INSTALLATION MANUAL
SP-3002
FIRE EXTINGUISHING PANEL
SERVICE
EDS Elektronik Destek
Sanayi ve Ticaret Ltd. Þti.
Meclis Mah. Teraziciler Cad.
Kýlýç Sok. No:4 34785
Sarýgazi/ Ýstanbul
Ph. : +90 216 528 45 00
Fax : +90 216 314 17 80
www.eds.com.tr eds@eds.com.tr
SP3002_R1_ENG_31Subat11
SP3002
FIRE EXTINGUISHING PANEL
SP3002
FIRE EXTINGUISHING PANEL
Connection
It is a two-area fire extinguishing panel (total 4 conventional areas). It provides audible and light warning when it
detects an alarm situation while it is scanning the areas. It enables fire to be extinguished by activating
extinguishing output of the area after adjusted time in automatic mode. It controls the areas, external butanes,
sirens and extinguishing outputs; if it detects a fault situation (short circuit or open circuit) it warns with
acoustic and light fault signal.
It is controlled with a microprocessor. Twenty detectors/fire warning buttons can be connected for every area.
Front panel is on its body. Led indicators are grouped as alarm, fault and situation indicators (Table 2). In addition,
there are 2 relay outputs, 2 siren outputs, 2 extinguishing outputs and 5 inputs.
EOL
10K
EOL
10K
HOLD/ABORT SWITCH
EOL
10K
MANUAL RELEASE CALLPOINT
EOL
10K
AUXILIARY
24V OUTPUT
EOL
10K
SIR1 FUSE 1A
+ZON1- +ZON2- +ZON3- +ZON4-
BATTERY FUSE
2A
24V FUSE
500mA
+24V-
SIR2 FUSE 1A
BT1 FUSE 1A
BT2 FUSE 1A
+BT2-
TABLE 1
+BT1-
2 8
MOMENTARY AUTO MANUAL SWITCH
MANUAL RELEASE
CALLPOINT
+SIR1- +SIR2-
Operation modes
Housing
Color
Dimension
Weight
Operation temperature
Extinguishing output delay
Max total output current
(BT1,BT2, sirens, zones, 24V output)
EOL 10K
NO NC COM
AUX 2
Key/Switch
Fault types
SIREN2
EOL 10K
NO NC COM
AUX 1
Front panel label
Indicator type
Voice warning
Buttons
SIREN1
220VAC
60W
2x12V 1.2Ah/7Ah
21V
20ad. (per zone)
10K
2A
500mA
2 (total 4 conventional)
2 (Aux1, Aux2)
2
2 (BT1, BT2)
5
(Auto/Man, Gas Fired, Hold/Abort, Man/Rel 1, Man/Rel 2)
Leksan
Led
Internal buzzer and external sirens
4
(Auto/Man, Reset, Silence, 1st stage)
Available
No supply, No battery, battery low, ground error, siren error
Zone error, external button errors and extinguishing output errors
Automatic and manual options
Metal
Cream
352x296x85mm
4900gr
-10ºC - +50ºC
10 - 310 sec, 10 sec adjustable intervals
3A
BOTTLED
SELENOID
BOTTLED
SELENOID
EOL 10K
Technical Specifications
AC Supply
Power consumption
Battery type
Battery Low Voltage
Number of Detectors
End of the resistor
Battery Fuse
24V output fuse
Zone number
Flasher output
Siren output
Extinguishing output
Inputs
EOL
10K
MAN/REL2 MAN/REL1 HOLD/ABORT GAS FIRED AUTO/MAN
Introduction
EOL
10K
EOL
10K
EOL
10K
EOL
10K
DETECTOR
DETECTOR
27VAC
SP3002 MAIN BOARD
+BAT-
+
-
+
-
2x12V BATTERY
27VAC
TRANSFORMER
Warnings & Precautions
An arrow in a triangle-sign warns user against dangerous voltage
Keep Users Manual; obey all the rules; follow all operations and instructions in line. Openings on the box are for ventilation
purpose; do not obstruct ventilation and do not cover it.
The equipment should be supplied with a power supplied specified on it and a three-wired power supply cord should be used.
