MQL • TABLE OF CONTENTS Product Overview .....................................................................................................................................3 Features and Benefits ...............................................................................................................................6 Application Considerations ......................................................................................................................5 Unit Configuration ...................................................................................................................................6 Electric Heat .............................................................................................................................................7 Coil and Filter Data ..................................................................................................................................9 Static Pressure Data ................................................................................................................................10 Weight and Electrical Data ......................................................................................................................12 Fan Notes ................................................................................................................................................13 Fan Performance Data .............................................................................................................................14 Guide Specifications................................................................................................................................25 Metric Conversion Chart..........................................................................................................................28 Features and Options ..............................................................................................................................30 GENERAL NOTES • Some drawings are not shown in this catalog. Please refer to www.enviro-tec.com for complete submittal drawings for your project. • All data herein is subject to change without notice. Refer to www.enviro-tec.com for current catalog and submittal drawings. • Drawings not for installation purposes; refer to IOM manual at www.enviro-tec.com. • ETL Report Number 3017723-001. • MEA Number MEA 107-02-E applies to all units with any combination of chilled water or R-22 direct expansion coils and either hot water coils, steam coils, or electric heat. 2 ENVIRO-TEC PRODUCT OVERVIEW • MQL The Perfect Solution for Schools, Hospitals, and Commercial Buildings. The flexibility of the Model MQL Indoor Air Handler allows you to design the unit to meet the specific project needs. The MQL design allows you to configure draw thru applications in horizontal, vertical, and footprint-saving arrangements. From basic air handling to the sophisticated isolation room systems required to meet challenging indoor air quality (IAQ), controls, and acoustic (sound sensitive) projects – the Model MQL Indoor Air Handler is your solution! Standard Features • Modular construction allows for footprint saving arrangements including stacking modules in two-high configuration. • IAQ galvanized drain pans are double sloped to prevent standing water and minimize microbial growth. Stainless steel drain pans are available. • Removable access panels for improved accessibility, cleanability, and serviceability. Hinged access doors with quick action latches are available. • Single point power connection – even with draw thru or blow thru electric heat – simplifies installation. Fan motors are factory mounted and wired to the junction box. • Available in nine sizes, from 600 to 10,000 CFM. • Internal spring isolation standard on all unit sizes 02 - 17. • Single wall and double wall-galvanized construction are available. Double wall construction enhances indoor air quality, protects insulation, and provides the ability to clean the inside of the unit. Optional Features • Factory-packaged air handlers are available with starters or variable frequency drives, factory mounted and wired. Simply connect power, piping, and ductwork, and the units are ready for operation. An excellent way to minimize installation time, coordination and costs, while increasing reliability. • Quiet, flexible, acoustical discharge plenums may be used for sound sensitive projects. • Exhaust / Return Fan with Economizer Sections for use with IAQ applications (“free” heating and cooling – cost savings for space conditioning). • Customized Options including: - Direct drive plug fans - High efficiency filters - Double wall perforated lining - External face and bypass dampers - Inspection windows ENVIRO-TEC 3 MQL • FEATURES AND Designed For Maximum Flexibility The ENVIRO-TEC ® Model MQL Indoor Air Handling Unit is designed to maximize flexibility of selection and installation. The unit is also designed to exceed the stringent quality standards of the institutional market, while remaining cost competitive in the light commercial segment of the market. ENVIRO-TEC® Model MQL sets the new standard for quality, flexibility, and competitive pricing. For the Building Designer: OPTIONAL COMPONENTS MEAN FLEXIBILITY The extensive variety of standard options available on the MQL is where you find the versatility to fit any HVAC system designer’s needs. Options include: Mixing boxes with standard low leak dampers, High efficiency filter sections for 2" prefilter and 4" final filter, blow thru electric heat with single point power connection. All electric heat units are listed with ETL as an assembly and carry the cETL label. BENEFITS Coil options allow for 4 or 6 row cooling coils. Water coils have optional circuiting that can be used to reduce Water Pressure Drop, which may also allow for pipe size reductions and lower material cost. Hot Water or Standard Steam coils may be placed in the Preheat or Reheat position. All Model MQL air handlers have the option of foil faced insulation. For the Contractor: LO W E R I N S TA L L E D C O S T Model MQL air handlers are shipped completely assembled, reducing field installation time and labor. All units are thoroughly inspected and tested prior to shipment, eliminating potential problems at startup. Motor wiring is brought to a junction box on the outside of the unit casing, reducing electrical hook-up time. For the Owner: QUALITY PRODUCT Model MQL air handling units are built from G60 minimum spangled galvanized steel with a chromate coating. This metal surpasses the ASTM 125 hour salt spray test for corrosion and rust. Standard insulation is 1 inch fiberglass insulation which is glued and pin spotted for maximum positive adhesion. Insulation complies with UL 181 and NFPA 90A. All units, with or without Electric Heat, are ETL listed and labeled. All wiring is in compliance with NEC, assuring safety and quality for the owner. A wide variety of fan discharge configurations allow for increased flexibility and easier installation on the jobsite, resulting in cost reductions by eliminating expensive elbows, etc. High Efficiency motors, starters, disconnects and fusing mean easier coordination between mechanical and electrical trades. 