COPT Presentation - NAIOP Northern Virginia

advertisement

Secure I Reliable I Flexible

COPT DC-6 Tour for CareFirst

Agenda

»

»

Welcome and Introductions

»

»

COPT Data Center Practice and COPT DC-6 Overview

Tour of the data center facility

Qs & As

COPT Overview

Why Partner with COPT

COPT Delivers client-focused data center solutions to meet the strategic and operational requirements of our customers, especially for mission critical secure environments.

»

Publicly traded (NYSE:OFC) $4.6 Billion Real Estate Investment Trust (REIT)

»

Own and operate 3.4 million SF of data centers in 4 states

»

Over 1.3 million SF of company data centers support USG and other government agencies

»

Office and data center assets in Maryland, Virginia, Texas, Alabama

»

Committed to long term ownership and tenant satisfaction

COPT Data Center Expertise

Data Center Projects

Northrop Grumman Corporation IT/VITA

Data Centers (2)

COPT DC-6 Data Center

Other Federal Government & Defense

Contractor Clients (ATFP & DCID compliant)

Multiple facilities

Data Center Projects

Total

Total

296,000 SF

243,000 SF

1,300,000 SF

1,582,000 SF

3,421,000 SF

Northrop Grumman IT/VITA data center

Lebanon, VA | 103,000 SF

COPT DC-6 | Manassas, VA | 233,000 SF

Northrop Grumman IT/VITA data center

Chester, VA | 193,000 SF

COPT’s Extensive Data Center Practice

»

»

COPT DC-6

9651 Hornbaker Road

Manassas, Virginia

Constructed in 2010

243,000 SF

COPT DC-6 Robust Fiber & Expansion Capability

EXPANSION LAND

COPT DC-6 Fiber Carriers

.

»

Current Connectivity Providers

»

»

»

»

»

»

»

»

»

Comcast

Verizon

AT&T

Orange

Sprint

Fiberlight

Lightower

LINX

Level 3

Zayo

»

»

»

»

»

»

»

»

»

»

»

Cogent

Hibernia Networks

Summit IG

FiberRing

IXreach

Novec

Tata Communications

TeliaSonera Int. Carrier

TW Cable

COX – at perimeter

NOVEC– at perimeter

COPT DC-6 Security Features

With a deep history of developing secure DoD-rated government office and data center facilities, COPT is uniquely qualified to secure your digital assets.

DC-6 has the necessary physical security to meet the most stringent Federal

Government requirements.

Anti-Terrorism/Force Protection (ATFP) compliance with a controlled perimeter greater than 150’ from the building

FISMA/DoD/ICD-705 support

Biometric access controls, man traps & video surveillance zones

K-12 fences and guarded security entrances

24x7x365 onsite security

SCIF space designs ready for construction

COPT DC-6 Data Center Cooling Advantage

»

Segregation of MEP from IT

»

»

»

»

Scales easily

Minimizes disruption

Preserves raised floor rack space

Hard security separation

»

»

AHU vs. CRAC

»

»

»

»

160 ton AHU v. 20 ton CRAC

VFD Drives

Unique Return Air plenum

Supports 300 w/sf (@N+1 MIN)

Chilled Water Loop

»

»

»

Concurrently maintainable

No water over raised floor

Taps for in-rack cooling

COPT DC-6 Central Chilled Water Plant

Exhaust Louvers Above

Intake Louvers Below

Under Floor Plenum

AHU

Warmed Water

Chilled Water

AHU AHU AHU

The COPT DC-6 Advantage

»

»

»

Location

Not on same power generation as Ashburn

Outside major flight paths to Dulles

International Airport, 15 miles away

30 miles west of Washington, DC

Operational

Energy Efficient

»

Designed PUE of 1.4

Lower Cost of Operations

»

CRAC-free design provides 10% power savings

»

Owned water sources provide savings

»

»

Tax Savings

Prince William County equipment taxes are 7% lower than in Loudoun and Fairfax Counties

Savings of $125,000 for every million dollars in equipment over 10 years

Technical

»

CRAC-free design allows highly

dense deployments

»

Support for racks up to 58u for

“super dense” vertical growth

»

»

Support for up to 270w/sf with traditional air cooling

Designed to a N+1 minimum level of reliability

»

Classified as Tier III+ when measured against the Uptime Institute’s reliability criteria

COPT DC-6 Summary Specifications

Raised Floor

• 100,000 SF raised floor area

• 16 bays each supported by 1.875 MW

• 300 lbs/SF floor loads

• Ability to scale from 150 to 300 w/SF with no disruption or loss to secure raised floor zone

Fuel Storage

• Up to 500,000 gal. of ultra-low sulfur diesel fuel storage

• Fuel polishing system, w/ redundant fuel piping systems

Power System

• 17 x 2.25 MW Diesel Gensets

• Block redundant catcher system

• Rotary or Static UPS available

• No electrical paralleling

• No Emergency Power Off system

• 2 MW diesel generators provide N+2 power to

mechanical plant

• Power topology with backbone designed to

accommodate AC or DC power loads

• Modular design that provides ability to expand power in place with minimal disruption and lead time

Thank you and Questions

»