FS SystemTM Ground Mount Installation Manual
FS System
The Schletter FS System for ground mount photovoltaic (PV) installations is specifically designed to meet or exceed applicable IBC,
ASCE, and UL standards. For more information on the FS System, please see system brochure.
Features
• Conforms to UL 27031
• Certified to ULC/ORD STD C1703
• Electrically Bonded Unit2
• 30 Amp Series Fuse Rating
• Pre-assembled Components
• Fully Integrated and Modular Components
• Includes grounding module clamps
The FS System is capable of accommodating nearly any framed or frameless PV module currently on the market.3 Each FS System
is custom designed to meet specific structural load requirements4. Included in the FS System are the Rapid5K™ grounding clamp
specifically designed to secure the frame of a PV module to the FS System.5 In turn, the components and assemblies that comprise
an FS System form an electrically bonded unit. While individual components and structural sections will vary between designs, the
primary assemblies and installation methods will remain the same.
6
5
7
3
2
Key Components
1. Foundation post
2. Head assembly
3. Girder
4. Strut
5. Locking wedge
6. Purlins
7. Rapid5KTM grounding module clamps
1
4
The FS System is evaluated for electrical bonding only. The FS System meets all IBC and ASCE requirements for structural loading; it has not been
evaluated for loading under UL 2703.
2
Installer is responsible for verifying that system meets applicable NEC and CSA standards.
3
Maximum number of modules shall not exceed system voltage.
4
Individual parts and components will vary from system to system. Please reference system specific drawings.
5
This racking system may be used to ground and/or mount a PV module complying with UL1703 only when the specific module has been evaluated for grounding
and/or mounting in compliance with the included instructions.
1
© Schletter Inc • 1001 Commerce Center Drive • Shelby, North Carolina 28150 • Tel: (704) 595 - 4200 • Fax: (704) 595 - 4210
mail@schletter.us • www.schletter.us
MI-008
072216
1/13
FS SystemTM Ground Mount Installation Manual
Sample Drawings
Specific drawings are provided for each project. Key information included on these drawings is as follows:
1. Design Criteria
4. Array Tilt
2. Notes Section
5. Array Dimensions
3. Module Dimensions
6. Post Embedment
2
1
2
4
3
5
7
6
8
9
11
10
12
6200 [24481 in]
[34
19 in]
4000 [15721 in]
1100
A
[43165
SPLICE
in]
(20 in])
16
17
LOADS:
MODULE DEAD LOAD = 2.23 PSF
SLOPED ROOF SNOW LOAD = 0 PSF
A
INSTALLATION TOLERANCES:
LATERAL POST PLACEMENT IS ±5.0"
TOTAL LATERAL DEVIATION OF POSTS WITHIN AN ARRAY IS ±5.0"
POST HEIGHT VARIATION TOLERANCE IS ±0.40"
POST VERTICALITY TOLERANCE <2.0° IN ALL DIRECTIONS
POST ROTATIONAL TOLERANCE <±7.0°
ARRAY TILT ANGULAR TOLERANCE ±1.0°
B
5
3
3
D
A
416 [16 3
8
3335
in]
833 [32 3
4
551 [21 11
E
16
2700
in]
2503
16
[106 5
16
1610 [6338 in]
in]
in]
2
15°
833 [32 3
[65 9
16
4
in] TY
416 [16 3
in]
88 [3 1
550 [2158 in]
2
549 [2158 in]
2900 [114163 in]
6
109 [4165 in]
1910 [75163 in]
1801 [7078 in]
2FT DIA X 6.25FT DEEP
CONCRETE FOOTING
I
in]
R
D
E
L
AMP
FINISHED GRADE
H
8
in]
5
[5016 in]
760 [2915
16 in]
1099 [4341 in]
1667 [6558 in]
P
S
893 [3581 in]
NO. DRAWN:
0
1
2
3
4
K 5
6
7
8
FOUNDATIONS:
1. NO SOILS REPORT PROVIDED. FOUNDATION DESIGN IS BASED ON MINIMUM IBC SOIL BEARING
VALUE = 1500 PSF PER IBC TABLE 1806.2. DRILLED SHAFT FOUNDATION SHALL BE BUILT IN
UNDISTURBED SOIL OR COMPACTED FILL MATERIAL NOT LESS THAN 12 INCHES IN DEPTH. THE
MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED GROUND SURFACE SHALL BE 12 INCHES.
2. THE STRUCTURAL ENGINEER IS NOT RESPONSIBLE FOR ANY GEOTECHNICAL ASPECTS OF THIS
PROJECT. IT IS RECOMMENDED THAT THE OWNER RETAIN A REGISTERED GEOTECHNICAL
ENGINEER TO CONDUCT A GEOTECHNICAL INVESTIGATION AND PREPARE A REPORT WITH
RECOMMENDATIONS FOR FOUNDATION AND EARTHWORK PROCEDURES.
CONCRETE:
1.All CONCRETE WORK SHALL CONFORM WITH THE REQUIREMENTS OF ACI 301 AND ACI 318
CEMENT PER ASTM C150, TYPE II. AGGREGATE PER ASTM C33. CONCRETE SHALL BE READY
MIXED IN ACCORDANCE WITH ASTM C94 AND SHALL BE DESIGNED FOR A MINIMUM 28 DAY
COMPRESSIVE STRENGTH AS FOLLOWS:
FOUNDATIONS…………………………………………………………3,000 PSI*
*DESIGNED FOR 2,500 PSI
Client:
Ground Mount FS 2V x 10 15°
4
5
4
3
7
6
5
8
7
6
ISSUED BY: SCHLETTER INC.