4 ENVIRO-TEC APPLICATION CONSIDERATIONS • MQL Application Considerations Model MQL Indoor Air Handling Units offer a wide range of application flexibility, while maintaining a simple, easy to install unit design. These units are intended to provide comfort cooling and heating within a small footprint. They may be applied in many types of building structures including schools, office buildings, hospitals, condominiums, assisted living facilities, apartments or stores. Applications can be constant or variable volume. There are many applications in which the MQL product can be utilized. Some examples include: Constant volume applications • Two-pipe hydronic system for cooling and/or heating • Two-pipe hydronic cooling system with electric heat • Four-pipe system with dedicated heating and cooling coils • Direct Expansion (DX) split systems with hydronic heat • Direct Expansion (DX) split systems with electric heat Variable volume applications • Two-pipe hydronic system for cooling and/or heating. • Two-pipe hydronic cooling system with electric heat. • Four-pipe system with dedicated heating and cooling coils. Acoustics Control of noise within both occupied and unoccupied spaces has become increasingly important to designers and building owners/occupants. Proper consideration must be given to placement of indoor air conditioning units, particularly in the occupied space. ENVIRO-TEC Inherent flexibility of the fan and coil combination in the vertical configuration allows application in sound-sensitive areas. In such instances, a fan running at low speed with a high capacity coil normally yields satisfactory results. It also may be desirable to select a larger nominal capacity unit and operate it at a less than nominal airflow for further acoustic benefit. Three phase motors are recommended for sound-sensitive applications to avoid potential single phase motor hum. Unit operation in the stall region of the fan curve is not recommended since it may cause unsatisfactory noise levels and excessive unit vibration. Installation These floor mounted or ceiling hung units can be installed on a base rail or hanger rods at the corner points. All units have internally isolated fan decks; therefore, flex connections are not required, which will reduce installation costs. One of the most important and basic IAQ issues is condensate management. The first step to ensure trouble-free operation is proper installation. It is very important that the unit be mounted high enough so that the condensate drain from the unit may be properly trapped. Please refer to the MQL IOM Manual at www.enviro-tec.com for specifics on this issue. As with all HVAC systems, these units should be installed according to all applicable ASHRAE standards, SMACNA and local code requirements. Operating Limitations Units must not be operated above maximum fan speed or unit airflow as listed in the Fan Performance section of this catalog. Unit operation at greater than maximum fan speed could drastically reduce bearing life and may result in a catastrophic failure. Operating at greater than the maximum allowable airflow in the cooling mode may result in unsatisfactory operation due to moisture carry over from the coil. In addition, it is often not economical to operate a unit at its maximum fan speed due to the greater motor power requirements. Units with electric heat should not be operated with leaving air temperature greater than 104°F, to prevent excessive leaving air temperatures and electric heat limit trips. A hydronic (or steam) coil and electric heat should not be operated simultaneously to prevent excessive leaving air temperatures and limit trips. Electric heat units are equipped with a lockout switch that disables the electric heater if the temperature of the hydronic (or steam) coil is greater than 104°F (40°C). Water coils must not be operated above a fluid velocity of 8 ft./sec. to reduce the possibility of velocity induced erosion and flow noise. Water coils must not be operated below a fluid velocity of 1 ft./sec. to prevent degraded coil performance caused by laminar flow. These high or low fluid flow rates may not be included in the ARI coil certification. 5 6 Horizontal FC Fan Horizontal Plug Fan Return FC Fan Return Plug Fan Vertical Coil Vertical FC Fan MBM Medium Face & Bypass MTM Medium Tall Coil STM Small Tall Coil Electric Heat Draw Thru Large Access H - in (mm) W - in (mm) Lg. INTELLITRAC® Mix. Box w/V-Bank Filters (2") Lg. INTELLITRAC® Inlet Plenum w/V-Bank Filters (2") L - in (mm) Large Mixing Box with V-Bank Filters (2") Large Inlet Plenum with V-Bank Filters (2") Large Discharge Plenum HFM HPM RFM RPM VCM VFM EHD LAM LFM LIM LMM LRM LPM Fig. 2 Fig. 2 Fig. 3 EHB Fig. 5 Electric Heat Blow Thru FCM FC Fan and Coil Combination (Horizontal Only) HEM Horizontal Economizer Fig. 4 Fig. 4 Fig. 2 3 03 4 04 22 (559) 30 (762) 22 (559) 36 (914) 22 (559) 36 (914) 42 (1067) 22 (559) 36 (914) 30 (762) 30 (762) 36 (914) 30 (762) 22 (559) 36 (914) 32 (813) 22 (559) 36 (914) 30 (762) 22 (559) 36 (914) 15 (381) 22 (559) 44 (1118) 22 (559) 44 (1118) 42 (1067) 22 (559) 44 (1118) 30 (762) 30 (762) 44 (1118) 30 (762) 22 (559) 44 (1118) 32 (813) 22 (559) 44 (1118) 30 (762) 22 (559) 44 (1118) 15 (381) H - in (mm) 13-1/2 (343) 13-1/2 (343) 13-1/2 (343) W - in (mm) 11-1/2 (292) 11-1/2 (292) 11-1/2 (292) L - in (mm) 22 (559) 22 (559) 22 (559) H - in (mm) W - in (mm) 22 (559) 30 (762) 30 (762) H - in (mm) W - in (mm) L - in (mm) 22 (559) 30 (762) 42 (1067) 30 (762) 30 (762) 30 (762) 22 (559) 30 (762) 32 (813) 22 (559) 30 (762) 30 (762) 22 (559) 30 (762) 15 (381) H - in (mm) W - in (mm) L - in (mm) H - in (mm) W - in (mm) L - in (mm) H - in (mm) W - in (mm) L - in (mm) Medium Access Medium Coil Med. INTELLITRAC® Mix. Box w/Flat Filters (2") Med. INTELLITRAC® Inlet Plenum w/Flat Filters (2") Medium Mixing Box with Flat Filters (2") Medium Inlet Plenum with Flat Filters (2") Medium V-Bank Filters (2") Fig. 2 02 2 06 5 08 6 10 7 12 8 14 9 UNIT CONFIGURATION (IN DIRECTION OF AIRFLOW) 10 17 18 (457) 17 (432) 22 (559) 30 (762) 44 (1118) 30 (762) 44 (1118) 42 (1067) 30 (762) 44 (1118) 30 (762) 40 (1016) 44 (1118) 30 (762) 30 (762) 44 (1118) 36 (914) 30 (762) 44 (1118) 30 (762) 30 (762) 44 (1118) 15 (381) 18 (457) 17 (432) 22 (559) 34 (864) 48 (1219) 34 (864) 48 (1219) 42 (1067) 34 (864) 48 (1219) 30 (762) 46 (1168) 48 (1219) 30 (762) 34 (864) 48 (1219) 36 (914) 34 (864) 48 (1219) 30 (762) 34 (864) 48 (1219) 15 (381) 18 (457) 17 (432) 22 (559) 34 (864) 58 (1473) 34 (864) 58 (1473) 42 (1067) 34 (864) 58 (1473) 30 (762) 46 (1168) 58 (1473) 30 (762) 34 (864) 58 (1473) 36 (914) 34 (864) 58 (1473) 30 (762) 34 (864) 58 (1473) 15 (381) 21 (533) 24 (610) 22 (559) 44 (1118) 66 (1676) 44 (1118) 66 (1676) 42 (1067) 44 (1118) 66 (1676) 30 (762) 56 (1422) 66 (1676) 30 (762) 44 (1118) 66 (1676) 40 (1016) 44 (1118) 66 (1676) 30 (762) 44 (1118) 66 (1676) 15 (381) 21 (533) 24 (610) 22 (559) 44 (1118) 70 (1778) 44 (1118) 70 (1778) 42 (1067) 44 (1118) 70 (1778) 30 (762) 58 (1473) 70 (1778) 30 (762) 44 (1118) 70 (1778) 40 (1016) 44 (1118) 70 (1778) 30 (762) 44 (1118) 70 (1778) 15 (381) 21 (533) 24 (610) 22 (559) 44 (1118) 82 (2083) 44 (1118) 58 (1473) 42 (1067) 44 (1118) 82 (2083) 30 (762) 58 (1473) 82 (2083) 30 (762) 44 (1118) 82 (2083) 40 (1016) 44 (1118) 82 (2083) 30 (762) 44 (1118) 82 (2083) 15 (381) H - in (mm) 17-3/8 (441) 17-3/8 (441) 17-3/8 (441) 26-3/8 (670) 26-3/8 (670) 26-3/8 (670) 41-3/16 (1046) 41-3/16 (1046) 41-3/16 (1046) W - in (mm) 28 (711) 34 (864) 42 (1069) 42 (1069) 46 (1168) 56 (1422) 64 (1626) 68 (1727) 80 (2032) L - in (mm) 5-1/4 (133) 5-1/4 (133) 5-1/4 (133) 5-1/4 (133) 5-1/4 (133) 5-1/4 (133) 5-1/4 (133) 5-1/4 (133) 5-1/4 (133) MAM MCM MFM MIM MMM MRM MVM External Flat Filters (2") H - in (mm) W - in (mm) L - in (mm) EFM 1 Dim. SAM Small Access SCM Small Coil SFM Small Flat Filters (2" and/or 4" Cartridge) Fig. 1 MQL - Module Size Lower Deck - A Position: Upper Deck - B Notes: 1. All dimensions are + 1/4" (6mm). Metric values are soft conversions. 2. Section images are for identification of unit configuration only. See individual section submittal drawings at www.enviro-tec.com for details. 3. Certain configuration rules apply; see catalog and selection program for details. 4. All data subject to change without notice. MQL • UNIT CONFIGURATION ENVIRO-TEC ELECTRIC HEAT • MQL STANDARD FEATURES OPTIONAL FEATURES • G60 galvanized steel casing • Flanged construction for direct unit mounting, in blow thru configuration • Listed for zero clearance installation • Meets National Electrical Code requirements • Ni-Chrome wire in ceramic insulators • Stainless steel element terminals and hardware • Element support brackets on maximum 3 1/2" centers • Solid cover with continuous full height hinge • Overtemperature protection • All internal wiring rated for 105°C minimum • Airflow switch • Incoming line power distribution block • ETL Listed in compliance with UL/ANSI Standard 1995 • Single point power connection • Heater factory mounted to unit with ETL listing as an assembly • Main incoming power disconnect (non-fused) (fused) • Fusing (main) (per stage) • Magnetic contactors wired for disconnecting operation • Solid state relay with 4-20 mA, thermistor 0-135 Ohm, 0-16 VDC, or 6-9 VDC control • Fan control package with heater interlock contacts (required for single point power connection) • De-rated elements (for longer life) Plan View Airflow Side View Front View Side View Airflow Draw Thru Blow Thru (installed upstream of fan) (installed on unit discharge) HEATER AMP CALCULATION AMPs per kW VOLTAGE 8.70 115/1 4.81 208/1 4.35 230/1 3.61 277/1 2.78 208/3 2.51 230/3 1.26 460/3 1.00 575/3 1.Refer to MCA/MOP Calculator at www.enviro-tec.com for MCA and/or MOP calculations. 