Catalog Number Notes Type System Accessories FEATURES SYA IPCL The SYA IPCL photosensor is an ambient light sensing device that connects to a Synergy™ panel, Synergy Remote Station (SYRSP EXT or DEQ LC), SwitchPak or SIMPLY5 Sensor Connector (S5SC), as an analog input. The photosensor provides control of lighting in response to ambient light conditions. • Indoor applications • Color compensated to provide accurate readings • Easy mounting • Class-2 wiring • Linear response curve • Multiple set-points from a single photocell when used with Synergy or SwitchPak panels • Ideal for Open Loop operation operation in Daylight-Harvesting applications • Switch or dim loads based on light level INDOOR ANALOG PHOTOSENSOR INSTALLATION The SYA IPCL is best used in Open Loop applications. Open Loop is defined as when the photosensor VIEWS DAYLIGHT ONLY, and does not respond to or “see” the electric light it controls. skylight skylight roof viewing angle roof lens half-stop viewing angle light well mount on south light well electric lighting mount on south electric lighting Open Loop Top-Lit Applications: To avoid direct exposure to sunlight, photosensor placement shall be on the south face of the light well (facing north) mounted toward the bottom of the light well. If placement cannot be45 isolated from electric light, then the contribution from electric light can be minimized with an Indoor Photosensor Lens Half-Stop. *6"-36" from glazing roof *6"-36" from glazing roof electric lighting electric lighting 45 viewing angle blinds viewing angle lens half-stop Open Loop Side-Lit Applications: Photosensor placement should be as close as possible to vertical glazing. Window treatments, such as blinds, should be inside the photosensor viewing angle. Placement is usually in the window well or the ceiling mounted near the window. Placement from 6"-36" is acceptable as long as the light seen from the window is the major contributor. This may require the use of an Indoor Photosensor Lens Half-Stop. ORDERING INFORMATION Example: SYA IPCL Choose the boldface catalog nomenclature that best suits your needs and write it on the appropriate line. Order accessories as separate catalog number. SYA IPCL Series SYA IPCL Analog photosensor Controls Sheet #: SYA IPCL SYA IPCL Indoor Photosensor SPECIFICATIONS ELECTRICAL • Accuracy: +/- 1% at 70°F (21°C) • Input Voltage: 12-24 VDC, Class 2, 3 conductor #18 AWG. MECHANICAL • Indoor Sensor – Mounts to accessible ceiling tile or light well with supplied nut and washer, or to 1/2” knockout. Mount from 6 inches to 36 inches from windows, central to the area being controlled. Indoor – 0-100 Fc = 10-0 VDC CONSTRUCTION • Material – UV stabilized plastic. • Color – White. DIMENSIONS ENVIRONMENTAL • Operating Temperature: 32-105°F (0-41°C). • 10-90% non-condensing .50” (12.7) .75” (19) FUNCTIONAL • Response – Linear to ambient light level over entire range. Single set point with deadband to prevent cycling or linked to outputs for multi-step or variable response; transmit up to 100 steps onto Synergy network. 1.86” (47.2) WIRING DIAGRAM SYA IPCL YELLOW/BLACK BLUE GREEN SYRSP EXT GRAY RED POWER PROVIDED BY SYNERGY ENCLOSURE CONNECTION TO SYRSP EXT RED BLACK YELLOW WHITE SYA CABLEA4 SYA IPCL DIM PLT COM ON 24V OFF DIM PLT COM ON 24V OFF DIM PLT COM ON 24V OFF DIM PLT COM ON 24V OFF SYPM 8L GREEN BLUE RED ON AUTO ON 24V OFF PWR AIN COM DIM PLT COM ON 24V OFF PWR AIN COM OFF COM ON OFF DIM PLT COM CONNECTION TO SYPM 8L RELAY MODULE ANALOG INPUTS Synergy Lighting Controls Sheet #: SYA IPCL ©2010 Acuity Brands Lighting, Inc. 1335 Industrial Blvd, Conyers, GA 30012 Phone: 800-533-2719 www.synergylightingcontrols.com