PROPRIETARY AND CONFIDENTIAL
9
8
10
9
12
11
10
A
12
13
1100 [43165 in]
(20 [34 in])
991 [39 in] TYP
FINISHED GRADE
833 [32 3
4
551 [21 11
16
in]
D
A
416 [16 3
550 [2158 in]
8
88 [3 1
2
in]
R
D
E
L
F
FINISHED GRADE
6
2901 [114163 in]
4000 [15712 in]
G
1610 [6338 in]
3490 [13738 in] TYP
760 [2915
16 in]
5
16
1278 [50
1610 [6338 in]
in]
in]
G
N
I
AW
FRONT ELEVATION
SCALE 1:35
549 [2158 in]
1099 [4314 in]
1667 [6558 in]
15°
833 [32 3
4 in]
1665
[65 9
16 in] TY
P
601 [23 5
8 in]
P
M
SA
POST EMBEDMENT IS PRELIMINARY
(SEE NOTES)
15
15
2
16
17
16
17
DESIGN CRITERIA:
2012 EDITION OF THE INTERNATIONAL BUILDING CODE, WITH LOCAL AMENDMENTS.
LOADS:
MODULE DEAD LOAD = 2.23 PSF
SLOPED ROOF SNOW LOAD = 0 PSF
A
B
GENERAL:
1. THE STRUCTURAL CONSTRUCTION DOCUMENTS REPRESENT THE FINISHED STRUCTURE.
THEY DO NOT INDICATE THE METHOD OR SEQUENCE OF CONSTRUCTION. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR AND PROVIDE ALL MEASURES NECESSARY TO
PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE,
BUT NOT BE LIMITED TO, BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION
EQUIPMENT, ETC. THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR THE
CONTRACTOR'S MEANS, METHODS, TECHNIQUES, SEQUENCES FOR PROCEDURE OF
CONSTRUCTION, OR THE SAFETY PRECAUTIONS AND THE PROGRAMS INCIDENT THERE TO
(NOR SHALL OBSERVATION VISITS TO THE SITE INCLUDE INSPECTION OF THESE
ITEMS). THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN AND
IMPLEMENTATION OF ALL SCAFFOLDING, BRACING AND SHORING.
2. WHERE REFERENCE IS MADE TO VARIOUS TEST STANDARDS FOR MATERIALS, SUCH
STANDARDS SHALL BE THE LATEST EDITION AND/OR ADDENDA.
3
3335
[131 5
16 in]
2700
[106 5
2503 116 in]
[98 in]
2
838 [33
in]
in]
SEE DRAWING VIEWS
14
INSTALLATION TOLERANCES:
LATERAL POST PLACEMENT IS ±5.0"
TOTAL LATERAL DEVIATION OF POSTS WITHIN AN ARRAY IS ±5.0"
POST HEIGHT VARIATION TOLERANCE IS ±0.40"
POST VERTICALITY TOLERANCE <2.0° IN ALL DIRECTIONS
POST ROTATIONAL TOLERANCE <±7.0°
ARRAY TILT ANGULAR TOLERANCE ±1.0°
C
in]
SCALE:
14
WIND DESIGN:
DESIGN BASED UPON WIND TUNNEL TEST REPORT # RC 1127/0611_1e
WIND SPEED = 115 mph (3 SECOND GUST)
EXPOSURE: C
RISK CATEGORY = II
B
4
SHEET: 1 of 2
13
1
4000 [15712 in]
A
19 [34 in]
UNLESS THIS DRAWING IS SIGNED
AND SEALED BY A LICENSED
STRUCTURAL ENGINEER, IT IS
A PRELIMINARY DESIGN AND SHALL K
NOT BE USED FOR CONSTRUCTION.
v.01
JOB NUMBER: v
11
PRELIMINARY
Drawing Number:
Project Site:
10200 [401169 in]
8
H
J
REVISIONS:
6200 [24418 in]
416 [16 3
G
ISOMETRIC VIEW
SCALE 1:40
3
2
F
MODULE SIZE:
RACKING SYSTEM DESIGNED FOR MODULE SIZE: 1665 mm x 991 mm x 46 mm
VERTICAL MODULE GAP: 23 mm
HORIZONTAL MODULE GAP: 5 mm
Dimensions and Specifications
1
H
NOTE: RECOMMENDED SPEED FOR INSTALLATION OF SELF-DRILLING 1/4" DIAMETER
SCREWS IS 1200-1800 RPMS.
Exterior Racking Structure
2
E
TORQUE:
TORX BOLT FOR RAPID 2+ MODULE CLAMPS IS 14 N-M (10.5 FT-LBS)
M6 AND 1/4" BOLT TORQUE IS 6 N-M (4.5 FT-LBS)
M8 AND 5/16" BOLT TORQUE IS 14 N-M (10.5 FT-LBS)
M10 AND 3/8" BOLT TORQUE IS 30 N-M (23 FT-LBS)
M12 AND 1/2" BOLT TORQUE IS 50 N-M (37 FT-LBS)
M16 AND 5/8" BOLT TORQUE IS 121 N-M (89 FT-LBS)
M20 AND 3/4" BOLT TORQUE IS 244 N-M (180 FT-LBS)
2340 [9281 in]
SECTION A-A
SCALE 1:15
CHECKED: REVIEWED: APPROVED:
1
E
STEEL:
1: ALL BOLTS AND WASHERS SHALL BE 304 STAINLESS STEEL CLASS 2 (A2-70).
