I Operating Instructions Electronic Star Delta Timer Type: 7PU60 20 Operating Voltage range : Not Applicable for 7PU6020 3NW2 0.8 to 1.1 x Us (Us = Rated Voltage) Setting accuracy: ±25% in sector scale Recovery time: £ 150 ms Repeat accuracy: ± 0.5% Selection The Siemens 7PU60 20 Timers provide adjustable star time i.e.[(2-20/6-60 sec)/(20-200 sec)] and fixed Star to Delta transfer time (i.e. 50 ms) Timers type 7PU60 20–3N..are provided with 2 time setting ranges. Selection of range is done with Selector Switch, Provided on the front plate of timer. Timer type 7PU60 20–4N.. has one setting range (Selector switch is not functional) AC Voltage 110V 220/240V 380/440V 220/400V Technical Data Rated insulation Voltage : 500V AC Voltage Code J2 N2 T2 W2 Installation Type Setting time range 7PU60-20-3N.. 2-20/6-60 secs. (can be selected with selector switches) 7PU60 20-4N.. 20-200 secs (Selector Switch is not functional) Snapped on standard DIN mounting rail (35 mm) to EN50022 or Fixed by two M 3.5 screws on a plain surface. Plain washers and Rated operating Current : Ie AC 15 at 220V=3A at 440V=1A Ie DC 13 at 220V=0.1A Can be mounted in any position. Allowable conductor Cross Section. – Solid 2 x 2.5 mm2 – Stranded with end sleeves: 2 x 1.5 mm2 Terminal screws: M3.5 Tightining Torgue: 80 to 120 N–Cm Terminal diagram: See front plate of the timer Functional diagram: Ref. Fig: 2 2) ‘Y’ contact (17/18) closes instantanously and remains closed for set time ty which is adjustable between 2-20/6-60/ 20-200 sec. 3) ‘D’ contact (27/28) closes after set time (ty) + dead time (td) (i.e. Star to Delta transfer time + 50 ms) M3.5 Fixing screws (2X) 88 DIN Rail mounting feature 95 Operating temperature: -25ºC to + 55ºC For mounting dimension refer fig-1 1) Apply rated voltage to terminals A1/A2 Setting time ranges 23.5 spring washers must be used. 112 15 Fig. - 1 2 Fig. - 2 Connection Diagram: Control Circuit Wiring Diagram Refer Fig – 3 1/N/PE ~ 50Hz Supply S0 = Push Button OFF (1NC) S1 = Push Button ON (1NO) K1 = Line Contactor with 2NO Auxiliary Contacts. K2 = Star Contactor with 1NO + 1NC Auxiliary Contacts. K3 = Delta Contactor with 1 NC Auxiliary Contacts. K4 = Star Delta Timer with 1NO instantaneous and 1NO delayed Auxiliary Contacts. F1 = Overload Relay. F0 = Backup Fuse. Main Circuit Wiring Diagram Refer Fig – 4 3 ~ 50Hz V K1 K2 K3 F1 F0 = = = = = Standard Products Division Control Systems & Products Thane Belapur Road, Thane - 400 601 Tel. : (022) 760 0001 Fax : (022) 760 0076 Siemens Ltd. SGR-01-111-006 This replaces SGR-01-111-005 Line Contactor Star Contactor Delta Contactor Overload Relay Backup Fuse Instruction No. 4I–0088–0115786 203 Product development is a continuous process. Consequently the data indicated in this leaflet is subject to change without prior notice. For latest issue contact our sales offices.