Protection, control, and monitoring for the generator shall be

advertisement
File: M-6280A-Sugg-Spec.doc
M-6280A DIGITAL CAPACITOR BANK CONTROL
SUGGESTED SPECIFICATIONS
Pole-Top/Pad Mount Capacitor Bank Control, metering, and monitoring for the
Capacitor Bank shall be provided by a microprocessor-based package. The
microprocessor-based package shall be suitable for Pole Top Mounted or Pad
Mounted Capacitor Banks, as well as Single-Stage Substation Capacitor Banks
operating in Non-Series configurations. The control shall have the following
minimum functional and behavioral attributes:
CONTROL FUNCTIONS
The capacitor bank control shall include the following features and can be used for pole-mounted
or pad-mounted capacitor banks as well as non-series, single-stage, substation banks where
SCADA communications are desired.
LOCAL AUTOMATIC CONTROL MODE:
The Control shall have the following selectable Local Automatic Capacitor Control
Methods: Classic Voltage, Adaptive Voltage, VAr, and Current with settings appropriate
to the method selected.
Capacitor Control Local Automatic Overrides: Maximum / Minimum Voltage Limits,
Temperature, Time.
CLOSE and OPEN timers shall be provided with selectable Definite or Inverse Time
Delays and Instantaneous or Integrating Reset Characteristics.
Timer Types: Selectable as Integrating or Instant Reset
CLOSE and OPEN Output Pulse Duration adjustments shall be provided.
CLOSE and OPEN Warning Delays shall be provided.
A mandatory Re-Close Delay shall be provided to permit capacitors to discharge before
re-closing after a prior trip.
A minimum time-between-operations timer shall be provided that begins timing when any
operation completes and prevents the OPEN or CLOSE timer from beginning operation
due to an out-of band condition until the timer’s setting is reached.
LOCAL MANUAL MODE:
Local Manual Mode of cap bank operation shall be indicated on the front panel when switched
into Local/Manual by a technician or an operator, and shall not be able to be operated by remote
SCADA or other host computer to maintain the safety of the technician or operator. Locally, the
technician shall be able to CLOSE or OPEN the cap bank with all safety timers nondefeatable.
Delta Voltage calculations shall be enabled during Local/Manual operation to block a technician
command that would cause the Maximum or Minimum Voltage Limits to be violated.
Page 1 of 10
File: M-6280A-Sugg-Spec.doc
CAPACITOR BANK CONTROL OPERATION:
Control Operating Characteristic: The capacitor bank control operating characteristic shall be
configurable for voltage, VArs, or current. The control’s configurable operating characteristic shall
employ definite as well as inverse timing and provide an adjustable bandwidth to optimize bank
operation and eliminate unnecessary switching. The configurable operating characteristic shall
allow time and/or temperature overrides.
The voltage control mode shall include two standard modes of automatic operation:
Classic voltage control shall make its Open and Close switching decisions based on
measured Line Voltage conditions and Time and/or Temperature overrides when applied.
Voltage excursions beyond the set value for greater duration than the time-delay will
result in appropriate control operation.
Adaptive voltage control contains two control methods, Fixed or Average. The Fixed
method provides a bandcenter setting the control uses for comparison to measured
voltage to make its open or close capacitor bank switching decisions. The Average
method uses an Effective Bandcenter based on a long-term average of the input voltage
to compare to measure voltage to open or close the capacitor bank. Both methods
employ an inverse timer and bandwidth to optimize bank operation, eliminating
unnecessary switching, and allow application of Time and/or Temperature overrides.
SCADA REMOTE MANUAL CONTROL MODE:
SCADA Remote Manual Mode: Remote Manual Mode may be used by the IVVC algorithm
residing at the Master Control Center of the SCADA computer or other Host computer. The
control shall be capable of operating from SCADA signals received through wired or wireless
communications media to command bank switches for OPEN and CLOSE operations. The cap
bank control shall maintain an Overvoltage and Undervoltage Limit supervision to protect the
“never to exceed” voltages set as standard by the local Public Utilities Commission and SCADA
shall be allowed to make OPEN and CLOSE commands as necessary when operating within
those safety limits. The cap bank control shall provide a means to switch from Remote Mode to
Automatic Mode if communications fail and continue to operate autonomously until
communications are restored. The control shall provide contingency responses upon extended
loss of communications.
The capacitor bank control shall utilize a SCADA integrity monitor (SCADA Heartbeat) as well as
additional means to monitor the on board communications module for loss of its own operation.