2. ALL NUTS SHALL BE 316 STAINLESS STEEL CLASS 2 (A4-70)
I
610 [24 in]
J
5
G
N
I
AW
FRONT ELEVATION
SCALE 1:35
in]
8
G
Y
L
N
O
D
ALUMINUM:
1. ALL ALUMINUM SHALL CONFORM WITH THE LATEST ALUMINUM DESIGN HANDBOOK.
2. ALL ALUMINUM SECTIONS SHALL BE:
1610 [6338 in]
in]
1665
1278
C
a. SEMI-HOLLOWS AND HOLLOWS SHALL BE 6105-T5, 6005A-T6, OR 6005-T5
b. SOLIDS SHALL BE 6063-T6
601 [23 5
F
3490 [13738 in] TYP
[98 1 in]
838 [33
in]
[131 5
B
GENERAL:
1. THE STRUCTURAL CONSTRUCTION DOCUMENTS REPRESENT THE FINISHED STRUCTURE.
THEY DO NOT INDICATE THE METHOD OR SEQUENCE OF CONSTRUCTION. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR AND PROVIDE ALL MEASURES NECESSARY TO
PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE,
BUT NOT BE LIMITED TO, BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION
EQUIPMENT, ETC. THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR THE
CONTRACTOR'S MEANS, METHODS, TECHNIQUES, SEQUENCES FOR PROCEDURE OF
CONSTRUCTION, OR THE SAFETY PRECAUTIONS AND THE PROGRAMS INCIDENT THERE TO
(NOR SHALL OBSERVATION VISITS TO THE SITE INCLUDE INSPECTION OF THESE
ITEMS). THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN AND
IMPLEMENTATION OF ALL SCAFFOLDING, BRACING AND SHORING.
2. WHERE REFERENCE IS MADE TO VARIOUS TEST STANDARDS FOR MATERIALS, SUCH
STANDARDS SHALL BE THE LATEST EDITION AND/OR ADDENDA.
FINISHED GRADE
C
4
15
DESIGN CRITERIA:
2012 EDITION OF THE INTERNATIONAL BUILDING CODE, WITH LOCAL AMENDMENTS.
WIND DESIGN:
DESIGN BASED UPON WIND TUNNEL TEST REPORT # RC 1127/0611_1e
WIND SPEED = 115 mph (3 SECOND GUST)
EXPOSURE: C
RISK CATEGORY = II
[34
991 [39 in] TYP
14
13
1
10200 [401169 in]
A
5
C
Y
L
N
O
D
ALUMINUM:
1. ALL ALUMINUM SHALL CONFORM WITH THE LATEST ALUMINUM DESIGN HANDBOOK.
2. ALL ALUMINUM SECTIONS SHALL BE:
a. SEMI-HOLLOWS AND HOLLOWS SHALL BE 6105-T5, 6005A-T6, OR 6005-T5
b. SOLIDS SHALL BE 6063-T6
STEEL:
1: ALL BOLTS AND WASHERS SHALL BE 304 STAINLESS STEEL CLASS 2 (A2-70).
2. ALL NUTS SHALL BE 316 STAINLESS STEEL CLASS 2 (A4-70)
E
TORQUE:
TORX BOLT FOR RAPID 2+ MODULE CLAMPS IS 14 N-M (10.5 FT-LBS)
M6 AND 1/4" BOLT TORQUE IS 6 N-M (4.5 FT-LBS)
M8 AND 5/16" BOLT TORQUE IS 14 N-M (10.5 FT-LBS)
M10 AND 3/8" BOLT TORQUE IS 30 N-M (23 FT-LBS)
M12 AND 1/2" BOLT TORQUE IS 50 N-M (37 FT-LBS)
M16 AND 5/8" BOLT TORQUE IS 121 N-M (89 FT-LBS)
M20 AND 3/4" BOLT TORQUE IS 244 N-M (180 FT-LBS)
F
NOTE: RECOMMENDED SPEED FOR INSTALLATION OF SELF-DRILLING 1/4" DIAMETER
SCREWS IS 1200-1800 RPMS.
MODULE SIZE:
RACKING SYSTEM DESIGNED FOR MODULE SIZE: 1665 mm x 991 mm x 46 mm
VERTICAL MODULE GAP: 23 mm
HORIZONTAL MODULE GAP: 5 mm
FOUNDATIONS:
1. FOUNDATION DESIGN IS BASED UPON GEOTECHNICAL REPORT/TESTING REQUIREMENTS
BY SCHLETTER; PROJECT NO: TO BE DETERMINED
ALL CONSTRUCTION SHALL CONFORM TO THE REQUIREMENTS OF THE GEOTECHNICAL REPORT.
GEOTECHNICAL TEST LOADS: UPLIFT (Tension) = 5.17 kips, LATERAL (Shear) = 1.52 kips.
2. THE STRUCTURAL ENGINEER IS NOT RESPONSIBLE FOR ANY GEOTECHNICAL ASPECTS OF
THIS PROJECT. IF THE INSTALLER NOTICES ANY SOIL THAT HAS DIFFERENT DRIVING
CHARACTERISTICS THAN EXISTED FOR TESTED DRIVEN POSTS, CONTACT THE ENGINEER
IMMEDIATELY.
NOTE:
THE POST EMBEDMENT DEPTH IS PRELIMINARY AND SHALL BE VERIFIED BY THE STRUCTURAL
ENGINEER OF RECORD PRIOR TO CONSTRUCTION. BASED UPON ON SITE TESTING BY THE
GEOTECHNICAL ENGINEER.
I
G
H
I
ISOMETRIC VIEW
SCALE 1:40
893 [3518 in]
J
2340 [9218 in]
SECTION A-A
SCALE 1:15
NO. DRAWN:
0
1
2
3
4
CHECKED: REVIEWED: APPROVED:
5
J
REVISIONS:
Client:
Ground Mount FS 2V x 10 15°
6
7
8
2/13
EMAIL: MAIL@SCHLETTER.US
WWW.SCHLETTER.US
1
Drawing Number:
Project Site:
2
3
4
5
6
7
8
9
Dimensions and Specifications
ISSUED BY: SCHLETTER INC.
