nle-001\temp2\tku\Data Sheet

advertisement
AC Current transducer AP-B10
IPN = 10 .. 400 A
Split core transducer for the electronic measurement AC waveforms
current, with galvanic isolation between the primary (High power) and
the secondary circuits (Electronic circuit). Switch selectable ranges
and RMS 0-5V and 0-10V switch selectable voltage output.
Electrical data
Primary Nominal Current
I PN (A.t.RMS)
10,25,50
50,75,100
100,150,200
200,300,400
RL
VC
IC
Analogue Output Signal
V OUT (V)
0-5V
0-5V
0-5V
0-5V
or
or
or
or
0-10V
0-10V
0-10V
0-10V
Load resistance
Supply voltage
Current Consumption
Limitation of voltage output (0-10V)
Limitation of voltage output (0-5V)
Overloaded input current
AP
AP
AP
AP
Type
Features
50 B10
100 B10
200 B10
400 B10
• RMS output
• Split core type
• 5V & 10V switch selectable voltage
≥ 10
kΩ
+24 ±5% V DC
< 30
mA
14
V
7
V
no limitation
X
L
VOE
VOT
TCε G
tr
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Frequency bandwidth (±1%)
< ±1
% of IPN
< ±0.5 % of IPN
< ±0.5 % of IPN
±1
mV/K
±0.1
%/K
< 150
ms
30 .. 2000 Hz
General data
TA
TS
m
dCp
dCl
CTI
Ambient operating temperature
Ambient storage temperature
Mass
Protection type
Creepage distance
Clearance distance
Comparative tracking index (Group I)
UL94 classification
• Eliminates insertion loss
• Switch selectable ranges
Advantages
Accuracy-Dynamic performance data
ε
output
• DIN mounting & Panel mounting
-20 .. +60
°C
-20 .. +85
°C
90
g
IP20
5.5
mm
5.5
mm
600
V
V0
• Large aperture for cable up to
Ø18mm
• High isolation between primary and
secondary circuits
• Easy to mount
Applications
• Automation systems
Analog current reading for remote
monitoring (e.g. motor) and
software alarms.
• Panelmeters
Simple connection displays power
consumption.
Insulation category
Vb
Vd
Ve
Vw
Rated Voltage
300
with IEC 61010-1 standards and following conditions :
- Single insulation
- Over voltage category CAT III
- Pollution degree PD2
- None uniform field
R.m.s. voltage for AC insulation test, 50Hz, 1mn
5
R.m.s. voltage for partial discharge extinction @ 10pC 1.5
Peak impulse withstand voltage 1.2/50µs
6.1
If insulated cable is used for the primary circuit, the voltage category
could be improved with the following table :
Cable insulation (primary)
Category
HAR 05
600V CAT III
HAR 07
1000V CAT III
Notes : Installation and maintenance should be done with power supply disconnected.
V
kV
kV
kV
041029/3
The operator must have accrediation to install this material.
The users must take care of all protection gurantee against electrical shock.
.
LEM Components
www.lem.com
Dimensions AP(R)-B10
Output Vo ltage
Selection Switch
(unit : mm, 1mm = 0.0394 inch)
Front Vie w
Left View
55
16.40
DIN size35.50
69
14.80
Rang e Selection Switch
4.7 0
20
40(distance between screws)
21
33.50
37
Axis of ape rture
25
18 .50
67
Plug-in connector included : XW4B-03C1-H1 (OMRON)
18.50
Bottom View
Mechanical characteristics
• General tolerance
• Primary aperture
±1 mm
∅ 18.5 mm
• Panel mounting
• Distance between holes
2 holes ∅ 4.0 mm
40.0 mm
For panel mounting, replace M4 screws by new one (not supplied) with appropriate length to panel´s thickness.
Connections
• Wires up to 2 mm ∅
0-5, 10V Selectable
GND
RL
OUTPUT
+24VDC
AP/APR
+24VDC
Is
OUT
Output
Connector
3(-) 2(out)1(+)
Output Switch
Ip
GND
Range Switch
Front
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.