Day-2 Series Compensation & Other FACTS Controllers Arindam Ghosh Dept. of Electrical Engineering Indian Institute of Technology Kanpur, India E-mail: aghosh@iitk.ac.in Series Compensation of Transmission Systems A device that is connected in series with the transmission line is called a series compensator. In the analysis given below, we shall investigate the effect of the series compensator on • the voltage profile • the power-angle characteristics • the stability margin • the damping of power oscillations 82 Ideal Series Compensator • The ideal series compensator is represented by a voltage source that only supplies reactive power and no real power. • The location of the series compensator is not crucial, and it can be placed anywhere along the transmission line. 83 Voltage Profile • The series voltage must be injected in such a way that the series compensator does not absorb any real power in the steady state. The injected voltage is then ~ ~ µ j 90° VQ = λI S e where λ is a proportionality constant. • The ratio λ/X is called the compensation level. For example, we call the compensation level to be 50% when λ = X /2. 84 Voltage Profile Let us assume Then ~ ~ VS = V∠δ , VR = V∠0°. ~ IS = ~ ~ ~ VS − VR − VQ jX V∠δ − V = j( X µ λ ) The choice of sign of the injected voltage visà-vis that of the current plays an important role in the operation of the series compensator. 85 Mode of Operation ~ ~ − j 90° ~ V∠δ − V Case − 1 : VQ = λI S e ⇒ IS = j( X − λ ) The above choice corresponds to the voltage source acting as a pure capacitor. Hence we call this as the capacitive mode of operation. ~ ~ + j 90° ~ V∠δ − V Case − 2 : VQ = λI S e ⇒ IS = j( X + λ ) Since the voltage source in this case acts as a pure inductor, we call this as the inductive mode of operation. 86 An Example Consider a system with sending and receiving end voltages being 1∠30º and 1∠ 0º per unit respectively, X = 0.5 per unit and λ = 0.15 per unit. Let us assume that the series compensator operates in the capacitive mode. Then we have ~ I S = 1.479∠15° per unit ~ VQ = 0.2248∠ − 75° per unit 87 Example (Continued) The phasor diagram is given left. Let us now investigate the impact of the location compensator placement on the voltage profile. We shall denote the voltage on the left of the compensator by VQL and on the right of the compensator by VQR. 88 Case-1: Compensator in middle • The series compensator is placed in the middle. • The worst voltage sag occurs at each side of the series compensator where the voltage vector aligns with the current vector. 89 Case-2: Compensator before the infinite bus • • The series compensator is placed just before the infinite bus. • The maximum voltage rise occurs just before the compensator. The worst voltage sag still occurs where the voltage vector aligns with the current vector. 90 Power-Angle Curve The real and reactive powers at the sending and receiving end are given by V sin δ V (1 − cos δ ) PS + jQS = +j X µλ X µλ 2 2 V sin δ V (cos δ − 1) PR + jQR = +j X µλ X µλ 2 2 The real power flow is then V 2 sin δ Pe = PS = PR = X µλ 91 Power-Angle Curve 92 Reactive Power Since the injected voltage and line current are in quadrature, • the real power supplied by the compensator is zero. • the reactive power supplied by the compensator operating in the capacitive mode is ( ) 2λV ~ ~∗ (cos δ − 1) QQ = Im VQ I S = j 2 (X − λ ) 2 93 Reactive Power Both the real power transfer and the reactive injection requirement increase with the increase in the compensation level (λ/X). 94 Alternate Method of Voltage Injection • The series compensator injects a voltage that is in quadrature with the line current. • So far we have assumed that the injected voltage magnitude is proportional to the magnitude of the line current. • If we now relax the assumption, then the magnitude of the injected voltage is given by ~ I S µ j 90° ~ VQ = ~ e IS 95 Phasor Diagrams Capacitive Operation Inductive Operation Note that it is assumed that ~ ~ VR = V∠0°, VS = V∠δ 96 Expression for Power For the capacitive operation ~ ~ X I S = VQ + 2V sin (δ 2 ) For the inductive operation ~ ~ X I S = − VQ + 2V sin (δ 2 ) The power flow is then given by 2 V V ~ Pe = sin δ ± VQ cos(δ 2 ) X X 97 Power-Angle Curve 98 