PROPRIETARY AND CONFIDENTIAL
10
JOB NUMBER: v
11
12
UNLESS THIS DRAWING IS SIGNED
AND SEALED BY A LICENSED
STRUCTURAL ENGINEER, IT IS
A PRELIMINARY DESIGN AND SHALL K
NOT BE USED FOR CONSTRUCTION.
v.01
Exterior Racking Structure
1001 COMMERCE CENTER DR. | SHELBY, NC 28150
TEL: (704) 595 - 4200 | Fax: ( 704) 595 - 4210
K 5
PRELIMINARY
13
SHEET: 1 of 2
SCALE:
14
SEE DRAWING VIEWS
15
16
© Schletter Inc • 1001 Commerce Center Drive • Shelby, North Carolina 28150 • Tel: (704) 595 - 4200 • Fax: (704) 595 - 4210
mail@schletter.us • www.schletter.us
17
MI-008
072216
FS SystemTM Ground Mount Installation Manual
Installation Tools
•
String line with Wood Line Blocks
for level foundation post installation
•
Marker/permanent pen
•
Tape Measure
•
Rubber Mallet
for locking wedge
•
2’ Carpenter’s Square
for square girder-to-purlin connection
•
Torpedo Level or Protractor
•
Wrench and/or Socket
for all bolted connections
•
Torque Wrench
•
Ratchet and/or Rechargeable Power Drill
•
Torx® Bit
for Rapid5K™ Module Clamps
15 mm
17 mm
18 mm
19 mm
TX40
•
•
3/8” Socket
for self-drilling screws
3/8” Socket
Hex Head Wrench
for standard module clamps
6 mm
© Schletter Inc • 1001 Commerce Center Drive • Shelby, North Carolina 28150 • Tel: (704) 595 - 4200 • Fax: (704) 595 - 4210
mail@schletter.us • www.schletter.us
MI-008
072216
3/13
FS SystemTM Ground Mount Installation Manual
Foundation Post Installation
1. Survey Proposed Site
•
Review final drawing at least one week
prior to post installation. Drawing will
include information vital to the proper
installation of the foundation posts such
as the embedment depth, post-to-post
spacing, slope, rotation, and
installation tolerances.
•
Please note: Schletter does not provide
construction layouts.
•
For longer racks, intermediate stakes may
be required.
•
Posts are installed vertical to grade.
•
Installation tolerances:
Lateral post placement is ±5.0”
Total Lateral deviation of posts within an array is ±5.0”
Post height variation tolerance ±0.50”
Post verticality tolerance <2.0° in
all directions
Post rotational tolerance <±7.0°
Array tilt angular tolerance ±1.0°
•
For East-West slopes greater than 7°,
contact your Schletter representative
4 inches
Tolerance
Maximum 7°
4” Maximum
Embedment depth
±0.5”
±7°
Rotation
Lateral cantilever
4/13
E-W slope
Elevation difference between
adjacent post
Support distance
© Schletter Inc • 1001 Commerce Center Drive • Shelby, North Carolina 28150 • Tel: (704) 595 - 4200 • Fax: (704) 595 - 4210
mail@schletter.us • www.schletter.us
MI-008
072216
FS SystemTM Ground Mount Installation Manual
2. Post Installation
•
Position each post at the respective
installation locations based on the
completed stake-out (use a forklift).
•
Position the hydraulic ram (GAYK) at the
installation location and lift the post into
position beneath the ram head.
•
Level mast of hydraulic ram.
•
Level post using a torpedo level.
•
Advance the post approximately two feet
into the subsurface then re-level the post.
•
Advance the post to the embedment
depth as shown on the final drawing.
•
Position string lines: bottom string line is
used for correct placement of post; top
string line indicates correct embedment
depth; string is run from the top of the
front post to the top of the last post.
•
When installing subsequent posts, ram
until the hammer head touches the top
string line.
Mark each post location using soil nails
with flagging
Position posts on marked locations
(use a forklift)
Ram two posts at opposite ends of array
for string line
Use string lines as guide to determine
correct placement and depth of posts
Position hydraulic ram and lift post into
position beneath ram head
Hammer head touching top string line
indicates correct depth is reached
© Schletter Inc • 1001 Commerce Center Drive • Shelby, North Carolina 28150 • Tel: (704) 595 - 4200 • Fax: (704) 595 - 4210
mail@schletter.us • www.schletter.us
MI-008
072216
5/13
FS SystemTM Ground Mount Installation Manual
Mounting the Individual Assembly Groups
1. Optional Post Splice
•
Verify torque on all bolts.
•
Splices are used to extend the length of
a post.
•
Splice location will vary depending
on project.
•
Consult project specific drawings.
1
2. Head Assembly
Install shim plates between post and splice tubing using 3/4” bolts,
washers, and nuts (front view)
2
3
4
0.051
Secure head assembly in place using
supplied hardware.
•
Head assembly has horizontal, vertical,
and rotational adjustment.
9.911
WEIV TNORF
4 : 1 ELACS
WEIV EDIS
4 : 1 ELACS
8
D
0.722
6.58
D
•
6
C
•
C
Run string line from first to last head piece
and adjust in between.
3
7
WEIV CIRTEMOSI DELBMESSA
5 : 4 ELACS
Head assembly
9
3. Mount Girder/Strut Assembly
B
•
B
2
Slide girder onto bolt within the
head assembly.
4
1
TSIL STRAP
LAIRETAM
REBMUN TRAP
THGIEW
NOITPIRCSED
957.1
6T-3606
5 noitareneG ,daeH SF ,esaB
100-005241
896.1
6T-3606
200-005241
5 noitareneG ,poT ,daeH SF
760.0
dliM ,leetS
2A ,339NID ,03x01M ,daeHxeH ,wercS
030-016349
820.0 01-81 iNrC5X/1034.1
2A ,9437 NID ,5.01 ,rehsaW
100-000349
430.0
)4A( 613 SS 4A ,3296 NID ,01M ,detarreS ,egnalF ,tuN
010-219349
600-000349
572.0
dliM ,leetS 2A ,139NID ,021x21M ,daeHxeH ,wercS
640.0
6T-3606
5 noitareneG ,etalP edilS oN
000-300161
070.0
6T-3606
mm18 ,5 noitareneG ,eveelS ,recapS
300-005241
750.0
1754.1 4A ,3296 NID ,21M ,detarreS ,egnalF ,tuN
210-219349
:LAIRETAM :SECNARELOT
8672 NID
•
Align strut with pre-drilled hole in
foundation post then secure with
provided hardware and tighten.
