two plain washers and spring washer of brass.
INSPECTION & TESTING: Each LIGHT FITTINGS will be subjected to routine tests in accordance with relevant Indian
Standards & including following:
(1) Dimensional check as per drawing. (2) Operation test. (3) Insulation test with 500V Megger. (4) HV Test at 2KV for 60
Seconds. (5) Earth continuity test.
SPECIFIC REQUIREMENTS FOR EXPLOSION/WEATHERPROOF WELGLASSES
CODE
DRAWING
HY53
DESCRIPTION
WITHOUT CONTROL
GEAR BOX
WITH CONTROL GEAR BOX
FRONT VIEW
HY62
SIDE VIEW
Supply of Flameproof/Explosion proof WELL GLASS light fitting
with Integral controlgear or without control gear. Constructed
from Die cast ALUMINIUM ALLOY LM-6, suitable for
installation in group IIA, IIB gas area Suitable for 80/125W
HPMV 240V Lamp, But without Bulb, separate terminal
chamber at the top for ease of maintenance. Loop in loop out
can be done. It is provided with flat reflector below lamp holder.
Borosilicate Glass with wire guard and J hook are provided.
Type: HY 53
NOTE: IMAGES, DRAWING AND WIRING DIAGRAM ARE
TYPICAL AND ACTUAL PRODUCT WILL BE AS PER YOUR
SPECIFICATION AND ORDER.
OPEN VIEW 1
OPEN VIEW 2
Supply of Flameproof/Explosion proof WELL GLASS light fitting
without control gear. Constructed from Die cast ALUMINIUM ALLOY
LM-6, suitable for installation in group IIA, IIB gas area Suitable upto
60 W Incandescent Lamp or upto 16W CFL lamp but without Bulb,
separate terminal chamber at the top for ease of maintenance. Loop
in loop out can be done. Borosil Glass with wire guard and J hook
are provided.
Type: HY 62
NOTE: IMAGES, DRAWING AND WIRING DIAGRAM ARE
TYPICAL AND ACTUAL PRODUCT WILL BE AS PER YOUR
SPECIFICATION AND ORDER.
FRONT VIEW
SIDE VIEW
OPEN VIEW
F/CATALOGUE / LIGHT-FITTINGS
CODE
PAGE
2 OF 6
DRAWING
DESCRIPTION
HY55
Supply of Flameproof/Explosion proof REACTOR VESSEL
LAMP fitting without control gear. Constructed from Die cast
ALUMINIUM ALLOY LM-6, suitable for installation in-group IIA,
IIB gas area Suitable upto 60W or 16W CFL 240V Lamp, But
without Bulb, switch will be in separate chamber at the top for
ease of maintenance. Loop in loop out can be done. 1:3/4"
cable entry will be provided.
Type: HY55
NOTE: IMAGES, DRAWING AND WIRING DIAGRAM ARE
TYPICAL AND ACTUAL PRODUCT WILL BE AS PER YOUR
SPECIFICATION AND ORDER.
FRONT VIEW
SIDE VIEW
HY57
OPEN VIEW 1
OPEN VIEW 2
Supply of Flameproof/Explosion proof W.PROOF HAND LAMP fitting
without control gear. Constructed from Die cast ALUMINIUM ALLOY
LM-6, suitable for installation in-group IIA, IIB gas area Suitable for
60W 240V Lamp, But without Bulb termination will be in separate
chamber at top for ease of maintenance. Porcelein Lamp Holder, wire
guard will be provided. Borosil toughened glass is provided 1:3/4"
cable entry will be provided.
Type: HY57
NOTE: IMAGES, DRAWING AND WIRING DIAGRAM ARE
TYPICAL AND ACTUAL PRODUCT WILL BE AS PER YOUR
SPECIFICATION AND ORDER.
FRONT VIEW
SIDE VIEW
OPEN VIEW
CATEGORY-HY
SPECIFICATION & QUOTATION FOR WEATHERPROOF LIGHT FITTINGS
Supply of Cast Aluminium LIGHT FITTINGS dust, vermin and Weather proof suitable for Structure mounting. All the
enclosures are cast out of superior quality aluminum alloy. All the surfaces are carefully cleaned and leveled so as to give
very smooth surface. All the enclosures are chromatised and finally epoxy powder coated by static charge spray method by
light grey shade 631 as per IS5. Powder coating gives very tough durable and extremely smooth surface. All the mating
surfaces are provided with round rubber gasket in the groove so as to make it effectively dust and vermin proof.