Either failure or loss of communications from master or from slave shall trigger the cap bank to
switch to Automatic operation. After communications are restored for a specified length of time,
the cap bank control shall revert to SCADA Remote Manual Control Mode. This may be done
automatically after a time-delay or as directed by SCADA Master.
SCADA Remote Manual Mode - SCADA Heartbeat: A SCADA Heartbeat Remote Mode shall
be provided as a means for the SCADA system to place the unit in Remote Operation and
perform Raise and Lower operations as directed by a central control source. This mode shall
have a timer, and as long as the Remote Timer setting in the control is refreshed by the SCADA
system receiving a valid DNP 3.0 command, and before timing out, the control shall remain in
Remote Manual Operation. If the delay times out, the control shall revert to Local Automatic
Operation. The Local Automatic Operation shall switch back to Remote Manual Operation upon
receipt of a valid DNP 3.0 command via SCADA.
Page 2 of 10
File: M-6280A-Sugg-Spec.doc
SCADA REMOTE MANAGEMENT OF LOCAL AUTOMATIC CONTROL MODE:
SCADA Remote Management of Local Automatic Control Mode: The capacitor bank control
shall have the capability to allow Remote SCADA Management of Local Automatic Capacitor
Control. In this way, the Centralized Control can monitor cap bank controls allowing them to
operate autonomously and only controlling them directly when emergency situations arise.
Management via SCADA or other Host computer capable of operating through wired or wireless
communications media allows SCADA to effect control by either changing the local automatic
control settings via analog signal or, by sending binary commands for direct OPEN and CLOSE
operations. Sending analog settings to the control and letting it operate based on its new
marching orders instead of directing each open and close or raise and lower commands
considerably conserves bandwidth and thereby minimizes the communications burden and total
cost of operation.
The control shall provide a SCADA Test Mode that blocks the unit’s physical outputs, removes
the Re-Close delay, and prevents a Close operation for a minimum of five minutes after an
OPEN. The control LEDs, front panel, and remote status indications shall still indicate bank
operations as if the outputs were not blocked to allow user verification of settings, correct SCADA
communications point mapping, and operation.
The control shall provide a Re-Close Delay override to allow a CLOSE operation after an OPEN
operation without time-delay. This feature is used only when the bank switches are physically
disconnected from the capacitor banks to allow lab- and field-testing of the unit’s wiring and
switches.
INSTALLATION CONFIGURATION SETTINGS:
VT Ratio Correction: The control shall provide VT ratio correction.
Phase Shift Compensation: The control shall provide phase shift compensation correction when
in VAr or Current Control mode to correct for phase shifts normally encountered in line post
sensors, and when current information sources are located on phases other than the measured
voltage source.
Operations Counter: The control shall provide a software counter that increments by one count
per either a CLOSE or an OPEN operation.
Re-settable Operations Counter: The control shall provide a second software counter similar to
the operations counter that may be reset by the user.
COMMUNICATIONS
The communication ports shall provide access to all features, including metering, software
updates, and programming of all functions. This shall be accomplished using a modem or direct
serial connection from any PC-compatible personal computer running the control’s
Communications Software package or via SCADA communications software.
Communications Ports: Communication ports shall be optionally available in the following
forms:
 Ethernet 10/100 Mbps through a copper RJ-45 connection (100 Base-T)
 Ethernet 100Mbps Fiber Optic with ST connectors (100 Base-FX)
 Serial Ports with RS-485, ST or V-Pin Fiber Optics, or RS-232
Page 3 of 10
File: M-6280A-Sugg-Spec.doc
Protocols: The control shall support the following standard protocols: DNP3.0 and MODBUS.
The USB port shall utilize MODBUS for local interface communications. The Ethernet port
supports DNP 3.0, MODBUS, and IEC 61850 protocols over TCP/IP.
Advanced SCADA Communications:
True Ethernet
The control shall provide an integrated, true 10/100 Mbps Ethernet, auto negotiable, capable of
supporting up to eight concurrent sessions and simultaneous multiple protocols with up to eight
sockets (concurrent sessions) open at a time. The eight sockets shall be capable of supporting
Modbus and DNP over TCP/IP and up to five of the eight sockets shall be capable of supporting
DNP 3.0. This requirement allows users simultaneous remote access to the control via the same
physical Ethernet port to view/change settings or retrieve data, without affecting the SCADA
communications.