1
•
:STNEMMOC
000-005241
21/11/4 HD THGIEW
ETAD YB NOISIVER
2
IMPORTANT! Insert locking wedge into
the connector using a rubber mallet
immediately after installing the girders.
After locking wedge is inserted it cannot
be removed.
•
Verify that assemblies are set
in place.
•
Strut-girder connection should be torqued
to 10 ft-lbs to avoid compression of
the assembly.
1
#
5 noitareneG ,ylbmessA daeH
:REBMUN TRAP
000-005241
YTQ METI
1
1
1
2
2
3
4
2
2
5
1
6
2
7
1
8
1
9
:YB NWARD
SRC
:DEKCEHC
:ETAD N OITAERC
2102/21/4
:ETAD DE KCEHC
: # TRAP DLO
:REMOTSUC / TCEJORP / ELTIT
5
WEIV CIRTEMOSI DEDOLPXE
5 : 4 ELACS
:TF/TW
:THGIEW
A
:NWORC :EZIS
C
1 FO 1:TEEHS 2^mm 571.421842 :AERA NWOHS SA :ELACS
3
Locking wedge
:SUTATS A
desaeleR
:GFM
:REM OTSUC
:E TAD LAV OR PPA GFM
:DEVORPPA
:ETAD LAVOR P PA GNE
REBMU N YL BMESSA
:R OTCAR TN OCBUS
Place head assembly onto foundation post
with M10 bolt, washer, and nut
smetsyS gnitnuoM raloS
S
RETTELH.cCnI
4
Insert locking wedge into connector after
installing girder and strut assembly
Installed girder and strut assembly on foundation post
6/13
© Schletter Inc • 1001 Commerce Center Drive • Shelby, North Carolina 28150 • Tel: (704) 595 - 4200 • Fax: (704) 595 - 4210
mail@schletter.us • www.schletter.us
MI-008
072216
FS SystemTM Ground Mount Installation Manual
4. Mount Purlins
•
Align purlins as shown on system
specific drawings.
•
Loosen upper mounting clamp
on girder.
•
Slide lip of purlin under lower
mounting clamp.
•
Verify purlins are installed perpendicular
to girder.
•
Secure purlin in place by tightening
upper mounting clamp over top lip
of purlin.
•
It may be necessary to loosen lower
mounting clamp. Mark location with
indelible marker prior to loosening.
Verify that purlin is positioned correctly before tightening mounting clamps
5. Optional Splice Connection
•
In order to form a longer section, splices
may be included to join two purlins.
•
Splices shall be located as specified on
project specific drawings.
•
Attach first purlin to girder as stated
in Step 4.
•
Insert splice piece halfway into the end
of first purlin section and secure in place
using one self-drilling screw.
•
Loosely attach second purlin section to
girder and slide over splice piece that is
connected to first purlin. Secure purlin in
place using one self-drilling screw.
•
Verify purlin is installed in correct location
as specified on the project
specific drawings.
•
Secure assembled purlin in place by
tightening all upper mounting clamps.
Installed purlin (side view)
Insert splice into end of two purlins and secure in place using self-drilling screws
© Schletter Inc • 1001 Commerce Center Drive • Shelby, North Carolina 28150 • Tel: (704) 595 - 4200 • Fax: (704) 595 - 4210
mail@schletter.us • www.schletter.us
MI-008
072216
7/13
FS SystemTM Ground Mount Installation Manual
6. Install Overcurrent Protection Device
(grounding)
•
Shares bolt that connects strut to post.
•
Remove serrated flange and install
grounding lug; torque to specification.
•
Accommodates stranded or solid copper
wire (14 gauge to 2 gauge).
•
Must use bare copper wire to connect
to the grounding lug. If using insulated
grounding wire, remove at least
2 inches of insulation to expose
copper wire.
Loosen or remove top portion of
grounding lug and insert grounding
wire into appropriate groove
Grounding wire must extend through
grounding lug by at least 1/4”
7. Ground Path Diagram
Grounding Clamp
Purlin Splice
Module Frame
Purlin
Girder
Head
Assembly
Foundation
Post
8/13
© Schletter Inc • 1001 Commerce Center Drive • Shelby, North Carolina 28150 • Tel: (704) 595 - 4200 • Fax: (704) 595 - 4210
mail@schletter.us • www.schletter.us
MI-008
072216
FS SystemTM Ground Mount Installation Manual
Optional Accessories
1. Bonding Jumper
•
Electrically bonds adjacent systems
forming a continuous ground path.
•
Available in 6-inch to 48-inch lengths.
•
Used for expansion joints or other breaks
in the racking system.
Bonding jumper can be installed on top
channel of purlin using M8 hardware
Bonding jumper connects directly
to purlin
2. Cable Management
•
3
2
If cable management was ordered with the
system, install before modules are in place.
1
3
4
•
4
WIDTH of
COMBINER
BOX
ENGTH
LENGTH
D
2
1
Snap ProKlip-Multi 8 into M8 3top channel
3
on purlin.
2
1
2
1
D
239.0
•
Snap
4 ProKlip2000-P or ProKlip-Q
cable clip onto side of S Purlin.
WIDTH of
239.0
COMBINER
BOX
WIDTH of
COMBINER
BOX
WIDTH of
LENGTH
COMBINER
BOX
•
3

2
D
5
239.0
For a more detailed cable
management
239.0
7
installation see:
LENGTH
ProKlip-Multi 8 (129065-008)
WIDTH of
COMBINER
BOX
3
9
239.0
Cable Management Installation Guide
2
6
7
5
9
4
2
7
6
9
5
1
5
4
ProKlip2000-P (129012-002)
ProKlip-Q (129012-001)
2
7
6
9
5
2
5
3
1
4
6
5
3
1
4
C
7
9
2
6
5
4
LENGTH
C
LENGTH
C
8
10
Attach cable duct (128014-000)
against side of purlin with selfdrilling screws
8
10
8
10
8
10
B
8
Combiner box mount is installed against
exterior end of foundation post
10
SIDE VIEW
SCALE 1 : 10
B
ASSEMBLY VIEW
SCALE 1 : 6
NT VIEW
SIDE VIEW
LE 1 : 10
SCALE 1 : 10
FRONT
VIEW
SIDE VIEW
B
SCALE 1 : 10
SCALE 1 : 10
FRONT
SIDE VIEW
NOTE:
INC. - PROPRIETARY
ANDVIEW
CONFIDENTIAL
d only with the express,
written1consent
SCALE
: 10 of the Co: Schletter Inc.
