ITB No. EMERGEN_MR&T/CW RIDER 101 SCOPE OF WORK/SPECIFICATIONS FOR ANNUAL PREVENTATIVE MAINTENANCE, LOAD BANK TESTING & CORRECTIVE MAINTENANCE SERVICES ON EMERGENCY GENERATORS FOR THE UNIVERSITY OF TEXAS M. D. ANDERSON CANCER CENTER 1.0 GENERAL SCOPE: Current Operations: M. D. Anderson Cancer Center “M. D. Anderson” Utility Resource Management currently operates forty-five (45) emergency generators dispersed across the Texas Medical Center in a variety of clinical, research, administrative and operational buildings. M. D. Anderson has dedicated significant resources to the dependability and functionality of its emergency generator fleet. The contractor selected to provide services (“Contractor”) plays an important role in M. D. Anderson’s reconfiguration of its emergency generator maintenance, testing and repair operations. The current contract is designed as a process to be completed on an annual basis and is described below. 2.0 1.1 Contractor shall provide Preventative Maintenance, Load Bank Testing and Corrective Maintenance services for M. D. Anderson’s emergency generators at the locations described in Section 2.0. 1.2 Contractor shall meet the qualifications and performance requirements described in Section 3.0. 1.3 Contractor shall perform Preventative Maintenance Load Bank Testing and Inspections on a scheduled basis as described in Section 4.0. 1.4 Contractor shall perform Corrective Maintenance on an as needed basis as described in Section 5.0. 1.5 Quoting procedures are described in Section 6.0. 1.6 Hardcopy and verbal reporting procedures are described in Section 7.0. EQUIPMENT DESCRIPTION: 2.1 Location: M. D. Anderson Cancer Center 1515 Holcombe Boulevard Houston, Texas 77030 2.1.1 Gimbel # 1 and 2 generators: (2) 1,100 Kw Detroit diesel engine/generators sets (480 volt ac output) MDA_________ Contractor__________ Page 1 of 15 ITB No. EMERGEN_MR&T/CW RIDER 101 2.2 2.1.2 Bates Freeman generator: (1) 1,200 Kw Detroit diesel engine/generator set (480 volt ac output) 2.1.3 Clinic & Lutheran generators: (2) 2,000 Kw Mustang/Caterpillar diesel engine/generators sets ( 4160 ac volt output) 2.1.4 New Clark Clinic generators: (2) 1,125 Kw Detroit diesel engine/generators sets (480 volt ac output) 2.1.5 Basic Research generator: (1) 1,000 Kw Detroit diesel engine/generator set (480 volt ac output) Location: M. D. Anderson Cancer Center 6723 Bertner Houston, Texas 77030 2.2.1 2.3 Location: M. D. Anderson Cancer Center 6767 Bertner Houston, Texas 77030 2.3.1 2.4 ACB/CPB/Pressler generators: (4) 1,500 Kw Mustang/Caterpillar diesel engine/generator set paralleled (4,160 volt ac output) Location: M. D. Anderson Cancer Center 1400 Holcombe Boulevard Houston, Texas 77030 2.5.1 2.6 Basic Science Research generator: (4) 1,500 Kw Detroit diesel engine/generator sets paralleled (480 volt ac output) Location: M. D. Anderson Cancer Center 1220 Holcombe Boulevard Houston, Texas 77030 2.4.1 2.5 Alkek/CRB generators: (7) 1,750 Kw Mustang/Caterpillar diesel engine/generator set (480 volt ac output) Faculty Center generator: (1) 600 Kw CUMMINS diesel engine/generator set (480 volt ac output) Location: M. D. Anderson Cancer Center 1700 Holcombe Boulevard Houston, Texas 77030 2.6.1 Radiation Outpatient Clinic generator: (1) 11.5 Kw Onan diesel engine/generator set (480 volt ac output) MDA_________ Contractor__________ Page 2 of 15 ITB No. EMERGEN_MR&T/CW RIDER 101 2.7 Location: M. D. Anderson Cancer Center 7227 Fannin Houston, Texas 77030 2.7.1 2.8 Location: M. D. Anderson Cancer Center 8515 Fannin Houston, Texas 77030 2.8.1 2.9 Naomi generator: (1) 200 Kw Onan natural gas engine/generator set (480 volt ac output) Location: M. D. Anderson Cancer Center 7555 Fannin Houston, Texas 77030 2.9.1 2.10 Fannin Office Building generator: (1) 80 Kw Kohler diesel engine/generator set (480 volt ac output) SCRB #1 generators: (2) 500 Kw diesel Mustang/Caterpillar engine/generator set (480 volt ac output) Location: M. D. Anderson Cancer Center 7435 Fannin Houston, Texas 77030 2.10.1 SCRB #2 generators: (2) 500 Kw diesel Mustang/Caterpillar engine/generator set (480 volt ac output) 2.11 Location: M. D. Anderson Cancer Center 7777 Knight Road Houston, Texas 77030 2.11.1 SRB generators: (1) 500Kw & (1) 450 Kw diesel Onan engine/generator set (480 volt ac output). 