PE100-1 - Leviton.com

advertisement
PE100-1
Product
Specifications
PE100-1 Power Extender
APPLICATION
PE100-1 Power Extender
Leviton’s PE100-1 Power Extender allows a dimming
zone’s power handling capacity to be extended to a
full 1920W/VA on 120V input power. It allows a zone
to dim or switch a fully loaded circuit of incandescent
and magnetic low voltage loads only.
FEATURES & BENEFITS
• Works with incandescent, magnetic low voltage,
halogen or neon/cold cathode lighting
• Low-end trim available for setting the
minimum brightness level
• Emulates the characteristics of the dimmer
that it is connected to in terms of dimming
range and resolution
• Works with any Dimensions Multi-zone
Controller/Dimmer to extend load capacity
on any zone
4.50
(114.3 mm)
2.80
(71.1 mm)
4.72
(119.9 mm)
2.06
(52.3 mm)
MOUNTING
All Power Extenders must have 4-1/2"
spacing above and below each unit for
proper ventilation and heat dissipation
(refer to figure 3). Line voltage wiring
should be at least 6ft away from sound or
electronic equipment wiring. Mount Power
Extender to wall box with “TOP” facing up
as follows: For Wall Box Mounting (refer
to figure 1), for Flush Mounting (refer to
figure 2) and for Panel Mounting (not
shown), proceed as follows:
a. The enclosure must be in accordance
with all local and national electrical codes.
b. Leviton DOES NOT recommend using a
door to enclose the front of a panel, since
this restricts airflow to the controls.
c. If mounting multiple controls in an
enclosure:
• Ambient timperature within an enclosure
“MUST REMAIN BETWEEN”32 o-104o F
(0 o-40 oC).
• If not mounting in a metal enclosure, all
units “MUST” be mounted in a wall box.
d. To improve heat dissipation of controls,
remove the faceplate from the unit.
Figure 3: Front View Spacing
1900 Box
TOP
2 Gang Raised Cover
Raised Cover
Mounting Screws
(4 Places)
TOP
4-1/2" (11.4 cm)
Minimum
Power
Extender
Power Extender
Wallplate
Figure 1: Surface Mounting
TOP
1900 Box
2 Gang Raised Cover
Raised Cover
Mounting Screws
(4 Places)
4-1/2" (11.4 cm)
Minimum
TOP
Power
Extender
Figure 2: Flush Mounting
Power Extender
Wallplate
SPECIFICATION SUBMITTAL
JOB NAME:
CATALOG NUMBERS:
JOB NUMBER:
Leviton Mfg. Co., Inc.
59-25 Little Neck Pkwy • Little Neck, NY 11362-2591 • Tech Line: 1-800-824-3005 • Fax: 1-800-832-9538
Visit our Website at: www.leviton.com
1
Product
Specifications
PE100-1
.........................
SPECIFICATIONS
Wiring Diagram 1A: Single Feed Wiring Application w/Controller
Warranty: Limited 2-Year Warranty
(Load)
Single Feed Wiring
Line Hot can be
controlled by one
circuit breaker as
long as the total
load does not
exceed the
Power
rating of the
Extender
circuit breakers.
D3206/08
Controller/Dimmer
HOT
Neutral
Line
SWITCH
HOT
LOAD
NEUTRAL
NEUTRAL
• For Box-Mounted Dimmers: Must use a
120V, 600W Incandescent version from
the following families: IllumaTech™,
Mural™, True Touch™, ToggleTouch™,
TouchPoint™ and Home Controls
• For Monet™ installations, use a 120V,
600VA Monet Magnetic Low Voltage
dimmer (requires a Neutral wire)
• For dimmers that include a Neutral
wire (such as some scene-capable
dimmers), the dimmer Neutral wire
must be connected
• For Architectural Systems: Works
with all families
Hot (Black)
(120VAC)
Environmental
Operating Temperature Range:
0ºC to 40ºC
Storage Temperature Range:
-10ºC to 85ºC
Relative Humidity: 20%-90%
non-condensing
CONTROL
Compatibility
Load
Green
Ground
LOAD
Neutral (White)
Wiring Diagram 1B: Single Feed Wiring Application w/Dimmer
Used if Dimmer/Switch has Neutral connection
Hot (Black)
(120VAC)
(Load)
Single Feed Wiring
Line Hot can be
controlled by one
circuit breaker as
long as the total
load does not
exceed the
rating of the
Power
Extender
circuit breakers.
Physical
Color: Aluminum clear anodized extruded heat sink with a snap-on
molded white cover
Size: 4.72"L x 4.5"W x 0.5"H (120mm x 114mm x 12.7mm)
HOT
LOAD
NEUTRAL
SWITCH
HOT
Dimmer
CONTROL
Input Voltage: 120V, 50/60Hz
Load Rating: 1920W/VA
Load Output Power: Phase independent of control device
Dimmer Input: 120V 50/60Hz
Testing/Code Compliance: UL Listed, CSA Certified and FCC Part 15
NEUTRAL
Electrical
White
Black
Load
Green
Ground
LOAD
Neutral (White)
Wiring Diagram 2A: Dual Feed Wiring Application w/Controller
Wiring Diagram 2B: Dual Feed Wiring Application w/Dimmer
Used if Dimmer/Switch has Neutral connection
Hot (Black)
Line 1 (120VAC)
(Load)
Green
Ground
LOAD
Hot (Black)
Line 2 (120VAC)
Neutral 2 (White)
Neutral 2 (White)
Wiring Diagram 3: Dual Feed Wiring Application w/Dimmer and Two Power Extenders
Hot (Black)
Line (120VAC)
(Load)
(Load)
D3206/08
Controller/Dimmer
HOT
SWITCH
HOT
NEUTRAL
LOAD
NEUTRAL
Power
Extender
CONTROL
SWITCH
HOT
HOT
LOAD
NEUTRAL
NEUTRAL
CONTROL
Neutral (White)
Dual Feed Wiring
The Input control
circuit and the
Output load circuit
can be supplied
by two circuit
Power
breakers on
Extender
a single phase
or by two
separate Hot (Black)
Line 1 (120VAC)
phases.
Neutral
Line
Load
Note:
Up to 4 Power
Extenders can
be Connected
together.
Green
Ground
LOAD 1
Neutral (White)
Hot (Black)
Line 2 (120VAC)
LOAD 2
Neutral (White)
Leviton Mfg. Co., Inc.
59-25 Little Neck Pkwy • Little Neck, NY 11362-2591 • Tech Line: 1-800-824-3005 • Fax: 1-800-832-9538
Visit our Website at: www.leviton.com
© Copyright 2003 Leviton Manufacturing Co., Inc. All rights reseved. G-6723/G3
SWITCH
HOT
HOT
LOAD
Dimmer
NEUTRAL
Dual Feed Wiring
The Input control
circuit and the
Output load circuit
can be supplied by
two circuit breakers
Power
on a single phase
Extender
or by two
separate phases.
Load
Hot (Black)
Line 2 (120VAC)
(Load)
Neutral 1 (White)
Neutral
Line
SWITCH
HOT
LOAD
HOT
CONTROL
NEUTRAL
Dual Feed Wiring
The Input control
circuit and the
Output load circuit
can be supplied by
two circuit breakers
on a single phase Power
Extender
or by two
separate phases.
NEUTRAL
D3206/08
Controller/Dimmer
CONTROL
Neutral 1 (White)
NEUTRAL
Hot (Black)
Line 1 (120VAC)
White
Black
Load
Green
Ground
LOAD
Download