PAGES
DIVISION 26 -- ELECTRICAL
260519
260526
260529
260533
260553
262200
262416
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS ------------HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS ---------------RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS ------------------IDENTIFICATION FOR ELECTRICAL SYSTEMS -----------------------------LOW-VOLTAGE TRANSFORMERS ----------------------------------------------PANELBOARDS --------------------------------------------------------------------------
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS PAGE 1
1
1
1
1-2
1
1
1-2
SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
1.1
MATERIALS
A.
Conductors and Cables:
1.
2.
1.2
Conductors: Copper.
Conductor Insulation: Type THHN/THWN-2
CONDUCTOR MATERIAL APPLICATIONS
A.
Feeders: Copper Solid for No. 10AWG and smaller; stranded for No. 8 AWG and larger.
B.
Branch Circuits: Copper. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and
larger.
1.3
CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND
WIRING METHODS
A.
Exposed Feeders: Type THHN/THWN-2, single conductors in raceway
B.
Feeders Concealed in Ceilings, Walls, Partitions, and Crawlspaces: Type THHN/THWN-2,
single conductors in raceway.
C.
Exposed Branch Circuits, Including in Crawlspaces: Type THHN/THWN-2, single conductors
in raceway
D.
Branch Circuits Concealed in Ceilings, Walls, and Partitions: Type THHN/THWN-2, single
conductors in raceway.
1.4
FIELD QUALITY CONTROL
A.
Testing: By Contractor.
B.
Infrared Scanning: For each splice in cables and conductors No. 3 AWG and larger.
END OF SECTION 260519
260519-1
Frostburg State University
SERF Building Electrical Upgrades
SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
1.1
QUALITY ASSURANCE
A.
1.2
Quality Standard for Grounding and Bonding Materials and Equipment: UL 467.
PRODUCTS
A.
Insulated Conductors: Copper wire or cable.
B.
Bare Copper Conductors:
1.
2.
3.
4.
5.
6.
Solid conductors.
Stranded conductors.
Tinned conductors.
Stranded bonding conductors.
Copper tape braided bonding jumpers.
Tinned-copper braided bonding jumpers.
C.
Grounding Bus: Predrilled rectangular copper bars with stand-off insulators.
D.
Connectors: Bolted.
1.3
FIELD QUALITY CONTROL
A.
Ground Resistance Testing: By Contractor-engaged agency.
END OF SECTION 260526
260526-1
Frostburg State University
SERF Building Electrical Upgrades
SECTION 260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
1.1
PERFORMANCE REQUIREMENTS
A.
1.2
Rated Strength: Minimum structural safety factor of five times the applied force.
PRODUCTS
A.
Support, Anchorage, and Attachment Components:
1.
2.
3.
4.
5.
6.
7.
Steel slotted support systems with metallic coatings.
Nonmetallic slotted support systems.
Raceway and cable supports.
Steel conduit and cable hangers, clamps, and associated accessories.
Support for non-armored conductors and cables in vertical conduit risers.
Structural steel for fabricated supports and restraints.
Mounting, Anchoring, and Attachment Components:
a.
b.
c.
d.
e.
f.
B.
Powder-actuated fasteners.
Mechanical-expansion anchors.
Concrete inserts.
Clamps for attachment to steel structural elements.
All steel, springhead toggle bolts.
Threaded hanger rods.
Fabricated Metal Equipment Support Assemblies: Welded or bolted steel shapes.
END OF SECTION 260529
260529-1
Frostburg State University
SERF Building Electrical Upgrades
SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
1.1
MATERIALS
A.
Metal Conduits, Tubing, and Fittings:
1.
2.
3.
4.
5.
GRC.
EMT.
FMC: Zinc-coated steel
LFMC.
Fittings:
a.
b.
B.
EMT: Steel compression type.
Expansion fittings.
Nonmetallic Conduits, Tubing, and Fittings:
1.
2.
RNC.
Fittings: Match conduit.
C.
Metal Wireways and Auxiliary Gutters: Sheet metal with hinged covers.
D.
Surface Metal Raceways: Metal, galvanized steel, with snap-on covers.
E.
Boxes, Enclosures, and Cabinets:
1.
2.
3.
4.
5.
6.
7.
1.2
Metal Outlet and Device Boxes: Aluminum.
Nonmetallic outlet and device boxes.
Small sheet metal pull and junction boxes.
Cast-metal access, pull, and junction boxes.
Box extensions.
Hinged-Cover Enclosures: Metal
Cabinets: Galvanized steel.
RACEWAY APPLICATION
A.
Indoors:
1.
2.
3.
4.
5.
6.
7.
B.
Exposed, Not Subject to Physical Damage: EMT
Exposed, Not Subject to Severe Physical Damage: EMT
Exposed and Subject to Severe Damage: GRC.
Concealed: EMT
Connection to Vibrating Equipment: FMC, except LFMC in damp or wet locations.
Damp or Wet Locations: GRC.
Boxes and Enclosures: Type 1.
