GAC 3.0 Tuning and Adjustment Manual 1-2-3500-951-00 REV B 15 August 2014 Please check with the factory for the latest version of this Manual, *Subject to change without notice* Table of Contents 1. Guide to Adjustment - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3 1.1 Equipment and Tools Required - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3 1.2 Mirror Attachment- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3 1.3 Scan Angle Adjustment - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3 1.4 Cautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4 2. Description and Location of Potentiometers, Jumper Configuration - - - - - - - - - - - - - - - - - - 5 2.1 Potentiometer Description - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5 2.2 Jumper Configuration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5 3. Initial Setting of Potentiometers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6 4. Fine Tuning- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -12 4.1 Example of Adjusted Waveforms - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 12 4.1.1 Small Angle Step Response - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -12 4.1.2 Full Field Large Angle Step Response - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -13 4.2 Waveform change for each Potentiometer adjustment - - - - - - - - - - - - - - - - - - - - - - - - 13 4.2.1 SRL - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 13 4.2.2 EG - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 14 4.2.3 SG - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - 16 4.2.4 EL - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 17 4.2.5 LFD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 19 4.2.6 HFZ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -20 4.2.7 HFD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 21 4.2.8 NF - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 23 5. Adjustment of Input Position Command Scan Angle Scale - - - - - - - - - - - - - - - - - - - - - - - - 24 2 1. Guide to Adjustment Every Galvo/Controller pair is tuned at Lincoln Laser to provide reasonable, stable performance. While faster performance may be obtained it may come at the cost of stability. Lincoln Laser strongly recommends only those familiar with galvanometer tuning attempt the steps in this manual. Caution: Galvanometers and Controllers MUST be operated at the same voltage used to perform the factory tuning or damage may result to the Motor and/or the Controller. Galvanometers and Controllers are tuned as a matched pair, failure to operate as a pair may result in damage to the Motor and/or Controller. Tuning voltage and paired serial numbers can be found on the Galvanometer Final Inspection Data Sheet 1.1 Equipment and Tools Required: For purposes of this manual a ± 24 VDC linear power supply rated at 6 amps (rms) was used a. Power Supply: Tuning should be performed with the ± voltage rating with which the system is intended to operate. Lincoln Laser recommends the use of linear power supplies where possible due to their typically large output capacitance and lack of switching noise. Minimum current rating of 3 amps (rms), capable of supplying short term (mSec) peaks up to 8 amps. A power supply of insufficient current capacity will inhibit system performance b. Oscilloscope: 3 channels minimum It will be necessary during the tuning of the system to observe: 1. Commanded Position (Input Signal) 2. Motor Response (PSD Signal) 3. Motor Current c. Function Generator: to supply Position Command Input for Amplitude, Notch Filter and Step Response adjustments. d. Flat blade screwdriver for potentiometer adjustment. 1.2 Mirror Attachment: CAUTION Prior to attaching, removing or adjusting the mirror, verify the Power Supply is switched OFF. 1. Fully seat the mirror onto the shaft 2. Tighten the clamping screws such that the gap on each side of the clamp is equal. 3. A loose mirror will result in system instability which could result in mirror, galvo or controller damage. 1.3 Scan Angle Adjustment: Section 5 describes one method to perform the Scan Angle Adjustment to the Position Command Voltage using a PSD (Position Sensitive Detector) and +θ table (please refer to p. 24). The adjustment can be made using other methods; however the method in Section 5 offers very high accuracy. 3 1.4 Cautions: 1. When an oscillation or an audible resonance sound is perceived during operation, an imbalance between the center frequency of the notch filter and resonance frequency may be the cause. Please refer to the adjustment of NF in section 4 to reduce or eliminate the oscillation The scanner motor must be securely mounted for operation as well as adjustment – ideally the scanner is adjusted in the mount in which it will be used for normal operation. The scanner mount and servo heat sink should supply sufficient heat sinking for both pieces to adequately dissipate enough heat to ensure operation within their thermal limits. The scanner housing temperature should never exceed 50° C even for short durations or there is the possibility of permanent damage to the galvanometer motor. 2. Avoid any external vibration or impact to the scanner. 