7000 SERIES CONTACT RATINGS SPECIFICATIONS WITH SKIP-A-DAY FEATURE RESERVE POWER OPTIONAL 24 HOUR TIME SWITCH TYPE INPUT VOLTAGE: 120 or 208-277 VAC 60 Hz varies by model. TERMINAL RANGE: #8 - #14 AWG. Resistive 120 -277VAC single phase 120 -277VAC single phase OPERATING TEMPERATURE: -40˚ to 165˚F (-40˚ to +74˚C). Tungsten 120VAC 40A Inductive 120, 277VAC single phase 20A Pilot Duty 120 -277VAC 1000VA Motor 120VAC 240VAC 2HP 5HP General Purpose TIMING ACCURACY: Line frequency. CALIFORNIA Title 24 APPLICATIONS ASHRAE 90.1 POWER CONSUMPTION: 3 watts, 5 watts for “L” models maximum. Lighting Heating Pumps Air conditioning Signs ENCLOSURE: Lockable hasp. Type varies by model (see page 153 for enclosure dimensions). NEW! FEATURES NEW! SCHEDULING: Minimum ON setting is 20 minutes with minimum OFF setting at 75 minutes. Dial accommodates up to 12 pairs of trippers. One pair included. SKIP-A-DAY: Omit operations on any day with a 7-spoke wheel marked with days of week. 3 omitting screws included. MANUAL OVERRIDE: Until the next regularly scheduled ON or OFF, automatic operation then resumes. OPTIONAL RESERVE POWER: “L” models keep dial on time up to 16 hours during power outage. ELECTROMECHANICAL CONTROLS TORK 33 CATALOG NO. UPC CODE INPUT SUPPLY (VAC) 60Hz OUTPUT CONTACTS 7100 10001 120 SPST 7102 10002 208-277 SPST 7200 11001 120 DPST 7200-O 10512 120 DPST 7202 11002 208-277 DPST 7202-O 10509 208-277 DPST 7300 7302 12001 12002 120 208-277 3PST 3PST 7120 13001 120 SPDT 7122 13002 208-277 SPDT 7220 14001 120 DPDT 7222 14002 208-277 DPDT ENCLOSURE TYPE Metal Indoor NEMA 1 Metal Indoor NEMA 1 Metal Indoor NEMA 1 Metal Indoor/Outdoor NEMA 3 Metal Indoor NEMA 1 Metal Indoor/Outdoor NEMA 3 Metal Indoor/Outdoor NEMA 3 Metal Indoor/Outdoor NEMA 3 Metal Indoor NEMA 1 Metal Indoor NEMA 1 Metal Indoor NEMA 1 Metal Indoor NEMA 1 Metal Indoor NEMA 1 Metal Indoor 7202L 19004 208-277 DPST NEMA 1 Metal Indoor/Outdoor 7300L 19005 120 3PST NEMA 3 Metal Indoor/Outdoor 7302L 19006 208-277 3PST NEMA 3 Metal Indoor 7120L 19007 120 SPDT NEMA 1 Metal Indoor 7220L 19009 120 DPDT NEMA 1 Metal Indoor 7222L 19011 208-277 DPDT NEMA 1 Replacement Order #P49 for a pair of ON/OFF per dial. Additional ON/OFF trippers per Trippers dial order #P47. 3 omitting screws #53005 supplied. Replacement #101 (120V) & #201 (208-277V). For "L" models #36 (120V) & #46 (208-277V). For Astronomic Conversion: Order #Z KIT for 7000 Series. Motor 19003 A DIVISION OF NSi INDUSTRIES, LLC USA • 800.321.5847 • www.nsiindustries.com 120 40A WIRING DIAGRAMS 7100 SPST 7200 DPST 7100 SPST M M M 7300 3PST 7200 DPST L L L 2 L H H N X L 1 2 LOAD H N H 7120 SPDT 2 X M X 1 L LOAD LOAD H N H 2 L 3 L L L 5 L 6 L DPST H 1 LOAD X L H A N LOAD B N 2 1 L H LOAD X LOAD A B N 2H H N H 1 L N 3 LOAD N 5 LOAD 6 LOAD LOAD LOAD 7302 3PST 7120Z (SPDT) M M X L H H 4 LOAD L 1 3 M M M L 2 N 7220 DPDT (DPST) 7200Z 7220 DPDT M X 1 4 L LOAD N 7120 SPDT M 2 LOAD LOAD LOAD N 1 7300 3PST M M WITH RESERVE POWER 7200L 40A OTHER MOUNTINGS: Intermatic® Adaptor Plate model #IAP allows any 7100 and 7200 series (except “L” models) to fit into an Intermatic case. ORDERING INFO Automatic ON/OFF control when operation is required at the same time every day, with optional versatility of one to six days omission. CONTACT RATING VOLTAGE 5 N 2 2 X LOAD L 4 H X 1LOAD LOAD LOAD 3 LOAD LOAD 2 L N 5 H LOAD N L 1 3H 2 L 4 H L 6 LOAD LOAD N 1 X 2 H LOAD 5 N 4 X LOAD LOAD LOAD A LOAD B N H FOR USE WITH 3 PHASE 4-WIRE N 120/208V SYSTEMS. SPECIFICATION WRITER’S GUIDE Furnish and install, where shown, a TORK time switch with 24 hour dial and day-omitting device. The time switch shall be powered by a self-starting synchronous motor. Time switch contacts shall be capable of switching 40 amperes per pole continuously at 277 volts and shall be SPST (DPST, 3PST, DPST, SPDT, as required). Removable ON/OFF trippers shall make possible automatic operation with a minimum ON period of 20 minutes and a minimum of 75 minutes between one OFF period and the next. Enclosure shall be NEMA 1 surface type, finished in beige enamel, with combination 1⁄2”, 3⁄4” knockouts on bottom, both sides and back. Provision shall be made for positive padlocking. Terminals shall be capable of receiving #8AWG wire. Time Switch shall be TORK Model 7_ _ _ (to fit requirement). FOR RESERVE POWER (MODELS WITH SUFFIX “L”): Spring-driven reserve shall be provided sufficient to operate the time switch contacts at least 16 hours after power failure. On restoration of power, time switch shall transfer to synchronous motor drive and automatically rewind reserve power unit. TORK 34