SEL-700G GENERATOR PROTECTION RELAY 2 KEY FEATURES Comprehensive Generator Protection Connect the SEL-700G Generator Protection Relay across small, medium, or large generators for complete primary and backup protection. Adding the neutral voltage connection provides 100 percent stator ground protection, based on fundamental-frequency and third-harmonic neutral-voltage measurements. Connecting the neutral current input provides protection for solidly grounded or resistance-grounded machines. Autosynchronizer Replace external generator control and synchronizer relays with the built-in automatic synchronizer function. Frequency, voltage, and phase control of the generator are automatically synchronized and connected to the power system. Monitor the generator synchronization process using generator start reports and the PC-based synchroscope. Current Differential Protection Apply sensitive percentage-restrained current differential elements and an unrestrained element, along with synchronism check and volts-perhertz elements, across the entire unit to protect both the generator and the step-up transformer. Optional current differential elements detect stator faults using a secure, sensitive current differential function. Power transformer and CT connection compensation allows the unit step-up transformer to be included in the generator differential zone. Breaker Wear Monitoring Record accumulated breaker contact wear with the breaker monitor function, which uses the manufacturer’s specifications for defining breaker operation limits. The internal monitor tracks the total number of close/open operations and integrates the interrupted current per phase. Set an alarm to alert operators when measured and accumulated quantities approach maintenance thresholds. This information facilitates proactive breaker maintenance and replacement without underutilizing resources. Easy Communications Choose from single or dual copper or fiber-optic Ethernet ports, or serial communications, and several protocols, including Mirrored Bits® communications and IEC 61850. Pick multiple Modbus® TCP or Modbus serial sessions for custom configuration of your application. Use DNP3 Serial or DNP3 LAN/WAN protocols. 3 FUNCTIONAL OVERVIEW SEL-700G P IAY, IBY, ICY ANSI NUMBERS/ACRONYMS AND FUNCTIONS 50 GQ 59S 21C/51VC 24 25G 27 32 40 46 49R 49T 50N 50 (P,G,Q) 51G 51N 59N (64G1) 59S 59 (P,G,Q) 60 64F 64G 67G 67N 78 81 (O,U,R) 87 87N REF 87 27S VS 50N 51N 67N 24 27 25G VAX, VBX, VCX ERATO EN 77 R G CBCT (Alternate IN) IN P O 59 GQ 64F 81 UR - SEL-2664 + ENV 49R SEL-2600 49T 32 78 40 67G 21 51VC 60 LOP 51G 46 BF IAX, IBX, ICX P 50 GQ IN 50N 51N REF 87N ADDITIONAL FUNCTIONS 52PB 85 RIO BF BRM DFR ENV HMI LDP LGC MET PMU SER RTU 64G 59N VN 52PB HMI DFR SER MET BRM RTU LGC PMU 85 RIO 4 EIA-232 EIA-485 2 Ethernet1 Compensator Distance, Voltage Restrained/Controlled Time-Overcurrent Volts/Hertz Synchronism Check Undervoltage Directional Power Loss-of-Field Neg. Seq. Overcurrent Thermal Overload (RTD) Thermal Model Neutral Overcurrent Overcurrent (Phase, Ground, Neg. Seq.) Ground Time-Overcurrent Neutral Time-Overcurrent Neutral Overvoltage Synchronism Overvoltage Overvoltage (Phase, Ground, Neg. Seq.) Loss-of-Potential Field Ground 100 Percent Stator Ground Directional Ground Overcurrent Directional Neutral Overcurrent Out-of-Step Frequency (Over, Under, Rate) Three-Phase Current Differential Neutral Current Differential Restricted Earth Fault 1 1 Pushbutton Trip/Close SEL Mirrored Bits Communications Breaker Failure Breaker Wear Monitor Event Reports SEL-2600 Operator Interface Load Data Profiling SELogic® Control Equations High-Accuracy Metering Synchrophasors Sequential Events Recorder Remote Terminal Unit Copper or Fiber-Optic IRIG-B FLEXIBLE COMMUNICATIONS Communications Media Communications Protocols Ethernet 10/100BASE-T SEL ASCII Ethernet 100BASE-FX Mirrored Bits communications Single or dual Ethernet ports IEC 61850 EIA-232 serial Modbus RTU/TCP EIA-485 serial Simple Network Time Protocol (SNTP) Fiber-optic, serial multimode ST® connectors DNP3 serial, LAN/WAN DeviceNet™ Telnet FTP Synchrophasors (IEEE C37.118) 4 PRODUCT OVERVIEW 1 Use default messages, or program up to 32 custom display labels. 2 Front-panel LEDs can be programmed to indicate custom alarms. 3 User-configurable label option. 4 Easy-to-use keypad aids simple navigation and set-point adjustment. 5 Use default pushbuttons, or program your own pushbutton actions and labels. 6 Power supply options include 24–48 Vdc, 110–250 Vdc, or 110–240 Vac. 7 Single or dual copper or fiber-optic Ethernet port. 8 Positions for optional expansion cards. 9 Voltage and current inputs. 10 Fiber-optic serial port. 11 Mirrored Bits® communications. 12 Optional RTD inputs. 