1 Rule # - Operation of controlled load contactor On/off status of the controlled load contactor (a) When the controlled load contactor is switched to the ‘on position’ [what happens?] (b) When the controlled load contactor is switched to the ‘off position’ [what happens?] Controlled load contactor actions (c) The controlled load contactor must be capable of the following actions when so instructed under one or more of the load control operations: (i) switch to the on position immediately; (ii) switch to the off position immediately; (iii) switch to the on position after a random delay, as described in Rule (d); (iv) [switch to the off position [after a random delay], as described in Rule (d);] [To discuss with M. Gill] (v) commence cycling after a random delay as described in rule (e) (vi) stop cycling. Switch time randomisation (d) When the instruction to the controlled load contactor is the switch to the on position after a random delay, the controlled load contactor will automatically switch to the: (i) (ii) on position at a time, randomly calculated by the meter using a uniform probability, which must fall within the minimum time delay setting and maximum time delay setting, where the required meter parameters are: (A) for the minimum time delay setting, 0 to 720 minutes, settable in one minute increments; and (B) for the maximum time delay setting, 0 to 720 minutes settable in one minute increments. off position at a time.... [see Rule 7.6.1.1.2]. [To discuss with M. Gill] Load cycling (e) When the instruction to the controlled load contactor is to commence cycling: (i) if the controlled load contactor is initially in the off position then, at the time randomly calculated by the meter using a uniform probability falling within the minimum time delay setting and maximum time delay setting, the controlled load contactor will switch to the on position and then cycle off at the cycle off time and cycle on at the File Name: Load Management Rule.doc 1 cycle on time until instructed to stop cycling or another instruction is effected; or (ii) if the controlled load contactor is initially in the on position then, at the time calculated by the meter using a uniform probability falling within the minimum time delay setting and maximum time delay setting, the controlled load contactor will switch to the off position and then cycle on at the cycle on time and cycle off at the cycle off time until instructed to stop cycling or another instruction is effected, where the required meter parameters are: (iii) for the minimum time delay setting, 0 to 120 minutes, settable in one minute increments; (iv) for the maximum time delay setting, 0 to 120 minutes settable in one minute increments; (v) for the cycle on time setting, 0 to 120 minutes settable in one minute increments; and (vi) for the cycle off time setting, 0 to 120 minutes settable in one minute increments. Controlled load contactor operations (f) The controlled load contactor must be capable of the following load control operations: Normal Load Control Schedules Operation (i) The meter shall be capable of recording two default day load control schedules each comprising a sequence of [up to] ten instructions, specifying for each instruction: (A) the required controlled load contactor action (as described in Rule # (c) above), and (B) the time in hours and minutes for effecting the required controlled load contactor action; so that a default day load control schedule may be set to apply for each day of the week. Alternative Load Control Schedule Operation (ii) The meter shall be capable of recording a special day load control schedule comprising [up to] ten instructions, specifying for each instruction: (A) the required controlled load contactor action (as described in Rule # (c) above), and (B) the time in hours and minutes for effecting the required controlled load contactor action so that a special day load control schedule may be set to apply for up to twelve dates during a year. File Name: Load Management Rule.doc 2 Priority Override Load Control Operation (iii) The meter shall be capable of receiving, locally and remotely, a priority override instruction, specifying: (A) the required controlled load contactor action (as described in Rule # (c) above); (B) the time in hours and minutes for effecting the required controlled load contactor action or that the required controlled load contactor action commence immediately; and (C) the duration of operation of the required controlled load contactor action from 1 to 1440 minutes, settable in 1 minute increments. (iv) The meter shall be capable of receiving, locally and remotely, a later priority override instruction, specifying those matters in paragraph (iii)(A), (B) and (C), which will replace the earlier priority override instruction. (v) The meter shall be capable of receiving, locally and remotely, an instruction to immediately cease the priority override controlled load contactor