The control shall provide full DNP implementation to support both report-by-exception and
unsolicited reporting within DNP 3.0 to aid in the reduction of bandwidth requirements. The
control shall also provide DNP File Transfer to permit the recovery of data logs and triggered
events, oscillography, and device discovery to facilitate setting up the integrated system.
Full DNP Implementation
The control shall provide full DNP implementation to support both report-by-exception and
unsolicited reporting within DNP 3.0 to aid in the reduction of bandwidth requirements. The
control shall also provide DNP File Transfer to permit the recovery of data logs and triggered
events, oscillography, and device discovery to facilitate setting up the integrated system.
The control shall have DNP addressing capability that allows networking of multiple controls. The
DNP implementation shall support the pre-defined global addresses within DNP 3.0 and allow the
user to define two additional global addresses. Each control shall be able to be assigned a
Device Address, Feeder Address, and Substation Address ranging from 1 to 65519. The control
shall support broadcast commands from the master to all controls on the network in order to allow
some or all controls to act on one command at the same time. This capability reduces bandwidth
and is critical for rapid response to changing system requirements with settings changes in
multiple controls in selected zones. The control shall provide a configuration program that allows
any point to be mapped into any DNP location and allows dummy filler points to be added to
facilitate interoperability by replicating legacy vendor point-maps to SCADA. This program shall
also allow for individual point dead-banding and individual point assignments into Class 1, 2, or 3.
Cyber Security
Within DNP, the control shall permit multiple master source-address authentications, sourceaddress validation, and multilevel access codes logged with date and time, with DNP
authentication using FIPS 180-2 Secure Hash Standard (SHA-1). The control shall be fully
compliant and offer all settings and configuration as defined by the DNP3 user group and IEC
62351-5. The control shall have a 6-15 character password and an audit log that shows when
someone is logged on the control and which password was used to gain access to the control, in
compliance with NERC CIP standards. The control shall allow for storage of 30 unique passwords
within each control and have an SD card slot to allow the use of a password-keyed SD card that
the control automatically reads to allow user login.
The control’s design shall include the ability to disable ports and services not required for normal
or emergency operations. In cases where disabling is not possible, the port or service shall be
password and access level protected through a communication access security and timeout
feature in the communication software.
Page 4 of 10
File: M-6280A-Sugg-Spec.doc
The control enclosure shall have a door contact for intrusion detection (part of NERC CIP security
requirements) wired into a digital input to alarm SCADA when someone opens the door of the
control. This alarm triggers a SCADA signal to block the address temporarily.
Bluetooth®
The control shall have an option for Bluetooth® capability to enable wireless access to the control
that allows the user to configure the control, read status and metering values, as well as change
set points. A generic serial service shall be provided by the control’s Bluetooth® capability to
facilitate establishing initial communications should the Bluetooth® not automatically recognize
listed services.
MONITORING
Harmonic Analysis: The control shall measure, log, and display individual harmonics including
THD (total harmonics distortion) of the load voltage and load current up to the 31st harmonic.
The control shall include a trip and lockout function that operates when Voltage or Current THD
increases above its associated THD Trip Pickup Setting for the period of the THD Trip TimeDelay setting. If THD is still present and rising above the THD Trip Pickup Setting after the trip
occurs, the lockout will remain in effect until THD decreases below a Voltage or Current THD
Lockout Reset setting for the duration of the THD Lockout Reset-Delay setting. This indicates that
the capacitor bank was resonating as part of the system L/C circuit and has the potential, if it
resonates for a long enough time, to explode
If the Voltage or Current THD levels that caused the trip drop immediately (within 1 second)
below the THD Trip Pickup Setting when the bank trips, then the Lockout shall remain in effect
only for the duration of a THD Lockout Reset-Delay setting. This case indicates that the capacitor
bank was actually part of the L/C system circuit and functioning as the filter, partially sinking the
harmonics.
The control shall have an internal counter that increments each time the following sequence
occurs:
1. A Voltage or Current THD Measurement exceeds its associated THD Trip pickup setting
for the duration of the THD Trip Time-Delay
2. The control trips the bank and locks out
3. The Voltage or Current THD measurement drops below the THD Lockout Reset Setting
as soon as the Trip occurs (within one second)
4. The THD Lockout Reset-Delay times out and the Lockout resets
The control’s design shall have a Maximum THD Lockout/Reset Operations setting that
determines the maximum number of Trip and Lockout/Reset Operations allowed within a period
of time specified by a Maximum Time for THD Lockout/Reset Operations before the control will
permanently lockout and require a user reset, either locally or remotely, to continue operation.