2. Non-Fused Door Interlock Disconnect Switch shall be sized according to MCA. 3. Fused Door Interlock Disconnect Switch and Main Fusing shall be sized according to MOP. 4. Heaters above 480v must utilize one time secondary limits only. ENVIRO-TEC 7 MQL • ELECTRIC HEAT BLOW-THRU ELECTRIC HEAT Single Phase UNIT VOLTAGE AND PHASE 115 208 230 277 Three Phase 208 230 460 575 kW AMPs kW AMPs kW AMPs kW AMPs kW AMPs kW AMPs kW AMPs kW AMPs Unit Size 02 Min 3 26.1 3 14.4 3 13.0 3 10.8 3 8.3 3 7.5 3 3.8 3 3.0 03 Max 5 43.5 9 43.3 11 47.8 13 46.9 13 36.1 13 32.6 13 16.3 13 13.1 Min 3 26.1 3 14.4 3 13.0 3 10.8 3 8.3 3 7.5 3 3.8 3 3.0 04 Max 5 43.5 9 43.3 11 47.8 13 46.9 16 44.4 18 45.2 20 25.1 20 20.1 Min 4 34.8 4 19.2 4 17.4 4 14.4 4 11.1 4 10.0 4 5.0 4 4.0 06 Max 5 43.5 9 43.3 11 47.8 13 46.9 16 44.4 18 45.2 26 32.6 26 26.1 08 10 12 14 17 Min Max Min Max Min Max Min Max Min Max Min Max 6 28.8 6.0 26.1 6.0 21.7 4.0 11.1 4.0 10.0 4.0 5.0 4.0 4.0 9 43.3 11 47.8 13 46.9 16 44.4 18 45.2 26 32.6 26 26.1 7 33.7 7 30.4 7 25.3 7 19.4 7 17.6 7 8.8 7 7.0 9 43.3 11 47.8 13 46.9 16 44.4 18 45.2 38 47.7 46 46.2 9 39.1 9 32.5 9 25.0 9 22.6 9 11.3 9 9.0 11 47.8 13 46.9 16 44.4 18 45.2 38 47.7 46 46.2 12 33.3 12 30.1 12 15.1 12 12.0 16 44.4 18 45.2 38 47.7 46 46.2 14 38.9 14 35.1 14 17.6 14 14.1 16 44.4 18 16 18 45.2 40.2 45.2 38 16 38 47.7 20.1 47.7 46 16 46 46.2 16.1 46.2 Notes: 1. 2. 3. 4. Blow thru heaters can have a maximum of two stages. VFD controllers cannot be supplied with blow thru heaters. Specific kW ratings are available within the ranges shown. Refer to selection program. Heaters above 480v must utilize one time secondary limits only. DRAW-THRU ELECTRIC HEAT UNIT VOLTAGE AND PHASE Single Phase 115 208 230 277 Three Phase 208 230 460 575 kW Unit Size 02 03 04 06 Min Max Min Max Min Max 3 5 3 5 4 5 08 10 12 Min Max Min Max Min Max 6.0 16 7 16 9 20 14 17 Min Max Min Max Min Max 12 46 14 46 16 46 AMPs 26.1 43.5 26.1 43.5 34.8 43.5 kW 3 10 3 10 4 10 AMPs 14.4 48.1 14.4 48.1 19.2 48.1 28.8 76.9 33.7 76.9 43.3 96.2 kW 3 11 3 11 4 11 6.0 18 7 18 9 22 AMPs 13.0 47.8 13.0 47.8 17.4 47.8 26.1 78.3 30.4 78.3 39.1 95.7 kW 3 13 3 13 4 13 6.0 22 7 22 9 26 AMPs 10.8 46.9 10.8 46.9 14.4 46.9 21.7 79.4 25.3 79.4 32.5 93.9 kW 3 AMPs 8.3 kW 3 AMPs 7.5 kW 3 AMPs 3.8 kW 3 AMPs 3.0 13 3 36.1 8.3 13 3 32.6 7.5 20 4 26 4.0 26 7 28 9 34 55.5 11.1 72.2 11.1 72.2 19.4 77.7 25.0 94.4 33.3 127.7 38.9 127.7 44.4 127.7 20 4 26 4.0 26 7 32 9 34 12 49 14 49 16 49 50.2 10.0 65.3 10.0 65.3 17.6 80.3 22.6 85.3 30.1 123.0 35.1 123.0 40.2 123.0 13 3 20 4 26 4.0 26 7 16.3 3.8 25.1 5.0 32.6 5.0 32.6 8.8 52 9 64 12 76 14 88 16 96 65.3 11.3 80.3 15.1 95.4 17.6 110.4 20.1 120.5 13 3 20 4 26 4.0 26 7 52 9 13.1 3.0 20.1 4.0 26.1 4.0 26.1 7.0 52.2 9.0 64 12 76 14 88 16 96 64.3 12.0 76.3 14.1 88.4 16.1 96.4 Notes: 1. 2. 3. 4. 8 Draw thru heaters can have a maximum of four stages. All heaters that have an AMP draw greater than 48 AMPs will have a minimum of two stages. Specific kW ratings are available within the ranges shown. Refer to selection program. Heaters above 480v must utilize one time secondary limits only. ENVIRO-TEC COIL AND FILTER DATA • MQL ENVIRO-TEC® offers hot water, chilled water, direct expansion (DX), and standard steam coils for specific application with all Model MQL air handlers. ARI 410 certified and labeled, and strict on-site inspection before, during, and after installation guarantees the highest quality and performance available. Optional Features Standard Features • ENVIRO-TEC® coils are designed, manufactured and tested by Johnson Controls • ARI 410 certified and labeled • 1/2" O.D. seamless copper tubes • Aluminum fin construction with die-formed spacer collars for uniform spacing • Mechanically expanded copper tubes leak tested to a minimum 450 PSIG air pressure under water • Manual air vent plug on all water coils • Copper ODM sweat connections • 300 PSIG working pressure at 200°F • Evaporator coils are factory sealed and charged with a minimum of 5 PSIG nitrogen or refrigerated dry air • Refrigerant coils are provided with a fixed orifice distributor. Thermal expansion valves are not included. • Steam coils rated at maximum for 15 PSIG • 0.016" tube wall thickness (0.025" on steam) • Stainless steel coil casings • Automatic air vents on water coils • Elevated working pressure ratings • Heat pump compatible cooling coils • Double circuit DX coils (50-50 split) • 0.025" tube wall thickness The ENVIRO-TEC® Windows® based ARI 410 certified Coil Selection Program provides all necessary selection and coil rating information for Model MQL Indoor Handling Units. The Coil Selection Program is available online at www.enviro-tec.com. COIL AND FILTER DATA Unit Sizes Coil Face Area Qty. Flat Filters Dimensions Face Area Qty. 02 V-Bank Filters Dimensions 2.1 [0.20] 1 16x20x2 [406x508x51] 2.2 [0.20] 2 16x20x2 [406x508x51] 4.4 [0.41] 03 2.9 [0.27] 1 16x25x2 [406x635x51] 2.8 [0.26] 2 16x25x2 [406x635x51] 5.6 [0.52] 04 3.8 [0.35] 2 16x20x2 [406x508x51] 4.4 [0.41] 2 20x25x2 [508x635x51] 6.9 [0.64] 06 5.6 [0.52] 2 20x25x2 [508x635x51] 6.9 [0.64] 4 20x20x2 [508x508x51] 11.1 [1.03] 08 7.4 [0.69] 2 20x25x2 [508x635x51] 6.9 [0.64] 2 2 16x20x2 [406x508x51] 20x25x2 [508x635x51] 11.4 [1.06] 10 9.7 [0.90] 1 2 16x25x2 [406x635x51] 20x25x2 [508x635x51] 9.7 [0.90] 2 4 16x20x2 [406x508x51] 20x20x2 [508x508x51] 15.6 [1.45] 12 12.6 [1.17] 4 20x25x2 [508x635x51] 13.9 [1.29] 6 20x25x2 [508x635x51] 20.8 [1.93] 14 14.3 [1.33] 8 16x20x2 [406x508x51] 17.8 [1.65] 3 6 20x25x2 [508x635x51] 20x20x2 [508x508x51] 27.1 [2.52] 17 17.0 [1.58] 6 20x25x2 [508x635x51] 20.8 [1.93] 12 20x20x2 [508x508x51] 33.3 [3.09] Face Area NOTES: 1. Standard filters are 2" throwaway; optional filters are 2" pleated. 2. Filter sizes are nominal and standard size, measured in inches [millimeters]. 3. Coil and filter face areas are measured in square feet [square meters]. 4. Cooling and heating coils have same face area. 5. For coil connection sizes, refer to the ENVIRO-TEC® Coil Selection Program. ENVIRO-TEC 9 MQL • STATIC PRESSURE DATA Section Pressure Drops COMPONENT AIR PRESSURE DROP (IN. W.G.) Cabinet Losses Unit Size 02 03 04 06 08 10 12 14 17 CFM Mixing EconoBox mizer Fan Modules Damper Losses Filter Access Plenum Coil Modules Modules Modules Module Mixing Box Electric Heater Losses Economizer Blow Thru Draw Thru MFM LFM MMM LMM HEM FCM RFM VFM SFM MVM SCM MCM VCM SAM MAM LAM LPM MFM LFM MMM LMM HEM EHB EHD 600 0.01 0.02 0.01 0.01 0.02 0.02 0.02 0.02 0.02 0.04 0.02 0.04 0.02 0.01 850 0.02 0.04 0.02 0.02 0.03 0.03 0.04 0.03 0.04 0.06 0.04 0.07 0.04 0.01 975 0.02 0.04 0.02 0.02 0.04 0.04 0.04 0.04 0.04 0.07 0.05 0.09 0.06 0.01 1100 0.03 0.05 0.03 0.03 0.05 0.05 0.05 0.05 0.05 0.08 0.06 0.11 0.08 0.01 900 0.01 0.02 0.01 0.01 0.02 0.02 0.02 0.02 0.02 0.06 0.02 0.06 0.05 0.01 1250 0.02 0.04 0.02 0.02 0.03 0.03 0.04 0.03 0.04 0.09 0.03 0.10 0.10 0.01 1425 0.03 0.05 0.02 0.02 0.04 0.04 0.05 0.04 0.05 0.11 0.04 0.13 0.13 0.01 1600 0.03 0.06 0.03 0.03 0.05 0.05 0.06 0.05 0.06 0.13 0.05 0.16 0.17 0.01 1200 0.01 0.02 0.01 0.01 0.02 0.02 0.02 0.02 0.02 0.04 0.02 0.07 0.09 0.01 1600 0.02 0.03 0.02 0.02 0.03 0.03 0.03 0.03 0.03 0.06 0.03 0.12 0.17 0.01 1800 0.02 0.04 0.02 0.02 0.04 0.04 0.04 0.04 0.04 0.07 0.04 0.15 0.21 0.01 2000 0.03 0.05 0.02 0.02 0.04 0.04 0.05 0.04 0.05 0.09 0.05 0.19 0.27 0.01 1800 0.01 0.02 0.01 0.01 0.02 0.02 0.02 0.02 0.02 0.04 0.02 0.07 0.04 0.01 2500 0.02 0.04 0.02 0.02 0.03 0.03 0.04 0.03 0.04 0.06 0.03 0.13 0.09 0.01 2850 0.03 0.05 0.02 0.02 0.04 0.04 0.05 0.04 0.05 0.08 0.04 0.17 0.12 0.01 3200 0.03 0.06 0.03 0.03 0.05 0.05 0.06 0.05 0.06 0.09 0.05 0.21 0.15 0.01 2300 0.01 0.02 0.01 0.01 0.02 0.02 0.02 0.02 0.02 0.03 0.02 0.06 0.07 0.01 3250 0.02 0.04 0.02 0.02 0.03 0.03 0.04 0.03 0.04 0.05 0.03 0.12 0.15 0.01 3725 0.03 0.05 0.02 0.02 0.04 0.04 0.05 0.04 0.05 0.06 0.04 0.16 0.20 0.01 4200 0.03 0.06 0.03 0.03 