Series Compensator Modes of Operation With appropriate control, the series compensator operates in two modes: • Constant Reactance ~ ~ µ j 90° VQ = λI S e • Constant Voltage ~ I S µ j 90° ~ VQ = ~ e IS 99 Comparison Between the Modes of Operation • The two curves match at π/2. • The maximum power for constant voltage case occurs earlier than π/2. • The power transfer for constant voltage case for δ = 0 is greater than zero. 100 Comparison Between the Modes of Operation • The increase in line current in either case is monotonic. • However the rate of rise in the constant voltage mode is lower than constant reactance mode. • Constant voltage is the more desirable mode of operation 101 Power Flow Control and Power Swing Damping Let us consider an example to illustrate • the power flow control and • The power swing damping capabilities of ideal series compensator. The system contains • a double circuit transmission line • one of the two lines compensated by an ideal series compensator. 102 An Example ~ ~ VS = VR = 1.0 pu, X = 0.5 pu, δ 0 = 30° Constant reactance mode with λ = 0.15 pu Pe1 = 1.0 pu, Pe 2 = 1.43 pu, Pm 0 = 2.43 pu 103 Example (Continued) For any increase or decrease in the power flow, the series compensator can be controlled in one of the following two modes. • Regulating Control: Channeling the increase (or decrease) in power through line-1. In this case the series compensator holds the power flow over line-2 constant. • Tracking Control: Channeling the increase (or decrease) in power through line-2. In this case the series compensator helps in holding constant the power flow over line-1. 104 Example (Continued) • The input to the control system is the power flow over line-2 (Pe2). • Pe2 is compared with the reference value Pref and the error is passed through a PI controller. • In addition, a damping controller is also added to the feedback loop. • The output of the controller is the compensation level CI (=λ/X). d∆δ C I = K P Pref − Pe 2 + K I ∫ Pref − Pe 2 dt + C P dt The controller parameters are ( ) ( ) K P = 0.1, K I = 1 and C P = 75 105 Example: Regulating Control • The system is in the nominal steady state with Pm0 = 2.43 per unit. • The mechanical power input is suddenly raised by 10% (i.e., 0.243 per unit). • It is expected that the series compensator will hold the power through line-2 constant at Pe2 such that entire power increase is channeled through line-1. • We then expect that the power Pe1 will increase to 1.243 per unit and the load angle to go up to 0.67 rad. • The compensation level will then change to 13%. 106 Example: Regulating Control 107 Example: Tracking Control • • • • • The system is in the nominal steady state with Pm0 = 2.43 per unit. The mechanical power input is suddenly raised by 25% (i.e., 0.6 per unti). It is expected that the series compensator will make the entire power increase to flow through line-2. Then both Pe1 and load angle are maintained constant at their nominal values. The power, Pe2, through line-2 will then increase to about 2.04 per unit and the compensation level will change to 51%. 108 Example: Tracking Control 109 Practical Series Compensator • The series compensator structure assumed throughout this section is essentially that of a static synchronous series compensator or SSSC . Like in the case of STATCOM, the SSSC includes an SVS (supplied by a dc capacitor) and a coupling transformer. • A thyristor controlled series compensator or TCSC is an older thyristor and passive element based devices that controls the fundamental reactance. We shall discuss it first. 110 Thyristor Controlled Series Compensator (TCSC) Equivalent Circuit Voltage-Current Waveforms 111 TCSC - Circuit Equations The TCSC voltage and currents are combination of two piecewise linear models. Let the system state vector be xT = [vc iP]. Then when the thyristor is on 0 x&= 1 L 1 − 1 C x + i C L 0 0 112 TCSC - Circuit Equations Similarly when the thyristor is off 1 0 0 x&= x + C iL 0 0 0 The waveform of vC is a combination of the solution of these two state equations and therefore is not a smooth sinusoidal function. Therefore both the inductor current and capacitor voltage are the solutions of two piece-wise linear models. 