4309 Series Vanguard

advertisement
VANGUARD
Series
T5 & T8 Lamps
4309
A P P L I C AT I O N S
The VANGUARD Prismatic wraparound
offers a simple look in a wraparound
yet delivers a positive functional design
providing effective illumination.
This rugged unit is made for areas of
abuse in Public Buildings, Schools,
Hotels, Parking Garages, Terminals,
Hallways, and Hospitals.
S P E C I F I C AT I O N S
CONSTRUCTION: Die formed of 20 gauge cold rolled prime steel,
rigidly fabricated to insure true and perfect alignment. Socket plate
securely mounted and cover is readily removable for socket maintenance.
REFLECTOR: XTA-XTRALUME® energy efficient reflector available
(see OPTIONS). Powder coated HiReflectance white is standard.
SHIELDING: One piece heavy gauge precision extruded acrylic
prismatic refractor with linear prisms on sides and optically
engineered debossed hexagonal prism on bottom. The lens is
positively held in place by the metal end caps which are screwed
in place. Consult factory for optional 100% “DR” acrylic lens and
“TP” tamperproof screws.
ELECTRICAL: 1 and 2 lamp T5 electronic quick start 450MA for 14W,
21W, 28W and 460MA to 300MA for 24W T5HO, or 2 and 3 lamp
Octic T8 265MA electronic instant start ballasts, or Rapid Start HPF
270MA Biax lamps. High Power Factor, Class A sound rated <10%
THD (less than 10% Total Harmonic Distortion). U.L., CSA, FCC listed
Type 1 for multi-voltage 120/277 59/60Hz operation. Other voltages
and frequencies available, CONSULT FACTORY.
MOUNTING: Installed flush with ceiling surface or stem mounted,
singly or in continuous rows. For continuous row mounting, end
caps are eliminated and replaced with a joiner band to prevent light
leakage between the two diffuser ends. Specify row lengths. End
caps are used at the ends of rows and on individual units. Adequate
knockouts and holes are provided for mounting and feeds, thru back.
FINISH: All steel component parts are completely protected against
rust and discoloration after fabrication through an automated
conveyorized multi-stage phosphate bonding process. Finished with
an electrostatic baked white polyester thermosetting powder coating. This electronic computer controlled integrated system assures
consistent 88%+ reflectance efficiency and maximum durability.
CERTIFICATION: The VANGUARD Series 4309 is U.L. and C.U.L.
listed and bears the label of the I.B.E.W./AFL-CIO, Local #3.
Optionally listed for Damp Locations “DL”.
XTRALUME® and LEGION® are registered trademarks of LEGION LIGHTING CO., INC.
®
L
I
G
H
T
I
N
G
C
O.,
I
N
C.
95/8"
41/4"
2 Lamps
T5
T8
3 Lamps
T5
RoHS
COMPLIANT
T8
®
ENERGY
STAR
PARTNER
8/10
Section A - Page 39
221 Glenmore Ave., Brooklyn, NY 11207 • Tel: 718/498-1770 • Fax: 718/498-0128
E-mail: sales@legionlighting.com • Website: www.legionlighting.com • Toll Free Fax: 800/4-LEGION
Series 4309
OPTIONS
ORDE R I N G DATA
Catalog No.
4309-217-ACP EBO
4309-317-ACP EBO
4309-1BX40-ACP EBX
4309-2BX40-ACP EBX
4309-225-ACP EBO
4309-325-ACP EBO
4309-232-ACP EBO
4309-332-ACP EBO
4309-225-6T-ACP EBO
4309-325-6T-ACP EBO
4309-232-8T-ACP EBO
4309-332-8T-ACP EBO
4309-214
4309-314
4309-224HO
4309-324HO
4309-221
4309-321
4309-239HO
4309-339HO
4309-228
4309-328
4309-254HO
4309-354HO
4309-221-6T
4309-321-6T
4309-239HO-6T
4309-339HO-6T
4309-228-8T
4309-328-8T
4309-254HO-8T
4309-354HO-8T
VANGUARD
T5 & T8 Lamps
No. and
Type Lamps
2-FO17-OCT-T8
3-FO17-OCT-T8
H H 1-F40W-TT/RS
H H 2-F40W-TT/RS
2-FO25-OCT-T8
3-FO25-OCT-T8
2-FO32-OCT-T8
3-FO32-OCT-T8
4-FO25-OCT-T8
6-FO25-OCT-T8
4-FO32-OCT-T8
6-FO32-OCT-T8
2-F14-T5
3-F14-T5
2-F24HO-T5
3-F24HO-T5
2-F21-T5
3-F21-T5
2-F39HO-T5
3-F39HO-T5
2-F28-T5
3-F28-T5
2-F54HO-T5
3-F54HO-T5
3-F21-T5
6-F21-T5
3-F39HO-T5
6-F39HO-T5
4-F28-T5
6-F28-T5
4-F54HO-T5
6-F54HO-T5
n
Nominal
Wt.