SCALE 1 :1.10MAXIMUM COMBINER BOX PLUS
ASSEMBLY VIEW
SCALE 1 : 6
ASSEMBLY VIEW
SCALE 1 : 6
ASSEMBLY VIEW
PARTS LIST
SCALE 1DESCRIPTION
:6
ITEM QTY PART NUMBER
MATERIAL
MASS
SAE J2340
6105-T5
6105-T5
0.157 kg
MATERIAL
MASS
DATE:
LECREATION
/ PROJECT
/
CUSTOMER:
NOTE:
kg/m
or
kg/sq
m:
RT
PART
#:
TOLERANCES:
MATERIAL:
ISSUED BY: SCHLETTER INC. - PROPRIETARY AND CONFIDENTIAL
4
4KIT119025-00200 Threaded Rod, 3/8"-16 UNC, 304 SS, Grade B8, L=200mmPARTS
304 SS
0.109 kg
CONTENTS WEIGHT = 100 lbs. PER
8/5/2013Reproduction of any kind only with the express, written consent of the Co: Schletter Inc.
LIST
1
1 143008-000
Post, 8, Custom, Galvanized
SAE J2340 A
s reserved.
1.
MAXIMUM
COMBINER
BOX
PLUS
000-000
TORQUE:
5
8AS943912-001
0.015 kg
Nut,ITEM
Flange,
Serrated,
3/8"-16
UNC, 316 SS
316 SS
CHECKED DATE:
2.
PARTS
LIST
REFLECTS
2
KITS,
PART
NUMBER
MATERIAL
QTY
DESCRIPTION
MASS
2
2
123001-001
Rail,
DN0,
Custom
6105-T5
WEIGHT:
CREATION DATE:
NOTE:
kg/m or kg/sq
TOLERANCES:
MATERIAL:
M6 AND 1/4" BOLT
TORQUE IS CONTENTS
6 N-M (4.5 FT-LBS)
ISSUED
BY:#RT
SCHLETTER
ANDm:CONFIDENTIAL
WEIGHT =6 1004lbs.943919-126
PER KIT3 Nut,
- 16 UNC, ASME-B18.2.2,
316 SSGalvanized
Square,
316 SS PARTS LIST
0.013 kg
OLD
PART
: PART #: INC. - PROPRIETARY
SHOWN
ABOVE
8/5/2013
1
13/8"143008-000
Post,
Custom,
2 000009-555
Angle, 40x40,
T=4,8,L=200,
2 Slots 41x11mm
6105-T5 SAE J2340
0.157 kg
All Directions,
rights reserved.
Reproduction
of any
kind only with the express, written consent
the Co:
Inc.
embly
Combiner
Box Mount,
M10
M8ofAND
5/16"Schletter
BOLT TORQUE
IS 14 N-M (10.5 FT-LBS)
CUSTOMER:
1.
MAXIMUM
COMBINER
BOX
PLUS
7
4
943914-010
0.013
kg
Nut,
Square,
M10,
DIN
557,
316
SS
316
SS
CHECKED
DATE:
2.
PARTS
LIST
REFLECTS
2
KITS,
AS
TITLE / PROJECT
/ CUSTOMER:
ITEMThreaded
NUMBER
QTY PART
DESCRIPTION
2
2 123001-001
Rail,
DN0, Custom
6105-T50.109 kgMATERIAL
CREATION DATE:
M10 AND
BOLT TORQUE
IS 30 N-M (23 FT-LBS)
4
4 119025-00200
Rod,
3/8"-16
UNC, 304 SS, Grade B8,
L=200mm 304 SS
A
# REVISIONWEIGHT:
BY DATE
Y:
kg/m or kg/sq
m: 3/8"
TOLERANCES:
MATERIAL:
CONTENTS
WEIGHT
= 100 lbs. PER
KIT3 M10,2 DIN
8
4 943921-010
Washer,
304 SS
316
SS 41x11mm 0.004 kg
OLD PART #RT: PART #:
8/5/2013
M12 AND 1/2" BOLTTORQUE:
TORQUE ISSHOWN
50 N-M (37ABOVE
FT-LBS)
1125,
143008-000
Post,
Custom,
Galvanized
on.Hurley
000009-555
Angle,
40x40,
T=4,8,
L=200,
Slots
6105-T50.015SAE
0.157 kg
000000-000
APPROVAL DATE:
PART NUMBER:
5
8 943912-001
kg J2340
Nut,1 Flange,
Serrated,
3/8"-16
UNC,
3162 SS
316 SS
E: MFGCROWN:
CUSTOMER:
9/13
©
Schletter
Inc
•
1001
Commerce
Center
Drive
•
Shelby,
North
Carolina
28150
•
Tel:
(704)
595
4200
•
Fax:
(704)
595
4210
MI-008
CHECKED
DATE: / PROJECT
2.