Settings Profiles and Triggers – the control shall provide up to eight settings profiles
programmable in the control that can be initiated based on Time, Temperature, Loss of
Communications, Reverse Power, or from SCADA. This feature shall allow the user the flexibility
to customize the operation of the control based on many different operational factors while
minimizing communications bandwidth. It shall also assist in maintaining local intelligence at the
device level in the event of either a loss of communications or with systems designed to operate
without communications.
Page 5 of 10
File: M-6280A-Sugg-Spec.doc
Alarms: The alarm relay shall be user-programmable with a non-latching output contact that
closes on one or more of the following conditions:
●Maximum Voltage Limit
●Minimum Voltage Limit
●Remote Undervoltage Limit
●Phase Overcurrent*
●Resettable Counter Limit
●Daily Operation Counter Limit
●Power Factor – Leading/Lagging
●Bank/Switch Failed - Level 1
●VAr – Leading/Lagging
●Bank/Switch Failed - Level 2
●Comm Block or Self-Test*
*Only available with VAr and Current Control Mode option
●Remote Manual
●Remote Overvoltage
●Voltage Harmonics
●Delta Voltage Alarm
● Current Harmonics*
Limit
Oscillographic Recorder: The control shall have a built-in Oscillographic Recorder that
continuously records voltage and current waveform data in a buffered memory. This memory
shall be configurable from 1 to 16 partitions. A snapshot of waveform data from 235 to 2,000
cycles shall be captured when triggered. The captured data shall be specified from 5% to 95%
post-trigger event. The remainder of the percentage shall be pre-trigger data (samples per cycle
shall be selectable as 16, 32, or 64 samples/cycle). Trigger Events include:
●Close Command
●Open Command
●Minimum Voltage Limit
●Remote Overvoltage Limit
●Bank/Switch Failed - Level 2
●Bank/Switch Failed - Level
●Voltage Harmonics
●Current Harmonics*
●Delta Voltage Alarm
●Phase Overcurrent*
*Only available with VAr and Current Control Mode option
1
●Maximum Voltage Limit
●Remote Undervoltage Limit
●CBEMA 1 Through 4
●SCADA HeartBeat
(with DNP3.0 only)
Data Logging: Data logging shall be provided that continually records data in non-volatile
memory. Data logging will continue indefinitely as long as the data interval is set to a non-zero
value. Data to be retrieved:
●Voltage
●Primary Voltage
●Adaptive
●Primary Neutral Current
●Operation Counter
●Resettable Counter
●Temperature
●Primary Phase Current*
●Primary Watts*
●Primary VArs*
*Only available with VAr and Current Control Mode option
●Delta Voltage
●Frequency
●Capacitor Bank
●Power Factor*
●Primary VA*
Status
Sequence Of Events (SOE): The Sequence of Events recorder shall be provided for
comprehensive data recording (of voltage, current, frequency, etc.). It shall be possible to
download Sequence of Events data to an SD Card, or a PC running the control’s communications
software. The control’s SOE shall be capable of storing up to 129 events in a first in/first out
memory scheme. The SOE shall be triggered by the status change of any of the following signals:
●Close Command
●Open Command
●Minimum Voltage Limit
●Remote Overvoltage Limit
●Bank/Switch Failed - Level 2
●Bank/Switch Failed - Level
●Voltage Harmonics
●Current Harmonics*
●Delta Voltage Alarm
●Phase Overcurrent*
*Only available with VAr and Current Control Mode option
Page 6 of 10
1
●Maximum Voltage Limit
●Remote Undervoltage Limit
●CBEMA 1 Through 4
●SCADA HeartBeat
with DNP3.0 only)
File: M-6280A-Sugg-Spec.doc
Computer Business Equipment and Manufacturers Association (CBEMA) Sag & Swell
Recorder: The control shall sample the input signals 64 times per cycle to allow for the detection
of sags and swells. Magnitude and duration shall be defined by the user (CBEMA events) for up
to four different levels. There shall be a counter for each level that increments the total number of
sags/swells as well as DNP points to alarm and report the duration, in cycles, of each sag/swell.
The control shall also capture and record the waveforms with oscillography during the sag/swell.
These sag/swell channels may be configured to aid in the reporting of Customer Average
Interruption Duration Index (CAIDI), System Average Interruption Duration Index (SAIDI),
Momentary Average Interruption Frequency Index (MAIFI), and Average Service Availability
Index (ASAI) numbers.
