Cut Sheet - Gexpro.com

advertisement
7000 SERIES
CONTACT RATINGS
SPECIFICATIONS
WITH SKIP-A-DAY FEATURE
RESERVE POWER OPTIONAL
24 HOUR TIME SWITCH
TYPE
INPUT VOLTAGE: 120 or 208-277 VAC
60 Hz varies by model.
TERMINAL RANGE: #8 - #14 AWG.
Resistive
120 -277VAC
single phase
120 -277VAC
single phase
OPERATING TEMPERATURE:
-40˚ to 165˚F (-40˚ to +74˚C).
Tungsten
120VAC
40A
Inductive
120, 277VAC
single phase
20A
Pilot Duty
120 -277VAC
1000VA
Motor
120VAC
240VAC
2HP
5HP
General Purpose
TIMING ACCURACY: Line frequency.
CALIFORNIA Title 24
APPLICATIONS
ASHRAE 90.1
POWER CONSUMPTION: 3 watts,
5 watts for “L” models maximum.
Lighting
Heating
Pumps
Air conditioning
Signs
ENCLOSURE: Lockable hasp. Type varies
by model (see page 153 for enclosure
dimensions).
NEW!
FEATURES
NEW!
SCHEDULING: Minimum ON setting is
20 minutes with minimum OFF setting at
75 minutes. Dial accommodates up to 12
pairs of trippers. One pair included.
SKIP-A-DAY: Omit operations on any
day with a 7-spoke wheel marked with
days of week. 3 omitting screws included.
MANUAL OVERRIDE: Until the next
regularly scheduled ON or OFF, automatic
operation then resumes.
OPTIONAL RESERVE POWER: “L”
models keep dial on time up to 16 hours
during power outage.
ELECTROMECHANICAL
CONTROLS
TORK 33
CATALOG
NO.
UPC
CODE
INPUT SUPPLY
(VAC) 60Hz
OUTPUT
CONTACTS
7100
10001
120
SPST
7102
10002
208-277
SPST
7200
11001
120
DPST
7200-O
10512
120
DPST
7202
11002
208-277
DPST
7202-O
10509
208-277
DPST
7300
7302
12001
12002
120
208-277
3PST
3PST
7120
13001
120
SPDT
7122
13002
208-277
SPDT
7220
14001
120
DPDT
7222
14002
208-277
DPDT
ENCLOSURE
TYPE
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1
Metal Indoor/Outdoor
NEMA 3
Metal Indoor
NEMA 1
Metal Indoor/Outdoor
NEMA 3
Metal Indoor/Outdoor
NEMA 3
Metal Indoor/Outdoor
NEMA 3
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1
Metal Indoor
NEMA 1
Metal
Indoor
7202L
19004
208-277
DPST
NEMA 1
Metal Indoor/Outdoor
7300L
19005
120
3PST
NEMA 3
Metal
Indoor/Outdoor
7302L
19006
208-277
3PST
NEMA 3
Metal
Indoor
7120L
19007
120
SPDT
NEMA 1
Metal Indoor
7220L
19009
120
DPDT
NEMA 1
Metal
Indoor
7222L
19011
208-277
DPDT
NEMA 1
Replacement Order #P49 for a pair of ON/OFF per dial. Additional ON/OFF trippers per
Trippers
dial order #P47. 3 omitting screws #53005 supplied.
Replacement
#101 (120V) & #201 (208-277V). For "L" models #36 (120V) & #46
(208-277V). For Astronomic Conversion: Order #Z KIT for 7000 Series.
Motor
19003
A DIVISION OF
NSi INDUSTRIES, LLC
USA • 800.321.5847 • www.nsiindustries.com
120
40A
WIRING DIAGRAMS
7100 SPST
7200 DPST
7100 SPST
M
M
M
7300 3PST
7200 DPST
L
L
L
2
L
H
H
N
X
L
1
2
LOAD
H
N
H
7120 SPDT
2
X
M
X
1
L
LOAD
LOAD
H
N
H
2
L
3
L
L
L
5
L
6
L
DPST
H
1
LOAD
X
L
H
A
N
LOAD
B
N
2
1
L
H
LOAD
X
LOAD
A
B
N
2H
H
N
H
1
L
N
3
LOAD
N
5
LOAD
6
LOAD
LOAD
LOAD
7302 3PST
7120Z (SPDT)
M
M
X
L
H
H
4
LOAD
L
1
3
M
M
M
L
2
N
7220
DPDT (DPST)
7200Z
7220 DPDT
M
X
1
4
L LOAD
N
7120 SPDT
M
2
LOAD
LOAD
LOAD
N
1
7300 3PST
M
M
WITH RESERVE POWER
7200L
40A
OTHER MOUNTINGS:
Intermatic® Adaptor Plate model #IAP
allows any 7100 and 7200 series (except
“L” models) to fit into an Intermatic case.
ORDERING INFO
Automatic ON/OFF control
when operation is required at
the same time every day, with
optional versatility of one to six
days omission.
CONTACT
RATING
VOLTAGE
5
N
2
2
X
LOAD
L
4
H
X
1LOAD
LOAD
LOAD
3
LOAD
LOAD
2
L
N
5
H
LOAD
N
L
1
3H
2
L
4
H
L
6
LOAD
LOAD
N
1
X
2
H
LOAD
5
N
4
X
LOAD
LOAD
LOAD
A
LOAD
B
N
H
FOR USE WITH 3 PHASE 4-WIRE
N
120/208V
SYSTEMS.
SPECIFICATION WRITER’S GUIDE
Furnish and install, where shown, a TORK time switch with 24 hour dial and day-omitting device. The time switch shall be powered by a self-starting synchronous
motor. Time switch contacts shall be capable of switching 40 amperes per pole continuously at 277 volts and shall be SPST (DPST, 3PST, DPST, SPDT, as required).
Removable ON/OFF trippers shall make possible automatic operation with a minimum ON period of 20 minutes and a minimum of 75 minutes between one OFF
period and the next. Enclosure shall be NEMA 1 surface type, finished in beige enamel, with combination 1⁄2”, 3⁄4” knockouts on bottom, both sides and back.
Provision shall be made for positive padlocking. Terminals shall be capable of receiving #8AWG wire. Time Switch shall be TORK Model 7_ _ _ (to fit requirement).
FOR RESERVE POWER (MODELS WITH SUFFIX “L”): Spring-driven reserve shall be provided sufficient to operate the time switch contacts at least 16 hours after
power failure. On restoration of power, time switch shall transfer to synchronous motor drive and automatically rewind reserve power unit.
TORK 34
Download