MOUNTING: Arrangement provided for fixing. CABLE ENTRIES: Threaded cable entries are provided. Unless otherwise
specified no gland will be provided. EARTHING: Earthing is provided on both sides of enclosures by 5mm screw with two
plain washers and spring washer of brass
INSPECTION & TESTING: Each LIGHT FITTINGS will be subjected to routine tests in accordance with relevant Indian
Standards & including following (1) Dimensional check as per drawing. (2) Operation test. (3) Insulation test with 500V
Megger. (4) HV Test at 2KV for 60 Seconds. (5) Earth continuity test.
HANSU CONTROLS
OFF: PLOT W -281, TTC INDUSTRIAL AREA, RABALE, MIDC, NEW MUMBAI-400 701.
TEL :( 022) 27690037, 65193145, CELL: 9821550302, FAX: 27690038, 25001021
WEB SITE:www.hansucontrols.com,E-Mail:hansucontrols29@rediffmail.com,hansucontrols@yahoo.com
HANSU CONTROLS
OFF: PLOT W -281, TTC INDUSTRIAL AREA, RABALE, MIDC, NEW MUMBAI-400 701.
TEL :( 022) 27690037, 65193145, CELL: 9821550302, FAX: 27690038, 25001021
WEB SITE:www.hansucontrols.com,E-Mail:hansucontrols29@rediffmail.com,hansucontrols@yahoo.com
F/CATALOGUE / LIGHT-FITTINGS
PAGE
3 OF 6
SPECIFIC REQUIREMENTS FOR WEATHERPROOF WELLGLASS LIGHT FITTINGS
CODE
DRAWING
SPECIFICATION
HY10
Supply Cast ALUMINIUM (LM-6) weatherproof well glass suitable for
80/125W HPMV lamp or 70W HPSV Lamp or 2X36W CFL or 1: 45W
spiral type CFL lamp or upto 200W GLS lamp without control gear
without bulb but with Heat resistant glass. 2: 3/4" cable entries will be
provided so that loop in and loop out can be done. mounting strip or
eye bolt will be provided.SIZE: 340x195x195mm
Type: HY10
NOTE: IMAGES, DRAWING AND WIRING DIAGRAM ARE TYPICAL AND
ACTUAL PRODUCT WILL BE AS PER YOUR SPECIFICATION
FRONT VIEW
SIDE VIEW
HY12
OPEN VIEW
Supply Cast ALUMINIUM(LM-6) weatherproof well glass
suitable for for 80/125W HPMV lamp or 70W HPSV Lamp or
2X36W CFL lamp complete with control gear in separate
enclosure mounted on top of well glass without bulb but with
Heat resistant glass.
SIZE: 455x195x195mm
Type: HY12
NOTE: IMAGES, DRAWING AND WIRING DIAGRAM ARE
TYPICAL AND ACTUAL PRODUCT WILL BE AS PER YOUR
SPECIFICATION AND ORDER.
FRONT VIEW
HY03
SIDE VIEW
OPEN VIEW 1
OPEN VIEW 2
Supply of cast aluminum (LM-6 Alloy) Weather proof
REACTOR VESSEL LAMP light fittings Suitable for 60W240V Lamp, But Without Bulb, either with switch or with
Automatic timer in separate chamber at the top for ease of
maintenance. Loop in loop out can be done. 1:3/4" cable entry
will be provided on each side at the top.
Size 262x130x130mm Dia
Type: HY03
NOTE: IMAGES, DRAWING AND WIRING DIAGRAM ARE
TYPICAL AND ACTUAL PRODUCT WILL BE AS PER YOUR
SPECIFICATION AND ORDER.
FRONT VIEW
OPEN VIEW 1
OPEN VIEW 2
F/CATALOGUE /LIGHT-FITTINGS
CODE
DRAWING
PAGE
4 OF 6
SPECIFICATION
HY08
Supply of Choke Box in CAST ALUMINIUM LM-6 enclosure
weather proof without canopy but with enclosure protection of
IP65 suitable for controlgear for 80/125W HPMV or 70W HPSV
or 2X26W CFL lamp fitting. Component like Choke/Ignitor,
Capacitor, Terminal will be fixed and wired internally.
