SensaModular - Thorn Lighting

advertisement
SensaModular
Simple, cost effective and easy to
install for single-room lighting control
Introduction
Thorn’s Indoor Lighting Controls portfolio is
grouped into three distinct usage types
1
2
1. SensaLite features Thorn luminaires
with built-in sensors and remote sensors,
offering standard presence detection,
daylight-linking and infra-red control.
SensaLite is the first step to comfort and
energy saving, and is used for small
office applications, simple classrooms,
corridors etc:
•SwitchLite consists of switching
presence detectors and photocells
•RotaryDIM offers precise manual
control via a wall plate
•SensaDigital covers both features:
Daylight-linked dimming, presence
detection and manual override via an
infra-red handheld controller
2
3
2. SensaModular is a portfolio of
lighting control products designed for
single room applications. The ‘modular’
concept allows customers to build-up a
set of components tailored specifically to
their needs:
•U
sers can select modules for creating
light scenes, enabling daylight-linking,
integrating presence detection,
switching, scene setting and infra-red
control
• Just the components needed are taken
and connected to, up to three groups of
dimmable luminaires via a controller
3. SensaAdvanced is a lighting
management system for larger projects
and those requiring greater levels of
comfort:
•For all types of dimmable or
switchable ballasts or lamps
• Daylight and Presence link
•Integration of blinds,
screens and room partitions
•Different user interfaces like touch
panels, wall units or PC
• Scene setting
• Time and Dynamic management
• A/V interface
What is SensaModular?
SensaModular is for everyone looking for a versatile
product that is easy to install and understand
SensaModular controller
with 3 luminaire outputs
(DSI or DALI)
Scene Plate
Plat
late
Scene
Multi-sensor
Infra-red handheld
controller
iX connection for
up to 8 devices
(sensors, scene plates,
switch inputs, 1 photo cell)
Multi-sensor
Photo cell (max. 1)
Standard double or single
momentary action switches to
dim/brighten luminaire groups
Unlike traditional dimmer pack
or building-wide solutions, it is
a simple, cost effective modular
solution capable of saving
time and labour for all indoor
single-room applications with
two or three luminaire groups.
Its modularity is based on the
controller which interfaces with
various combinations of scene
plates, sensors, switches and
receivers to operate groups of
luminaires, thus offering users
flexibility and comfort with the
reassurance that all components
integrate fully with each other.
Key benefits are:
1Different ways of
presence linking, allowing
SensaModular to be adapted
to the required detection
pattern, and different
operation modes.
2.Three methods of daylightlinking, making it easy to
tailor SensaModular to the
application, especially in terms
of size, usage and ceiling
height.
3.Scene setting via: Scene plate,
Infra-red handheld control
or Switch input device.
4.DSI/DALI auto detection
outputs (patented) for
controlling luminaire groups,
the large SensaModular
controller allows three
digital outputs, the small
controller two.
5.Easy installation via polarityfree 2-wire connections,
using standard mains rated
installation material.
3
Performance, Efficiency and Comfort
(PEC) – for a better lit environment
SensaModular evokes the spirit of Thorn Lighting’s
dynamic, results-orientated PEC programme
The programme is based on
the principle that Performance,
Efficiency and Comfort determine
the effectiveness of lighting, its
impact on the people using it,
and its impact on the natural
environment. SensaModular
delivers the right light on the
right place at the right time.
Performance: Providing the
best visual effectiveness
•Dimming and Scene setting
gives flexibility of the lighting
configuration, therefore
SensaModular ensures
good task lighting wherever
the task is.
4
Efficiency: Conserving
energy and effort, reducing
CO2 emissions and waste,
providing lighting that is practical
and efficient to install, operate
and maintain.
•Presence-link conserves energy
by ensuring unnecessary
lighting is turned off.
•Daylight-link conserves energy
by ensuring the task is lit to
the correct level and not over
lit, irrespective of the source
of light.
•Maintenance control
is provided with the
SensaModular multi-sensors,
i.e. constant task illuminance
is given throughout the
maintenance cycle of the
lighting, conserving energy
and easing the maintenance
requirements.
• Polarity-free connections make
SensaModular quick and
easy to install with reduced
possibility of errors.
• There are two screwdriver
adjustable rotary switches
on the front of the controller,
which will set the operation
mode and off delay time for
the presence-link function.
This makes commissioning
quick, easy and safe being
operated from the ground.
• SensaModular gives us a
lighting system we can
manage effectively and
ensures that the whole lighting
performs as designed.
Comfort: giving people
satisfaction and stimulation
•Personalised light, either with
dimming or with scene setting,
allows the ambience of the
space to be altered to suit the
usage requirements.
•SensaModular allows the
variability of the light through
time, giving a more interesting
and stimulating environment.
Energy saving potential
By conserving energy we give better value
for money whilst saving global resources
Milestones to energy conservation with modern lighting
Fluorescent lamp
and conventional
ballast
0%
Fluorescent lamp
and low-loss
ballast
Fluorescent lamp
and electronic
ballast
Fluorescent lamp
and dimmable
electronic ballast
Fluorescent lamp
and dimmable
electronic ballast
-7%
Manual dimming
-22%
Daylight-link
-42%
Presence-link
-55%
-61%
System with T26
fluorescent lamps
-82%
System with T16
fluorescent lamps
-71%
Baseline
Savings potential
The CELMA (Federation of National Manufacturers Associations for Luminaires and Electrotechnical
Components for Luminaires in the European Union) highlights the potential energy savings that dimmable
electronic ballasts, day-light link and presence-link offer, as shown in the picture above. SensaModular
allows the realisation of these energy savings in every single room indoor lighting application.