INPUTS
The control shall have the following inputs:
Control Voltage Input: The nominal control voltage input shall be 120 VAC, 60 Hz. The control
shall operate properly from 90 VAC to 140 VAC. At 60 Hz, the operating system frequency range
shall be from 55 to 65 Hz. The burden imposed on the input shall be 8 VA or less. The unit shall
be powered from a voltage transformer located at the bank. The control shall be capable of
withstanding twice the voltage input for one second and four times the voltage input for one cycle.
Line Current Input: Line current input shall be provided to the control from a 5A CT for operation
as a VAr or Current Control. The burden imposed on the current source shall be 0.03 VA or less.
An optional input configuration for phase current shall be available for Line Post Current Sensors
adjustable for various manufacturers.
Neutral Unbalance Current Input: Neutral Current Unbalance Detection shall be provided to
detect bank capacitor can, fuse or switch failures as well as CLOSED or OPEN bank status. This
shall be accomplished by measuring the magnitude of unbalance current in the bank’s neutral
line. Three optional input configurations for inputting this current into the control shall be
available: 200 mA CT input, 5 A CT Input, Line Post Current Sensor. The control shall also have
contingency operations and actions that can be taken upon detection of neutral current. The
controls shall allow a programmable number of retries and shall have a lockout and a reset to
block operation or allow operation to start again after the reset.
Switch Status Inputs: The control shall have three inputs for connection to the auxiliary switch
status contacts supplied with each phase of the capacitor switches to permit detection of
individual phase switch operation.
OUTPUTS
The control shall have the following outputs:
CLOSE Output: The CLOSE output signal shall be capable of switching 10 A for 30 seconds or
45 A for 100 ms.
OPEN Output: The OPEN output signal shall be capable of switching 10 A for 30 seconds or 45
A for 100 ms.
The CLOSE and OPEN outputs shall have two modes of operation for the intended switch type.
The first shall be a pulsed mode of operation, adjustable from 50 to 100 ms in duration, for use
with solenoid driven switches. The second shall be a pulsed mode of operation, adjustable from 5
to 15 seconds in duration for use with motor driven switches.
User-Programmable Alarm Output: The control shall have one (1) Form “CLOSED” contact
capable of switching 6 A at 150 VAC or 200 mA at 125 Vdc.
Page 7 of 10
File: M-6280A-Sugg-Spec.doc
FRONT PANEL HUMAN MACHINE INTERFACE (HMI)
The control shall have menu-driven access to all functions by way of navigational pushbuttons
and an alphanumeric display. There shall be two programmable password levels available to
provide limited or more complete access to the control functions. One of the HMI navigation
buttons shall allow user to instantly (with a single push) retrieve important metering data in any
order the user would like to see it displayed. The data shall also scroll at a configurable rate.
Display: The control shall have at a minimum a 2-line by 20-character LCD display for enhanced
viewing in direct sunlight. The control shall also offer a low-level LED backlight for reading in
darker environments.
Smart Flash SD Card Slot: The control shall have an SD Card slot that allows the user to
perform the following functions without the need for a laptop:
●Load Set Points
●Load DNP Configuration
●Save DNP Configuration
●Save Wake Screen Data
●Multi-user Password File
●SD Card User Access (Physical
●Save Set Points
●Clone Save
● Save Sequence of Events
● Save Oscillographic Records
●Password Access Log
Security Key)
●Save Data Log
●Clone Load
●Save Metering Data
●Firmware Update
●DNP Map Files
●Quick Capture
LED Indicators: The control shall have the following LED Indicators on the front panel:
REMOTE/AUTO, LOCAL/MANUAL, ALARM, NEUTRAL UNBALANCE, CLOSE, OPEN, CPU
OK, RSSI and TX (Transmit) and RX (Receive).
Switches: The control shall have the following switches on the front panel:



The control shall have a momentary toggle switch for initiating CLOSE and OPEN
operations when in the Manual Mode of Operation
The control shall have a 3-position switch for hardwired Voltage Source Selection of
INTERNAL, EXTERNAL (Front Panel Jacks), or OFF
The control shall have a 2-position switch for “Remote/Auto” or “Local/Manual” operation
Terminals: The control shall have front panel binding posts for External Power, Common, and
Meter Out (voltage).
TESTS AND STANDARDS
Voltage Measurement Accuracy
The control shall have a voltage measuring accuracy of + 0.3 % when tested over a temperature
range of – 40° C to + 85° C.