2.11.2 MOD LAB & PPB generators: (1) 350 Kw & (1) 500 Kw diesel Onan engine/generator set (480 volt ac output) 2.12 Location: M. D. Anderson Cancer Center 8000 El Rio Houston, Texas 77030 2.12.1 El Rio generator: (1) 250 Kw diesel Kohler engine/generator set (480 volt ac output) MDA_________ Contractor__________ Page 3 of 15 ITB No. EMERGEN_MR&T/CW RIDER 101 2.13 Location: M. D. Anderson Cancer Center 3000 Pawnee Houston, Texas 77030 2.13.1 Pawnee generator: (1) 250 Kw diesel Onan engine/generator set (480 volt ac output) 2.14 Location: M. D. Anderson Cancer Center 5610 Guhn Road Houston, Texas 2.14.1 Guhn Road generator: (3) 1000 Kw diesel Mustang/Caterpillar engine/generator sets paralleled (480 volt ac output) 2.15 Location: M. D. Anderson Cancer Center 1100 Holcombe Boulevard Houston, Texas 2.15.1 HMB Road generator: (1) 1500 Kw diesel Detroit engine/generator sets (480 volt ac output) 2.16 Location: M. D. Anderson Cancer Center 1840 Old Spanish Trail Houston, Texas 2.16.1 Proton Therapy generator: (1) 750 Kw diesel Onan engine/generator sets (480 volt ac output) 2.17 Location: M. D. Anderson Cancer Center 1600 Holcombe Boulevard Houston, Texas 2.17.1 RHI Road generator: (1) 350 Kw diesel Onan engine/generator set (480 volt ac output) 2.18 Location: M. D. Anderson Cancer Center 6900 Fannin Houston, Texas 2.18.1 FHB generator: (1) 400Kw diesel Onan engine/generator sets (480 volt ac output) 2.19 Location: M. D. Anderson Cancer Center 7510 Bertner Houston, Texas MDA_________ Contractor__________ Page 4 of 15 ITB No. EMERGEN_MR&T/CW RIDER 101 2.19.1 O & M building generator: (1) 500 Kw diesel Onan engine/generator sets (480 volt ac output) 3.0 QUALIFICATIONS AND PERFORMANCE REQUIREMENTS: 3.1 Contractor must provide M. D. Anderson the names and resumes of the contract manager and lead technician. 3.2 A lead technician shall be present for all service calls unless otherwise approved by M. D. Anderson’s Project Coordinator. No more than two (2) lead technicians shall be designated. A non-lead technician may respond to emergency service calls if a lead technician is not available. 3.3 Unless notified otherwise, Contractor shall provide all tools and equipment necessary to meet all requirements specified by any subsequent maintenance contract arising from this bid. 3.4 Contractor will be placed on M. D. Anderson’s security access list. When admitted to the facility, Contractor shall report to M. D. Anderson’s Project Coordinator. 3.5 Contractor shall keep the job site free of debris and in a safe condition throughout the service call. 3.6 Contractor shall remove waste oil, oil filters and fuel filters from the job site for proper disposal. 3.7 Contractor shall use only new parts and supplies in accordance with the equipment manufacturer’s specifications unless otherwise authorized by the Project Coordinator. 3.8 Prior to the commencement of any service call, Contractor shall confer with the Project Coordinator prior to any proposed modifications to the maintenance descriptions and schedules described in this Scope of Work/Specifications. 3.9 Service calls shall not be considered complete until Contractor has submitted the suitable report to the Project Coordinator. Project Coordinator must approve and sign all reports within five (5) business days. 3.10 Contractor must have the necessary experience and capability to timely service and repair the following diesel engine brands: Detroit Diesel, Cummins, Caterpillar and ONAN. MDA_________ Contractor__________ Page 5 of 15 ITB No. EMERGEN_MR&T/CW RIDER 101 3.11 Schedule of Annual Requirements: 3.11.1 Contractor shall propose a qualified test lab that shall be reviewed and approved by M. D. Anderson’s Project Coordinator. 3.11.2 With an authorized M. D. Anderson representative in attendance, Contractor shall procure 100% of samples described in Paragraph 3.11.3 below from all generators. 3.11.3 Samples of engine lubrication oil, fuel oil and engine coolant from all generators must be sent to a qualified lab as described in Paragraph 3.11.1 above and this Paragraph 3.11. 