2:3/4"Cable entries will be provided. Choke/Ignitor
will be
CROMPTON MAKE. Capacitor will be ASIAN Make.
SIZE :210X125X75mm TYPE: HY08
FRONT VIEW
NOTE: IMAGES, DRAWING AND WIRING DIAGRAM ARE TYPICAL
AND ACTUAL PRODUCT WILL BE AS PER YOUR SPECIFICATION
TOP/BOTTOM VIEW
SIDE VIEW
OPEN VIEW
HY09
Supply of choke box in cast aluminium lm-6 enclosure weather
proof with integral canopy covering three sides and with
enclosure protection of IP65 suitable for 125w hpmv or 70w
hpsv or 2x26w CFL lamp fitting. Component like choke/ignitor,
capacitor, terminal will be fixed and wired internally. 2:3/4"cable
entries will be provided. Choke/ignitor will be crompton make.
Capacitor will be Asian make.
TYPE HY09
NOTE: IMAGES, DRAWING AND WIRING DIAGRAM ARE TYPICAL
AND ACTUAL PRODUCT WILL BE AS PER YOUR SPECIFICATION
FRONT VIEW
HY17
TOP/BOTTOM VIEW
SIDE VIEW
OPEN VIEW
Supply Cast ALUMINIUM (LM-6 Alloy) weatherproof hand
lamp suitable for 60W GLS LAMP or 16W CFL lamp without
bulb but with heat resistant glass. 1:3/4” cable entry will be
provided at the top and with PVC cap on handle.
SIZE: 285x108x108mm
Type: HY 17 Qty:
NOTE: IMAGES, DRAWING AND WIRING DIAGRAM ARE
TYPICAL AND ACTUAL PRODUCT WILL BE AS PER YOUR
SPECIFICATION AND ORDER.
FRONT VIEW
FRONT VIEW 2
OPEN VIEW
HANSU CONTROLS
OFF: PLOT W -281, TTC INDUSTRIAL AREA, RABALE, MIDC, NEW MUMBAI-400 701.
TEL :( 022) 27690037, 65193145, CELL: 9821550302, FAX: 27690038, 25001021
WEB SITE:www.hansucontrols.com,E-Mail:hansucontrols29@rediffmail.com,hansucontrols@yahoo.com
HANSU CONTROLS
OFF: PLOT W -281, TTC INDUSTRIAL AREA, RABALE, MIDC, NEW MUMBAI-400 701.
TEL :( 022) 27690037, 65193145, CELL: 9821550302, FAX: 27690038, 25001021
WEB SITE:www.hansucontrols.com,E-Mail:hansucontrols29@rediffmail.com,hansucontrols@yahoo.com
F/CATALOGUE /LIGHT-FITTINGS
PAGE
5 OF 6
CODE
DRAWING
SPECIFICATION
HY26
Supply Cast ALUMINIUM (LM-6 Alloy) weatherproof Welglass
suitable for 60W GLS LAMP or 16W CFL lamp without bulb but
with heat resistant glass. 2:3/4” cable entry will be provided at
the top for loop in and loop out facility. Porcelain Lamp Holder,
wire guard will be provided. Mounting bracket is provided at the
top.
SIZE: 205x108x108mm
TYPE HY26
NOTE: IMAGES, DRAWING AND WIRING DIAGRAM ARE TYPICAL
AND ACTUAL PRODUCT WILL BE AS PER YOUR
SPECIFICATION AND ORDER.
FRONT VIEW
OPEN VIEW
CATEGORY-HY
SPECIFICATION & QUOTATION FOR IND. WEATHER PROOF FRP WELGLASS
Supply of FRP (FIBRE GLASS POLYSTER) WELLGLASS dust and vermin proof & weatherproof suitable for Structure
mounting. All enclosures are hot press moulded in single piece out of 20-25% DMC/SMC light grey shade 631 compound.
