12-2499 FIREGUARD Closer-Holder Device
PUSH SIDE INSTALLATION INSTRUCTIONS
®
CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR DAMAGE
For assistance, contact SARGENT at 800-810-WIRE (9473) or www.sargentlock.com
NOTE: AN AUXILIARY DOOR STOP IS REQUIRED AT HOLD OPEN
! CAUTION:
1. DISCONNECT ALL POWER BEFORE INSTALLATION.
2. ALL WIRING TO BE PERFORMED BY QUALIFIED
PERSONNEL TO COMPLY WITH ALL APPLICABLE
LOCAL CODES.
3. MAXIMUM WIRE SIZE IS 18 AWG.
Left Hand Shown
1
2
Right Hand Shown
Use template on page 4. Drill and tap door for 12-24 machine screws and frame for 1/4-20 machine screws.
Prepare hole for conduit. Do not drill through channel, as damage will occur voiding warranty.
Install closer body to door with spring
power nut away from hinge.
3
Following local codes, attach cable or conduit to track. Secure
track to frame with electronics away from hinge with screws
provided.
Wire unit as shown on Page 3; install cover as shown.
LH
4
With wrench on bottom spindle, rotate spindle approximately 45°. Use screw and washer to secure main arm to
top spindle with index mark as shown.
Closer, spindle,
Closer, spindle,
washer, and screw
washer, and screw
Hinge
Hinge
L. H. Door
R. H. Door
Index mark
on spindle
Index mark
on spindle
45°
45°
Copyright © 2015, Sargent Manufacturing Company, an ASSA ABLOY Group
company, All rights reserved. Reproduction in whole or in part without the
express written permission of Sargent Manufacturing Company is prohibited.
A8199 (10/15)
1
5
Adjust hold open angle by adjusting arm length:
Range of 85° to 110° is obtainable. A) Place slider in
hold-open setting, B) open door, C) insert slide insert
into main arm. Open door to desired hold-open
position and D) secure arms with 9/64” hex screw.
Main Arm
6
To adjust holding
tension:
Insert 9/64” allen
wrench thru hole in
track end cap into cap
screw in spring
mechanism. Rotate
allen wrench for
desired tension.
C
D
A
Slide Insert
B
FINAL ADJUSTMENT AND REGULATING PROCEDURES
Closing and latching speed:
Turn valves clockwise to slow down or counterclockwise to speed up door movement.
Backcheck:
Turn valve clockwise to increase or counterclockwise to decrease.
CAUTION: SET VALVE FOR SLIGHT CUSHIONING EFFECT. NEVER USE THE BACKCHECK AS A DOOR STOP.
ALWAYS USE A DOOR STOP TO STOP THE DOOR.
Delayed action feature (optional):
When provided, turn valve clockwise to slow down or counterclockwise to speed up door movement.
Delayed Action
Range
Backcheck
Valve
Closing Speed
Range
Delayed Action
Valve (optional)
Back
Check
Range
Closing Speed
Valve
Latching Speed
Valve
Latching Speed
Range
NOTE: If adjustments are
ineffective, check
indexing from step 5
Install cover as shown.
Adjust power to allow door to close and latch
Number of Turns of Spring Power Adjusting Nut
Door Width
(inches)
24 - 30
30 - 36
36 - 42
42 - 48
Exterior Doors
1 - 3 CCW
Factory Set
1 - 4 CW
7 - 9 CW
Increase
Interior Doors
1 - 3 CCW
Factory Set
1 - 4 CW
4 - 6 CW
Adjusting door to close due to high draft conditions may exceed
ADA standards. Consult local ordinances when fire doors are involved.
Decrease
5/8”
Adjusting Nut
Insert is removable.
Place in unused opening.
Copyright © 2015, Sargent Manufacturing Company, an ASSA ABLOY Group
company, All rights reserved. Reproduction in whole or in part without the
express written permission of Sargent Manufacturing Company is prohibited.
A8199 (10/15)
2
INSTALLER: LEAVE INSTRUCTIONS WITH BUILDING OWNER
CAUTION
1. Disconnect all power before beginning
installation to prevent electrical shock
and equipment damage.
2. Installer must be a trained, experienced
service person.
12- Smoke Detector Unit
(120VAC shown)
3. All wiring must comply with
applicable local electrical codes,
ordinances and regulations.
4. Maximum wire size is 14AWG.
Smoke Detector
Unit
Header for Solenoid
Connection
Red LED/
Reset Switch
Test Swtich
Fuse (PTO120V)
125V / 1/2A
- Wire stand alone unit to appropriate power supply and fire
system.
- Refer to data sticker on back of hook-up box for proper input
power voltage and current specifications.
- Solenoid Connector must be attached to Header on circuit board
before hold open will function.
- Energize power supply. Current draw of .074Amps max per unit.
- Open door to hold open point. Door should hold open.
- Depress Test Switch. Door should close and latch.
- Test Switch is a momentary switch. Once released, hold open
should re-energized.
- Adjust closer spring power to insure proper latching.
Terminal Strip for
Power Input Connection
Opening for Concealed
Wiring
Smoke
Detector
120VAC Circuit Board
3
2
1
SOL
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Wiring Diagram for Master to Companion
To Solenoid
Companion Unit - 24v ONLY
(2499 / 9-2499)
Field Wiring Provided by Others
Wire Nut or Splice Connector (Provided)
Master Unit -120v or 24v Input
(12-2499)
To Solenoid
87654321
4
1
7654321
- Companion units are designed to work with 12- smoke detector
units.
- Wire companion unit to smoke detector unit as shown on wiring
diagram.
- Do not disconnect any existing wires on smoke detector unit’s
terminal strip.
- Energize power supply. Current draw of .074Amps max per unit.
- Open door to hold open point. Door should hold open.
- Depress Test Switch on master unit. Doors should close and latch.
- Test Switch is a momentary switch. Once released, hold open
should re-energized.
- Adjust closer spring power to insure proper latching.
Copyright © 2015, Sargent Manufacturing Company, an ASSA ABLOY Group
company, All rights reserved. Reproduction in whole or in part without the
express written permission of Sargent Manufacturing Company is prohibited.
A8199 (10/15)
3
Copyright © 2015, Sargent Manufacturing Company, an ASSA ABLOY Group
company, All rights reserved. Reproduction in whole or in part without the
express written permission of Sargent Manufacturing Company is prohibited.
A8199 (10/15)
4
2
(51)
3-7/8
(98)
35-13/16
(910)
29-1/2
(749)
9
2
2-7/16
(227)
(51)
(62)
2-15/16
(4) #12 x 3” Wood Screws
(75)
or #12-24 x 2-1/4” Flat head
machine screws
CL Hinge: Butts, center hung
or offset pivots
1-1/8 (29) hole
for Conduit
(1) 1/4-20 x 5/8”
Pan head machine screws
35-5/16
(897)
34-3/16
(868)
(3) 1/4-20 x 2”
Flat head machine screws
12
(305)
NOTES:
1. Reinforced metal doors and frames per ANSI
A250.8 & SDI-100, 12 gauge recommended.
2. Left hand door shown, right hand opposite.
3. For narrow rail doors (minimum 3”), use 351-D
drop plate.
Bottom
of stop
2-7/16
(62)
3-1/8
(79)
19
(486)
1-1/2
(38)
Edge of
stop
1
(25)
2-3/16
(56)
2” Min
stop
1-1/2
(38)
5-15/16
(151)
Edge of
stop