3.11.4 M. D. Anderson must receive reports on samples no less than thirty (30) calendar days prior to Contractor’s initiation of the required annual Preventative Maintenance and Inspections. 3.11.5. Any laboratory samples received that are not acceptable shall immediately be discussed with M. D. Anderson’s Project Coordinator and appropriate corrective action shall be taken as needed in coordination with the Project Coordinator. 3.11.6 For all generator samples received that are acceptable, Contractor shall schedule such respective generators for Preventative Maintenance and Inspections no later than thirty (30) calendar days from date of receipt of acceptable samples. 3.11.7 After performing its annual Preventative Maintenance and Inspections on M. D. Anderson’s emergency generators, Contractor shall complete all records of Preventative Maintenance and Inspections on each generator and submit original records to M. D. Anderson’s Project Coordinator within five (5) business days except as described for LIFE SAFETY circuits in Paragraph 4.6.3 below. Contractor shall then discuss with the Project Coordinator any Corrective Maintenance and Repairs and shall schedule such in coordination with the Project Coordinator. 3.12 As its needs may change with the grown of the institution, M. D. Anderson may add additional generators, replace existing generators or remove certain generators from service during the course of the Preventative and Corrective Maintenance Agreement. Such changes shall be communicated to Contractor. Any modifications to Preventative Maintenance and Inspection pricing to reflect those changes shall be negotiated by Contractor and M. D. Anderson. MDA_________ Contractor__________ Page 6 of 15 ITB No. EMERGEN_MR&T/CW RIDER 101 4.0 PREVENTATIVE MAINTENANCE & INSPECTIONS: 4.1 4.2 Preventative Maintenance Schedule: 4.1.1 Each generator will be inspected and serviced once each year between February 28th and May 31st. The generators CANNOT be run between the hours of 6:00 a.m. and 12:00 noon any day of the week. If Contractor test runs any generator under the maintenance and repair contract in violation of this time restriction, M. D. Anderson shall consider any such action of Contractor as a material breach of the contract and may terminate the contract in accordance with its terms and conditions. 4.1.2 Contractor will assume all material, equipment and labor cost to complete the Preventative Maintenance and Inspections described in this Paragraph 4.0. PLEASE NOTE: In Paragraphs 4.2 through 4.8 below, all underlined descriptions that direct Contractor to repair or replace parts/equipment as needed or as necessary shall be considered separate from Preventative Maintenance and shall be appropriately quoted and provided to Project Coordinator, Barry Carmical, as Corrective Maintenance or Repair according to procedures described in Paragraph 6.2 below. Engines: 4.2.1 Lubrication System: Contractor will visually check for leaks and condition of the oil. The Contractor will provide the appropriate oil and filter, shall change engine lubricating oil and oil filters and shall properly dispose of the used oil and filters. 4.2.2 Air Cleaners: Contractor will visually check the condition of all air cleaners. Contractor shall check the condition of all air filters and will provide labor to change the filters as necessary. Wet Type Air Cleaners: Clean and change oil once a year. Clean or replace filter if needed. Contractor shall visually inspect cover seal gaskets on air filter assemblies and replace as needed. 4.2.3 Governor: Contractor will check and set speed, sensitivity and oil level in accordance with manufacturer’s recommendation. Contractor shall lubricate the over speed governor. 