PARTS
LIST
REFLECTS
2
KITS,
AS
9
4
129010-001
KlickIn,
M10
Polyamide
(Nylon)
0.002
kg
TITLE
/
CUSTOMER:
M16
AND
5/8"
BOLT
TORQUE
IS
121
N-M
(89
FT-LBS)
NOTE:
000000-000
M6 AND 1/4" BOLT TORQUE IS 6 N-M (4.5 FT-LBS)
ISSUED BY: SCHLETTER INC.WEIGHT:
- PROPRIETARY AND CONFIDENTIAL
2 Nut,2 Square,
123001-001
Rail,3/8"-16
DN0, Custom
D:
4
4 119025-00200
Threaded
Rod,
UNC, 304316
SS,SS
Grade B8,316
L=200mm
304 SS
6
4 943919-126
3/8" - 16 UNC,
ASME-B18.2.2,
SS
0.0136105-T5
kg 0.109 kg
LIST
ANDwritten
3/4" BOLT
TORQUE
IS 244
N-M (180
FT-LBS)
AllDirections,
rights reserved.
Reproduction
kind only
with the M20
express,
consent
the Co:
Schletter
Inc.
OLD
PART
: of any
Screw,5 Hex Head,
DIN
933,
304 SS
304UNC,
SS
0.024 kg PARTS
Assembly
Combiner
Box #Mount,
M10
SHOWN
M8ofAND
5/16"
BOLT
TORQUE
IS 14ABOVE
N-M10(10.5 4FT-LBS)
mail@schletter.us
• www.schletter.us
072216
1. 943610-020
MAXIMUM
PLUS
3M10x20mm,
000009-555
Angle,
40x40,
T=4,
L=200,
Slots 41x11mm
000000-000
MFG APPROVAL DATE:
TORQUE:
8BOX
943912-001
Nut,
Flange,
Serrated,
3162 SS
316 SS 0.0136105-T5
ENG APPROVAL DATE:
7 COMBINER
4 943914-010
kg 0.015 kg
Nut,2 Square,
M10,
DIN QTY
557,
316
SS3/8"-16
316 SS DESCRIPTION
ITEM
PART
NUMBER
1DATE:
SHEET:
OF / 1CUSTOMER:
ALE:
AS SHOWN
CREATION
M10 AND
ISTORQUE
30 N-M (23
FT-LBS)
TITLE
/ PROJECT
# REVISION
BY DATE
DRAWN AREA:
BY: CUSTOMER:
kg/m or kg/sq
m: 3/8"
TOLERANCES:
MATERIAL:
RT PART
#:
M6BOLT
AND TORQUE
1/4" BOLT
IS 6CONTENTS
N-M (4.5 FT-LBS)
4
4
119025-00200
Threaded
Rod,
3/8"-16
UNC,
304
SS,
Grade
B8,
L=200mm
304
WEIGHT
=
100
lbs.
PER
KIT
6
4 943919-126
316 316
SSGalvanized
Nut,
Square,
- 16 UNC, ASME-B18.2.2,
316 SS 0.004 kg SS 0.013 kg
8
4 943921-010
Washer, M10,
DIN
SS
3 Box Mount, M10
1 Post, 8, Custom,
8/5/2013
M12 AND 1/2"
IS TORQUE
50 N-M (37IS2FT-LBS)
rkInProgress
1125, 304
13/8"SS
143008-000
Dillon.Hurley
PART NUMBER:
SIZE: CROWN:
Assembly Directions,
Combiner
ASSEMBLY NUMBER
M8BOLT
AND TORQUE
5/16"
BOLT
14 N-M (10.5 FT-LBS)
000000-000
MFG APPROVAL DATE:
TORQUE:
5
8AS943912-001
ENG APPROVAL DATE:
Serrated,
316 SS 0.013 kg
7
4 2943914-010
Nut, Square,Nut,
M10,Flange,
DIN 557,
316 SS3/8"-16 UNC, 316 SS
316 SS
CHECKED DATE:
2. PARTS LIST REFLECTS
KITS,
PART #:
kg/m or kg/sq m:
TOLERANCES: MATERIAL:
CONTENTS WEIGHT = 100 lbs. PER KIT
1
1 143008-000
Post, 8, Custom, Galvanized
2. PARTS
LIST
REFLECTS 2 KITS, AS
FRONT
SIDE
VIEW
NOTE:
2
2 123001-001
Rail, DN0, Custom
ED BY: SCHLETTER INC. WEIGHT:
- PROPRIETARY
ANDVIEW
CONFIDENTIAL
ASSEMBLY PARTS
VIEWLIST
Deproduction
PART # : of any kind only with the express,
written1
consent
SHOWNSCALE
ABOVE 1 :1.10
SCALE
: 10 of the Co: Schletter Inc.
2 000009-555
Angle, 40x40, T=4, L=200, 2 Slots
41x11mm1 : 6
MAXIMUM COMBINER BOX3 PLUS
SCALE
ITEM QTY PART NUMBER
DESCRIPTION
FS SystemTM Ground Mount Installation Manual
Module Mounting
1. Position Modules
20 mm
•
Position end clamps approximately 20 mm
from end of purlin.
•
Position first module and secure
prepositioned end clamps; do not tighten.
•
Attach middle clamps to purlin on the
exposed side of first module.
•
Place second module and secure using the
middle clamp; do not tighten.
•
Repeat until end of row, then secure
exposed side with end clamps.
End (left) and middle (right)
grounding clamps
Rapid5KTM
Grounding Clamp
Horizontal module orientation
2. Secure Modules
•
Verify that the module clamp is fully
engaged on the purlin and that the
module clamp is aligned with the module
frame.
•
Secure in place to specified torque.
•
When mounting modules, please observe
the clamping points specified by the
module manufacturer.
Vertical module orientation
23 mm max.
1.5 mm
maximum
middle clamp
to module
offset
5 mm
If adjustable end clamps are
provided, slide attachment on to
desired height.
10/13
Allowable gaps between modules
© Schletter Inc • 1001 Commerce Center Drive • Shelby, North Carolina 28150 • Tel: (704) 595 - 4200 • Fax: (704) 595 - 4210
mail@schletter.us • www.schletter.us
MI-008
072216
FS SystemTM Ground Mount Installation Manual
Torque Specifications and Tolerances
Systems are specifically designed for each project. Please reference the specific project drawing for allowable tolerances and
recommended torque for each size of bolt used in the system.