113 TCSC - Fundamental Characteristics • A TCSC is a parallel combination of a fixed capacitor and a thyristor controlled reactor. • Therefore the steady state fundamental impedance of the TCSC is given by X TCSC X C X P (α ) = X C − X P (α ) • We can therefore see that by varying the conduction angle, the fundamental frequency reactance of the TCSC can be made inductive or capacitive. 114 TCSC - Fundamental Reactance The fundamental reactance of the TCSC is given by X TCSC = β1 ( X C + β 2 ) − β 4 β 5 − X C β1 = 2(π − α ) + sin 2(π − α ) π XC X P , β2 = , β3 = XC − X P XC XP 4 β 22 cos 2 (π − α ) β 4 = β 3 tan[β 3 (π − α )] − tan (π − α ), β 5 = π XP • α is the firing angle • XC and XP respectively are the reactances of the capacitor and parallel inductor. 115 TCSC - Fundamental Reactance Plot 116 TCSC - Fundamental Impedance Plots for Finite Q • • The fundamental reactance and resistance change with the quality factor of the coil. The above design curves can be used for characterizing the TCSC. 117 TCSC Waveforms for Finite Q Factor 118 TCSC Control A TCSC can be controlled in three modes. Blocking Mode: • The thyristors are not gated (i.e., the TCR is blocked). • The line current passes through the capacitor. • The TCSC performs the task of a fixed series capacitor. Bypass Mode: • The thyristors are gated for full conduction of inductor current. • The TCSC behaves as a parallel of fixed capacitor and inductor. 119 TCSC Control Bypass Mode (continued): • The capacitor voltage is less for a given line current. • Therefore this mode is utilized to reduce capacitor stress during faults. Vernier Control Mode: • The conducting angle of the TCSC is continuously varied to operate in either capacitive boost or inductive boost modes. • In this mode the TCSC follows the fundamental reactance curve shown earlier. 120 Static Synchronous Series Compensator (SSSC) • An SSSC contains an SVS and a coupling transformer that is connected in series with the line. • The SSSC is operated such that the injected voltage is almost in phase quadrature with the line current. 121 Equivalent Circuit of SSSC Compensated System • In the equivalent circuit of an SSSC compensated system, the SSSC is represented by a voltage source and impedance (Lr,Rr). • The SSSC is connected between buses 1 and 2. • The pair (L1,R) represent the line and L2 represents a transformer. 122 SSSC Control 123 SSSC Control • An instantaneous 3-phase set of line voltages at bus 1 is used to calculate the angle θ that is phase locked to the phase-a of the line voltage. • An instantaneous 3-phase set of measured line currents is first decomposed into real and reactive components. • The amplitude and the relative angle of the line current θir are then calculated. • The phase locked angle θp and θir are added to obtain the angle θl which is the angle of the line current. 124 SSSC Control • The are two control loops. • Since the SSSC voltage must lag the line current by 90º, a fixed angle equal to -90º is added to θl to obtain θfref in the main loop. • In the auxiliary loop, the reactance demand Xtref is added to Xr of SSSC. • The sum is multiplied by the magnitude of the line current and a constant to obtain Vdcref. • The error between Vdcref and the actual value of Vdc is passed through a PI controller to obtain θd. • This quantity is then added to θfref to obtain θf of the inverter. 125 SSSC Control • The PI controller retains the charge on the dc capacitor by injecting a voltage nearly in quadrature with the line current. • The real power exchange between the ac system and SSSC takes place if the injected voltage is not in quadrature with the line current, which either charges or discharges the dc capacitor. • The PI controller then advances or retards the phase of the injected voltage relative to line current in order to adjust the power at ac terminals and keep the dc voltage constant. 