INSTALLATION MANUAL SP-3002 FIRE EXTINGUISHING PANEL SERVICE EDS Elektronik Destek Sanayi ve Ticaret Ltd. Þti. Meclis Mah. Teraziciler Cad. Kýlýç Sok. No:4 34785 Sarýgazi/ Ýstanbul Ph. : +90 216 528 45 00 Fax : +90 216 314 17 80 www.eds.com.tr eds@eds.com.tr SP3002_R1_ENG_31Subat11 SP3002 FIRE EXTINGUISHING PANEL SP3002 FIRE EXTINGUISHING PANEL Connection It is a two-area fire extinguishing panel (total 4 conventional areas). It provides audible and light warning when it detects an alarm situation while it is scanning the areas. It enables fire to be extinguished by activating extinguishing output of the area after adjusted time in automatic mode. It controls the areas, external butanes, sirens and extinguishing outputs; if it detects a fault situation (short circuit or open circuit) it warns with acoustic and light fault signal. It is controlled with a microprocessor. Twenty detectors/fire warning buttons can be connected for every area. Front panel is on its body. Led indicators are grouped as alarm, fault and situation indicators (Table 2). In addition, there are 2 relay outputs, 2 siren outputs, 2 extinguishing outputs and 5 inputs. EOL 10K EOL 10K HOLD/ABORT SWITCH EOL 10K MANUAL RELEASE CALLPOINT EOL 10K AUXILIARY 24V OUTPUT EOL 10K SIR1 FUSE 1A +ZON1- +ZON2- +ZON3- +ZON4- BATTERY FUSE 2A 24V FUSE 500mA +24V- SIR2 FUSE 1A BT1 FUSE 1A BT2 FUSE 1A +BT2- TABLE 1 +BT1- 2 8 MOMENTARY AUTO MANUAL SWITCH MANUAL RELEASE CALLPOINT +SIR1- +SIR2- Operation modes Housing Color Dimension Weight Operation temperature Extinguishing output delay Max total output current (BT1,BT2, sirens, zones, 24V output) EOL 10K NO NC COM AUX 2 Key/Switch Fault types SIREN2 EOL 10K NO NC COM AUX 1 Front panel label Indicator type Voice warning Buttons SIREN1 220VAC 60W 2x12V 1.2Ah/7Ah 21V 20ad. (per zone) 10K 2A 500mA 2 (total 4 conventional) 2 (Aux1, Aux2) 2 2 (BT1, BT2) 5 (Auto/Man, Gas Fired, Hold/Abort, Man/Rel 1, Man/Rel 2) Leksan Led Internal buzzer and external sirens 4 (Auto/Man, Reset, Silence, 1st stage) Available No supply, No battery, battery low, ground error, siren error Zone error, external button errors and extinguishing output errors Automatic and manual options Metal Cream 352x296x85mm 4900gr -10ºC - +50ºC 10 - 310 sec, 10 sec adjustable intervals 3A BOTTLED SELENOID BOTTLED SELENOID EOL 10K Technical Specifications AC Supply Power consumption Battery type Battery Low Voltage Number of Detectors End of the resistor Battery Fuse 24V output fuse Zone number Flasher output Siren output Extinguishing output Inputs EOL 10K MAN/REL2 MAN/REL1 HOLD/ABORT GAS FIRED AUTO/MAN Introduction EOL 10K EOL 10K EOL 10K EOL 10K DETECTOR DETECTOR 27VAC SP3002 MAIN BOARD +BAT- + - + - 2x12V BATTERY 27VAC TRANSFORMER Warnings & Precautions An arrow in a triangle-sign warns user against dangerous voltage Keep Users Manual; obey all the rules; follow all operations and instructions in line. Openings on the box are for ventilation purpose; do not obstruct ventilation and do not cover it. The equipment should be supplied with a power supplied specified on it and a three-wired power supply cord should be used. 78 SP3002 FIRE EXTINGUISHING PANEL Faults SP3002 FIRE EXTINGUISHING PANEL Indicators Indicator Zone1, Zone2, Zone3, Zone4 General Fire Zone1 Fault, Zone2 Fault, Zone3 Fault, Zone4 Fault, Bottle1 Fault, Bottle2 Fault Type Alarm Alarm Fault Man/Rel Fault Fault Hold/Abort Fault, Auto/Man Fault, Gas Fired Fault Siren Fault Fault Batt Fault Fault If battery voltage decreases less 21V, led should flash. If battery is not Earth Fault Fault connected or there is a fault in charge circuit, led lights continually. If there is another leak other than toward earth line of the system, led lights continually. Line Situation It shows that system is supplied from network power. Batt Situation It shows that system is supplied from battery power. 1st Stage Situation It shows that system is in alarm 1 stage. 