operation. (vi) When the priority override controlled load contactor operation ceases the default day load control schedule for that day [or special day load control schedule shall recommence] [(and where the next instruction in that schedule is either switch to the on position after a random delay or commence cycling after a random delay, following setting of a new random delay [to discuss with M. Gill – this should happen merely as an incidence of that action])]. Meter loss of supply load control operation (vii) If the meter loss of supply load control operation is enabled, locally or remotely, then the load controlled load contactor, if on, will automatically: (A) turn off upon detection of meter loss of supply; and (B) upon restoration of supply, return to the default day load control schedule [or special day load control schedule (and where the next instruction in that schedule is either switch to the on position after a random delay or commence cycling after a random delay, following setting of a new random delay [to discuss with M. Gill – this should happen merely as an incidence of that action]). Demand limit load control operation (viii) Where the demand limit load control operation is enabled, locally or remotely, then the controlled load contactor will, if on, automatically: (A) File Name: Load Management Rule.doc turn off if the average exported active energy demand across the last set X minutes if greater than the set demand limit (Y kW) during the period from the start observation setting to the stop observation setting; and 3 (B) remain turned off for the set P minutes, [and then does it return to the normal schedule – discuss with M Gill] where the required meter parameters are: (C) for the X setting, settable from 1 to 30 minutes in 1 minute increments; (D) for the Y setting, settable from 0.5 to 99 kW in 0.5 kW increments; (E) for the P setting, settable from 1 to 60 minutes in 1 minute increments; (F) for the start observation setting, the time in hours and minutes; and (G) for the stop observation setting, the time in hours and minutes. Boost load control operation (ix) Where the boost load control operation is enabled locally or remotely: (A) then the controlled load contactor shall automatically turn on for a set time, settable locally and remotely, from 1 to 6 hours in 30 minute increments when the customer presses a button located on the meter (unless this operation has been set to be disabled automatically by the activation of emergency supply capacity control and that control is activated – discuss with M Gill); and (B) [then return to the normal schedule – discuss with M Gill] , (C) it shall be possible, locally and remotely, to set the controlled load contactor to follow the instruction of this operation rather than following the instructions of the priority override load control operation and the demand limit load control operation Mains frequency monitoring load control operation (g) Subject to Rule A2, the controlled load contactor must be capable of a mains frequency monitoring load control operation. (h) If the mains frequency monitoring load control operation is enabled, locally or remotely, then the controlled load contactor will automatically: (i) turn off upon if mains frequency is below the set X Hz for more than the set U seconds; and (ii) return to the default day load control schedule or [special default day load control schedule] for that day [(and where the next instruction in that Schedule is either switch to the on position after a random delay or commence cycling after a random delay, following setting of a new random delay [to discuss with M. Gill – this should happen merely as an incidence of that action])] when mains frequency increases above the set X Hz for more than the set V minutes, File Name: Load Management Rule.doc 4 where the required meter parameters are: (iii) for the X setting: 49Hz to 50 Hz, settable in 0.1 Hz increments; (iv) for the U setting: 5 to 60 seconds, settable in 5 second increments; (v) for the V setting: 1 minute to 60 minutes, settable in 1 minute increments. Controlled load contactor operations hierarchy (i) If a controlled load contactor operation is inconsistent with another load control operation, the controlled load operation higher in the list will prevail over the other controlled load operation to the extent of that inconsistency: (i) Where enabled Meter Loss of Supply Load Control Operation (ii) Where enabled: Under Frequency Load Control Operation (iii) Where Boost Load Control Operation and Boost Primacy enabled: Boost (iv) Where enabled: Priority Override Load Control Operation (from Alternative Load Control Operation) [to discuss with M. Gill] (v) Where enabled: Demand Limit Load Control Operation (vi) Where Boost Load Control Operation enabled and Boost Primacy disabled: Boost (vii) Alternative Load Control Schedules Operation (viii) Normal Load Control Schedules Operation File Name: Load Management Rule.doc 5