78
SP3002
FIRE EXTINGUISHING PANEL
Faults
SP3002
FIRE EXTINGUISHING PANEL
Indicators
Indicator
Zone1, Zone2, Zone3, Zone4
General Fire
Zone1 Fault, Zone2 Fault,
Zone3 Fault, Zone4 Fault,
Bottle1 Fault, Bottle2 Fault
Type
Alarm
Alarm
Fault
Man/Rel Fault
Fault
Hold/Abort Fault, Auto/Man Fault,
Gas Fired Fault
Siren Fault
Fault
Batt Fault
Fault
If battery voltage decreases less 21V, led should flash. If battery is not
Earth Fault
Fault
connected or there is a fault in charge circuit, led lights continually.
If there is another leak other than toward earth line of the system,
led lights continually.
Line
Situation
It shows that system is supplied from network power.
Batt
Situation
It shows that system is supplied from battery power.
1st Stage
Situation
It shows that system is in alarm 1 stage.
2nd Stage
Situation
It shows that system is in alarm 2 stage.
Gas Imminent
Situation
In case that the Panel detects any leak to any line other than ground line, Earth Fault Led and General Fault Led light
continually; Buzzer sounds intermittently.
Gas Fired
Situation
Battery Fault
Manual Release 1,
Situation
The panel checks both whether battery is connected and battery voltage is within limits when it is supplied from battery. If
battery is not connected, it lights Battery Fault Led and General Fault Led in 30 seconds and buzzer sounds intermittently.
Battery voltage gets down 21 Volt, Battery Fault Led light flashes; General Fault Led lights continually and buzzer sounds
intermittently.
It indicates that extinguishing delay time is started after second
alarm stage and it shows that at least one extinguishing output
will be active.
t shows that at least one of the extinguishing outputs is active
and therefore, related system is active (it means that gas fired
input is short circuited).
It shows that external Manual Release Button is pressed
(It means that Man/Rel input is short circuited).
Manual Release 2
Manual
Situation
It indicates system in manual mode.
Auto
Situation
It indicates system in automatic mode.
Hold/Abort
Situation
It shows that external hold/abort button is pressed.
Area Faults
The panel checks all areas constantly. In case that it detects any short circuit situation it flashes the area-related led. General
Fault Led lights continually and buzzer sounds intermittently. If a short circuit is detected in any area, fault led in relation to the
area and General Fault Led light continually and buzzer sounds intermittently.
Extinguishing Output Faults
Extinguishing outputs are controlled continually as those areas. If a short or open circuit is detected in any extinguishing
output, the related fault led (Bottle Fault or Bottle 2 Fault) and General Fault Led light continually and buzzer sounds
continually.
NOTE: In case of an alarm situation, it does not activate the output from which a short circuit fault is detected.
Fault
Fault
Siren Faults
In case that an open or short circuit is detected in siren output, Siren Fault and General Fault Led light continually. If an open or
short circuit is detected in siren 2 output, Siren Fault Led flashes; General Fault Led lights continually; buzzer sounds
intermittently.
Explanation
When an alarm is detected, related led lights continually.
When an alarm is detected, related led lights continually.
If a short circuit is detected in any areas, related led flashes;
if an open circuit is detected, related led lights continually.
If an open or short circuit is detected in extinguishing outputs,
related led lights continually.
If there is an open circuit in Man/Rel 1 input,
related led lights continually, if there is a short circuit, it flashes.
If there is an open circuit in any of Hold/Abort,
Auto/Man Gas Fired inputs, related led lights continually.
If there is an open or short circuit in Siren 1 output, led lights
continually. If there is an open or short circuit in Siren 2 output,
led flashes.
NOTE: In case of an alarm situation, it does not activate the output from which a short circuit fault is detected.
External Button Faults
Only open circuit is controlled in all external buttons. If an open circuit is detected in Auto/Manual, Gas Fired, Hold/Abort
buttons, the Button Fault Led, General Fault Led light continually and buzzer sounds intermittently. If an open circuit is
detected in Manual Release Button, Manual/Release Led and General Fault Led light continually; buzzer sounds intermittently.
If an open circuit is detected in Manual Release 2 Button, Man/Rel Fault Led lights intermittently; General Fault Led lights
continually and Buzzer sounds intermittently.
Ground Fault
Network Fault
If network supply is disconnected, panel is supplied from battery and Line Led lights out in 5 seconds and Battery Led lights.
When network supply is connected again, panel turns to network supply again; Line Led lights; Battery Led lights out and
battery starts to be charged.