5
Key Benefit - Tailored-fit presence-link
The most expensive light is the one that
is still on in unoccupied rooms or areas.
SensaModular enables you to automatically
conserve energy whenever people are absent,
allowing you to choose between three options:
Using one SensaModular multi-sensor per luminaire group
•The SensaModular multi-sensors provide a presence-link function that
may be allocated to the luminaire groups individually.
•This option is perfect for applications with zoned lighting, e.g. group
offices, and considers the recommendations regarding presence-link
stated in EN 15193, asking for zoned presence-link in applications
larger than 30m².
Using one SensaModular multi-sensor for all luminaire
groups
•This option provides a presence-link function for all luminaire groups
connected to the SensaModular controller, and is ideal in small
applications where daylight-link and infra-red control are required.
Using one SwitchLite presence detector for all luminaire
groups
•Any standard 230 VAC presence detector, e.g. one of the
Thorn SwitchLite portfolio, can be used as an alternative to the
SensaModular multi-sensors. This can be connected to the dedicated
“PD” input of the controller and is allocated to all luminaire groups.
•This option is perfect for any application requiring a different
detection pattern to that of the SensaModular multi-sensor, for
instance corridors and staircases, and also for applications
where no daylight-link and infra-red control is needed.
6
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
only
only
only
Off
Off
Off
PD
PD
PD
On/Corridor
On/Corridor
On/Corridor
PD
PD
PDMode
Mode
Mode
PD
PD
PDMode
Mode
Mode
PD
PD
PDMode
Mode
Mode
On/Corridor
On/Corridor
On/Corridor
PD
PD
PDMode
Mode
Mode
PD
PD
PDMode
Mode
Mode
PDPD
PD
On/Corridor
On/Corridor
On/Corridor
Absence-link (only Off
mode) Lighting is slowly faded
to Off, after a set Off delay time,
as soon as a connected
sensor
000
60
60
60 If several
0.5
0.5
0.5 sensors
detects absence.
are used
thenOn/Off
SensaModular
On/Off
On/Off111
45
45
45
will delay fading to Off until all
of the 30
sensors
555
30
30 have reported
only
only
absence.
The lighting willonly
never
PDPD
PD
10
10
10Off
20
20
20
Off
Off
be switched
On15
automatically
15
15
in this mode and will have to
be activated manually, using
On/Corridor
On/Corridor
On/Corridor
the scene plate, the momentary
action switches or the infra-red
handheld control.
Off
Off
OffDelay
Delay
Delay(min)
(min)
(min)
PD
PD
PDMode
Mode
Mode
On/Off
On/Off
On/Off
0 00
6060
60
0.5
0.5
0.5
only
only
only
Off
Off
Off
only
only
only
Off
Off
Off
PD
PD
PD
On/Corridor
On/Corridor
On/Corridor
Presence- and absence-link
(On/Off mode) Lighting is
switched On whenever a person
is detected On/Off
by
a connected
On/Off
On/Off
sensor, and is slowly faded to
Off, after a On/Off
set
Off delay time,
On/Off
On/Off
only
only
only
as soon as the sensor detects
PD
PD
PD
Off
Off
Off
absence. If several sensors
are
only
only
only
usedPD
then
PD
PD SensaModular will
Off
Off
delay fading to Off untilOff
all
of the
On/Corridor
On/Corridor
On/Corridor
sensors have
reported absence.
On/Off
On/Off
On/Off
only
only
only
Off
Off
Off
PD
PD
PD
On/Corridor
On/Corridor
On/Corridor
The SensaModular control
unit features two inbuilt rotary
switches that allow the user to
determine the desired operation
mode and Off Delay time for the
presence-link
function. These are
On/Off
On/Off
On/Off
easily and quickly set using a
screwdriver
only
only
only
PDPD
PD
Off
Off
Off
PD
PD
PDMode
Mode
Mode
On/Off
On/Off
On/Off
4545
45
3030
30
1 11
5 55
PDPD
PD
Presence-linked Corridor
scene (On/Corridor
mode) Lighting is switched on
whenever a person
is detected
On/Off
On/Off
On/Off
by a connected sensor, and is
slowly faded to a lower corridor
only
only
only
illuminance level, after a set
Off
PD
PD
PD
Off
Off
delay time, as soon as theOff
sensor
detects absence. If several sensors
are used then SensaModular
On/Corridor
On/Corridor
On/Corridor
will delay fading
to the corridor
illuminance level until all of the
sensors have reported absence.
The corridor illuminance level
is set to 10% light output for all
luminaires.
PD
PDMode
Mode
Mode
PD
45
45
45
30
30
30
20
20
20
1
Off
Off
OffDel
De
De
6060
600 000.5
0.5
0.5
only
only
only
Off
Off
Off
4545
45
1 11
3030
30
5 55
On/Corridor
On/Corridor
On/Corridor
1010
10
2020
20
1515
15
On/Corridor
On/Corridor
On/Corridor
2020
20
1010
10
1515
15
PD
PD
PDMode
Mode
Mode
Off
Off
OffDelay
Delay
Delay(min)
(min)
(min)
PD
PDMode
Mode
Mode
PD
Off
Off
OffDelay
Delay
Delay(min)
(min)
(min)
Deactivated presence-link
SensaModular allows all
connected presence detectors
or the presence-link function of
all connected SensaModular
multi-sensors to be deactivated.