3. If the Gain setting is too high during adjustment, uncontrolled oscillations may occur. In such a condition, immediately reduce Gain (SG) to eliminate the condition. The scanner and driver will overheat if extended operation during an uncontrolled oscillation is permitted. Although the thermal protection circuit of the servo driver will attempt to protect the galvanometer scanner, a prolonged uncontrolled oscillation condition may overheat the servo and scanner causing permanent damage to both. If the uncontrolled oscillation condition can not be immediately corrected then turn off the power supply, restore all adjustments to their previous states and carefully attempt the tuning again. When the thermal protection function is activated, the driver disables supply power and the output to the motor internally. Turn off the power supply, make the required adjustments to eliminate or reduce the uncontrolled oscillations, then wait until the heat sink temperature drops sufficiently (cool to the touch) before turning on the power again. 4 2. Description and Location of Potentiometers, Jumper Configuration 2.1 Potentiometer Description Potentiometer PS SRL EG SG EL LFD HFZ HFD NF PF LIN Description Position Command Input Scale Position Command Slew Rate Limiter Position Deviation Amplifier Gain (Error) Position Signal Proportional Gain Error Limiter Position Signal Derivative Gain Frequency Band of the Current Integral Feedback Signal Current Integral Gain Notch Filter Center Frequency Position Signal Scale Linearity Compensation 2.2 Jumper Configuration. Control P control P I control J1 2-3 1-2 J2 open short J3 open open J4 1-2 2-3 J5 open short J6 open open J7 short short CN5 J7 1234 4 3 2 1 CN4 CN1 J2 5 4 3 2 1 CN3 CN6 J1 2 1 CN7 J3 321 J4 2 1 CN2 123 J8 J6 J5 PS SRL EG SG EL LFD HFZ HFD NF PF LIN Fig. 1 Potentiometer and Jumper Location 5 J8 short short 3. Initial Setting of Potentiometers Perform this step when other attempts to correct an uncontrolled oscillation condition have failed. *Refer To Figure 1 for Potentiometer Locations* a. Verify power supply is switched off and scanner is disabled (CN3-4 Open) b. Set Function Generator to provide a 10HZ, 100mVP-P, Square Wave output. c. Monitor the following signals on an oscilloscope. CN3-3 may be used as GND reference 1. Position Command Input CN3-1 2. Motor Position Output CN5-1 3. Motor Current CN5-2 4. Refer to Figure 2 for other circuit connections. d. Initial Potentiometer Settings: These are 12 turn potentiometers. These settings are initial reference settings, actual settings may vary depending on scanner model, load and application. SRL EG SG EL LFD HFZ HFD NF *PF *LIN : : : : : : : : : : 4 turns in CCW direction from full CW Full CCW 7 turns in CW direction from full CCW 5 turns in CW direction from full CCW 7 turns in CW direction from full CCW 7 turns in CW direction from full CCW 7 turns in CW direction from full CCW 7 turns in CW direction from full CCW --------------------------------- (Used only when PI control is used) (Used only when PI control is used) (Used only when P control is used) * For PF and LIN, adjustment should be performed per Section 5 (or equivalent) otherwise we recommend not re-adjusting the potentiometers from the original factory adjustment. 6 Power input Galvanometers - GVD‐Series + GND * CN4 For Motor Drive CN5 1234 N.C. After connecting, Servo ON Position Command Input 4 3 2 CN1 1 CN6 CN7 2 1 5 4 3 CN3 2 1 2 1 CN2 For Position Sensor GND * CN4 is not used for PHX 030,050,075 Position Signal Output Scanner Current Output Fig. 2 Position Signal Output (CN5-1) is ½ the voltage scale of Position Command Input (CN3-1). If you need to have the same voltage scale, prepare a circuit per Fig.3. Position Signal Output waveforms shown in this manual are from the circuit shown in Fig.3. 10kΩ 20kΩ CN7 -1 Position Input 10kΩ CN5 -1 CN6 -2 GND CH2 Position Output GND CN7 -2 Fig. 3: Example of Differential Amplification Circuit 3.1 Tuning 3.1.1 Verify CN3-4 is OPEN 3.1.2 Potentiometers set per Step d. 3.1.3 Turn on Power Supply 7 3.1.4 After confirming the amplitude and frequency of the Position Input Command from the Function Generator, enable the servo loop by connecting CN3-4 to GND. 3.1.5 Proceed to tune the system for Small Angle Step Response per the following steps EG should be full CCW so scanner does not move at all. If a malfunction such as an abnormal oscillation is observed, please turn off the power supply and verify the Potentiometers are at their initial settings. If the oscillation is still present adjust the Notch Filter per Section 4.2.8 Fig. 4 8 Slowly turn EG in the CW direction, the rotor shaft should begin to follow the Input Command Waveform. This will be indicated by the Output Position and Motor Current Waveforms. Fig.5 Continue to slowly turn EG in the CW direction. Overshoot (under damping) of scan position may be observed when EG is turned in CW direction. A small amount of overshoot is desired at this point in the tuning process. Fig.6 9 To reduce the overshoot observed in Fig. 6, adjust SG, LFD, HFD and HFZ either CW or CCW to obtain desired result Fig.7 Fig. 7 10 3.1.6 After adjusting Small Angle Step response to resemble the waveform as shown in