Dimensions
10
4¼" x 24"
4¼" x 36"
4¼" x 48"
4¼" x 72"
4¼" x 96"
12
17
20
20
23
33
36
40
43
4¼" x 24"
10
4¼" x 36"
20
Suffix ‘‘LT’’ after catalog no. for cold weather ballast.
Suffix ‘‘EM’’ after cat. no. for emergency battery packs and see price list for types.
Suffix ‘‘DL’’ after catalog no. for damp location.
Suffix ‘‘TP’’ after catalog no. for tamperproof screws, spanner or
torx head (consult factory)
n Suffix ‘‘XTA’’ after cat. no. for XTRALUME® reflector standard with 85% reflectance, for 95% reflectance specify your requirements.
Change suffix ‘‘ACP’’ to ‘‘ACPDR’’ for 100% DR acrylic prismatic
lens. (Consult factory for availability).
DIMMING BALLASTS
Suffix “EBDO” to catalog no. for T8 Dimming Ballast.
Suffix “EBDP” to catalog no. for T5 Dimming Ballast.
Suffix “EBDX” to catalog no. for BIAX Twin-Tube Dimming Ballast.
Suffix “EBDOA” to catalog no. for electronic dimming ballast.
ADVANCE MARK X.
Suffix “ECO-10” to catalog no. for electronic dimming ballast
LUTRON ECO-10.
Suffix “HIL” to catalog no. for LUTRON HI-LUME dimming ballast.
Suffix “H3D” to catalog no. for LUTRON HI-LUME 3D dimming ballast.
Suffix “ECO-5” to catalog no. for LUTRON ECO SYSTEM.
Legion is a Lutron® Silver Partner
Lutron® is a registered trademark of Lutron Electronics
OTHER DIMMING BALLASTS AVAILABLE, CONSULT FACTORY.
4¼" x 48"
23
BACK PLANS
24", 36"
5" (Typ.)
4¼" x 72"
4¼" x 96"
36
43
45/8"
(Typ.)
48"
5"
★★F40TT/RS is the ANSI designation of various lamp manufacturers,
i.e.: G.E. Lighting “BIAX™”, Phillips “PL”, Osram “DULUX L”,
Sylvania “TWIN TUBE”. For F50TT/RS change cat. number.
Example: 4309-1BX50-ACP and CONSULT FACTORY.
ADVISE RUN LENGTHS WHEN USED IN CONTINUOUS ROWS.
72", 96"
48"
BIAX™ is a trademark of G.E. Lighting.
OCTRON™ is a trademark of SYLVANIA LIGHTING
5"
2" dia. K.O. (Typ.)
n NOTE: 1 lamp units available for XTA reflector – CONSULT FACTORY.
PHOT O M E T R I C DATA - Illuminance (Footcandles)
Cat. No. 4309-232-ACP
Extruded Wrap Around
Lamps: (2) FO32T8/CW
each rated 2800 lumens.
Total Luminaire Efficiency = 69.1%
Plane
0-Deg. 90-Deg.
Spacing Criteria
1.25
1.39
90˚
60˚
45˚
90˚
0˚
Zonal Lumen Summary
Zone Lumens % Lamp % Fixt.
0-30
1019
17.0 024.6
0-40
1697
28.3 041.0
0-60
2879
48.0 069.5
0-90
3553
59.2 085.7
90-120 0443
07.4 010.7
90-130 0501
08.3 012.1
90-150 0570
09.5 013.8
90-180 0591
09.8 014.3
00-180 4144
69.1 100.0
30˚
Average Luminance (Footlamberts)
Vertical
Horizontal Plane
Angle
0˚
90˚
0
351
351
45
301
266
55
211
155
65
144
097
75
091
062
85
021
022
Coefficients of Utilization - Zonal Cavity Method
Floor
20%
Ceiling
80%
70%
50%
Walls 70% 50% 30% 10% 70% 50% 30% 10% 50% 30%
0
80 80 80 80 77 77 77 77 71 71
1
72 69 66 63 70 57 64 61 62 60
2
66 60 56 52 63 58 54 51 54 51
3
60 53 48 44 58 51 47 43 48 44
4
55 47 42 37 53 46 40 36 43 38
5
51 42 36 32 49 41 35 31 38 34
6
47 38 32 28 45 37 31 27 35 30
7
44 35 29 25 42 33 28 24 32 27
8
40 31 26 22 39 31 25 21 29 24
9
38 29 23 20 36 28 23 19 26 22
10
35 26 21 18 34 26 21 17 24 20
10%
71
58
48
40
35
30
26
23
21
19
17
®
Information supplied primarily for illustrative purposes, subject to change.
Consult factory for verification and minimum quantity orders.