This mode also helps when the
SensaModular installation is
commissioned.
Off Delay time After detecting
absence SensaModular will wait
for a configurable Off time delay
before fading to the absence
setting specified with the set
operation mode. This time delay
can be between 0 seconds and
1 hour.
Note: If a standard presence
detector (e.g. SwitchLite) is used,
its own Off Delay time is added
to that set on the SensaModular
controller.
60
60
60
Staircase function
By connecting a standard
momentary action switch to
the SensaModular controller’s
presence detector input,
a ‘staircase’ function can
be realised. Activating the
momentary action switch
announces presence and the
lighting is switched On.
After the set Off delay time the
lighting is faded to Off, if the
operation mode is set to On/
Off, or alternatively faded to a
corridor illuminance level of 10%,
if the mode is set to On/Corridor.
7
Key Benefit - Tailored-fit daylight-link
0%
25%
50%
0%
500lux
Daylight
Artificial light
0%
50%
Daylight
Artificial light
25%
50%
500lux
500lux
Daylight
Artificial light
Using one ‘look down’ sensor per
luminaire group
Using one ‘look out’ photocell for
all luminaire groups
Using one ‘look down’ sensor for all
luminaire groups
For daylight-linking one multi-sensor per
luminaire group is installed on the ceiling,
aimed at the working plane to register the
light level.
For daylight-linking one photocell sensor
is installed on the ceiling and aimed in the
direction of the window to register incoming
daylight.
Advantages:
Advantages:
For the daylight-linking of smaller rooms,
e.g. a single office or meeting room,
one multi-sensor for all luminaire groups
is installed on the ceiling, aimed at the
working plane to register the light level.
•Supports the recommendations stated in
EN 15193, which ask for daylight-linking
of zones smaller than 30m2, thus resulting
in a good rating of the installation for
‘building passport’ purposes
•Visual and physical intrusion on the
ceiling is kept to a minimum as only one
sensor is needed to register the flow
of daylight for up to three individually
controlled luminaire groups.
•Maintains illuminance despite aging
of lamps and dirt on luminaires.
•With only daylight to register
measurements are precise, thus
maximising daylight saving potential.
•Ideal for larger, zoned applications,
like group offices.
•SensaModular multi-sensor heads
combine daylight with presence linking
and infra-red control.
Points to consider:
•Measures daylight and artificial light
reflected from desktop – therefore
influenced by reflecting material
and colour.
•Several sensors needed (one per luminaire
group), therefore more obtrusive.
•Impact of overlapping detection zones.
8
25%
•Ideal for applications with luminaire
rows and/or ceiling heights of more than
3m, or where zoned presence-link is not
required, e.g. classrooms, industrial or
sports halls.
Points to consider:
•Does not consider aging of lamps and
luminaires becoming dirty.
•SensaModular photocell does not provide
presence-linking and infra-red control.
Advantages:
•For applications not requiring zoned
areas, visual and physical intrusion on
the ceiling is kept to a minimum as only
one sensor is needed to register the flow
of daylight for up to three individually
controlled luminaire groups.
•Maintains illuminance despite aging of
lamps and dirt on luminaires.
•The SensaModular multi-sensor head
combines daylight with presence-linking
and infra-red control.
Points to consider:
•Measures daylight and artificial light
reflected from one local desktop –
therefore influenced by reflecting material
and colour.
•Does not consider the recommendations
stated in EN 15193 in applications
larger than 30m².
Key Benefit - Scene setting
No application is used for only one activity or task:
Therefore SensaModular allows a user to set scenes
and to adapt the lighting to the different tasks.
Scene plate
With the wall recessed SensaModular scene plate three scenes as well
as the Off scene can be set and recalled. The active scene is visualised
with indicator LEDs integrated into the keys. Three pairs of keys are
used to dim and brighten the luminaire groups individually and a
further pair allow all luminaires to be dimmed or brightened. The scene
plate has a brass front in satin steel finish, matching back boxes are
available as accessories.
Infra-red handheld control
The SensaModular infra-red
handheld controller allows the
setting and recalling of three
scenes and the Off scene. The
whole lighting can be dimmed
and brightened via a rocker key,
or after using the pre-selection
buttons the luminaire groups
can be dimmed individually.
This device is also used to
allocate the SensaModular multisensors to the luminaire groups.
For the reception either the
SensaModular multi-sensors or
(if these are not planned in) the
SensaModular infra-red sensors
can be used.
Switch input device
As an alternative to the wallrecessed scene plate, standard
momentary action switches can
be used in conjunction with
the SensaModular switch input
device to recall three scenes and
the Off scene.