The control shall comply with the following type tests and standards:
Voltage Withstand
Dielectric Withstand
IEC 60255-5: 1,500 VAC for 1 minute applied to each independent circuit to earth; 1,500 VACc
for 1 minute applied between each independent circuit.
Impulse Voltage
IEC 60255-5 -2000: 5,000 V pk, +/- polarity applied to each independent circuit to earth; 5,000 V
pk, +/- polarity applied between each independent circuit 1.2 by 50 s, 500 Ω impedance, three
surges at 1 every 5 seconds IEC 60255-5 > 100 MΩ.
Page 8 of 10
File: M-6280A-Sugg-Spec.doc
Electrical Environment
Electrostatic Discharge Test
IEC 60255-22-2-2008: Class 4 (±8 kV)—point contact discharge
IEC 60255-22-2-2008: Class 4 (±15kV)–air discharge
Fast Transient Disturbance Test
IEC 60255-22-4-2008: Class A (±4 kV, 5 kHz)
Surge Withstand Capability
 ANSI/IEEE® 2,500 V pk-pk oscillatory applied to each independent circuit to earth
 C37.90.1- 2,500 V pk-pk oscillatory; applied between each independent circuit
 1989 5,000 V pk Fast Transient applied to each independent circuit to earth
 5,000 V pk Fast Transient applied between each independent circuit
 ANSI/IEEE 2,500 V pk-pk oscillatory applied to each independent circuit to earth
 C37.90.1- 2,500 V pk-pk oscillatory; applied between each independent circuit
 2002 4,000 V pk Fast Transient burst applied to each independent circuit to earth
 4,000 V pk Fast Transient burst applied between each independent circuit
NOTE: The signal shall be applied to the digital data circuits (RS-232, RS-485, Ethernet
communication port coupling port) through capacitive coupling clamp.
Surge Immunity
IEC 60255-22-5 2,000 V pk, ± polarity applied, 1.2 s by 50 s, five surges, 1 every 5 seconds
Radiated Electromagnetic Withstand Capability


IEC 60255-22-2 2007 Radiated RFI Immunity
IEC 60255-22-6-2001 Conducted RFI Immunity
All units shall be protected against electromagnetic radiated interference from portable
communications transceivers.
Atmospheric Environment
Temperature: Control shall operate from – 40° C to +85° C




IEC® 60068-2-1 Cold, – 40° C
IEC 60068-2-2 Dry Heat, + 85° C
IEC 60068-2-78 Damp Heat, + 40° C @ 95% RH
IEC 60068-2-30 Damp Heat Condensation Cycle, 25° C, + 55° C @ 95% RH
Page 9 of 10
File: M-6280A-Sugg-Spec.doc
Mechanical Environment
The control shall meet the following mechanical environmental specifications:
Vibration
IEC 60255-21-1
Vibration response Class 1, 0.5 g
Vibration endurance Class 1, 1.0 g
IEC 60255-21-2
Shock Response Class 1, 5g
Shock Response Class 1, 15g
Bump Endurance Class 1, 10g
Cyber Security Compliance
The control’s design shall be in compliance with the following Cyber Security standards:
IEC 62351-1
Data and Communications Security - Part 1: Introduction
IEC 62351-2
Data and Communications Security - Part 2: Glossary
IEC 62351-3
Data and Communications Security - Part 3: Communication Network and
PSystem Security- Profiles Including TCP/IP
IEC 62351-5
Data and Communications Security - Part 5: Security for IEC 60870-5 and
derivatives
ISO/IEC 9798-4 Information Technology- Security techniques- Entity authentication - Part 4:
Mechanisms using cryptographic check function
RFC 2104
HMAC: Keyed - Hashing for Message Authentication
RFC 3174
Secure Hash Algorithm (SHA-1)
FIPS 186-2
Digital Signature Standard (DSS), USA NIST, February 2000 Including Change
Notice #1, October 2001. Only the random number generation algorithms in the
appendix are used.
RFC 3394
Advanced Encryption Standard (AES) Key Wrap Algorithm
FIPS 180-2
Secure Hash Standard (includes SHA-1, SHA-224, SHA-256, SHA-334 and
SHA-512)
RFC 3629
UTF-8 a transformation format of ISO 10646
cULus-Listed per 508 – Industrial Control Equipment
Industrial Control Equipment Certified for Canada CAN/CSA C22.2 No. 14-M91
cULus-Listed Component per 508A Table SA1.1 Industrial Control Panels
Page 10 of 10
Download