4.2.4 Cooling System: Contractor will check the condition of the belts and hoses and replace as needed. Contractor will check the overall general condition of the cooling system. Contractor will check the condition of the cooling water pump and replace seals as required. Contractor shall inspect the visible internal coolant system component condition for corrosion damage through the radiator opening. Contractor shall check the external condition of the radiator and clean as MDA_________ Contractor__________ Page 7 of 15 ITB No. EMERGEN_MR&T/CW RIDER 101 needed. Contractor shall check the antifreeze and add, if needed. Contractor shall check coolant level and change coolant filter. Contractor shall check the condition of the water-to-water heat exchanger and clean as needed. Contractor shall pressure test the coolant system and add additives to antifreeze once a year as needed. Contractor shall check heat exchanger zinc electrodes and repair or replace as needed.. 4.2.5 Ignition System: Contractor shall check the magneto and shall set the timing, if needed, in accordance with manufacturer’s recommendation. Contractor shall verify power loss sensing and automatic start along with all timer settings for sensing, start up, transfer, cool down and shut down. 4.2.6 Electrical System: 4.2.6.1 Contractor will hydrometer test the lead acid battery. Contractor will check and adjust said battery for proper charge. Contractor will check the condition of alternator/battery charger belts and adjust or replace as required. Contractor shall clean and lubricate battery posts and cables and check the battery charger for proper operation. Contractor shall inspect and lubricate the battery charging alternator bearings. Contractor shall check the specific gravity of the electrolyte of each cell of each battery and correct as necessary. 4.2.6.2 Contractor shall test and certify the generator amp and voltmeters at least once every two years to UL standards. Contractor shall place a tag in visible sight with the certification date and Contractor’s company name. 4.3 Fuel System: 4.3.1 Contractor will visually check all generator fuel systems for leaks. Contractor will check all visible connections for leaks and tighten as required. Contractor will check all flexible hoses and replace as needed. Contractor will check all fuel injectors and clean if needed. Contractor will check and clean all fuel strainers as necessary. Contractor shall check the fuel float switch and the fuel transfer pump. Contractor will check for water in day tank and main fuel tanks and for proper valve system alignment. Contractor shall drain water from fuel tanks and test fuel. Contractor shall add fuel treatment as required. Contractor will replace flexible fuel hoses as needed. 4.3.2 Contractor will send diesel fuel samples for analysis, as described above, to an off-site independent lab approved by M. D. Anderson. The lab reports will be returned to M. D. Anderson’s Project Coordinator within 24 hours for record keeping and analysis. MDA_________ Contractor__________ Page 8 of 15 ITB No. EMERGEN_MR&T/CW RIDER 101 4.3.3 Contractor shall visually inspect all external fuel lines for signs of deterioration, damage or leakage. Contractor shall visually inspect the turbo charger for loose connections or leakage and adjust, tighten or repair as needed. Contractor shall adjust carburetor and change fuel filters once per year with oil as needed. 4.4 4.5 Exhaust System: Contractor will visually check the system for leaks and corrosion. Contractor will check condensation trap and muffler condition. 4.4.1 Contractor will inspect the crankcase breather assembly, shall clean as necessary and shall ensure that the assembly is unrestricted. 4.4.2 Contractor will check all jacket water heaters for proper operation and adjust or repair as needed. 4.4.3 Contractor will check lubrication of free standing radiator bearings. M. D. Anderson will lubricate as advised by Contractor. AC Generator and Electrical Switchgear: 4.5.1 Contractor will visually inspect the generator condition. 4.5.2 Contractor will check lubrication of the rear generator bearing and the end frame bearing and lubricate as necessary. M. D. Anderson will further lubricate as advised by the Contractor. Contractor will check slip rings and commentator for wear and adjust or repair as needed. 4.5.3 Contractor will measure the megawatt output of all generators once a year and submit all readings in its report within 24 hours to the Project Coordinator. 