9
Key Benefit - DSI/DALI auto detection
SensaModular uses DSI/DALI auto detection luminaire outputs
(patented), and allows you to connect either:
Maximum number of ballasts
connected to ‘SensaMod-2DIG’ controller
•Luminaires with electronic ballasts showing DSI (Digital Serial
Interface) controllability, e.g. Thorn HFD luminaire versions
Output
• Luminaires with DALI (Digital Addressable Lighting Interface)
controllability, e.g. Thorn HFX luminaire versions
HFD luminaires only
50 DSI
50 DSI
HFX luminaires only
25 DALI
25 DALI
25 DSI or DALI
25 DSI or DALI
•One ballast type, either DSI or DALI, can be connected to
each controller output (see table for permitted configurations
and quantities)
Every luminaire output of a SensaModular controller will check,
individually, the type of ballasts used and automatically adapt its
control “language”.
HFD or HFX luminaires
Grp1
Grp2
Maximum number of ballasts
connected to ‘SensaMod-3DIG’ controller
Output
Grp1
Grp2
Grp3
HFD luminaires only
50 DSI
50 DSI
50 DSI
HFX luminaires only
25 DALI
25 DALI
25 DALI
HFD or HFX luminaires 25 DSI or DALI 25 DSI or DALI 25 DSI or DALI
Note: A DSI amplifier is available as accessory to increase the number of connectable DSI
ballasts (DSI-V, 20975705).
Key Benefit - Easy to Install
• When wiring the system, the
two or three groups of HFD or
HFX luminaires are allocated to
the momentary action switches
for direct manual control = plug
& play.
• One intelligent interface (‘iX’
connection) is used for all user
interfaces and sensors, e.g.
multi-sensor heads or photocell,
infra-red sensor, scene plate,
momentary action switch input.
DSI or DALI wiring,
iX wiring
• Polarity-free
•S
tandard mains wiring, e.g.
H05VV-U 2 x 1.5mm² and
H05VV-U 2 x 0.75mm²
• There is no extra commissioning
tool required.
• F or maximum lengths see table
below
• The infra-red handheld
controller is used to allocate
the multi-sensors to the
luminaire groups.
•W
iring typologies: tree, star,
line, radial.
Wire
diameter
2
2
2
2
10
•R
egarding installation material;
installers benefit from polarityfree connections and the
possibility to use standard
mains rated wiring.
x
x
x
x
0.5mm²
0.75mm²
1.0mm²
1.5mm²
Maximum length iX
and DALI wires
Maximum length
DSI wires
100m
150m
200m
300m
125m
125m
125m
250m
How to plan a SensaModular installation
The ‘cascading’ diagram below helps you
evaluate and chart possible outcomes when
seeking the benefits of energy saving and comfort
Luminaire grouping chosen for application?
Rows in parallel with window
(or ceiling higher than 3m)
Zones
(and ceiling height max. 3m)
Yes
No
Yes
No
Presence linked?
Presence linked?
Presence linked?
Presence linked?
Yes
No
Yes
Yes
No
Yes
Multi-sensors
(look down)
Multi-sensors
(look down, PD)
Multi-sensors
(look down)
Photocell
(look out)
Photocell
(look out)
SwitchLite
presence
detector
No
No
Energy Saving
Daylight linked?
SwitchLite
presence
detector
Via wall mounted plate?
Via infra-red
handheld control?
Via standard switches?
Yes
Yes
Yes
Remote Control *
Input for standard switches
Scene Plate
Comfort
Scene setting?
* plus Infra-red Sensor if
no Multi-sensor is used
Energy Saving
•How are the luminaire groups arranged – in zones (e.g. using
recessed louvre luminaires) or in rows (e.g. using suspended
linear luminaires)?
• How high is the ceiling?
• Is daylight available and daylight-linking possible?
• Is presence-link also required?
Based on the answers to these questions you decide to select either:
• the SensaModular multi-sensors,
• or the SensaModular photocell perhaps combined with a SwitchLite
presence detector.
Comfort
Now choose any additional modular items:
•Do you want to set scenes? (Note: Scene 1 would be the daylightlinked one).
•If yes, would you prefer:
-The SensaModular Scene Plate, that allows you to brighten and
dim the luminaire groups individually and jointly, and to set and
recall three scenes plus Off? It also indicates the active scene.
This plate is perfect for meeting rooms, retail applications and
much more.
-Or an Infra-red handheld control? This would be optimal in any
office application. (Note: If you have not chosen a multi-sensor
head above, then you will need a Infra-red Sensor as well.)
-Or standard momentary action switches for recalling scenes? These
would interface via the SensaModular Switch Input into the system.
11
Application example - Group Office
Description of application:
Example:
Graphic design agency
Number of users:
< 15
Size:
< 100m²
Activities:
PC work, desk work, break, cleaning
Area of activity:Zone within an area, e.g. a working team’s
desk cluster
Luminaire layout:Arranged in three zones, with a group of
recessed luminaires above each desk cluster
Ceiling height:
2.8m
Needs and requirements
• Light level per zone adaptable to activities
• Saving Energy
• Easy to install and to commission, no need for a specialist or training
Solution
• Multi-sensors detect presence/absence and dim/brighten light
according to incoming daylight
• Individual manual dimming is provided via momentary action
switches, or optional infra-red handheld controller, to override a
zone’s light level if needed
• Infra-red handheld controller used to allocate multi-sensors to
the luminaire groups
One of three zones
• Detection mode and Off delay set via rotary switches, illuminance
levels programmed via infra-red handheld controller, or via
momentary action switch temporarily connected to ‘lux’ input
of SensaMod-3DIG.