1 4 2 5 3 6 10 7 11 8 12 9 5 APPLICATIONS COMPLETE GENERATOR PROTECTION The SEL-700G provides a complete protection and synchronization solution for synchronous generators. Eliminate the complexity and cost of standalone synchronizer packages. Integrating the synchronization capability into the generator protection relay provides the most cost-effective and reliable solution. Utility Bus IAY, IBY, ICY VS Breaker Control The optional SEL-2664 Field Ground Module accurately detects field ground faults whether the generator is operating, stopped, or de-energized. SEL- 700G VAX, VBX, VCX UNIT PROTECTION Internal RTDs or SEL-2600 RTD Module Apply sensitive percentage-restrained current differential elements and an unrestrained element, along with synchronism check and volts-per-hertz elements, across the entire unit to protect both the generator and the step-up transformer. Use harmonic blocking elements to protect the unit transformer bushing and end windings while maintaining security for inrush and through-fault conditions. 2664 SEL- IAX, IBX, ICX STATOR/FIELD GROUND PROTECTION IN Adding the neutral voltage connection provides 100 percent stator ground protection for most machines, based on fundamental-frequency and third-harmonic neutral-voltage measurements. Connecting the neutral current input provides protection for solidly grounded or resistance-grounded machines. Monitor field ground insulation resistance with state-of-the-art voltage injection, provided by the SEL-2664 Module. Protect generators from damage by responding to low field ground insulation resistance warnings. AUTOMATIC GENERATOR CONTROL SEL’s generation control system regulates generator power outputs and manages utility interties to maximize system stability, minimize electrical disturbances, and mitigate loadshedding requirements. The SEL-700G in combination with SEL’s powerMAX® Power Management and Control System can balance generation loading, control tie line power flow, and maintain bus voltage. The automatic MVAR and voltage control system maintains MVAR flows on interties and system bus voltages by controlling load tap changers, generator field and large synchronous motor exciters, synchronous and static condensers, and capacitor banks. 6 VN To the Power System From the Stator CTs and VTs Transf. To the Field Exciter Exciter Controller SEL Volt/VAR Controller G Generator Prime Mover Fuel, Water, or Steam Governor Controller SEL Generator Controller METERING AND REPORTING SYNCHROPHASOR DATA View generator autosynchronizer, Sequential Events Recorder (SER), and 180-cycle oscillographic event reports to analyze generator startup, shutdown, or system faults. Measure electrical, thermal, and generator run-time quantities. Apply SEL synchrophasors (IEEE C37.118) to turn state estimation into state measurement, and provide early warning of potential system instability. The SEL-700G phasor measurement accuracy meets the IEEE C37.118-2005 Level 1 requirement. 59.996 Hz Pullman, WA 60.003 Hz Chicago, IL 59.996 Hz Philadelphia, PA Ch ica go Tampa Mo nte r n Sa il rey t An Ph Pullman ia lph e ad io on 60.015 Hz 60.0 Hz 60.007 Hz Monterrey, Mexico San Antonio,TX Tampa, FL AUTOSYNCHRONIZER RETROFIT REPLACEMENT KITS The optional, built-in automatic synchronizer function eliminates the need for expensive external synchronizing equipment. Frequency, voltage, and phase angle of the generator are automatically synchronized and connected to the power system. Replace existing generator protection with the SEL-700G and the applicable mounting kit. These kits provide everything needed to replace many existing generator relays with the SEL-700G. No cutting or drilling is required when you use the optional mounting kits. Replacement of existing protection is quick and easy. RTD-BASED THERMAL PROTECTION Acquire thermal data for alarm, monitoring, and trip functions in the SEL-700G with a 10 resistance temperature detector (RTD) input card or an external 12 RTD SEL-2600 RTD Module. GENERATOR PRIME MOVER 7 EASY TO SET AND USE USE ACSELERATOR QUICKSET® SEL-5030 SOFTWARE TO SET, MONITOR, AND CONTROL THE SEL-700G • Save engineering time while keeping flexibility. Communicate with the SEL-700G through any ASCII terminal, or use the acSEL erator QuickSet graphical user interface. • Develop settings offline with a menu-driven interface and completely documented help screens. Speed installation by copying existing settings files and modifying application-specific items. • Simplify the settings procedure with rules-based architecture to automatically check interrelated settings. Out-of-range or conflicting settings are highlighted for correction. • Use the acSEL erator® human-machine interface (HMI) synchroscope to view the realtime synchronization process. • Initiate the generator synchronization process using an HMI pushbutton. USE ACSELERATOR SOFTWARE TO RETRIEVE AND DISPLAY EVENT REPORTS RECORDED BY THE SEL-700G • Display event report oscillograms. View each report as a plot of magnitude versus time. Select analog and digital points to build a custom display. • Display phase and symmetrical component phasors. Display the phasor view of electrical data to better understand asymmetrical, three-phase faults. Build a custom plot using per-phase and symmetrical component sequence currents and voltages. • Retrieve event reports using serial or Ethernet communications links. MAKING ELECTRIC POWER SAFER, MORE RELIABLE, AND MORE ECONOMICAL SCHWEITZER ENGINEERING LABORATORIES, INC. Tel:+1.509.332.1890 Email:info@selinc.com Web:www.selinc.com © 2009–2014 by Schweitzer Engineering Laboratories, Inc. PF00211 · 20140425