4.5.3.1 To further clarify the above Paragraph 4.5.3 and what in the industry is frequently referred to as “megger” testing, M. D. Anderson acknowledges that “megger” is a brand name of measuring/testing instruments. As part of this contract, M. D. Anderson expects contractor to use a megohmmeter to measure and/or to annually test the insulation resistance of generator main rotors and exciter rotors on M. D. Anderson’s generators. 4.5.3.2 The minimum acceptable criteria for M. D. Anderson’s generators are as follows: 4.5.3.2.1 Test # 1 Insulation resistance of main rotors 1.5 megohms on the 480v generators 100.0 megohms on the 4160v generators MDA_________ Contractor__________ Page 9 of 15 ITB No. EMERGEN_MR&T/CW RIDER 101 4.5.3.2.2 4.5.3.3. 4.6 Test # 2 Insulation resistance of exciter rotors 1.5 megohms on the 480v generators 100.0 megohms on the 4160v generators If minimum acceptable values described above are not attained, Contractor shall immediately page the Project Coordinator or Designee from the site of test. Emergency Generator Controls Monitoring 4.6.1 Contractor will check all the following instrumentation for proper operation: tachometer, oil & pressure gauge, amp meter, voltmeter, engine temperature and frequency meter and shall adjust, repair or replace as necessary. Contractor shall lubricate the tachometer drive. 4.6.2 Contractor will check all timers and relays for proper operation and adjust as needed. Contractor shall check all generator brushes and valve lashes and shall adjust, repair or replace as needed. 4.6.3 Contractor will check and verify that all LIFE SAFETY circuits, shut down devices, pre-alarms and alarms operate properly and shall adjust, repair or replace as needed. CONTRACTOR SHALL IMMEDIATELY NOTIFY PROJECT COORDINATOR OR HIS ALTERNATES OF ANY IMPROPER OPERATION OF ANY LIFE SAFETY CIRCUIT, SHUT DOWN DEVICE, PRE-ALARM OR ALARM. 4.6.4 Contractor shall check all controls and monitoring checks both locally at the generator and at the remote annunciators located at M. D. Anderson facilities and shall adjust, repair or replace as necessary. 4.6.5 Contractor shall annually test protective relays on the emergency switchgear of the six (6) 4160 voltage generators.. 4.6.6 Contractor will annually install batteries in all generator programmable logic controllers (PLCs). 4.7 Generator Run Tests: Contractor will check all water, oil, oil and fuel levels and for leaks and shall adjust, repair or replace as needed. Contractor will check for excessive/unusual vibration or noise. Contractor will make operating adjustments as needed. Contractor will run engine unloaded before returning engine to service after any Preventative Maintenance and Inspection work has been performed. 4.8 Contractor shall visually inspect the condition of all belts and tension adjustments and adjust or replace as needed. MDA_________ Contractor__________ Page 10 of 15 ITB No. EMERGEN_MR&T/CW RIDER 101 4.9 Load Testing. 4.9.1 Contractor shall perform load testing on those generators that fail to meet the NFPA 110 Standard for ESPS (2005 Edition) Section 8.4.2 that requires generators to be tested for a minimum of thirty (30) minutes, using one of the following methods: (1) under operating temperature conditions and at not less than thirty (30) percent of the Emergency Power System (EPS) nameplate kW rating; or (2) through loading that maintains the minimum exhaust gas temperatures as recommended by the manufacturer. Diesel powered EPS installations that do not meet these requirements must be load tested annually with supplemental loads according to ESPS Section 8.4.2.3 as follows: 25% of the nameplate rating for 30 minutes 50% of the nameplate rating for 30 minutes 75% of the nameplate rating for 1 hour, for a total of 2 continuous hours. 4.9.2 Load testing must be started by May 1 and be completed no later than May 30. The generators CANNOT be run between the hours of 6:00 a.m. to 12:00 p.m. noon any day of the week. All load testing will be done after hours or on weekends. If Contractor load tests any generator in violation of this time restriction, M.D. Anderson shall consider any such action of Contractor as a material breach of the contract and may terminate the contract in accordance with its terms and conditions. 