• Standard mains wiring only, polarity-free DSI/DALI and sensor wires
Group 3: DSI or DALI out
Group 2: DSI or DALI out
Group 1: DSI or DALI out
iX Intelligent
connection for sensors
and scene setting
devices
Group 1
Group 2
Group 3
Optional
L
12
N
Group 1
Group 2
Group 3
Application example - Classroom
Description of application
Example:
Primary school
Number of users:
< 25
Size:
< 70m²
Activities:
Lessons, breaks, cleaning
Area of activity:
Room
Luminaire layout:Arranged in rows, two groups,
parallel to the window
Ceiling height:
3m
Needs and requirements
• Saving energy
• Vandal resistant operation, optionally ‘protected’
• Easy to use (especially in shared or ‘public’ rooms)
• Easy to install and to commission, no need for a specialist or training
Solution
• Lighting is linked to the incoming daylight using 1 photocell
(looking towards the window) for all luminaire groups
• Wall mounted passive infra-red or unobtrusive Microwave presence
detector for all luminaire groups, e.g. one of Thorn’s SwitchLite
portfolio
•Manual switching and dimming via standard ‘key operated’
double momentary action switches to override light levels if needed
(keys for teachers, facility manager, cleaner)
• Detection mode and Off delay set via rotary switches, illuminance
level programmed either via push button built into photocell, or via
momentary action switch temporarily connected to ‘lux’ input of
SensaMod-2DIG
• Standard mains wiring only, polarity-free DSI/DALI and
photocell wires
Group 2: DSI or DALI out
Group 1: DSI or DALI out
iX Intelligent
connection for
sensors and scene
setting devices
All groups
L
N
Presence detector
allocated to all groups
Group 1
Group 2
13
Application example - Sports Hall
Description of application
Example:
Number of users:
Size:
Activities:
Area of activity:
Luminaire layout:
Ceiling height:
Swimming pool without large windows
< 50
< 500m²
Public swimming, competition, cleaning
Hall
Arranged in rows, three groups
5 to 10m
Needs and requirements
• Light level adaptable to different activities
• Saving energy
• Easy to use
• Easy to install and to commission, no need for a specialist or training
Solution
• A scene plate allows the setting and selection of 3 scenes,
thus matching the lighting to the different activities taking place.
Light levels can be overridden individually if required.
• Standard mains wiring only, polarity-free DSI/DALI and scene
plate wires
Group 3: DSI or DALI out
Group 2: DSI or DALI out
Group 1: DSI or DALI out
iX Intelligent
connection for
sensors and
scene setting
devices
L
14
N
Product details
22154742 SensaMod-3DIG
Digital output unit for controlling three luminaire groups, with three control outputs for DSI or DALI compatible
lamp control gears (auto detection). Up to 25 DALI or 50 DSI ballasts per output channel are connected via a
polarity-free two-wire connection using standard mains rated wiring. Dimming range 1 to 100% (depending
on ballasts). The unit shows an intelligent input for the connection of multi-sensors, infra-red sensors, a
photocell, scene plates and switch input devices (max. 8 devices in parallel) via a polarity-free two-wire
connection using standard mains rated wiring. Additionally standard single or double momentary action
switches can be connected to switch, dim and brighten the luminaire groups individually; standard mains
rated presence detectors can be connected to link all luminaire groups to presence. Two rotary switches to
set presence detection mode and Off delay time. All connections made via screw-terminals. Status LED and
test button. Housing made of flame-retardant polycarbonate, halogen free, for installation into distribution
cabinets on 35mm DIN rail, according to EN 50022, IP20 degree of protection, ambient temperature
0 to 50°C. Width 140mm (8 units), height 90mm, depth 59mm. Weight 650g.
22154741 SensaMod-2DIG
Digital output unit for controlling two luminaire groups, with two control outputs for DSI or DALI compatible
lamp control gears (auto detection). Up to 25 DALI or 50 DSI ballasts per output channel are connected via a
polarity-free two-wire connection using standard mains rated wiring. Dimming range 1 to 100% (depending
on ballasts). The unit shows an intelligent input for the connection of multi-sensors, infra-red sensors, a
photocell, scene plates and switch input devices (max. 8 devices in parallel) via a polarity-free two-wire
connection using standard mains rated wiring. Additionally standard single or double momentary action
switches can be connected to switch, dim and brighten the luminaire groups individually; standard mains
rated presence detectors can be connected to link both luminaire groups to presence. Two rotary switches to
set presence detection mode and Off delay time. All connections made via screw-terminals. Status LED and
test button. Housing made of flame-retardant polycarbonate, halogen free, for installation into distribution
cabinets on 35mm DIN rail, according to EN 50022, IP20 degree of protection, ambient temperature
0 to 50°C. Width 70mm (4 units), height 90mm, depth 59mm. Weight 350g.
22154744 SensaX-MULTISENSOR
Multi-sensor for presence-link, daylight-link and integration of infra-red handheld controllers. Presence-link
via passive infra-red sensor, circular detection pattern at 2.5(3)m ceiling height is diameter 6(7)m for seated
persons, and diameter 7(9)m for persons in motion. Daylight-link is realised with sensor looking down at
task area, measuring the daylight as well as the artificial light reflected from the task area. Connected to
and supplied by central control device via a polarity-free two-wire connection using standard mains rated
wiring. Either semi-recessed into single Euro ceiling back box, diameter 60mm, or surface-mounted onto
ceiling or fully recessed into suspended ceiling (cut out diameter 92mm) with accessory rings provided,
mounting height 3m max. Connection made via screwless push-in terminals. Green status LED behind lens
for indication. Housing made of flame-retardant polycarbonate, white (RAL 9003), lens made of high density
polyethylene, both halogen free. IP40 degree of protection, ambient temperature 0 to 50°C. Weight 50g.
