Nuclear Power Corporation of India Limited Narora Atomic Power Station-1&2 Technical Specification for 250V DC Power and Control Batteries Inspection & Testing Section: CC-5 Page 1 of 4 Rev-0 1.0 General 1.1 The overall requirements for in-stage inspection and testing, material tests etc. in respect of equipment covered in this contract. The routine tests, acceptance tests, special tests and type tests are covered in this section. Inspections and tests at raw material stage, semi finished or module level are detailed in the typical QAP given in section CC-6. 1.2 Offered equipment should have been successfully type tested as per the relevant standards, amended up to date. If offered equipment has already been type tested, bidder shall furnish type test reports before proceeding with manufacture. Type tests must not have been conducted earlier than five years from the date of opening of bids. In case the type tests were conducted earlier than five years, such type tests shall be repeated by the successful bidder free of cost before commencement of supply. The undertaking to this effect shall be furnished along with the offer without which the offer shall be liable for rejection. As a part of technical offer, bidder shall include a tabulation detailing various type tests on each type of equipment along with applicable type test certificate number, details of the equipment subjected to type test, place of testing and final results. 1.3 If there are changes in the components or in the design/type already type tested and the design/type offered against this specification, the purchaser reserves the right to demand repetition of tests without any extra cost before commencement of supply. 1.4 The cells used for acceptance and type tests etc shall not be supplied to purchaser. 1.5 Type Tests 1.5.1 Type tests on Containers 1.5.1.1.1 The following type tests shall be carried on containers in accordance with IS: 1146 and containers used for type tests should not be included in the supply. 1.5.1.1.2 Verification of constructional requirements. 1.5.1.1.3 Verification of marking and packing. 1.5.1.1.4 High voltage test. 1.5.1.1.5 Drop ball test. 1.5.1.1.6 Plastic yield test. 1.5.1.1.7 Hydraulic thrust endurance test as per IS. SPECIFICATION NO.: PP-E-2405 April, 2009 Nuclear Power Corporation of India Limited Narora Atomic Power Station-1&2 Technical Specification for 250V DC Power and Control Batteries Inspection & Testing Section: CC-5 Page 2 of 4 Rev-0 1.5.1.1.8 Acid resistance test. 1.5.2 Type Tests on Separators 1.5.2.1 Tests on separators shall be carried out as per IS: 6071. In case of other plastic like PE any internationally acceptable standard recognizing such material shall be followed. 1.5.3 Type Test on Completed Cells 1.5.3.1 Following type tests specified in IS: 1651 shall be carried out on three cells of each rating of battery: 1.5.3.1.1 Verification of constructional requirements. 1.5.3.1.2 Verification of marking. 1.5.3.1.3 Verification of dimensions. 1.5.3.1.4 Test for capacities (C10, C1 and high rate specified) as per guaranteed technical particulars furnished along with the bid. 1.5.3.1.5 Test for voltage during discharge. 1.5.3.1.6 Ampere-hour and watt-hour efficiency tests. 1.5.3.1.7 Test for retention of charge. 1.5.3.1.8 Life cycle endurance tests. 1.6 Acceptance Tests 1.6.1 Acceptance Tests for Containers 1.6.1.1 Acceptance tests as per IS: 1146 shall be carried out on the containers for lead acid cells. 1.6.2 Acceptance tests on Separators 1.6.2.1 Acceptance tests on separators shall be carried out as per IS: 6071. In case of other plastic like PE any internationally acceptable standard recognizing such material shall be followed. 1.6.3 Acceptance Tests on Completed Cells 1.6.3.1 Acceptance tests as per IS: 1651 shall be performed at least on two samples drawn from each lot of batteries comprising one battery bank. SPECIFICATION NO.: PP-E-2405 April, 2009 Nuclear Power Corporation of India Limited Narora Atomic Power Station-1&2 Technical Specification for 250V DC Power and Control Batteries Inspection & Testing Section: CC-5 Page 3 of 4 Rev-0 1.7 Routine Tests 1.7.1 Routine Tests on Containers 1.7.1.1 Containers for all lead acid cells shall be tested in accordance with IS: 1146. 1.7.2 Routine Tests on Separators 1.7.2.1 Routine tests shall be carried out as specified in applicable standards. 2 Special Tests 2.1 Seismic qualification The battery system shall be designed to meet the specified seismic requirements and same shall be demonstrated by qualifying the battery by following :Qualification by testing two cells (with all accessories) along with dummy cells accommodated in single battery rack on shake table as per IEEE-344 & procedure to be submitted by vendor in a format provided by NPCIL and subsequently approval of NPCIL. The applicable floor response spectra for the three principle directions (horizontal and vertical) will be forwarded to the successful bidder. If the TENDERER has already carried out tests on similar batteries with racks, and accessories, to meet the specified response spectra or for a more severe condition, the type test certificates for the same should be furnished for review and acceptance by the PURCHASER. Tests must have been conducted within five years from the date of opening of bids. If the equipment fails to pass the seismic test due to deficiencies in design or manufacture or malfunctioning of test set up, the CONTRACTOR shall bear such testing charges payable to test facility. Safe transportation of the equipment to and from the Supplier's works to the testing laboratory, engineering and supply of materials required (for making base plates, base frames etc.) for mounting the equipment on shake table and required manpower are to be provided by the CONTRACTOR. The CONTRACTOR shall also arrange for various testing and measuring instruments (such as battery load bank, fast Analogue recorder, megger, DC power supply rectifiers, storage oscilloscope etc.) required for these tests. In consultation with the PURCHASER and the testing agency, the CONTRACTOR shall prepare a detailed testing procedure including the list of parameters to be monitored during the testing as well as the tests to be carried SPECIFICATION NO.: PP-E-2405 April, 2009 Nuclear Power Corporation of India Limited Narora Atomic Power Station-1&2 Technical Specification for 250V DC Power and Control Batteries Inspection & Testing Section: CC-5 Page 4 of 4 Rev-0 out on the batteries before, during and after the seismic test. The seismic testing procedure and acceptance criteria will be finalized after placement of P.O. As a minimum requirement, the following tests shall be included for the battery, battery racks. Cells & battery stand used for seismic tests shall not be supplied to purchaser. a) b) c) d) Visual inspection. Monitoring of current and voltage. Performance of C10 capacity test before and after the seismic test. Seismically qualified cells and stands shall not be supplied as a part of the supplies against this tender. SPECIFICATION NO.: PP-E-2405 April, 2009