0.05 0.05 0.06 0.05 0.06 0.07 0.05 0.20 0.26 0.01 2900 0.01 0.02 0.01 0.01 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.09 0.12 0.01 4100 0.02 0.04 0.02 0.02 0.03 0.03 0.04 0.03 0.04 0.04 0.03 0.17 0.25 0.01 4700 0.03 0.05 0.02 0.02 0.04 0.04 0.05 0.04 0.05 0.06 0.04 0.22 0.33 0.01 5300 0.03 0.06 0.03 0.03 0.05 0.05 0.06 0.05 0.06 0.07 0.05 0.27 0.42 0.01 3800 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.04 0.02 0.08 0.07 0.01 5325 0.02 0.03 0.01 0.01 0.02 0.02 0.03 0.02 0.03 0.07 0.04 0.16 0.14 0.01 6090 0.02 0.03 0.02 0.02 0.03 0.03 0.03 0.03 0.03 0.09 0.05 0.21 0.18 0.01 6850 0.02 0.04 0.02 0.02 0.03 0.03 0.04 0.03 0.04 0.11 0.06 0.26 0.23 0.01 4400 0.01 0.02 0.01 0.01 0.01 0.01 0.02 0.01 0.02 0.02 0.02 0.08 0.09 0.01 6200 0.02 0.03 0.02 0.02 0.03 0.03 0.03 0.03 0.03 0.04 0.03 0.15 0.19 0.01 7100 0.02 0.04 0.02 0.02 0.03 0.03 0.04 0.03 0.04 0.05 0.04 0.20 0.25 0.01 8000 0.03 0.05 0.02 0.02 0.04 0.04 0.05 0.04 0.05 0.07 0.05 0.25 0.32 0.01 5100 0.01 0.02 0.01 0.01 0.01 0.01 0.02 0.01 0.02 0.02 0.02 0.10 0.13 0.01 7225 0.02 0.03 0.02 0.02 0.03 0.03 0.03 0.03 0.03 0.04 0.04 0.20 0.26 0.01 8290 0.02 0.04 0.02 0.02 0.03 0.03 0.04 0.03 0.04 0.05 0.05 0.26 0.35 0.01 9350 0.02 0.04 0.02 0.02 0.04 0.04 0.04 0.04 0.04 0.06 0.06 0.33 0.45 0.01 Notes: 1. Figures do not include pressure drop of internal filter media. Refer to Air Pressure Drop Through Filter Section table for filter air pressure drop adders. 2. Figures do not include pressure drop of internal heating and/or cooling coils. Refer to Air Pressure Drop Through Dry Coil Section table for coil air pressure drop adders. 3. Mixing box with single damper in fully opened position operating at 100% air volume. 4. Economizer with outside air and exhaust dampers in fully opened position operating at 100% air volume. 10 ENVIRO-TEC STATIC PRESSURE DATA • MQL Filter Pressure Drops AIR PRESSURE DROP THROUGH FILTER SECTION (IN. W.G.) Filter Size & Type Efficiency 200 250 300 350 400 450 500 550 600 650 700 750 800 2" @ 30% 0.12 0.15 0.18 0.21 0.24 0.27 0.30 0.33 0.36 0.39 0.42 0.45 0.48 4" @ 65% 0.18 0.23 0.27 0.32 0.36 0.41 0.45 0.50 0.54 0.59 0.63 0.68 0.72 4" @ 85% 0.26 0.33 0.39 0.46 0.52 0.59 0.65 0.72 0.78 0.85 0.91 0.98 1.04 4" @ 95% 0.30 0.38 0.45 0.53 0.60 0.68 0.75 0.83 0.90 0.98 1.05 1.13 1.20 High Efficiency Pleated Air Velocity (FPM) Notes: 1. Figures listed represent air pressure drop of clean filters. 2. Usable pressure drop across pleated media not recommended to exceed 1.0 inch w.g. 3. Air velocities associated with pressure drops in the shaded region not recommended. Coil Pressure Drops AIR PRESSURE DROP THROUGH DRY COIL SECTION (IN. W.G.) Rows Fins per Inch 1 2 3 4 6 8 Air Velocity (FPM) 200 250 300 350 400 450 500 550 600 650 700 750 800 8 0.01 0.02 0.03 0.04 0.05 0.05 0.06 0.08 0.09 0.10 0.11 0.13 0.14 10 0.02 0.03 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.11 0.13 0.15 0.16 12 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.11 0.13 0.15 0.16 0.18 14 0.02 0.03 0.04 0.05 0.07 0.08 0.10 0.11 0.13 0.14 0.16 0.18 0.20 8 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.25 0.28 10 0.04 0.05 0.07 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 0.29 0.32 12 0.04 0.06 0.08 0.10 0.12 0.14 0.17 0.20 0.23 0.26 0.29 0.33 0.36 14 0.05 0.07 0.09 0.11 0.13 0.16 0.19 0.22 0.25 0.29 0.33 0.36 0.40 8 0.04 0.06 0.09 0.11 0.14 0.16 0.19 0.23 0.26 0.30 0.34 0.38 0.42 10 0.05 0.08 0.10 0.13 0.16 0.19 0.22 0.26 0.30 0.34 0.39 0.44 0.48 12 0.06 0.09 0.12 0.15 0.18 0.22 0.26 0.30 0.34 0.39 0.44 0.49 0.55 14 0.07 0.10 0.13 0.16 0.20 0.24 0.29 0.33 0.38 0.43 0.49 0.55 0.61 8 0.06 0.09 0.11 0.15 0.18 0.22 0.26 0.30 0.35 0.40 0.45 0.51 0.57 10 0.07 0.10 0.13 0.17 0.21 0.25 0.30 0.35 0.40 0.46 0.52 0.58 0.65 12 0.08 0.12 0.15 0.19 0.24 0.29 0.34 0.40 0.46 0.52 0.58 0.65 0.73 14 0.09 0.13 0.17 0.22 0.27 0.32 0.38 0.44 0.51 0.58 0.65 0.73 0.81 8 0.09 0.13 0.17 0.22 0.27 0.33 0.39 0.45 0.52 0.60 0.68 0.76 0.85 10 0.11 0.15 0.20 0.26 0.32 0.38 0.45 0.52 0.60 0.69 0.78 0.87 0.97 12 0.12 0.17 0.23 0.29 0.36 0.43 0.51 0.59 0.68 0.78 0.88 0.98 1.09 14 0.14 0.20 0.26 0.33 0.40 0.48 0.57 0.66 0.76 0.87 0.98 1.09 1.21 8 0.12 0.17 0.23 0.29 0.36 0.44 0.52 0.61 0.70 0.80 0.90 1.01 1.13 10 0.14 0.20 0.27 0.34 0.42 0.51 0.60 0.70 0.80 0.92 1.04 1.16 1.29 12 0.16 0.23 0.31 0.39 0.48 0.58 0.68 0.79 0.91 1.04 1.17 1.31 1.45 14 0.19 0.26 0.35 0.44 0.54 0.65 0.76 0.89 1.02 1.15 1.30 1.46 1.62 Note: Dehumidifying cooling coils with face velocities exceeding 525 fpm not recommended. ENVIRO-TEC 11 MQL • WEIGHT DATA Coil Weight Data COIL WEIGHTS UNIT SIZE 02 03 04 06 08 10 12 14 17 COIL ROWS 1 2 3 4 6 8 1 2 3 4 6 8 1 2 3 4 6 8 1 2 3 4 6 8 1 2 3 4 6 8 1 2 3 4 6 8 1 2 3 4 6 8 1 2 3 4 6 8 1 2 3 4 6 8 8 FPI 10 [5] 16 [7] 21 [10] 28 [13] 40 [18] 57 [26] 13 [6] 19 [9] 26 [12] 34 [15] 50 [23] 71 [32] 15 [7] 23 [11] 32 [14] 41 [19] 60 [27] 80 [36] 19 [9] 32 [14] 45 [20] 59 [27] 87 [39] 117 [53] 23 [11] 40 [18] 57 [26] 75 [34] 111 [50] 157 [71] 28 [13] 48 [22] 68 [31] 89 [41] 133 [60] 183 [83] 35 [16] 62 [28] 88 [40] 116 [53] 173 [78] 233 [106] 39 [18] 69 [31] 98 [45] 130 [59] 194 [88] 272 [123] 45 [20] 79 [36] 114 [52] 150 [68] 224 [102] 206 [93] DRY COIL 10 FPI 12 FPI 11 [5] 11 [5] 16 [7] 17 [8] 22 [10] 23 [11] 29 [13] 30 [14] 42 [19] 44 [20] 61 [28] 65 [30] 13 [6] 13 [6] 20 [9] 21 [10] 28 [13] 29 [13] 36 [16] 38 [17] 53 [24] 56 [25] 76 [34] 81 [37] 15 [7] 16 [7] 24 [11] 26 [12] 33 [15] 35 [16] 44 [20] 46 [21] 64 [29] 68 [31] 85 [38] 90 [41] 20 [9] 21 [10] 34 [15] 36 [16] 48 [22] 50 [23] 62 [28] 66 [30] 92 [42] 98 [44] 125 [57] 133 [61] 25 [11] 26 [12] 43 [19] 45 [20] 61 [27] 64 [29] 80 [36] 85 [38] 118 [54] 126 [57] 169 [77] 182 [83] 30 [13] 31 [14] 51 [23] 54 [25] 73 [33] 77 [35] 96 [43] 102 [46] 142 [64] 152 [69] 197 [90] 212 [96] 37 [17] 39 [18] 66 [30] 70 [32] 94 [43] 101 [46] 125 [57] 133 [60] 186 [84] 199 [90] 251 [114] 269 [122] 41 [19] 44 [20] 74 [33] 78 [36] 106 [48] 113 [51] 140 [63] 149 [68] 208 [94] 223 [101] 295 [134] 318 [144] 48 [22] 51 [23] 85 [39] 91 [41] 122 [56] 131 [59] 162 [73] 173 [79] 241 [109] 259 [117] 206 [93] 206 [93] 14 FPI 11 [5] 18 [8] 24 [11] 32 [14] 46 [21] 69 [31] 14 [6] 22 [10] 31 [14] 40 [18] 59 [27] 86 [39] 17 [8] 27 [12] 37 [17] 49 [22] 72 [33] 95 [43] 22 [10] 38 [17] 53 [24] 70 [32] 104 [47] 142 [64] 27 [12] 48 [22] 68 [31] 90 [41] 133 [60] 195 [88] 33 [15] 57 [26] 82 [37] 108 [49] 161 [73] 226 [103] 42 [19] 74 [34] 107 [49] 142 [64] 211 [96] 287 [130] 46 [21] 83 [38] 120 [55] 159 [72] 237 [108] 341 [155] 53 [24] 97 [44] 140 [63] 185 [84] 276 [125] 206 [93] 8 FPI 12 [5] 19 [9] 27 [12] 35 [16] 51 [23] 71 [32] 15 [7] 24 [11] 34 [15] 44 [20] 64 [29] 89 [41] 18 [8] 29 [13] 40 [18] 53 [24] 78 [35] 103 [47] 24 [11] 41 [19] 58 [26] 76 [35] 113 [51] 152 [69] 30 [14] 52 [24] 75 [34] 98 [45] 146 [66] 204 [92] 36 [16] 63 [28] 90 [41] 119 [54] 176 [80] 241 [109] 45 [21] 81 [37] 118 [53] 155 [70] 231 [105] 311 [141] 50 [23] 91 [41] 132 [60] 174 [79] 260 [118] 359 [163] 58 [26] 106 [48] 153 [69] 203 [92] 302 [137] 309 [140] 100% 10 FPI 12 [5] 20 [9] 28 [13] 36 [16] 53 [24] 75 [34] 16 [7] 25 [12] 35 [16] 46 [21] 67 [31] 95 [43] 18 [8] 30 [14] 42 [19] 55 [25] 82 [37] 108 [49] 25 [11] 43 [20] 61 [28] 80 [36] 119 [54] 160 [73] 31 [14] 54 [25] 78 [36] 103 [47] 153 [69] 216 [98] 37 [17] 66 [30] 95 [43] 125 [57] 186 [84] 255 [116] 48 [22] 86 [39] 124 [56] 164 [74] 244 [111] 329 [149] 53 [24] 96 [43] 139 [63] 184 [83] 274 [124] 382 [173] 61 [28] 112 [51] 162 [73] 214 [97] 319 [145] 309 [140] WATER 12 FPI 13 [6] 21 [10] 29 [13] 37 [17] 55 [25] 79 [36] 16 [7] 26 [12] 37 [17] 48 [22] 70 [32] 100 [45] 19 [9] 32 [15] 44 [20] 58 [26] 86 [39] 113 [51] 26 [12] 45 [20] 64 [29] 84 [38] 124 [56] 169 [77] 32 [15] 57 [26] 82 [37] 108 [49] 161 [73] 229 [104] 39 [18] 69 [31] 99 [45] 131 [60] 195 [88] 270 [122] 50 [23] 90 [41] 130 [59] 172 [78] 257 [117] 347 [157] 55 [25] 101 [46] 146 [66] 194 [88] 289 [131] 405 [184] 64 [29] 117 [53] 170 [77] 226 [102] 336 [153] 309 [140] 14 FPI 13 [6] 21 [10] 30 [14] 39 [18] 57 [26] 83 [38] 17 [8] 27 [12] 38 [17] 50 [23] 73 [33] 105 [47] 20 [9] 33 [15] 46 [21] 60 [27] 89 [41] 118 [54] 27 [12] 47 [21] 67 [30] 88 [40] 130 [59] 177 [80] 33 [15] 59 [27] 86 [39] 113 [51] 168 [76] 241 [110] 40 [18] 72 [33] 104 [47] 138 [62] 204 [93] 284 [129] 52 [24] 94 [43] 137 [62] 181 [82] 270 [122] 365 [165] 58 [26] 106 [48] 154 [70] 203 [92] 303 [138] 428 [194] 67 [30] 123 [56] 179 [81] 237 [108] 354 [160] 309 [140] 8 FPI 12 [5] 20 [9] 27 [12] 35 [16] 51 [23] 72 [33] 15 [7] 25 [11] 34 [15] 44 [20] 65 [20] 91 [41] 18 [8] 30 [13] 41 [19] 54 [24] 79 [36] 105 [47] 24 [11] 42 [19] 59 [27] 77 [35] 115 [52] 155 [70] 30 [14] 53 [24] 76 [34] 100 [45] 148 [67] 207 [94] 36 [16] 64 [29] 91 [41] 120 [55] 179 [81] 244 [111] 46 [21] 83 [38] 119 [54] 158 [72] 235 [107] 316 [143] 51 [23] 92 [42] 134 [61] 177 [80] 264 [120] 365 [166] 59 [27] 108 [49] 155 [71] 206 [93] 307 [139] 315 [143] 40% GLYCOL 10 FPI 12 FPI 12 [5] 13 [6] 20 [9] 21 [10] 28 [13] 29 [13] 36 [16] 38 [17] 53 [24] 55 [25] 76 [34] 80 [36] 16 [7] 16 [7] 26 [12] 27 [12] 36 [16] 37 [17] 46 [21] 48 [22] 68 [31] 71 [32] 96 [43] 101 [46] 19 [9] 19 [9] 31 [14] 32 [15] 43 [19] 45 [20] 56 [25] 59 [27] 83 [38] 87 [39] 110 [50] 115 [52] 25 [11] 26 [12] 43 [20] 45 [20] 62 [28] 65 [29] 81 [37] 85 [39] 120 [55] 126 [57] 163 [74] 171 [78] 31 [14] 32 [15] 55 [25] 58 [26] 79 [36] 83 [38] 105 [47] 110 [50] 155 [70] 163 [74] 219 [99] 232 [105] 38 [17] 39 [18] 67 [30] 70 [32] 96 [44] 101 [46] 127 [58] 133 [60] 188 [85] 198 [90] 259 [117] 273 [124] 48 [22] 50 [23] 87 [39] 91 [41] 126 [57] 132 [60] 166 [75] 175 [79] 248 [112] 261 [118] 334 [151] 352 [160] 54 [24] 56 [25] 97 [44] 102 [46] 141 [64] 149 [67] 187 [85] 197 [89] 279 [126] 293 [133] 388 [176] 411 [186] 62 [28] 65 [29] 113 [51] 119 [54] 164 [74] 173 [78] 217 [99] 229 [104] 324 [147] 341 [155] 315 [143] 315 [143] 14 FPI 13 [6] 22 [10] 30 [14] 39 [18] 58 [26] 84 [38] 17 [8] 28 [13] 39 [17] 50 [23] 74 [34] 106 [48] 20 [9] 33 [15] 47 [21] 61 [28] 90 [41] 120 [54] 27 [12] 47 [21] 67 [30] 89 [40] 132 [60] 179 [81] 34 [15] 60 [27] 87 [39] 115 [52] 170 [77] 245 [111] 41 [18] 73 [33] 106 [48] 139 [63] 207 [94] 288 [131] 52 [24] 95 [43] 139 [63] 184 [83] 274 [124] 370 [168] 58 [26] 107 [49] 156 [71] 206 [94] 308 [140] 434 [197] 68 [31] 125 [57] 181 [82] 240 [109] 359 [163] 315 [143] NOTE: Unit weight data is shipping weight in pounds [kilograms]. 12 ENVIRO-TEC WEIGHT AND ELECTRICAL DATA • MQL Motor/Drive Weight Data MOTOR WEIGHTS MOTOR HORSEPOWER MOTOR TYPE 1/3 1/2 3/4 1 1 1/2 2 3 5 7 1/2 10 15 ODP 25 [11] 28 [13] 30 [762] 35 [16] 45 [20] 35 [16] 75 [34] 100 [45] 125 [57] 125 [57] 220 [100] TEFC 28 [13] 35 [16] 33 [338] 45 [20] 65 [29] 70 [32] 85 [39] 105 [48] 145 [66] 160 [73] 295 [134] E+ N/A N/A N/A 40 [18] 55 [25] 55 [25] 90 [41] 100 [45] 145 [66] 130 [59] 300 [136] 2 SPEED 45 [20] 35 [16] 33 [338] 45 [20] 40 [18] 70 [32] 75 [34] N/A N/A N/A N/A NOTES: 1. Includes motor, pulleys, belts, and motor base. 2. Motor/drive weight data is shipping weight in pounds [kilograms]. Motor Electrical Data HORSEPOWER 1/3 1/2 3/4 1 1 1/2 2 3 5 7 1/2 10 15 115/1 6.3 7.8 10.6 15.0 - 208/1 3.5 4.3 5.4 8.3 - MAXIMUM MOTOR AMPERAGE VOLTAGE 230/1 277/1 208/3 230/3 3.2 2.6 1.7 1.5 3.9 3.6 2.2 2.1 5.3 5.0 3.2 3.0 7.5 5.5 4.0 3.6 5.3 5.0 7.0 6.4 9.1 9.0 14.2 12.8 22.2 21.6 28.6 28.4 44.9 40.6 460/3 0.8 1.1 1.5 1.8 2.5 3.2 4.5 6.4 10.8 14.2 20.3 575/3 0.9 1.2 1.4 1.9 2.5 3.2 5.2 8.2 11.4 16.2 NOTES: 1. Actual motor nameplate AMPs may vary, but will not exceed values shown. 2. Consult factory for applications requiring special motors. General Fan Notes Forward Curved Fans (Belt Drive) 1. 2. 3. 4. 5. Consult factory for applications at operating conditions not in the following table and curves. Fan motor voltage, fan rotation, and fan RPM may require field setting/adjustment. Drive losses not included in fan performance table and curves. In direction of airflow, after fan discharge – only LPM (Large Plenum) and EHB (Electric Heat Blow Thru) are available. Section will have internal isolation. Plug Fans (Direct Drive) 1. 2. 3. 4. Consult factory for applications at operating conditions not in the following table and curves. VFD's are recommended for operation and field balancing of units whether factory supplied and factory mounted, field supplied and factory mounted, or field supplied and field mounted. In direction of airflow, there must be space prior to the plug fan inlet. For sizes 02 through 06, the minimum requirement is either an SAM (Small Access) or an MCM (Medium Coil). For sizes 08 through 17, the minimum requirement is an MAM (Medium Access). Section will have internal isolation. ENVIRO-TEC 13 MQL • FAN PERFORMANCE DATA Forward Curved Fan Performance Data TSP (in-wg) 3.5 3.0 2.5 2.0 1.5 1.0 0.5 TSP (in-wg) 3.5 3.0 2.5 2.0 1.5 1.0 0.5 TSP (in-wg) 3.5 3.0 2.5 2.0 1.5 1.0 0.5 650 – – – – – – – – – – 1126 0.18 829 0.10 750 – – – – – – – – – – 1136 0.22 863 0.14 02 850 – – – – – – – – 1382 0.37 1154 0.27 904 0.18 950 – – – – – – 1594 0.55 1395 0.43 1181 0.32 * * 1050 – – – – 1782 0.76 1605 0.63 1415 0.50 1215 0.39 * * 950 – – – – – – – – – – 1107 0.29 814 0.17 1100 – – – – – – – – 1353 0.50 1117 0.36 846 0.22 03 1250 – – – – – – 1562 0.75 1360 0.59 1136 0.43 * * 1400 – – – – 1747 1.06 1567 0.87 1375 0.70 1161 0.52 * * 1550 – – 1913 1.41 1753 1.21 1580 1.01 1395 0.82 1195 0.63 * * 1200 – – – – – – – – – – 962 0.35 718 0.22 1400 – – – – – – – – 1175 0.61 976 0.44 * * 04 1600 – – – – – – 1357 0.92 1186 0.74 1000 0.56 * * 1800 – – – – 1517 1.30 1366 1.09 1204 0.89 1035 0.71 * * 2000 1793 1.99 1663 1.75 1526 1.51 1383 1.29 1231 1.08 * * * * UNIT SIZE Actual CFM 1900 RPM – BHP – RPM – BHP – RPM – BHP – RPM – BHP – RPM – BHP – RPM 798 BHP 0.52 RPM 590 BHP 0.32 2200 – – – – – – – – 973 0.88 809 0.65 * * 06 2500 – – – – 1251 1.58 1123 1.32 983 1.07 823 0.81 * * 2800 – – 1371 2.14 1256 1.85 1132 1.57 995 1.29 842 1.00 * * 3100 1482 2.80 1376 2.48 1264 2.16 1143 1.85 1010 1.53 * * * * 2400 – – – – – – – – – – 801 0.66 598 0.42 2800 – – – – – – – – 978 1.14 816 0.85 * * 08 3200 – – – – – – 1129 1.73 990 1.39 835 1.07 * * 3600 – – 1379 2.83 1263 2.44 1139 2.06 1007 1.69 858 1.33 * * 4000 1490 3.70 1384 3.27 1273 2.85 1155 2.44 1028 2.04 * * * * 3100 – – – – – – 933 1.51 812 1.18 673 0.87 * * 3600 – – 1141 2.60 1044 2.22 938 1.84 820 1.47 689 1.12 * * 10 4100 1234 3.50 1145 3.07 1049 2.64 945 2.22 833 1.82 711 1.43 * * 4600 1239 4.07 1151 3.59 1057 3.12 958 2.67 852 2.23 * * * * 5100 1245 4.70 1160 4.18 1070 3.68 975 3.19 875 2.71 * * * * UNIT SIZE Actual CFM 3900 RPM – BHP – RPM – BHP – RPM – BHP – RPM – BHP – RPM 697 BHP 1.42 RPM 574 BHP 1.02 RPM 428 BHP 0.65 4600 – – – – – – 805 2.25 701 1.78 585 1.34 * * 12 5300 6000 – 1065 – 5.13 – 987 – 4.50 901 906 3.28 3.90 809 819 2.74 3.32 711 724 2.22 2.7500 600 619 1.72 2.18 * * * * 6700 1068 5.94 994 5.28 915 4.63 832 3.99 741 3.35 * * * * 4600 – – – – – – – – 705 1.86 581 1.31 431 0.80 5400 – – – – – – 814 2.92 710 2.28 591 1.67 448 1.08 14 6200 – – – – 911 4.21 819 3.48 718 2.78 604 2.09 * * 7000 1077 6.59 1000 5.75 917 4.93 827 4.13 729 3.36 620 2.60 * * 7800 1081 7.55 1005 6.64 925 5.75 838 4.88 743 4.03 638 3.19 * * 5200 – – – – – – 814 2.79 708 2.17 588 1.57 444 1.00 6200 – – – – 911 4.21 819 3.48 718 2.78 604 2.09 * * 17 7200 1078 6.82 1001 5.96 919 5.13 830 4.31 733 3.52 624 2.74 * * 8200 1084 8.06 1009 7.12 930 6.20 844 5.29 751 4.40 * * * * 9200 1094 9.49 1021 8.46 944 7.44 862 6.44 773 5.45 * * * * UNIT SIZE Actual CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP * Contact factory. 