15
22154745 SensaX-IRSENSOR
Infra-red sensor for integration of infra-red handheld controllers. Connected to and supplied by central
control device via a polarity-free two-wire connection using standard mains rated wiring. Either semi-recessed
into single Euro ceiling back box, diameter 60mm, or surface-mounted onto ceiling or fully recessed into
suspended ceiling (cut out diameter 92mm) with accessory rings provided. Connection made via screw less
push-in terminals. Status LED behind lens for indication. Housing made of flame-retardant polycarbonate,
white (RAL 9003), lens made of high density polyethylene, both halogen free. IP40 degree of protection,
ambient temperature 0 to 50°C. Weight 50g.
22154746 SensaX-DAYSENSOR
Photocell for daylight-link. Daylight-link is realised with sensor looking from ceiling towards window,
measuring the daylight entering a room. Connected to and supplied by central control device via a polarityfree two-wire connection using standard mains rated wiring. Surface-mounted onto ceiling. Connection
made via screw-terminals. Status LED behind lens for indication. Integrated test and program button. Housing
made of flame-retardant polycarbonate, white (RAL 9003), halogen free. IP20 degree of protection, ambient
temperature 0 to 50°C. Weight 40g.
22154743 SensaX-IRCONTROL
Infra-red hand held controller for setting and recalling three scenes and Off scene. Controller includes one
On/Off key, three scene keys, one dimming rocker key and five keys for pre-selection of luminaire groups.
The whole lighting can be dimmed and brightened via the rocker key, or after using the pre-selection keys the
luminaire groups can be dimmed and brightened individually. Device additionally used for allocation of multisensors to luminaire groups. Status LED for indication. Supplied by 2 batteries type AAA, included. Range
up to 10m, IR protocol RSTEP, 38kHz. Housing made of ABS, halogen-free, wall-mounting bracket included,
ambient temperature 0 to 40°C.
22154747 SensaX-SCENE
Scene plate for setting and recalling three scenes and Off scene. Active scenes visualised with indicator LEDs
integrated into the keys. Four pairs of keys for dimming and brightening luminaire groups individually as well
as jointly. Connected to and supplied by central control device via a polarity-free two-wire connection using
standard mains rated wiring. Front plate made of brass in satin steel finish, hiding screws after installation.
Wall recessed into back boxes, available as accessories. Connection made via detachable plug with screwterminals. Connection of protective earth via separate screw-terminal. IP20 degree of protection, ambient
temperature 0 to 50°C. Width 145mm, height 86mm. Depth without plate 25mm, depth of plate 4mm.
Weight 350g.
16
96233754 RBOX2 PS CONTROLITE
Back box plastic (polystyrene, halogen-free) 2-gang for the wall recessed installation of the SensaX-SCENE
scene plate. Suitable for flush fitted installation into cavity walls. Outside dimensions 134x74mm, depth 36mm
(without rim and clamps).
96233752 RBOX2 ST CONTROLITE
Back box stainless steel 2-gang for the wall recessed installation of the SensaX-SCENE scene plate.
Suitable for flush fitted concealed installation into brick or concrete walls. Outside dimensions 134x74mm,
depth 28mm.
22162242 SensaX-4SWITCH
Switch input device to recall three scenes and the Off scene, or alternatively to switch, dim and brighten three
luminaire groups individually and jointly, via volt-free standard momentary action switches. Connected to and
supplied by central control device via a polarity-free two-wire connection using standard mains rated wiring.
Connection of up to four volt-free momentary action switches, switch function, scene recall or group dimming
and brightening, set via built-in rotary switch. Recessed into back box behind switches. Connection made
via pre-connected wires, length approx. 30cm. Housing made of flame-retardant polycarbonate, transparent,
halogen free. IP20 degree of protection, ambient temperature 0 to 50°C. Diameter 53mm, height 13mm.
Weight 100g.
22154307 PDAX 500VA
Phase dimmer/Reverse phase dimmer (automatic load detection) with DSI interface, controllable via
SensaModular output, for continuous dimming of ohmic light sources, LV halogen lamps with magnetic or
electronic transformers. A total connected load of 40 to 500VA can be operated. Dimming range
1 to 100%. Connection via screw terminals, housing made of flame-resistant polycarbonate, halogen-free,
suited for ceiling recess, ambient temperature 0 to 60°C (max. 300VA)/0 to 45°C (max. 500VA).
IP20 degree of protection. Length 167mm, width 42mm, height 31mm. Weight 200g.
17
22154306 PDAS 1000VA
Phase dimmer/Reverse phase dimmer (automatic load detection) with DSI interface, controllable via
SensaModular output, for continuous dimming of ohmic light sources, LV halogen lamps with magnetic or
electronic transformers. A total connected load of 40 to 1000VA can be operated. Dimming range 1 to 100%.