All the mating surfaces are provided with round Neoprene rubber gasket in the groove so as to make it effectively dust/nd
vermin proof. It is provided with S.S. wire guard & J hook.MOUNTING: S.S. Strip is provided for fixing. CABLE ENTRIES:
Threaded cable entries are provided. Unless otherwise specified no gland will be provided. EARTHING: Earthing is
provided on both sides of enclosures by 5mm screw with two plain washers and spring washer of brass. INSPECTION &
TESTING: Each WELL GLASS will be subjected to routine tests in accordance with relevant Indian Standards and including
following.(1) Dimensional check as per drawing. (2) Operation test. (3) Insulation test with 500V Megger.(4) HV Test at 2KV
for 60 Seconds. (5) Earth continuity test. HARDWARE: All external hardware will be of S.S.316 with degree of protection
IP65.
SPECIFIC REQUIREMENTS FOR INDUSTRIAL WEATHER PROOF FRP WELGLASS
CODE
DRAWING
HY28
FRONT VIEW
SPECIFICATION
Supply HOT PRESS MOULDED FRP (FIBRE GLASS RE_INFORCED
POLYSTER) Industrial weatherproof well glass LIGHT FITTING for
80/125W HPMV lamp or 70W HPSV Lamp or 2X36W CFL lamp without
control gear without bulb but with Heat resistant Glass. Direct cable
termination on. CERAMIC ES type threaded lamp holder. S.S. Strip will
be provided at the top for structure mounting. It will be complete with S.S.
wire guard and J Hook.
SIZE: 340x195x195mm Type: HY28
NOTE: IMAGES, DRAWING AND WIRING DIAGRAM ARE TYPICAL
AND ACTUAL PRODUCT WILL BE AS PER YOUR SPECIFICATION
SIDE VIEW
OPEN VIEW
F/CATALOGUE /LIGHT-FITTINGS
CODE
DRAWING
PAGE
HY29
FRONT VIEW
TOP/BOTTOM VIEW
HY30
6 OF 6
SPECIFICATION
Supply HOT PRESS MOULDED FRP (FIBRE GLASS RE_INFORCED
POLYSTER) Industrial weatherproof well glass LIGHT FITTING for
80/125W HPMV lamp or 70W HPSV Lamp or 2X36W CFL lamp with
control gear in top FRP enclosure without or with integral canopy,
without bulb but with Heat resistant Glass. It will be with terminals in
top enclosure. CERAMIC ES type threaded lamp holder
will be
provided S.S. Strip will be provided at the top for structure mounting. It
will be complete with S.S. wire guard and J Hook.
SIZE: 455x195x195mm Type: HY29
NOTE: IMAGES, DRAWING AND WIRING DIAGRAM ARE TYPICAL
AND ACTUAL PRODUCT WILL BE AS PER YOUR SPECIFICATION
AND ORDER.
OPEN VIEW 1
OPEN VIEW 2
Supply of Hot Moulded FRP (Fiber Glass Re-inforced Polyster) control
gear box without any canopy suitable for 80/125W HPMV lamp or
70W HPSV Lamp or 2X36W CFL lamp with capacitor and discharge
resistor.2:3/4” cable entry will be provided at the bottom.1:3/4” cable
entry will be plugged by PVC plug.
TYPE: HY30
NOTE: IMAGES, DRAWING AND WIRING DIAGRAM ARE TYPICAL
AND ACTUAL PRODUCT WILL BE AS PER YOUR SPECIFICATION
AND ORDER.
FRONT VIEW
TOP/BOTTOM VIEW
HY31
FRONT VIEW
TOP/BOTTOM VIEW
SIDE VIEW
OPEN VIEW
Supply of hot moulded FRP (fiber glass re-inforced polyster) control
gear box with integral canopy suitable for 80/125w HPMV lamp or 70w
HPSV lamp or 2x36w cfl lamp with capacitor and discharge
resistor.2:3/4” cable entry will be provided at the bottom.1:3/4” cable
entry will be plugged by pvc plug.
TYPE: HY31
NOTE: IMAGES, DRAWING AND WIRING DIAGRAM ARE TYPICAL
AND ACTUAL PRODUCT WILL BE AS PER YOUR SPECIFICATION
AND ORDER.
SIDE VIEW
OPEN VIEW