6 8
TABLE 2
38
SP3002
FIRE EXTINGUISHING PANEL
SP3002
FIRE EXTINGUISHING PANEL
Panel Installation
System Operation
After panel is mounted on wall, area, siren, etc connections are performed. Terminating resistors are connected on farthest
units as parallel. It is checked whether there is any open circuit or short circuit in areas and other connections. In case of no
problem, the panel is energized. All leds light approximately 5 seconds and then, all of them except Line and Auto Leds light
out. At this stage, delay time of extinguishing outputs should be adjusted (Table 3). Select a mode on the panel at your
selection (automatic or manual). In order to turn off the system, both network and battery power supplies should be
disconnected.
Delay in Extinguishing Output
In order to adjust delay time, press both Reset and Silence buttons simultaneously. In this case, Man/Rel Fault, Hold/Abort
Fault, Auto/Manual Fault, Gas Fired Fault and Manual Leds are used for indication time. When this adjustment is finished, all
the leds get into normal operation. Silence button is used to increase time; Reset button to decrease time. In order to record
after adjustment of time, press 1st stage button; recorded value is lights three times on leds and leds get into normal
operation again. Time value is recorded in permanent memory and even if panel is disconnected, this time value is not lost. In
order to terminate without recording the time value, press Auto/Manual Button.
LED
TIME (sec.)
LED
TIME (sec.)
LED
Automatic Mode
On this mode, Area 1 and 2 compose extinguishing area one. Area 3 and 4 compose extinguishing area 2. Also, Siren 1 and Aux 1 are
related to extinguishing area 1 and Siren 2 and Aux 2 are related to extinguishing area 2.
If an alarm is obtained from an area in extinguishing sectors while system is working in manual mode, panel goes into alarm stage 1
position. On this situation, buzzer sounds continually; area led, general alarm led and 1st stage led light continually; external siren
sounds in 1 second intervals. If another alarm is obtained from that extinguishing sector, panel goes into alarm stage 2 position. On
this situation, in addition to stage 1, 2nd Stage and Gas Imminent Leds light continually; external siren sounds continually. Delay time
is counted according to adjusted extinguishing delay and extinguishing output is activated after that period, and when feedback is
obtained from the unit connected to that output, Gas Fired led lights and Aux output and flasher or another unit connected to that
output is activated. Owing to that feedback obtained in Gas Fired input, it is checked whether gas or water is released into location.
That operation can be followed with a flasher connected to location input (connected to Aux output).
If Hold/Abort button is pushed in any stage, no extinguishing output is activated or extinguishing outputs activated previously are
cancelled.
Automatic/Manual Mode Selection
In order to change panel operation mode, Auto/Manual button on front panel or external Auto/Manual button can be used. Auto and
Manual leds on front panel indicate which system mode is in operation.
TIME (sec.)
Silencing the Panel
In case of any fault or alarm situation, when buzzer or external siren sounds, in order to silence the panel, push Silence Button. Sirens
and buzzer sound off. If there is another fault or alarm situation happens, buzzer and sirens are activated again. Only the authorized
persons who have key can silence panel.
Panel Reset
Before silencing panel, please be sure that all fault and alarm situations are resolved. In order to take panel in starting position, pres
Reset button. All leds light during 5 seconds and buzzer sounds and therefore, led and buzzer test has been performed. After panel is
reset, extinguishing delay time and panel operation mode does not change. Only authorized persons who have key can reset panel.
Establishing an Alarm
Although panel does not detect any alarm from any area, user can take panel into alarm stage 1 or alarm stage 2. That can be made in
two different ways:
1)
TABLE 3
2)
System Operation
Manual mode
While system is in manual mode, it functions as a conventional fire detection panel in four areas. When an alarm is detected,
stage 1 and 2 is not valid and panel does not activate extinguishing outputs. On this mode, if an authorized person detects fire
and pushes one of the Manual Release buttons, necessary extinguishing output is activated after adjusted delay time.
4 8
58
User can push stage 1 button. On that situation; Siren 1 and 2 sounds intermittently; Stage 1 led lights and buzzer
sounds continually. On this situation, extinguishing outputs are not active.
User can push external Manual Release 1 or 2 buttons and as a consequence, panel goes into alarm stage 2. On this
situation, 1st Stage, 2nd Stage, Gas Imminent leds light; in addition, if Manual Release 1 button is pushed, Siren 1
sounds continually and Manual Release 1 led lights. If Manual Release 2 button is pushed, Siren 2 sounds continually
and Manual Release 2 led lights. Panel extinguishing output counts delay time and after that period, related
extinguishing output (BT 1 or BT 2) is activated and if Gas Fired feedback is obtained, necessary Aux output is also
activated.