126 Comparison Between SSSC and TCSC 127 Comparison (Continued) 128 Comparison (Continued) 129 Other FACTS Controllers There are many other FACTS controllers that use the power electronic technology. We shall briefly discuss the following: • Interline Power Flow Controller (IPFC) • Thyristor Controlled Braking Resistor (TCBR) • Thyristor Controlled Phase Angle Regulator (TCPAR) • Unified Power Flow Controller (UPFC) 130 Interline Power Flow Controller (IPFC) An IPFC contains two or more SSSCs that are connected to a common dc bus to facilitate real power exchange between them. 131 IPFC (Continued) • Each individual SSSC can provide controllable series compensation to the line it is connected. • In addition, it can also exchange power between them. • Example: Assume that Line-1 is lightly loaded while Line-2 is heavily loaded. • SSSC-1 then absorbs power to charge the dc capacitor. • SSSC-2 is then supplied real power by the dc capacitor. • In this way the load sharing between the lines can be equalized. 132 Thyristor Controlled Braking Resistor This is a shunt connected thyristor switched resistor, which is used for minimizing the power acceleration during a fault. • In the schematic diagram, the thyristors are usually blocked. • They are switched on when a fault is detected. 133 Braking Resistor For the system shown above, the critical clearing angle is computed to be 52.24º. We shall now place a dynamic brake at the generator terminals. 134 Braking Resistor We assume that the braking resistor is pressed into service as soon as the fault occurs and is removed as soon as the fault is cleared. Then 2 ′ E ∗ Pe = Re (E ′∠δ )I ≈ 10 R { } 135 Braking Resistor It can be seen that the critical clearing angle increases with the increase in the value of the resistor. 136 Phase Angle Regulator (PAR) 137 PAR - Operation • • • The PAR is inserted between the sending end and transmission line. It is a sinusoidal voltage source with controllable amplitude. For an ideal PAR the angle of the phasor Vσ is stipulated to vary such that the magnitude of Vseff remains constant. 138 PAR - Power-Angle Curve 139 PAR - Phase Shifting Assume that a resistive load is connected at the output. 140 PAR - Phase Shifting The voltages obtained at the lower and upper taps are v1 and v2 respectively. • At the zero crossing of these voltages, the switch Sw1 is turned on. • At α the switch Sw2 is turned on. • This commutates the current of Sw1 by forcing a negative anode to cathode voltage across it, thereby making the voltage across the load v2. • The switch Sw2 turns off when the current through it reverses. 141 PAR - Phase Shifting The voltage thus obtained contains harmonics. The fundamental component of the voltage is given by ~ 2 2 −1 a V0 = a + b ∠ tan b ~ ~ ~ ~ V2 − V1 ~ V2 − V1 (cos 2α − 1), b = V1 + a= 2π 2π sin 2α π − α + 2 We can therefore vary the fundamental voltage by varying the delay angle α. 142 Unified Power Flow Controller (UPFC) A UPFC contains a shunt SVS and a series SVS that are connected to a common dc bus such that real power exchange can take place between them. 143 UPFC - Equivalent Circuit The term Ppq indicates real power exchange between the shunt and series branches. 144 UPFC - Phasor Diagrams (a) Voltage Regulation, (b) Line impedance compensation, (c) Phase shifting and (d) simultaneous control. 145 UPFC - Real & Reactive Power Let ~ ~ ~ VS = V∠0°, VR = V∠ − δ , V pq = V pq ∠ − ρ Then for the uncompensated system (Vpq = 0) we have 2 V sin δ P = P0 = X 2 V (cos δ − 1) QR = −Q0 = X 146 UPFC - Real & Reactive Power For the compensated system V − V∠ − δ + V pq ∠ − ρ P − jQR = V∠ − δ jX ∗ Solving we get P = P0 − VV pq QR = Q0 − sin (δ − ρ ) X VV pq X cos(δ − ρ ) 147 UPFC - Real & Reactive Power Then (P − P0 ) + (QR − Q0 ) 2 2 VV pq = X 2 • This is the equation of circle with its center at P0,Q0 and radius of VVpq/X. • Suppose V2/X = 1.0 and Vpq = 0.5V. • Then VVpq/X = 0.5. 148 Real Versus Reactive Power Even though the uncompensated system cannot transfer any power in this case, the UPFC is capable of transmitting power in either direction. 149 Real Versus Reactive Power 150 Real vs Reactive Power • The figures show that the UPFC has the unique capability to control independently the real and reactive power flow at any transmission angle. • It is however assumed here that the sending and receiving end voltages are provided by independent power systems which are able to supply and absorb real power without any internal angular change. • In practice the situation will be different depending on the change in load angle. 151