Connection via screw terminals, housing made of flame-resistant polycarbonate, halogen-free, suitable for
installation in switch or distribution cabinets on 35mm DIN rail. Ambient temperature 0 to 40°C. IP20 degree
of protection. Width 105mm (6 units), height 90mm, depth 59mm. Weight 400g.
86457873 TE one4all sc 105VA
Digital, dimmable transformer with DSI/DALI interface; controllable via SensaModular output (identified
as DALI ballast), dimming range of 1 to 100%; for operation of 12V low voltage tungsten-halogen lamps
with a lamp power of between 20 and 105VA; lamp leads up to 2m; housing made of flame-resistant
polycarbonate, halogen-free; suitable for ceiling recess; protection class II; ambient temperature -25 to
+60°C. Length 167mm, width 42mm, height 31mm. Weight 180g.
86457874 TE one4all sc 150VA
Digital, dimmable transformer with DSI/DALI interface; controllable via SensaModular output (identified
as DALI ballast), dimming range of 1 to 100%; for operation of 12V low voltage tungsten-halogen lamps
with a lamp power of between 50 and 150VA; lamp leads up to 2m; housing made of flame-resistant
polycarbonate, halogen-free; suitable for ceiling recess; protection class II; ambient temperature -20 to
+50°C. Length 207mm, width 46mm, height 40mm. Weight 290g.
20975705 DSI-V
Digital device for amplifying the DSI signal, enables connection of 50 additional DSI compatible operating
devices, like digital electronic ballasts, phase dimmers or electronic transformers, to the DSI output of
SensaModular after the maximum number of DSI ballasts has been reached. The DSI load of the DSI-V is
equivalent to the load of 2 DSI ballasts. Serial connection of up to 5 amplifiers possible. DSI input and
output. Connections made with push-in terminals; housing made of flame-resistant polycarbonate, halogenfree, suitable for ceiling-recess, IP20 degree of protection, protection class II with fitted terminal covers,
ambient temperature 0 to 60°C.
18
Ordering Guide
Ordering guide
Weight Kg
SAP code
SENSAMOD-3DIG
0.65
22154742
SENSAMOD-2DIG
0.35
22154741
SENSAX-MULTI-SENSOR
0.05
22154744
SENSAX-IRSENSOR
0.05
22154745
SENSAX-DAYSENSOR
0.04
22154746
0.09
22154743
SENSAX-SCENE
0.35
22154747
RBOX2 PS CONTROLITE
0.06
96233754
RBOX2 ST CONTROLITE
0.16
96233752
0.10
22162242
PDAX 500VA
0.20
22154307
PDAS 1000VA
0.40
22154306
TE ONE4ALL SC 105VA
0.18
86457873
TE ONE4ALL SC 150VA
0.29
86457874
0.15
20975705
Description
SensaModular DSI/DALI Output 3x and 2x
SensaModular multi-sensor, infra-red sensor and photocell
SensaModular Infra-red Handheld Control
SENSAX-IRCONTROL
SensaModular Scene Plate and back boxes, polystyrene and steel
SensaModular 4-fold scene or group switch input
SENSAX-4SWITCH
Accessories: DSI phase/reverse phase dimmers, auto load detection, 40-500VA and 40-1000VA
Accessories: DSI/DALI electronic transformers, 12V, 20-105VA and 50-150VA
Accessory: DSI amplifier for 50 additional DSI loads
DSI-V
Connecting Accessories
Further
DALI out
Further
DSI out
DSI in
load out
PDAX/PDAS
DSI in
DSI out
DSI-V
DALI in
Further
50 DSI out
load out
TE one4all
19
Lighting people and places
Thorn Lighting Main Offices
Thorn Academy of Light
Green Lane Industrial Estate, Spennymoor
County Durham DL16 6HL, UK
Tel:
(44) 1388 420 042
E-mail:
academy@thornlighting.com
Website:
www.thornacademyoflight.com
Australia
Thorn Lighting Pty Limited
43 Newton Road, Wetherill Park
NSW 2164
Tel:
(02) 8786 6000
Fax:
(02) 9612 2700
E-mail:
infoaustralia@thornlighting.com
Website:
www.thornlighting.com.au
Austria
Thorn Licht GmbH
Donau-City-Straße 1,
1220 Wien, Austria
Tel:
(43) 1 202 66 11
Fax:
(43) 1 202 66 11 82712
E-mail:
office.at@thornlighting.com
Website:
www.thornlighting.at
China
Thorn Lighting (Guangzhou) Operations Ltd,
No.12 Lian Yun Road, Eastern Section,
GETDD, Guangzhou 510530, China
Tel:
(86) 20 3228 2706
Fax:
(86) 20 3228 1777
E-mail:
sales.cn@thornlighting.com
Thorn Lighting (Tianjin) Co. Ltd
332 Hongqi Road, Tianjin 300190,
China
Tel:
(86) 22 8369 2303
Fax:
(86) 22 8369 2302
E-mail:
info.tj@thornlighting.com
Czech Republic
Thorn Lighting CS spol. s.r.o.,
Na Březince 6/930, 150 00 Praha 5
Czech Republic
Tel:
(420) 224 315 252
Fax:
(420) 233 326 313
E-mail:
thorn.cz@thornlighting.com
Website:
www.thornlighting.cz
Denmark
Thorn Lighting A/S
Kanonbådsvej 12B, Holmen,
1437 København K, Denmark
Tel:
(45) 76 96 36 00
Fax:
(45) 76 96 36 01
E-mail:
info.dk@thornlighting.com
Website:
www.thornlighting.dk
France
Thorn Europhane SA
156 Boulevard Haussmann,
Cedex 08, Paris 75379, France
Tel:
(33) 1 49 53 6262
Fax:
(33) 1 49 53 6240
Website:
www.thornlighting.fr
Hong Kong
Thorn Lighting (Hong Kong) Limited
Unit 4301, Level 43, Tower 1,
Metroplaza,223 Hing Fong Road,
Kwai Chung, N.T., Hong Kong
Tel:
(852) 2578 4303
Fax:
(852) 2887 0247
E-mail:
info.hk@thornlighting.com
India
Thorn Lighting India Pvt. Ltd.