4.9.3 Generators that were load tested during FY06 per the criteria in Paragraph 4.9 above are as follows: OC1 & OC2; Pressler #1-4; OP #1 & 2; Gimbel #2; BF; MOD LAB; PPB; EL RIO; SCRB 8, 10 & 11; Guhn Road 1-3; HMB; RHI; Pawnee; Fannin Holcombe Building; and the O&M Building. 5.0 CORRECTIVE MAINTENANCE & REPAIRS. 5.1 Anticipated Repairs are defined as those non-emergency repairs identified by Preventative Maintenance, Inspections and Load Bank Testing including those items underlined in Paragraphs 4.2 through 4.9 above. 5.1.4 Contractor shall perform periodic repairs as scheduled by the Project Coordinator in accordance with the quoting procedures described in Paragraph 6.0 and the reporting procedures described in Paragraph 7.0 5.1.5 All repairs requiring the generator to be out of service for any length of time must be coordinated with the Project Coordinator before being taken out of service. MDA_________ Contractor__________ Page 11 of 15 ITB No. EMERGEN_MR&T/CW RIDER 101 5.2 5.3 5.1.6 Permission must be granted by the Project Coordinator who shall schedule the repairs in coordination with Contractor and other necessary M. D. Anderson personnel before the identified generator is taken out of service. 5.1.7 After any repairs are made to a generator under a subsequent maintenance agreement, the unit or units must then be started and its/their operation must then be verified by the designated M. D. Anderson representative before returning the generator to service and the lead technician leaving the site. Unanticipated Repairs: Unanticipated repairs are defined as those non-emergency repairs identified during normal operations. 5.2.1 Contractor shall perform periodic repairs as scheduled by the Project Coordinator in accordance with the quoting procedures described in Paragraph 6.0 and reporting procedures in Paragraph 7.0. 5.2.2 M. D. Anderson shall pay for all parts/supplies and labor in accordance with the periodic inspections or operations of the equipment. M. D. Anderson shall pay for all parts/supplies and labor that are needed to repair damages caused by abuse, theft, improper operation, acts of third persons, forces of nature or alteration of the equipment. Any repairs requested by M. D. Anderson that are outside of those listed above will be quoted to M. D. Anderson at current rates for parts and labor and expenses. Emergency Repairs are defined as those repairs required to sustain LIFE SAFETY circuits for M. D. Anderson. 5.3.1 6.0 Contractor shall respond on a twenty-four (24) hour basis to an emergency service call within two (2) hours. QUOTING PROCEDURES: 6.1 Preventative Maintenance (described in Section 4.0) 6.1.1 Contractor shall provide costs for Preventative Maintenance and Inspection Services in a lump sum amount with a payment schedule as per Pricing Schedule No. 1, Rider No. 102. 6.1.2 Contractor shall provide costs for Load Bank Testing Services in a lump sum amount with a payment schedule as per Pricing Schedule No. 1, Rider No. 102. 6.1.3 Contractor shall provide costs for Bundled Services (Preventative Maintenance, Inspections and Load Bank Testing) in a lump sum amount with a payment schedule as per Pricing Schedule No.1, Rider 102. MDA_________ Contractor__________ Page 12 of 15 ITB No. EMERGEN_MR&T/CW RIDER 101 6.2 Corrective Maintenance (described in Section 5.0) 6.2.1 Contractor shall provide labor costs for Corrective Maintenance and Repairs as described below in Paragraphs 6.2.2 and 6.2.3 on Pricing Schedule No. 2, Rider No. 102. 6.2.2 Hourly Labor Rates: Contractor shall provide all its personnel labor rates including straight time, overtime, emergency time and M.D. Anderson holidays (See Rider 101 – Appendix B for M. D. Anderson holidays). 