14 ENVIRO-TEC FAN PERFORMANCE DATA • MQL Plug Fan Performance Data TSP (in-wg) 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0 0.5 TSP (in-wg) 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0 0.5 TSP (in-wg) 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0 0.5 450 2870 0.92 2704 0.79 2527 0.67 2336 0.55 2139 0.44 1924 0.33 1683 0.23 1415 0.14 1118 0.07 650 2881 1.08 2725 0.93 2559 0.79 2387 0.65 2207 0.52 2007 0.40 1810 0.29 1597 0.19 1366 0.11 02 850 2950 1.24 2805 1.07 2651 0.91 2499 0.77 2347 0.63 2179 0.50 2020 0.39 1833 0.27 1650 0.18 1050 3068 1.42 2946 1.25 2816 1.08 2677 0.92 2552 0.79 2413 0.65 2257 0.50 2117 0.41 1940 0.28 1250 3246 1.65 3135 1.47 3028 1.31 2913 1.15 2788 0.98 2660 0.83 2542 0.71 2401 0.55 2239 0.40 650 2869 1.32 2703 1.13 2526 0.96 2336 0.79 2141 0.62 1926 0.47 1687 0.32 1419 0.20 1128 0.10 900 2877 1.52 2721 1.31 2555 1.10 2380 0.91 2199 0.73 2000 0.56 1797 0.40 1580 0.27 1345 0.15 03 1150 2931 1.71 2786 1.48 2632 1.26 2466 1.05 2313 0.86 2145 0.68 1975 0.52 1788 0.36 1595 0.24 1400 3017 1.92 2891 1.68 2761 1.46 2622 1.24 2479 1.03 2340 0.85 2183 0.66 2029 0.52 1848 0.34 1650 3170 2.20 3048 1.94 2927 1.70 2812 1.49 2687 1.27 2549 1.04 2420 0.88 2280 0.69 2112 0.50 800 2868 1.58 2701 1.36 2524 1.15 2340 0.94 2146 0.75 1931 0.56 1698 0.39 1433 0.24 1153 0.12 1150 2890 1.85 2734 1.59 2572 1.35 2406 1.12 2226 0.90 2037 0.69 1846 0.51 1644 0.35 1422 0.21 04 1500 2974 2.13 2829 1.85 2683 1.59 2543 1.34 2391 1.10 2236 0.89 2079 0.69 1904 0.51 1721 0.33 1850 3122 2.48 3000 2.19 2870 1.89 2748 1.65 2622 1.40 2484 1.15 2343 0.94 2202 0.75 2030 0.52 2200 3318 2.91 3218 2.63 3111 2.34 2996 2.04 2871 1.74 2759 1.54 2641 1.31 2500 0.99 2344 0.75 UNIT SIZE Actual CFM 1200 RPM – BHP – RPM – BHP – RPM – BHP – RPM – BHP – RPM – BHP – RPM – BHP – RPM 1202 BHP 0.61 RPM 967 BHP 0.36 RPM 706 BHP 0.16 1700 – – – – – – 1700 1.73 1541 1.37 1368 1.03 1192 0.71 999 0.44 784 0.22 06 2200 2074 3.25 1946 2.79 1810 2.35 1679 1.93 1539 1.54 1394 1.18 1238 0.85 1071 0.56 895 0.32 2700 2056 3.55 1944 3.06 1823 2.59 1707 2.17 1581 1.76 1451 1.38 1313 1.03 1172 0.73 1021 0.45 3200 2081 3.89 1979 3.40 1871 2.93 1763 2.47 1645 2.03 1531 1.63 1411 1.27 1288 0.94 1159 0.67 1600 1605 2.65 1520 2.29 1429 1.95 1332 1.61 1226 1.29 1166 1.07 998 0.74 817 0.44 617 0.20 2300 – – 1646 3.06 1532 2.57 1410 2.11 1289 1.67 1159 1.26 1025 0.91 876 0.58 720 0.32 08 3000 1728 3.99 1633 3.44 1532 2.90 1432 2.42 1326 1.97 1214 1.54 1096 1.14 976 0.80 848 0.50 3700 1755 4.47 1670 3.91 1581 3.37 1490 2.85 1391 2.34 1299 1.89 1200 1.48 1098 1.11 992 0.80 4400 1812 5.10 1733 4.49 1649 3.89 1572 3.37 1488 2.83 1407 2.39 1320 1.93 1229 1.49 1140 1.14 1900 – – – – – – – – – – – – 1002 0.91 817 0.54 609 0.24 2800 – – 1650 3.79 1535 3.18 1413 2.61 1288 2.07 1158 1.56 1021 1.11 870 0.71 710 0.38 10 3700 1727 4.95 1632 4.27 1531 3.61 1429 3.00 1323 2.44 1211 1.90 1091 1.41 970 0.98 841 0.61 4600 1754 5.57 1669 4.87 1579 4.19 1488 3.54 1389 2.91 1296 2.35 1197 1.84 1094 1.37 987 0.98 5500 1812 6.38 1733 5.61 1649 4.86 1572 4.21 1488 3.54 1407 2.99 1320 2.42 1229 1.87 1140 1.43 UNIT SIZE Actual CFM 2600 RPM 1576 BHP 3.98 RPM 1490 BHP 3.46 RPM 1398 BHP 2.94 RPM 1300 BHP 2.45 RPM 1192 BHP 1.98 RPM 1071 BHP 1.52 RPM 933 BHP 1.09 RPM 736 BHP 0.65 RPM 558 BHP 0.30 3800 1604 5.04 1516 4.39 1422 3.76 1316 3.13 1182 2.47 1042 1.87 924 1.35 797 0.89 660 0.48 12 5000 6200 7400 1592 1584 1645 5.93 6.72 7.79 1484 1508 1581 5.09 5.88 6.92 1378 1429 1512 4.32 5.07 6.06 1291 1355 1442 3.62 4.35 5.24 1197 1274 1375 2.95 3.63 4.49 1102 1192 1300 2.34 2.95 3.70 1001 1107 1238 1.75 2.3000 3.20 898 1029 1167 1.23 1.83 2.50 798 857 1023 0.82 1.00 1.00 2900 1584 4.25 1498 3.69 1406 3.15 1307 2.63 1197 2.12 1076 1.63 918 1.14 746 0.70 579 0.34 4300 1613 5.47 1524 4.77 1411 4.02 1287 3.30 1167 2.64 1063 2.05 952 1.51 835 1.02 718 0.62 14 5700 1563 6.32 1488 5.53 1407 4.75 1320 4.00 1239 3.33 1150 2.67 1062 2.07 971 1.55 788 1.00 7100 1625 7.47 1560 6.64 1491 5.81 1417 4.98 1348 4.26 1273 3.51 1203 2.95 1132 2.33 982 1.00 8500 1722 8.95 1661 8.02 1604 7.16 1541 6.26 1477 5.42 1424 4.88 1364 4.12 1175 2.82 1175 1.00 3400 1413 5.11 1336 4.44 1254 3.78 1166 3.15 1068 2.54 960 1.96 831 1.39 661 0.83 507 0.40 4800 1436 6.34 1357 5.53 1273 4.73 1176 3.93 1056 3.11 934 2.36 828 1.70 716 1.12 595 0.62 17 6200 1426 7.38 1330 6.34 1231 5.36 1154 4.50 1069 3.67 984 2.90 893 2.18 801 1.53 711 1.01 7600 1413 8.28 1345 7.25 1273 6.24 1205 5.33 1133 4.44 1057 3.60 981 2.81 909 2.21 753 1.25 9000 1460 9.47 1402 8.42 1341 7.37 1275 6.32 1215 5.42 1148 4.46 1088 3.79 1024 2.99 891 1.25 UNIT SIZE Actual CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP ENVIRO-TEC 15 MQL • FAN PERFORMANCE CURVES MQL02 (Fan 09-04 Class I) 4.0 2200 RPM SE = CFM x SP 6362 x BHP STATIC PRESSURE - INCHES WATER GAUGE 3.5 2000 3.0 1800 2.5 2 HP 1600 2.0 1400 1.5 1200 1.5 HP 1.0 1000 800 0.5 1 HP 3/4 HP 1/2 HP 600 1/3 HP 0.0 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 CFM MQL03 (Fan 09-06 Class I) 4.0 STATIC PRESSURE - INCHES WATER GAUGE 3.5 SE = CFM x SP 6362 x BHP 2 HP 2000 RPM 3.0 1800 2.5 1.5 HP 1600 2.0 1400 1.5 1200 1 HP 1.0 1000 3/4 HP 800 1/2 HP 0.5 1/3 HP 600 0.0 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 CFM 16 ENVIRO-TEC FAN PERFORMANCE CURVES • MQL MQL04 (Fan 10-07 Class I) 4.0 STATIC PRESSURE - INCHES WATER GAUGE 3.5 SE = CFM x SP 6362 x BHP 1800 RPM 3.0 2 HP 1600 2.5 1400 2.0 1.5 HP 1200 1.5 1000 1.0 1 HP 800 3/4 HP 0.5 1/2 HP 600 0.0 1100 1/3 HP 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 CFM MQL06 (Fan 12-09 Class I) 4.0 STATIC PRESSURE - INCHES WATER GAUGE 3.5 SE = CFM x SP 6362 x BHP 1400 RPM 3.0 3 HP 2.5 1200 2.0 1000 1.5 2 HP 800 1.0 1.5 HP 0.5 600 1 HP 3/4 HP 1/2 HP 400 0.0 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600 3800 CFM ENVIRO-TEC 17 MQL • FAN PERFORMANCE CURVES MQL08 (Fan 12-12 Class I) 4.0 SE = CFM x SP 6362 x BHP STATIC PRESSURE - INCHES WATER GAUGE 3.5 5 HP 1400 RPM 3.0 2.5 1200 2.0 1000 1.5 3 HP 1.0 800 2 HP 600 0.5 1.5 HP 1 HP 3/4 HP 1/2 HP 0.0 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600 3800 4000 4200 4400 4600 4800 5000 5200 CFM MQL10 (Fan 15-11 Class I and II) 4.0 CLASS I SE = CFM x SP 6362 x BHP STATIC PRESSURE - INCHES WATER GAUGE 3.5 CLASS II 1200 RPM 5 HP 3.0 2.5 1000 2.0 1.5 800 3 HP 1.0 600 2 HP 1.5 HP 0.5 1 HP 400 3/4 HP 0.0 2400 2600 2800 3000 3200 3400 3600 3800 4000 4200 4400 4600 4800 5000 5200 5400 5600 5800 CFM 18 ENVIRO-TEC FAN PERFORMANCE CURVES • MQL MQL12 (Fan 18-13 Class I and II) 4.0 CLASS I SE = CFM x SP 6362 x BHP 3.5 STATIC PRESSURE - INCHES WATER GAUGE CLASS II 7.5 HP 1000 RPM 3.0 2.5 2.0 800 5 HP 1.5 600 1.0 3 HP 0.5 2 HP 400 1.5 HP 1 HP 0.0 3000 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 CFM MQL14 (Fan 18-18 Class I and II) 4.0 CLASS I SE = CFM x SP 6362 x BHP 3.5 STATIC PRESSURE - INCHES WATER GAUGE CLASS II 1000 RPM 3.0 2.5 7.5 HP 2.0 800 1.5 600 1.0 5 HP 0.5 400 3 HP 1 HP 2 HP 1.5 HP 0.0 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 9500 10000 CFM ENVIRO-TEC 19 MQL • FAN PERFORMANCE CURVES MQL17 (Fan 18-18 Class I and II) 4.0 CLASS I SE = CFM x SP 6362 x BHP 3.5 STATIC PRESSURE - INCHES WATER GAUGE CLASS II 15 HP 1000 RPM 3.0 2.5 2.0 800 10 HP 1.5 600 1.0 7.5 HP 5 HP 400 0.5 3 HP 2 HP 1.5 HP 0.0 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 9500 10000 10500 11000 11500 12000 12500 13000 CFM MQL02 Plug Fan 5.5 3000 RPM SE = CFM x SP 6362 x BHP 5.0 STATIC PRESSURE - INCHES WATER GAUGE 2800 1.5 HP 4.5 2600 4.0 3.5 2400 1 HP 3.0 2200 2.5 2000 3/4 HP 1800 2.0 1600 1.5 1/2 HP 1400 1.0 1200 1000 1/3 HP 0.5 800 600 0.0 0 200 400 600 800 1000 1200 1400 CFM 20 ENVIRO-TEC FAN PERFORMANCE CURVES • MQL MQL03 Plug Fan 5.5 3000 RPM SE = CFM x SP 6362 x BHP 5.0 2 HP 2800 STATIC PRESSURE - INCHES WATER GAUGE 4.5 2600 4.0 1.5 HP 3.5 2400 3.0 2200 1 HP 2.5 2000 1800 2.0 3/4 HP 1600 1.5 1400 1.0 1/2 HP 1200 1000 0.5 1/3 HP 800 600 0.0 0 200 400 600 800 1000 1200 1400 1600 1800 CFM MQL04 Plug Fan 5.5 3 HP 3000 RPM SE = CFM x SP 6362 x BHP 5.0 2800 STATIC PRESSURE - INCHES WATER GAUGE 4.5 2600 4.0 2 HP 3.5 2400 3.0 2200 1.5 HP 2.5 2000 2.0 1800 1600 1.5 1 HP 1400 1.0 3/4 HP 1200 1000 0.5 800 1/2 HP 600 1/3 HP 0.0 0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 CFM ENVIRO-TEC 21 MQL • FAN PERFORMANCE CURVES MQL06 Plug Fan 5.5 SE = CFM x SP 6362 x BHP 5.0 2200 RPM STATIC PRESSURE - INCHES WATER GAUGE 4.5 2000 4.0 3 HP 3.5 1800 3.0 1600 2 HP 2.5 1400 2.0 1.5 HP 1200 1.5 1 HP 1000 1.0 3/4 HP 800 0.5 600 1/2 HP 400 1/3 HP 0.0 0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 CFM MQL08 Plug Fan 5.5 SE = CFM x SP 6362 x BHP 5.0 1800 RPM 5 HP STATIC PRESSURE - INCHES WATER GAUGE 4.5 4.0 1600 3.5 3.0 1400 3 HP 2.5 1200 2.0 2 HP 1000 1.5 1.5 HP 1.0 800 600 1 HP 0.5 400 1/3 HP 1/2 HP 3/4 HP 0.0 0 500 1000 1500 2000 2500 3000 3500 4000 4500 CFM 22 ENVIRO-TEC FAN PERFORMANCE CURVES • MQL MQL10 Plug Fan 5.5 7.5 HP SE = CFM x SP 6362 x BHP 5.0 1800 RPM STATIC PRESSURE - INCHES WATER GAUGE 4.5 4.0 1600 5 HP 3.5 1400 3.0 2.5 1200 3 HP 2.0 1000 1.5 2 HP 800 1.0 1.5 HP 600 0.5 400 1/2 HP 1/3 HP 3/4 HP 1 HP 0.0 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 CFM MQL12 Plug Fan 5.5 5.0 1600 RPM STATIC PRESSURE - INCHES WATER GAUGE 4.5 SE = CFM x SP 6362 x BHP 7.5 HP 4.0 1400 3.5 3.0 1200 5 HP 2.5 1000 2.0 1.5 3 HP 800 1.0 600 2 HP 0.5 400 1/3 HP 1/2 HP 3/4 HP 1 HP 1.5 HP 0.0 