SIGA-AB4GT CO Compatible Sounder Base Installation Sheet AB4G-SB: When using the AB4G-SB surface mount box, install a reinforcing plate at every knockout. (Reinforcing plates are included with the box.) Remove the knockout first, and then slide the reinforcing plate into the plastic housing. After the plate is in place, install a conduit connector and nut (not supplied). See Figure 1. Figure 1: Installing reinforcing plates on the AB4G-SB box Description The Signature Series model SIGA-AB4GT CO Compatible Sounder Base is a sounder base specifically designed for use with CO sensors. It is not compatible with a coded system. The base uses the same address and programming label as the detector it supports. It requires a SIGA-TCDR Temporal Pattern Generator to add the audible output function to any Signature Series detector. Refer to Figure 4 when following the installation steps below. To install the sounder base: 1. Select and install a compatible electrical box, and bring the field wiring into the box. 2. The default volume setting for the base is high dBA. To configure it for low dBA, cut the circuit board trace on the back of the circuit board. See item 4 of Figure 2, and Table 4. 3. Connect the field wiring to the terminals on the back of the base plate. For the unit to function properly, observe polarity. See Figure 2. 4. Attach the base plate to the electrical box. See Figure 4. 5. Align the trim ring so that the four tabs on the ring mate with the four slots in the base plate, and then press the trim ring onto the base plate until the tabs lock. Installation ATTENTION: Read this installation sheet in its entirety before beginning. Follow the installation instructions and keep them for future reference. Install in accordance with applicable requirements of the latest editions of the NFPA codes and standards, and the authority having jurisdiction. In Canada, install according to CAN/ULC-S524 Standard for the Installation of Fire Alarm Systems, CSA C22.1 Canadian Electrical Code, and the local authority having jurisdiction. Caution: To avoid accidental damage to the panel, disconnect all power before wiring the unit. Notes • Do not loop the signaling circuit field wires around the terminals. • Do not use AB4G and AB4GT on the same power riser circuit. Base Location: Refer to the detector installation instructions. Sleeping Rooms: In sleeping areas, use the high dBA output. © 2011 UTC Fire & Security. All rights reserved. 1/4 P/N 3101824 • REV 2.0 • ISS 10AUG11 Figure 2: Output configuration and basic wiring 1. 2. 3. 4. 5. 6. 7. 8. 4 Default volume setting (high dBA) Reserved for future use Reserved for future use Volume setting trace cut for low dBA To next SIGA-AB4GT sounder base or EOL relay SLC_OUT to next intelligent addressable device SLC_IN from intelligent addressable controller or previous device From SIGA-TCDR Temporal Pattern Generator or previous SIGA-AB4GT sounder base TCDR_RISER + TCDR_RISER SLC + TCDR_RISER + TCDR_RISER SLC + SLC - SLC - Figure 3: Base control through detector object programming AB4GT AB4GT 2 SLC_OUT+ SLC_OUT– 1 AUX_RISER + AUX_RISER – - + + - 3 SLC_IN + SLC_IN – 1. 2/4 Use a power-limited and regulated 24 VDC power supply that is UL/ULC Listed for fire protective signaling systems. 2. 3. RM1 module or equivalent Data from signature controller P/N 3101824 • REV 2.0 • ISS 10AUG11 Figure 4: Installing the Audible Detector Base Operating environment Temperature Relative humidity 32 to 120°F (0 to 49°C) 0 to 93% noncondensing Storage temperature −4 to 140°F (−20 to 60°C) [1] A TCDR is required to modulate the riser for the AB4GT to work as designed. Table 1: Operating current (RMS) Low dBA High dBA 31 mA 52 mA Table 2: Audible directional characteristics [1] Angle (degrees) Output sound pressure level 90 (ref) 0 dBA 70 and 110 −3 dBA Wiring diagram 55 and 115 −6 dBA See Figure 2. For additional wiring details, see the applicable control panel installation manual. [1] ULC anechoic room Figure 3 shows the components and wiring required for system detector operation of bases. Maintenance Do not change the factory-applied finish. Table 3: Sound pressure level per CAN/ULC-S525 [1] Signal High dBA Low dBA Temporal 95 91 Steady 93 89 [1] Voltage is regulated 24 DC. Table 4: Sound level output (dBA) Specifications Riser [1] operating voltage 16 to 33 VDC Current Operating Supervisory See Table 1 DC = 1.46 mA Default output volume High dBA Sound level output ULC UL See Table 3 See Table 4 Resonant frequency 3.2 kHz Audible directional characteristics See Table 2 Temporal pattern As determined by the SIGA-TCDR Compatible detectors All Signature Series detectors Compatible electrical boxes AB4G-SB surface box for audible base; 4 in. square by 2-1/2 in. (64 mm) deep box; 3-1/2 in. octagonal by 2-1/2 in. (64 mm) deep box; Standard European 100 mm² box Wire size 12 to 18 AWG (0.75 to 2.50 mm²) Base diameter 6.8 in. (173 mm) Base height from box 0.8 in. (21 mm) Maximum distance from ceiling (wall mount) 12 in. (305 mm) Environment type Indoor only P/N 3101824 • REV 2.0 • ISS 10AUG11 Low dBA [1] High dBA [1] [2] 86.8 90.8 [1] For NFPA 72 applications, the low or high dBA settings may be used for evacuation [2] For NFPA 720 applications, only the high dBA settings may be used for evacuation Regulatory information Manufacturer Edwards, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA Year of manufacture The first two digits of the date code (located on the product identification label) are the year of manufacture. UL and ULC voltage ratings Regulated 24 DC North American standards Meets: CAN/ULC-S525-07, CAN/ULC-S529-09, CAN/ULC-S530-M91, UL 268, and UL 464, UL 521 ULC Listed to CAN/CSA 6.19-01 Follow: CSA C22.1 and CAN/ULC-S524 FCC compliance This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Industry Canada This Class A digital apparatus complies with compliance Canadian ICES-003. 3/4 Contact information For contact information, see www.utcfireandsecurity.com. 4/4 P/N 3101824 • REV 2.0 • ISS 10AUG11