501, 5th Floor, Tanishka
Opp. Gundecha Industrial Estate
Akurli Road, Kandivali (E), Mumbai – 400 101, India
Tel:
(91) 22-67839100
Fax:
(91) 22-67839106
E-mail:
international_sales@thornlighting.com
Website:
www.thornlighting.com
International Sales
Thorn Lighting Limited
Silver Screens, Elstree Way, Borehamwood,
Hertfordshire, WD6 1FE, UK
Tel:
(44) 20 8732 9800
Fax:
(44) 20 8732 9819
E-mail:
international_sales@thornlighting.com
Website:
www.thornlighting.com
Ireland
Thorn Lighting (Ireland) Limited
Century House
Harolds Cross Road
Dublin 6W
Tel:
(353) 1 4922 877
Fax:
(353) 1 4922 724
E-mail:
dublinsales@thornlighting.com
Website:
www.thornlighting.co.uk
Italy
Thorn Europhane Spa
Via G Di Vittorio, 2, Cadriano di Granarolo,
Bologna 40057, Italy
Tel:
(39) 051 763391
Fax:
(39) 051 763088
E-mail:
info@thornlighting.it
Website:
www.thornlighting.it
New Zealand
Thorn Lighting (NZ) Ltd
399 Rosebank Road, Avondale, Auckland 1026
PO Box 71134, Rosebank, Auckland 1348
Tel:
(64) 9 828 7155
Fax:
(64) 9 828 7591
E-mail:
info.NZ@thornlighting.com
Website:
www.thornlighting.co.nz
Norway
Thorn Lighting AS
Strømsveien 344, 1081 Oslo,
Norway
Tel:
(47) 22 82 07 00
Fax:
(47) 22 82 07 01
E-mail:
info.no@thornlighting.com
Website:
www.thornlighting.no
Singapore
Thorn Lighting (Singapore) Pte Ltd
5 Kaki Bukit Crescent, 04-02 Koyotech
Building, 416238 Singapore
Tel:
(65) 6844 5800
Fax:
(65) 6745 7707
E-mail:
info.sg@thornlighting.com
Sweden
Thorn Lighting AB
Industrigatan, Box 305, SE-261 23
Landskrona, Sweden
Tel:
(46) 418 520 00
Fax:
(46) 418 265 74
E-mail:
info.se@thornlighting.com
Website:
www.thornlighting.se
United Arab Emirates
Thorn Lighting Ltd Dubai
Al Shoala Building, Office 301,
Block E, Airport road, P.O. Box 1200,
Deira, Dubai, UAE
Tel:
(971) 4 2940181
Fax:
(971) 4 2948838
E-mail:
tlluae@emirates.net.ae
Website:
www.thornlighting.com
Thorn Gulf LLC
Al Shoala Building, Office 301/2, Block E,
Airport road, P.O. Box 22672, Deira,
Dubai, UAE
Tel:
(971) 4 2948938
Fax:
(971) 4 2948838
E-mail:
thorng@emirates.net.ae
Website:
www.thornlighting.com
United Kingdom
Thorn Lighting Limited
Silver Screens, Elstree Way, Borehamwood,
Hertfordshire, WD6 1FE, UK
Tel:
(44) 20 8732 9800
Fax:
(44) 20 8732 9801
E-mail:
brochures.uk@thornlighting.com
Thorn Olympics Sports Lighting Team
Tel:
07785 251 438
E-mail:
olympics.team@thornlighting.com
Website:
www.thornlighting.co.uk
www.thornlighting.com
Poland
Thorn Lighting Polska Sp.z.o.o.,
Ul. Gazowa 26A, Wrocław 50-513,
Poland
Tel:
(48) 71 7833 740
Fax:
(48) 71 3366 029
E-mail:
thorn.pl@thornlighting.com
Website:
www.thornlighting.pl
Russia
Thorn Lighting
Novoslobodskaya Str., 21, office 406
Business Center “Novoslobodskaya 21”,
Moscow 127030, Russia
Tel:
(7) 495 981 35 41
Fax:
(7) 495 981 35 42
E-mail:
kristina.skachinskaya@thornlighting.com
Website:
www.thornlighting.ru
Thorn Lighting is constantly developing and improving its products. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part
of any contract. The right is reserved to change specifications without prior notification or public announcement. All goods supplied by the company are supplied subject to the company’s General
Conditions of Sale, a copy of which is available on request. All measurements are in millimetres and weights in kilograms unless otherwise stated.
Publication No: 397 (IS) Publication Date: 02/10
Download