In the event of deviation from approved drawings, contact Schletter immediately.
Torx Bolt for Rapid5K Module Clamps
14 N-M
10.5 FT-LBS
M6 and 1/4” Bolt
6 N-M
4.5 FT-LBS
M8 and 5/16” Bolt
14 N-M
10.5 FT-LBS
M10 and 3/8” Bolt
30 N-M
23 FT-LBS
M12 and 1/2” Bolt
50 N-M
37 FT-LBS
M16 and 5/8” Bolt
121 N-M
89 FT-LBS
M20 and 3/4” Bolt
244 N-M
180 FT-LBS
Note: Recommended speed for installation of self-drilling 1/4”
diameter is 1200-1800 RPMS.
Equipment Grounding
Many PV installations contain more than one mounting system. Such cases call for electrically bonding each of the different
manufacturers systems. Since individual racks are fully bonded units it is only necessary to connect individual racks together
from one single point to another single point.6 Only use stainless steel hardware when connecting harnesses or jumpers to the
mounting system. Take care to prevent copper wires from directly contacting aluminum surfaces as this will cause corrosion. For
this purpose, Schletter offers a bonding jumper (see page 9).
•
The PV INSTALLER of Schletter’s electrically bonded FS system must provide the components necessary for the final
connections to the grounding electrode system. Typically the installation will incorporate a grounding electrode (ground
rod), appropriately sized copper wire, rated wire connectors, and grounding lugs which are rated for this purpose. The PV
INSTALLER must follow all manufacturers’ installation literature. Installation must comply with all applicable NEC/CSA sections
including but not limited to; NEC 250 (Grounding and Bonding), NEC 690 (Solar Photovoltaic Systems), CSA 22.1 (Safety
Standard for Electrical Installations), and all other applicable state, and local electrical code requirements.
•
PV INSTALLER shall be fully responsible for all connections between Schletter’s bonded FS system and PV grounding electrode
system.
•
Equipment grounding conductors shall be no less than 14AWG (copper) or 12AWG (aluminum).
•
Equipment grounding conductors can be connected to any exposed metallic portion of rack system provided that:
a.
b.
c.
d.
connection area is sufficiently sized
dissimilar metals are not in direct contact
connection does not interfere with other components
connection is protected from damage
Safety Precautions
Follow proper installation and safety procedures at all times. Edges of parts may be sharp. Follow proper lifting procedures.
6
Schletter recommends two bonding jumpers to connect separate systems for redundancy.
© Schletter Inc • 1001 Commerce Center Drive • Shelby, North Carolina 28150 • Tel: (704) 595 - 4200 • Fax: (704) 595 - 4210
mail@schletter.us • www.schletter.us
MI-008
072216
11/13
FS SystemTM Ground Mount Installation Manual
Maintenance
•
Yearly inspection of system should be conducted to maintain optimal performance.
•
Visually inspect for signs of damage, wear, corrosion, or movement. Replace any affected components immediately.
•
Check for loose wiring
•
Mechanical details of the structure
•
At least 2% of bolted connections must be checked using a calibrated torque wrench. The torque wrench must have a display or be a click type torque wrench.
•
Torque wrench should be set at 50% of the intended tightening torque. Check is successful if the bolt cannot
be loosened.
•
If >10% of the checked bolted connections are loose, the check has to be increased by a factor of five.
•
If more than 10% of connections are still loose, all bolted connections much be checked.
•
Tighten to specified torques
•
Requirements per ASME B107 and AISC
•
WARNING: Risk of death by electric shock
•
Maintenance should only be performed by qualified personnel.
For More Information
For more information on the FS System, please see:
 FS System Product Sheet
 Ground Mount System Overview
 FS Mounting Kit Product Sheet
Torx® is a registered trademark of the Camcar Corp. division of Textron Industries.
12/13
© Schletter Inc • 1001 Commerce Center Drive • Shelby, North Carolina 28150 • Tel: (704) 595 - 4200 • Fax: (704) 595 - 4210
mail@schletter.us • www.schletter.us
MI-008
072216
FS SystemTM Ground Mount Installation Manual
Approved Module Manufacturers
Bonding and Grounding
Canadian Solar
CS6X-310|315|320P
CS6X-P-FG
CS6K-P-FG
CS6K-M
CS6K-M AB
CS6P-P
CS6P-P-SD
CS6V-M
Yingli Green Energy
YL300C|295C|290C|285C|280C|275C-30b
YL290D|285D|280D|275D|270D-30b
YL340D|335D|330D|325D|320D|315D-36b
YL275P|270P|265P|260P|255P|250P-29b
YL260P|255P|250P|245P|240P-29b
YL325P|320P|315P|310P|305P|300P-35b
Hanwha Q Cells
Q.PRO BFR G4|G4.1|G4.3
Q.PLUS BFR G4.1
Q.PRO L G4.1
Q.PLUS L G4.1|G4.2
LG
LGxxxN1C-G4
LGxxxN1W-G4
LGxxxS1C-G4
LGxxxS1W-G4
LGxxxN1K-G4
LGxxxN2C-B3
LGxxxN2W-B3
SolarWorld
Sunmodule SW 80 MONO RHA
Sunmodule SW 150 POLY R6A
Sunmodule SW 150 MONO R6A
Sunmodule SW 100 POLY RGP
Sunmodule Plus SW 280-295 MONO
Sunmodule Plus SW 285-300 MONO (5-busbar)
Sunmodule Plus SW 280-290 MONO BLACK
(5-busbar)
Sunmodule Plus SW 275-290 MONO BLACK
Sunmodule Pro-Series SW 260 POLY WOB
Sunmodule Protect SW 275-280 MONO BLACK
Sunmodule SW 320-325|340-350 XL MONO
Trina
TSM-PD14
TSM-PD05
TSM-PD05.08
TSM-PD05.05
TSM-PEG5
TSM-PEG5.07
TSM-PEG14
TSM-PEG40.07