6.2.3 After performing Preventative Maintenance, Inspections and Load Bank Testing, Contractor shall under all circumstances provide Project Coordinator a written cost estimate for Corrective Maintenance and Repair work on each emergency generator requiring such work. The written estimate shall include the following: (1) Itemized labor rates as provided in Pricing Schedule No. 2, Rider 102 referenced above; (2) Parts and materials itemized at Contractor’s cost; and (3) Contractor’s percentage (%) markup for parts and materials. The written estimate shall also be provided in a “total not to exceed” pricing format. 7.0 REPORTING PROCEDURES: 7.1 Contractor shall verbally confer with the Project Coordinator to ascertain the status of each emergency generator prior to any Preventative or Corrective Maintenance or Load Bank Testing service work. 7.2 During any scheduled service, Contractor shall verbally confer with the Project Coordinator upon encountering any emergency situation or any safety hazard. 7.3 Contractor shall verbally confer with the Project Coordinator after any and all service work is completed. 7.4 Contractor shall provide a written report immediately following a service call. Contractor may use its own reporting system but such system, if used, must be discussed and approved by the Project Coordinator before executing any final inspection and maintenance agreement. Project Coordinator must approve and sign all reports. 7.5 The reporting procedures and formats described above in Paragraphs 7.5 through 7.6 are required for data collection and performance metrics purposes. M. D. MDA_________ Contractor__________ Page 13 of 15 ITB No. EMERGEN_MR&T/CW RIDER 101 Anderson shall consider this information in any decision regarding Contractor’s performance. 7.6 M. D. Anderson reserves the right to refuse payment for any services performed by Contractor on M. D. Anderson’s emergency generators if Contractor fails to first contact Project Coordinator or his designated representative. 8.0 PROJECT COORDINATOR/ DESIGNEE: 8.1 Service Calls are scheduled through and reports made to the personnel listed below. 8.1.1 8.2. Project Coordinator: Barry Carmical, Facilities Engineer Phone Number: 713-792-2878 Pager: 713-404-6543 8.1.2 Project Coordinator Designees: Doan Vu, USO Phone: 713-404-9891 Winfred Meadows, Phone: 713-606-3714 Diesel Mechanic Contractor shall submit all invoices in the identical format as used for written estimates described in Paragraph 6.2.3. above to M. D. Anderson’s Accounts Payable Department as described in 8.2.1. below: 8.2.1. Accounts Payable The University of Texas M. D. Anderson Cancer Center P.O. 301401 Houston, Texas 77230-1401 9.0 CONTRACT PERFORMANCE METRICS. M. D. Anderson shall compile the following contract performance data during the term of the maintenance and repair contract. The data shall then be used to evaluate Contractor’s contract performance to assist M. D. Anderson in making its determination whether to renew the contract for an additional term. 9.1 The number of invoice discrepancies that vary from requirements described herein: unapproved modifications (Para. 3.8); post service call verbal communications (Para 7.3); and satisfactory written report summaries describing parts, evaluation, data, action taken, summary (Para. 7.5). 9.2 The number of complaints filed by M. D. Anderson personnel that Contractor left job site in an unclean condition (pares. 3.5 & 3.6). MDA_________ Contractor__________ Page 14 of 15 ITB No. EMERGEN_MR&T/CW RIDER 101 9.3 The number of times Contractor submitted its service call reports to Project Coordinator later than the five (5) business day period requirement (Para. 3.9). 9.4 The number of times Contractor submitted lab sample reports on specific generators to Project Coordinator less than 30 days prior to commencing its Preventative Maintenance and Inspections on the respective generator (Para. 3.11.4). 9.5 The number of times Contractor scheduled its Preventative Maintenance and Inspections on specific generators later than the thirty (30) day period following M. D. Anderson’s receipt of the respective acceptable lab sample report (Para. 3.11.6). 9.6 The number of times Contractor failed to report to the M. D. Anderson work site location within two (2) hours of being notified by M. D. Anderson of an EMERGENCY REPAIR (Paras. 5.3 & 5.3.1). MDA_________ Contractor__________ Page 15 of 15