Minimum Raceway Size: 3/4-inch (21-mm) trade size.
260533-1
Frostburg State University
SERF Building Electrical Upgrades
C.
Raceway Fittings: Compatible with raceways and suitable for use and location.
1.
2.
3.
Rigid and Intermediate Steel Conduit: Threaded rigid steel conduit fittings.
EMT: compression, steel fittings.
Flexible Conduit: Fittings listed for use with flexible conduit.
END OF SECTION 260533
260533-2
Frostburg State University
SERF Building Electrical Upgrades
SECTION 260553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS
1.1
QUALITY ASSURANCE
A.
1.2
Comply with ANSI A13.1 and IEEE C2.
PRODUCTS
A.
Power and Control Raceway Identification: Vinyl labels.
B.
Power and Control Cable Identification: Vinyl labels.
C.
Conductor Identification: Color-coding conductor tape.
D.
Floor Marking Tape: Pressure-sensitive vinyl tape.
E.
Warning Labels and Signs: Self-adhesive warning labels.
F.
Instruction Signs: Engraved, laminated acrylic or melamine plastic.
G.
Equipment Identification Labels: Engraved, laminated acrylic or melamine plastic.
END OF SECTION 260553
260553-1
Frostburg State University
SERF Building Electrical Upgrades
SECTION 262200 - LOW-VOLTAGE TRANSFORMERS
1.1
PRODUCTS
A.
General Transformer Requirements:
1.
B.
Coils: Copper, continuous windings without splices except for taps.
Distribution Transformers:
1.
2.
3.
4.
5.
6.
Core: One leg per phase.
Coils: Copper, continuous windings without splices except for taps.
Enclosure:
a.
Ventilated.
Taps for Transformers 25 kVA and Larger: Two 2.5 percent taps above and two 2.5
percent taps below normal full capacity.
Insulation Class: 220 deg C, with maximum 150 deg C rise above 40 deg C.
Features:
a.
b.
c.
d.
e.
1.2
K-factor rating.
Electrostatic shielding.
Wall brackets.
Fungus proofing.
Low sound level.
SOURCE QUALITY CONTROL
A.
1.3
Transformers: Factory tested and inspected.
FIELD QUALITY CONTROL
A.
Testing: By Contractor.
END OF SECTION 262200
262200-1
Frostburg State University
SERF Building Electrical Upgrades
SECTION 262416 - PANELBOARDS
1.1
QUALITY ASSURANCE
A.
1.2
Manufacturer Qualifications: ISO 9001 or 9002 certified.
WARRANTY
A.
1.3
Panelboards: 18 months.
PRODUCTS
A.
General Requirements for Panelboards:
1.
2.
Constructed to withstand seismic forces.
Enclosures: Surface mounted.
a.
b.
3.
4.
Incoming Mains: Top.
Phase, Neutral, and Ground Buses: Copper.
5.
Conductor Connectors:
a.
b.
c.
6.
7.
B.
Material: Hard-drawn Copper.
Main and Neutral Lugs: Mechanical type.
Ground Lugs and Bus-Configured Terminators: Mechanical type.
Percentage of Future Space Capacity: Ten percent.
Service equipment label for panelboards incorporating one or more main service
disconnecting and overcurrent protective devices.
Panelboard Short-Circuit Current Rating: Fully rated to interrupt symmetrical short-circuit
current available at terminals.
1.
2.
3.
4.
C.
Front: Hinged Cover.
Directory card.
Mains: Circuit Breaker or Lugs.
Branch Overcurrent Protective Devices for Circuit-Breaker Frame Sizes 125 A and
Smaller: Bolt on Circuit Breakers.
Branch Overcurrent Protective Devices for Circuit-Breaker Frame Sizes Larger than
125 A: Bolt on Circuit Breakers.
Branch Overcurrent Protective Devices: Fused switches.
Lighting and Appliance Branch-Circuit Panelboards:
1.
2.
Mains: Circuit Breaker or Lugs.
Branch Overcurrent Protective Devices: Bolt on circuit-breaker type.
262416-1
Frostburg State University
SERF Building Electrical Upgrades
3.
D.
Doors: Concealed hinge.
Disconnecting and Overcurrent Protective Devices:
1.
MCCB: Interrupting Capacity.
a.
b.
Circuit Breakers: Thermal magnetic type.
MCCB Features and Accessories:
1)
2)
3)
4)
2.
E.
Panelboard labels.
Breaker labels.
Circuit Directory: Computer generated, metal frame with transparent cover.
Accessories:
1.
2.
1.4
Type-HD fused switch.
Identification:
1.
2.
3.
F.
Lugs: Mechanical style.
Appropriate for Application: Type SWD for switching fluorescent lighting
loads; Type HID for feeding fluorescent and HID lighting circuits.
Rating Plugs: Three-pole breakers with ratings greater than 150A.
Multipole units enclosed in a single housing with single handle.
Accessory set including tools.
Portable test set.
FIELD QUALITY CONTROL
A.
Testing: By Contractor.
END OF SECTION 262416