2nd Stage Situation It shows that system is in alarm 2 stage. Gas Imminent Situation In case that the Panel detects any leak to any line other than ground line, Earth Fault Led and General Fault Led light continually; Buzzer sounds intermittently. Gas Fired Situation Battery Fault Manual Release 1, Situation The panel checks both whether battery is connected and battery voltage is within limits when it is supplied from battery. If battery is not connected, it lights Battery Fault Led and General Fault Led in 30 seconds and buzzer sounds intermittently. Battery voltage gets down 21 Volt, Battery Fault Led light flashes; General Fault Led lights continually and buzzer sounds intermittently. It indicates that extinguishing delay time is started after second alarm stage and it shows that at least one extinguishing output will be active. t shows that at least one of the extinguishing outputs is active and therefore, related system is active (it means that gas fired input is short circuited). It shows that external Manual Release Button is pressed (It means that Man/Rel input is short circuited). Manual Release 2 Manual Situation It indicates system in manual mode. Auto Situation It indicates system in automatic mode. Hold/Abort Situation It shows that external hold/abort button is pressed. Area Faults The panel checks all areas constantly. In case that it detects any short circuit situation it flashes the area-related led. General Fault Led lights continually and buzzer sounds intermittently. If a short circuit is detected in any area, fault led in relation to the area and General Fault Led light continually and buzzer sounds intermittently. Extinguishing Output Faults Extinguishing outputs are controlled continually as those areas. If a short or open circuit is detected in any extinguishing output, the related fault led (Bottle Fault or Bottle 2 Fault) and General Fault Led light continually and buzzer sounds continually. NOTE: In case of an alarm situation, it does not activate the output from which a short circuit fault is detected. Fault Fault Siren Faults In case that an open or short circuit is detected in siren output, Siren Fault and General Fault Led light continually. If an open or short circuit is detected in siren 2 output, Siren Fault Led flashes; General Fault Led lights continually; buzzer sounds intermittently. Explanation When an alarm is detected, related led lights continually. When an alarm is detected, related led lights continually. If a short circuit is detected in any areas, related led flashes; if an open circuit is detected, related led lights continually. If an open or short circuit is detected in extinguishing outputs, related led lights continually. If there is an open circuit in Man/Rel 1 input, related led lights continually, if there is a short circuit, it flashes. If there is an open circuit in any of Hold/Abort, Auto/Man Gas Fired inputs, related led lights continually. If there is an open or short circuit in Siren 1 output, led lights continually. If there is an open or short circuit in Siren 2 output, led flashes. NOTE: In case of an alarm situation, it does not activate the output from which a short circuit fault is detected. External Button Faults Only open circuit is controlled in all external buttons. If an open circuit is detected in Auto/Manual, Gas Fired, Hold/Abort buttons, the Button Fault Led, General Fault Led light continually and buzzer sounds intermittently. If an open circuit is detected in Manual Release Button, Manual/Release Led and General Fault Led light continually; buzzer sounds intermittently. If an open circuit is detected in Manual Release 2 Button, Man/Rel Fault Led lights intermittently; General Fault Led lights continually and Buzzer sounds intermittently. Ground Fault Network Fault If network supply is disconnected, panel is supplied from battery and Line Led lights out in 5 seconds and Battery Led lights. When network supply is connected again, panel turns to network supply again; Line Led lights; Battery Led lights out and battery starts to be charged. 6 8 TABLE 2 38 SP3002 FIRE EXTINGUISHING PANEL SP3002 FIRE EXTINGUISHING PANEL Panel Installation System Operation After panel is mounted on wall, area, siren, etc connections are performed. Terminating resistors are connected on farthest units as parallel. It is checked whether there is any open circuit or short circuit in areas and other connections. In case of no problem, the panel is energized. All leds light approximately 5 seconds and then, all of them except Line and Auto Leds light out. At this stage, delay time of extinguishing outputs should be adjusted (Table 3). Select a mode on the panel at your selection (automatic or manual). In order to turn off the system, both network and battery power supplies should be disconnected. Delay in Extinguishing Output In order to adjust delay time, press both Reset and Silence buttons simultaneously. In