Fig. 7, slowly increase the Input Command Waveform square wave to an amplitude of ±10VP-P at 10 HZ . SRL (Slew Rate Limit) when turned in the CCW Direction will increase the response speed. Slew Rate should be adjusted for the fastest speed possible consistent with stable operation. Adjust EG, SG, LFD, HFD and HFZ either CW or CCW to obtain desired result. Fig. 8 Rough Tuning is completed when the waveforms are as shown in Fig. 9. Fig. 9 11 4. Fine Tuning Slowly adjust each potentiometer as desired while monitoring the Output Position and Motor Current Waveforms to match the waveforms shown in this manual 4.1 Example of Adjusted Waveforms: * The following waveform examples are for a specific motor/load combination. Your results may vary slightly, but should still closely resemble the depicted waveforms. 4.1.1 Small Angle Step Response: Input Position Command of ±100 mVP-P, 10Hz square wave with Position Output Signal Small Angle Step Response and Motor Current. Sample waveform: Fig. 10 12 4.1.2 Full Field Large Angle Step Response: Input Position command of ±10 VP-P, 10Hz square wave with Position Output Signal, Large Angle Step Response and Motor Current. Fig.11 4.2 Waveform change for each potentiometer adjustment Based on the waveform examples when adjusted to the Initial Potentiometer Settings, the charts below represent the waveform changes of each potentiometer when the potentiometers are turned in CW and CCW directions. 4.2.1 SRL Input Position Command of ±10 VP-P, 10Hz square wave Turning in CCW direction SRL is used to reduce the large angle speed. Fig. 12 13 Turning in CW direction SRL is used to increase the large angle speed. Fig. 13 4.2.2 EG Input Position Command of ±100 mVP-P, 10Hz square wave Fig. 14 14 Turning in CCW direction Rising edge and scanning speed are slow. (Over damped) Fig. 15 Turning in CW direction Rising and scanning speed are fast. (Under damped resulting in Overshoot) Fig. 16 . 15 4.2.3 SG Input Position Command of ±100 mVP-P, 10Hz square wave Fig. 17 Turning in CCW direction Fig. 18 16 Turning in CW direction Fig. 19 4.2.4 EL Input Position Command of ± 1.0 VP-P, 10Hz square wave Fig. 20 17 Turning in CCW direction SRL is used to reduce the large angle speed. Fig. 21 Turning in CW direction SRL is used to increase the large angle speed. Fig. 22 18 4.2.5 LFD Input Position Command of ±100 mVP-P, 10Hz square wave Fig. 23 Turning in CCW direction The damping of scan position signal is reduced. Oscillation occurs easily if it is turned excessively in CCW direction Fig. 24 Turning in CW direction The damping of scan position signal is increased. Fig. 25 19 4.2.6 HFZ Input Position Command of ±100m VP-P, 10Hz square wave Fig. 26 Turning in CCW direction Over damped. Fig. 27 20 Turning in CW direction Under damped. Fig. 28 4.2.7 HFD Input Position Command of ±100 mVP-P, 10Hz square wave Fig.29 21 Turning in CCW direction The damping of scan position signal is reduced. Oscillation occurs easily if it is turned excessively in CCW direction. Fig. 30 Turning in CW direction The damping of scan position signal is increased. Fig. 31 22 4.2.8 NF Input Position Command ±50 mVP-P, sine wave 5kHZ to 30kHz NF adjusts the center frequency of the Notch Filter circuit to reduce the effects of shaft/load resonance frequencies. Slight oscillations may appear over the entire waveform if the adjustment is not performed properly. Fig.32 4.2.8.1 Set the Input Position Command of the function generator to a sine wave of ± 50 mVP-P and Target frequency (the first torsional resonant frequency of the galvanometer scanner and mirror). 4.2.8.2 Adjust the function generator in 100 Hz increments; tune NF to obtain the least visible p-p voltage on the Position Output and Motor Current waveforms. This should also correspond to a decrease in the audible noise from the scanner. Resonant frequency will depend on the scanner type and mirror size. When NF is adjusted properly, the p-p voltage near the resonant frequency as shown on channel 2 shall be less than 10mV. 23 5. Adjustment of Input Position Command Scan Angle Scale 1) Adjustment preparation Adjustment of the Scan Angle scale is performed optically by using the adjustment tools as shown in Fig. 33. Fig. 33 Fixture for Scan Angle Adjustment 2) Position Command Input Input 0 VDC as the Position Command signal and then turn on power to the driver. Enable the servo by connecting CN3-4 to GND. 3) Initial Positioning Set the angle of θ table to be 0°. Mechanically adjust the scanner so that the light of the laser hits at the center of PSD (Position Sensitive Detector) and for the Position Output Voltage to indicate zero. 4) Input of Position Command (Full Scale) Input +10 VDC as Position Command Signal. The mirror moves in accordance with the change of voltage and the reflected beam will move off the active area of the PSD. 24 5) θ Table Angle Adjustment Rotate the scanner by turning the θ table to the desired full scale scanning angle. (The direction of rotation of the θ table is opposite to the moving direction of mirror. 6) Angle Adjustment After the θ table is set to the target angle the laser should fall onto the PSD. Adjust PF so that the position output voltage of the PSD is zero degrees. 25