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 CFM ENVIRO-TEC 23 MQL • FAN PERFORMANCE CURVES MQL14 Plug Fan 5.5 1800 RPM 1600 RPM 5.0 SE = CFM x SP 6362 x BHP 4.5 STATIC PRESSURE - INCHES WATER GAUGE 10 HP 4.0 7.5 HP 1400 3.5 3.0 1200 2.5 5 HP 1000 2.0 1.5 800 1.0 3 HP 600 0.5 400 1/3 HP 1/2 HP 3/4 HP 1 HP 2 HP 1.5 HP 0.0 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 CFM MQL17 Plug Fan 5.5 SE = CFM x SP 6362 x BHP 5.0 1400 RPM 10 HP STATIC PRESSURE - INCHES WATER GAUGE 4.5 4.0 7.5 HP 1200 3.5 3.0 2.5 1000 5 HP 2.0 800 1.5 3 HP 1.0 600 0.5 400 1/3 HP 1/2 HP 3/4 HP 1.5 HP 1 HP 2 HP 0.0 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 9500 CFM 24 ENVIRO-TEC GUIDE SPECIFICATIONS • MQL Guide Specifications Central Station Air-Handling Unit HVAC Guide Specifications - Section 15XXX Size Range: 600 – 10,000 CFM ENVIRO-TEC® Model Number: MQL Part 1 — General 1.01 SYSTEM DESCRIPTION A. Indoor mounted central station air-handling unit designed to provide air to a conditioned space as required to meet specified performance requirements for ventilation, heating, cooling, filtration and air distribution. Unit shall be assembled for draw thru application and shall be arranged to discharge conditioned air horizontally or vertically as shown on the contract drawings. B. Unit with a direct-expansion cooling coil shall have the capability to be used in a refrigerant circuit in conjunction with a field supplied and matched air-cooled condensing unit. 1.02 QUALITY ASSURANCE A. Coils shall be certified in accordance with ARI 410 “Standard for Forced-Circulation Air-Cooling and AirHeating Coils”, display certification symbol on units of certified models. B. Direct expansion coils shall be designed and tested in accordance with ANSI/ASHRAE 15 “Safety Code for Refrigeration Systems”. C. Insulation and insulation adhesive shall comply with NFPA 90A and 90B requirements for flame spread and smoke generation. D. Unit shall be constructed in accordance with UL 1995 standards, comply with NEMA standards and shall carry the cETL label, display certification symbol on units of certified models. Installation of ancillary electrical components shall comply with NEC. 1.03 DELIVERY, STORAGE AND HANDLING Unit shall be stored and handled in accordance with the unit manufacturer’s instructions. Part 2 — Products 2.01 EQUIPMENT A. General: Factory assembled central station air-handler that is modular in design and construction. Unit may consist of a fan and coil section with factory-installed chilled water or direct expansion coil, preheat or reheat coil, heating coil section, filter section, combination filter/mixing box (flat or V-bank arrangement), economizer, or access section(s) as indicated on the equipment schedules. B. Unit Cabinet: 1.0 Unit panels shall be constructed of G60 galvanized steel and shall be capable of withstanding 125-hour salt spray test per ASTM Standard 117. All casing panels shall be removable for easy access to the unit. All panels shall be gasketed to ensure a tight seal. 2.0 Double wall unit panels (includes corner posts, mullions and access doors) shall be 1-in. nominal thickness using 1.5-lbs/ft3 fiberglass insulation between galvanized steel panels. 3.0 Single wall unit panels shall be 1-in. nominal thickness using matt-faced fiberglass insulation with a nominal density of not less than 1.5-lbs/ft3. 4.0 Insulation shall be secured to casing with water based adhesive corresponding to 25/50-flame spread/smoke developed. Testing criteria and weld pins where necessary. 5.0 Condensate drain pans shall be sloped to prevent standing water and shall be constructed of 18 gauge G90 galvanized steel or stainless steel; they shall have a galvanized steel or stainless steel male pipe threaded drain connection. C. Fan Section: 1.0 Fan sections shall be constructed of G60 steel and shall have a formed channel base for integral mounting of fan, motor, and casing panels. Fan housing, wheel, shaft, and bearings shall be rigidly secured to the base unit. ENVIRO-TEC 25 MQL • GUIDE SPECIFICATIONS 2.0 Fan decks shall be internally spring isolated (one-inch deflection) with the fan outlet connection to be made using canvas duct. 3.0 Each unit shall have one fan wheel and housing only. 4.0 Fan wheels shall be designed for continuous operation at the maximum rated fan speed and motor horsepower. Fan wheels and shafts shall be selected to operate at least 25% below the first critical speed, and shall be statically and dynamically balanced as an assembly. 5.0 Fan shafts shall be solid steel, turned, ground and polished. 6.0 Fan bearings shall be self-aligning, non-regreasable (permanent) ball bearing type selected for an average life (L50) of 100,000 hours at design operation conditions, per ANSI Code B3.15. 7.0 Fan motor shall be mounted within the fan section casing. Motor shall be NEMA Design B with sizes and electrical characteristics as shown on the equipment schedule. 8.0 Fan drive shall be designed for a minimum of 1.15 service factor and shall be factory mounted and aligned. Belt drive package shall be variable-pitch type (constant volume) or fixed-pitch type (variable volume). D. Coil Sections: 1.0 All coils shall have aluminum plate fins mechanically bonded to 1/2-in. OD seamless copper tubes by mechanical expansion. Coils shall be factory leak tested at 450-psig air pressure under water in an illuminated test tank. Copper tubes shall be either 0.016” or 0.025” copper tube wall thickness. Coils shall have G90 galvanized steel or stainless steel casings with copper headers and sweat connections. 2.0 Chilled water coils shall have a working pressure of 300-psig at 200° F. No turbulence-promoting devices will be permitted inside the tubes. Headers shall have vent connections. 3.0 Direct-expansion coils shall be provided with pressure-type brass distributors with solder-type connections. Coils shall be designed and tested in accordance with ANSI/ASHRAE 15. 4.0 Hot water coils shall have a working pressure of 300-psig at 200° F. No turbulence-promoting devices will be permitted inside the tubes. Headers shall have vent connections. 5.0 Steam distributing coils (standard single tube type) shall have a maximum working pressure of 15-psig at ambient temperatures above 35° F. Tube wall thickness shall be 0.025” as standard. 6.0 Electric heat coils for use in air-handling units shall be open coil type, nichrome wire resistance elements, insulated by floating ceramic bushings. Thermal cutouts for primary and secondary over-temperature protection shall be provided to meet UL and NEC requirements. Maximum element watt density shall be 55-watts/sq inch. The manufacturer shall furnish an integral control box. It shall contain primary and secondary control thermal cutouts, relays, airflow switch, and fused control transformer. E. Filter Sections: 1.0 Each filter section shall be designed and constructed to house the specific type of filter specified on the equipment schedule. 2.0 Flat filter sections shall accept 2-in. 30% (MERV-6) pleated filters of standard sizes. Sections shall include side access slide rails. Flat filter section shall be arranged with minimum depth in direction of airflow. 3.0 Angle filter section shall accept 2-in. 30% (MERV-6) pleated filters of standard sizes arranged in horizontal V formation. Sections shall include side access slide rails. Angle filter section shall be arranged with minimum depth in direction of airflow. F. Damper Sections: 1.0 Mixing boxes, filter mixing boxes and economizers shall have parallel blade, interconnecting dampers. Damper blades shall have parallel bends for stiffness and shall be mechanically fastened to steel rods rotating in brass bushings and mounted in rigid galvanized steel frames. Dampers shall be sectionalized to limit blade width, minimize blade warpage, and ensure tight closure. 2.0 All dampers for mixing boxes and filter mixing boxes shall be rated with a leakage rate not to exceed 5% of air quantity calculated at 2000 fpm velocity though damper and 4.0-in.wg. pressure difference. Damper blades shall be gasketed and stainless steel perimeter-sealing strips shall be provided. Damper linkage shall be provided and installed with all mixing boxes. G. Access Sections: 1.0 Access sections shall be installed where indicated on the drawings and shall be as specified on the equipment schedule. 