this case, Man/Rel Fault, Hold/Abort Fault, Auto/Manual Fault, Gas Fired Fault and Manual Leds are used for indication time. When this adjustment is finished, all the leds get into normal operation. Silence button is used to increase time; Reset button to decrease time. In order to record after adjustment of time, press 1st stage button; recorded value is lights three times on leds and leds get into normal operation again. Time value is recorded in permanent memory and even if panel is disconnected, this time value is not lost. In order to terminate without recording the time value, press Auto/Manual Button. LED TIME (sec.) LED TIME (sec.) LED Automatic Mode On this mode, Area 1 and 2 compose extinguishing area one. Area 3 and 4 compose extinguishing area 2. Also, Siren 1 and Aux 1 are related to extinguishing area 1 and Siren 2 and Aux 2 are related to extinguishing area 2. If an alarm is obtained from an area in extinguishing sectors while system is working in manual mode, panel goes into alarm stage 1 position. On this situation, buzzer sounds continually; area led, general alarm led and 1st stage led light continually; external siren sounds in 1 second intervals. If another alarm is obtained from that extinguishing sector, panel goes into alarm stage 2 position. On this situation, in addition to stage 1, 2nd Stage and Gas Imminent Leds light continually; external siren sounds continually. Delay time is counted according to adjusted extinguishing delay and extinguishing output is activated after that period, and when feedback is obtained from the unit connected to that output, Gas Fired led lights and Aux output and flasher or another unit connected to that output is activated. Owing to that feedback obtained in Gas Fired input, it is checked whether gas or water is released into location. That operation can be followed with a flasher connected to location input (connected to Aux output). If Hold/Abort button is pushed in any stage, no extinguishing output is activated or extinguishing outputs activated previously are cancelled. Automatic/Manual Mode Selection In order to change panel operation mode, Auto/Manual button on front panel or external Auto/Manual button can be used. Auto and Manual leds on front panel indicate which system mode is in operation. TIME (sec.) Silencing the Panel In case of any fault or alarm situation, when buzzer or external siren sounds, in order to silence the panel, push Silence Button. Sirens and buzzer sound off. If there is another fault or alarm situation happens, buzzer and sirens are activated again. Only the authorized persons who have key can silence panel. Panel Reset Before silencing panel, please be sure that all fault and alarm situations are resolved. In order to take panel in starting position, pres Reset button. All leds light during 5 seconds and buzzer sounds and therefore, led and buzzer test has been performed. After panel is reset, extinguishing delay time and panel operation mode does not change. Only authorized persons who have key can reset panel. Establishing an Alarm Although panel does not detect any alarm from any area, user can take panel into alarm stage 1 or alarm stage 2. That can be made in two different ways: 1) TABLE 3 2) System Operation Manual mode While system is in manual mode, it functions as a conventional fire detection panel in four areas. When an alarm is detected, stage 1 and 2 is not valid and panel does not activate extinguishing outputs. On this mode, if an authorized person detects fire and pushes one of the Manual Release buttons, necessary extinguishing output is activated after adjusted delay time. 4 8 58 User can push stage 1 button. On that situation; Siren 1 and 2 sounds intermittently; Stage 1 led lights and buzzer sounds continually. On this situation, extinguishing outputs are not active. User can push external Manual Release 1 or 2 buttons and as a consequence, panel goes into alarm stage 2. On this situation, 1st Stage, 2nd Stage, Gas Imminent leds light; in addition, if Manual Release 1 button is pushed, Siren 1 sounds continually and Manual Release 1 led lights. If Manual Release 2 button is pushed, Siren 2 sounds continually and Manual Release 2 led lights. Panel extinguishing output counts delay time and after that period, related extinguishing output (BT 1 or BT 2) is activated and if Gas Fired feedback is obtained, necessary Aux output is also activated.