SIGA-AB4GT CO Compatible Sounder Base Installation

SIGA-AB4GT CO Compatible Sounder Base
Installation Sheet
AB4G-SB: When using the AB4G-SB surface mount box,
install a reinforcing plate at every knockout. (Reinforcing plates
are included with the box.) Remove the knockout first, and then
slide the reinforcing plate into the plastic housing. After the
plate is in place, install a conduit connector and nut (not
supplied). See Figure 1.
Figure 1: Installing reinforcing plates on the AB4G-SB box
Description
The Signature Series model SIGA-AB4GT CO Compatible
Sounder Base is a sounder base specifically designed for use
with CO sensors. It is not compatible with a coded system.
The base uses the same address and programming label as
the detector it supports. It requires a SIGA-TCDR Temporal
Pattern Generator to add the audible output function to any
Signature Series detector.
Refer to Figure 4 when following the installation steps below.
To install the sounder base:
1.
Select and install a compatible electrical box, and bring
the field wiring into the box.
2.
The default volume setting for the base is high dBA. To
configure it for low dBA, cut the circuit board trace on the
back of the circuit board. See item 4 of Figure 2, and
Table 4.
3.
Connect the field wiring to the terminals on the back of the
base plate. For the unit to function properly, observe
polarity. See Figure 2.
4.
Attach the base plate to the electrical box. See Figure 4.
5.
Align the trim ring so that the four tabs on the ring mate
with the four slots in the base plate, and then press the
trim ring onto the base plate until the tabs lock.
Installation
ATTENTION: Read this installation sheet in its entirety before
beginning. Follow the installation instructions and keep them
for future reference.
Install in accordance with applicable requirements of the latest
editions of the NFPA codes and standards, and the authority
having jurisdiction. In Canada, install according to
CAN/ULC-S524 Standard for the Installation of Fire Alarm
Systems, CSA C22.1 Canadian Electrical Code, and the local
authority having jurisdiction.
Caution: To avoid accidental damage to the panel, disconnect
all power before wiring the unit.
Notes
•
Do not loop the signaling circuit field wires around the
terminals.
•
Do not use AB4G and AB4GT on the same power riser
circuit.
Base Location: Refer to the detector installation instructions.
Sleeping Rooms: In sleeping areas, use the high dBA output.
© 2011 UTC Fire & Security. All rights reserved.
1/4
P/N 3101824 • REV 2.0 • ISS 10AUG11
Figure 2: Output configuration and basic wiring
1.
2.
3.
4.
5.
6.
7.
8.
4
Default volume setting (high dBA)
Reserved for future use
Reserved for future use
Volume setting trace cut for low dBA
To next SIGA-AB4GT sounder base or EOL relay
SLC_OUT to next intelligent addressable device
SLC_IN from intelligent addressable controller or previous device
From SIGA-TCDR Temporal Pattern Generator or previous
SIGA-AB4GT sounder base
TCDR_RISER +
TCDR_RISER SLC +
TCDR_RISER +
TCDR_RISER SLC +
SLC -
SLC -
Figure 3: Base control through detector object programming
AB4GT
AB4GT
2
SLC_OUT+
SLC_OUT–
1
AUX_RISER +
AUX_RISER –
- + + -
3
SLC_IN +
SLC_IN –
1.
2/4
Use a power-limited and regulated 24 VDC power supply that is
UL/ULC Listed for fire protective signaling systems.
2.
3.
RM1 module or equivalent
Data from signature controller
P/N 3101824 • REV 2.0 • ISS 10AUG11
Figure 4: Installing the Audible Detector Base
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
Storage temperature
−4 to 140°F (−20 to 60°C)
[1] A TCDR is required to modulate the riser for the AB4GT to work as
designed.
Table 1: Operating current (RMS)
Low dBA
High dBA
31 mA
52 mA
Table 2: Audible directional characteristics [1]
Angle (degrees)
Output sound pressure level
90 (ref)
0 dBA
70 and 110
−3 dBA
Wiring diagram
55 and 115
−6 dBA
See Figure 2. For additional wiring details, see the applicable
control panel installation manual.
[1] ULC anechoic room
Figure 3 shows the components and wiring required for system
detector operation of bases.
Maintenance
Do not change the factory-applied finish.
Table 3: Sound pressure level per CAN/ULC-S525 [1]
Signal
High dBA
Low dBA
Temporal
95
91
Steady
93
89
[1] Voltage is regulated 24 DC.
Table 4: Sound level output (dBA)
Specifications
Riser [1] operating
voltage
16 to 33 VDC
Current
Operating
Supervisory
See Table 1
DC = 1.46 mA
Default output volume
High dBA
Sound level output
ULC
UL
See Table 3
See Table 4
Resonant frequency
3.2 kHz
Audible directional
characteristics
See Table 2
Temporal pattern
As determined by the SIGA-TCDR
Compatible detectors
All Signature Series detectors
Compatible electrical
boxes
AB4G-SB surface box for audible base;
4 in. square by 2-1/2 in. (64 mm) deep box;
3-1/2 in. octagonal by 2-1/2 in. (64 mm) deep
box; Standard European 100 mm² box
Wire size
12 to 18 AWG (0.75 to 2.50 mm²)
Base diameter
6.8 in. (173 mm)
Base height from box
0.8 in. (21 mm)
Maximum distance
from ceiling (wall
mount)
12 in. (305 mm)
Environment type
Indoor only
P/N 3101824 • REV 2.0 • ISS 10AUG11
Low dBA [1]
High dBA [1] [2]
86.8
90.8
[1] For NFPA 72 applications, the low or high dBA settings may be
used for evacuation
[2] For NFPA 720 applications, only the high dBA settings may be
used for evacuation
Regulatory information
Manufacturer
Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL 34202,
USA
Year of
manufacture
The first two digits of the date code (located on the
product identification label) are the year of
manufacture.
UL and ULC
voltage ratings
Regulated 24 DC
North American
standards
Meets: CAN/ULC-S525-07, CAN/ULC-S529-09,
CAN/ULC-S530-M91, UL 268, and UL 464, UL 521
ULC Listed to CAN/CSA 6.19-01
Follow: CSA C22.1 and CAN/ULC-S524
FCC compliance This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
Industry Canada This Class A digital apparatus complies with
compliance
Canadian ICES-003.
3/4
Contact information
For contact information, see www.utcfireandsecurity.com.
4/4
P/N 3101824 • REV 2.0 • ISS 10AUG11