2.0 Access sections shall have removable access panels. 26 ENVIRO-TEC GUIDE SPECIFICATIONS • MQL H. Special Features: The following unit options shall be available. 1.0 Fan Section: a. Variable frequency drives. b. Motor starters – contactor with overload for three phase and contactor for single phase. c. High-efficiency motors (inverter-duty). d. Totally enclosed fan cooled (TEFC) motors (inverter-duty). e. Two-speed motors. f. Direct drive plug fans with internal isolation. g. Class II forward curved fans with regreasable pillow block bearings. h. Exhaust or return fans for use with economizer sections. 2.0 Coil Section: a. Chilled water coil with copper plate fins and/or stainless steel casing. b. Direct-expansion coil with copper plate fins and/or stainless steel casing. c. Hot water coil with copper plate fins and/or stainless steel casing. d. Steam distributing coil with copper plate fins and/or stainless steel casing. 3.0 Filtration: a. 4” pleated filter type (standard size), 60-65% efficiency (MERV-11) b. 4” pleated filter type (standard size), 80-85% efficiency (MERV-13) c. 4” pleated filter type (standard size), 90-95% efficiency (MERV-14) 4.0 Access Doors: Hinged (lift-off type) doors with quick-action latches (handles) on both sides of the section for access to both the fan and filter from either side of the unit. 5.0 Base Rail: Unit mounted base rail shall be a minimum of 4” in height and constructed of galvanized steel, structurally capable of supporting unit on floor or by ceiling suspension. I. End Devices: The following guide specifications should be used as a basis for design when using optional factory/fieldmounted direct digital controls. These specifications should be reviewed to match the specific system control requirements and available control packages. 1.0 The electrical components shall be recognized by UL. The unit shall be in compliance with the UL 1995 standards. Fan motors are wired and terminated in the control enclosure. 2.0 All application software performing the required control functions shall be field-supplied with the DDC controller factory or field mounted and wired (tested and configured). 3.0 Available End Devices and Controls: a. Variable Frequency Drives • Factory supplied and mounted • Field supplied and factory mounted b. Motor Starters • Factory supplied and mounted • Field supplied and factory mounted c. End Devices (factory supplied and mounted) • Disconnect switch (fused or non-fused) • Damper actuator (modulating from 100% OA to 100% RA) • Fuses, relays, transformers, etc. • Electric heat interlock relay • Hand off auto switch ENVIRO-TEC 27 MQL • METRIC CONVERSION Metric Conversion Chart SI UNIT CONVERSION FACTOR = ENGLISH UNIT CONVERSION FACTOR = SI UNIT 100 645.2 0.09290 mm2 mm2 m2 25.4 304.8 0.3048 0.9144 mm mm m m mm3 mm3 L 28.35 0.4536 0.9072 g kg tonne, Mg m3 L L mL, cm3 6.102x10 0.03531 1.308 0.2642 2.113 0.03381 1.163 0.2931 0.7355 W W kW m3/h m3/h m3/h 0.5886 4.403 0.7457 kW L/h SI UNIT Area cm2 cm2 m2 0.1550 10.76 mm mm m m 0.03937 0.003281 3.281 1.094 g kg tonne, Mg 0.03527 2.205 1.102 kcal/h kcal/h HP metric 3.968 HP metric 0.9863 Mcal/h Mcal/h mm w.g. 4°C mm w.g. 4°C mm Hg 0°C mm Hg 0°C kgf /cm2 2 in ft2 Length in. ft. ft. yd. Mass oz. lb. U.S. ton (2000 lb.) Power Btu/h HP (550 ft. lb. ) S 0.3307 Ton refr. Pressure 0.03937 in H2O 39.2°F 0.03937 in Hg 32°F 1.163 3.517 kW kW 9.806 249.1 0.1333 3.386 98.07 Pa Pa kPa kPa kPa °C m/s m/s L/h SI UNIT 14.22 psi 6.895 kPa °C mH2O 3.281 ft H2O 2.989 kPa °C 28 MEGAKILODECI CENTI MILLI 106 103 10-1 10-2 10-3 LEGEND m cal kg kgf kp L °C K W Pa J N h m s g 3.281 196.9 ft/s ft/min Volume -5 3 in. ft3 yd3 U.S. gal U.S. pint U.S. oz Volume / Time ft3/min U.S. gal/min -3 4.403x10 (m3/h)/ (1000 kcal/h) kgf /cm2 PREFIXES M k d c m CONVERSION = ENGLISH CONVERSION FACTOR UNIT FACTOR Temperature Interval 1.8 °F 0.5556 Velocity 1.780 METER CALORIE KILOGRAM (mass) KILOGRAM — FORCE KILOGRAM — FORCE LITER DEGREES CELSIUS KELVIN WATT PASCAL JOULE NEWTON HOUR MINUTE SECOND GRAM °C 0.3048 0.00508 m/s m/s 1.0x10-6 0.01639 28.32 0.7646 3.785 0.4732 29.57 L L L m3 L L mL 0.2778 0.4719 0.06309 L/s L/s L/s 2.778x10-4 L/s U.S. gal/min 0.06309 L/s cfm/ton 0.1342 L/s - kW CONVERSION FACTOR = SI UNIT °C + 273.15 °K (°F - 32) ÷ 1.8 °C CONVERSION = ENGLISH FACTOR UNIT Temperature (°C x 1.8) + 32 = SI UNIT °F UNITS HP metric = METRIC HORSEPOWER mm w.g. MILLIMETERS WATER GAUGE mmCE MILLIMETERS WATER GAUGE mmHg MILLIMETERS MERCURY tonne = 1000 kg kcal = KILOCALORIES bar = 100 kPa ENVIRO-TEC NOTES ENVIRO-TEC 29 MQL • STANDARD & OPTIONAL FEATURES STANDARD FEATURES Construction • Modular design facilitates retrofit • Galvanized steel cabinet construction • 1" thick fiberglass insulation, glued and pinned in place • Gasketed, removable access panels sized for easy handling • Left and right hand arrangement • Access panels on all sections Fan Assembly • Single forward-curved fan sections • Statically and dynamically balanced • Solid steel shafting • Ball bearings with a minimum design average life (L50) of 100,000 hours • Fan decks with internal vibration isolation Fan Motor and Drive • Single speed ODP motors • 1750 RPM single speed, 60 Hertz • Single phase motors with inherent thermal protection • Three phase motors • Standard cross section "V-belt" drive with 1.2 service factor • Adjustable pitch motor pulley and fixed pitch blower pulley Coils • ARI 410 Certified and Labeled • 1/2" O.D. seamless copper tubes • G90 steel coil casings • Collared aluminum fins • Manual air vent plug on all water coils • 300 PSIG Working Pressure at 200°F • Copper ODM sweat connections • 0.016" tube wall on water and evaporator coils • 0.025" tube wall on steam coils Filters and Filter Rack • Hinged side access flat filter rack • 2" pleated filters (30%) Electrical • Fan motor wired and terminated to junction box • All units cETL listed in compliance with UL/ANSI 1995 Electric Heat Section • Draw Thru or Blow Thru configurations • Factory mounted electric heater with single point power connection, ETL listed as an assembly OPTIONAL FEATURES Construction • Double wall (solid or perforated) cabinets • Stainless steel IAQ drain pan with stainless steel male pipe threaded connection • Fan discharge arrangements • Scrim reinforced foil faced insulation • Hinged access panels with lift and turn fasteners • 4" Base rails with rigging slots factory assembled and installed Fan Motor and Drive • Direct drive plug fans with internal rubber-in-shear (RIS) isolation • TEFC motors • High efficiency motors • Two-speed motors with contactors • Variable frequency drives, factory installed (mounted and wired) • Motor starter (contactor with overload for three phase; contactor for single phase), factory installed (mounted and wired) • Return FC and plug fan sections Coils • 3, 4, 6 and 8 row chilled water or R22 DX coils • Up to 4 rows hot water or up to 2 rows standard steam • Heating coil in preheat or reheat position • Coil connections opposite handing • Stainless steel coil casings • 0.025" tube wall thickness • Auto air vents Printed on recycled paper Catalog: ET102.19-EG1 (410) Supersedes Catalog: ET102.19-EG1 (809) © 2010 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53201 Printed in USA www.johnsoncontrols.com Filters and Filter Rack • 4" high efficiency pleated filters (65, 85, and 95%) • Mixing box with filter sections (flat or v-bank filter arrangements) Inlet Damper Section • Factory assembled and installed • Heavy gauge galvanized steel formed blade dampers • Low leak dampers with extruded vinyl blade seals and flexible metal jamb seals • Medium and large inlet plenums with v-bank or flat filters • Parallel blade operation • Interconnecting damper linkage • Damper actuator (modulating from 100% OA to 100% RA) Additional Modules • Face and bypass with medium and small coils • Economizer sections • Discharge plenums • Access sections • High efficiency filter sections Electrical • Motor wiring in conduit • Single phase fan control package • Three phase fan control package • Door interlocking disconnect switch (non-fused or fused) • Fusing (main or per stage) • Hand off auto switch (HOA) • Frequency inverters • Electric heat interlock relay • Relays, transformers, etc.