IFP-2000 Farenhyt PHD Signaling Line Circuit - Hochiki Module 5B Objectives At the end of this section you will be able to: Describe how to calculate wiring distances for an SLC loop Explain the functions of each SLC device Explain the unique wiring considerations for each SLC device Demonstrate how to address SLC devices from the FACP Terminology SLC Sensor Any addressable smoke or heat detector SD505 - AHS SD505 - APS SLC Module Any Hochiki addressable input or output SD500 – AIM SD500 – Zone SD500 - ARM Wiring Requirements Maximum resistance 50 ohms Measure from start to last device Class A measures the whole loop Has to be the same gauge if you want to T-tap T-taps cannot exceed 40,000 feet for the whole SLC Wire gauge Max Distance 22 AWG 1,500 ft 18 AWG 3,900 ft 16 AWG 6,200 ft 14 AWG 10,000 ft Wiring Requirements Wire distance is calculated to the end of the run One way - NOT back Wire distance must be less than max for the gauge Distance to end of run Wiring Requirements TT-Taps Furthest from the FACP Use the distance of the device that is furthest from the FACP to determine the gauge DO NOT mix gauges for the whole loop Wiring Requirements TT-Taps Furthest smoke 3600 Feet away Wire gauge Max Distance 22 AWG 1,500 ft 18 AWG 3,900 ft 16 AWG 6,200 ft 14 AWG 10,000 ft Need 18 AWG for the entire SLC SD505 - AHS Addressable Heat Sensor An absolute temperature device Responds to an alarm immediately if the temperature goes above the trip point Programmed in the zone characteristics Used in areas with a lot of steam and fumes Example = a kitchen Programmable set temperature from 135 to 150 degrees F Resettable SD505 - AIS Addressable Ion Sensor Provide early warning in fast-flaming fires that show little visible smoke Hospitals Industrial environments Places where rapid fire development is expected SD505 - APS Addressable Photoelectric Sensor Particularly suited to detecting dense smoke in smoldering fires Fires involving materials such as: Soft furnishings Plastic Foam SLC LEDs Smoke detector heads - two LEDS Both red SLC modules – 1 LED Can be red or green Flash once every 15-20 seconds during communications with FACP First two devices in alarm latch their LEDs on However, all other devices will flash their LEDs 3 times when they go into alarm, then turn them off Heat & Smoke Detector Install 30-32 VDC across the SLC terminals SD505 – 6SB SLC Sounder Base Used in Hotels Apartments Assistant living Needs 24 VDC aux power Capable of single and multi-station formats Single station – single room alarm Multi-station – multiple room alarm Can be mapped like any output The sounder base shares the same address as the detector Makes installation and programming easy SD505 – 6SB Wiring SD505 – 6SB Wiring Aux power supervised by the device SD505 – 6RB SLC Relay Base The relay base shares the same address as the detector Rated for 8A @ 30V or 240V Example Door holders Elevator recall Fan shutdown SD505 – 6RB Wiring SD505 – 6RB Wiring SD505 - DUCTR Addressable Duct Housing Formally known as SD505-ADHR Has photo smoke and relay Works the same as DUCT The built-in relay module can be programmed to turn off fans, blowers, and other devices Connects to remote test switch with LED annunciator DUCTR Connections 24VDC Power SLC DUCTR Connections Alarm Contacts 10A @ 250VAC Trouble Contacts 2.5A @ 30VDC SD505 DTSDTS-K Accessory to SD505 – DUCTR Allows you to remotely test the duct detector Remote test switch Alarm LED Pilot LED Looks like a single gang annunciator DUCTR Connections 24VDC Power SD505 - DUCT Addressable Duct Housing Detects smoke moving through an HVAC duct to prevent re-circulation of smoke into the air handling system When smoke is detected, the unit communicates the condition to the FACP Use SD505-ARM to shut down air handler Don’t need AUX power No remote test switch! Duct Detector Install Address the head before attaching to the base Connect tubes at back of housing SD500 - AIM Addressable Input Module Supervises non-addressable devices Conventional pullstations Waterflow switches, Other dry contact alarm initiation devices Mounts in a 4 square electrical box Now supports Class A wiring! SD500 - MIM Mini Input Module Smaller version of the AIM Can be mounted in the single gang box to save space Example – Conventional pullstations Class B Only AIM & MIM Wiring AIM Class A Wiring Brand NEW to AIM! SD500 - ARM Addressable Relay Module Two relays on each module Cannot separate functions of each relay Electronic latching relay Even when power from SLC is removed SLC must be reset to unlatch ARMs only draws current when it communicates & switches SD500 - ARM Allows you to control a wide variety of normally open and normally closed applications, including: Elevator recall Magnetic locks Fan operation Auxiliary notification SD500 – ARM Wiring LED flashes only during communications with FACP Blinks Green when normal Blinks Red when active Rated 2.0A @ 30VDC .6A @ 120VAC LED blinks once every 15-20 seconds when communicating with the FACP SD500 - ANM Addressable Notification Module Supervised addressable notification device that provides you with additional notification circuits SD500 – ANM Wiring Used as input for conventional power supplies Supervises, triggers SD500 - LIM SLC Isolator Module Doesn’t take up an address Mounts in a 4 square box If short occurs across the SLC loop, it opens the SLC to prevent the SLC from shutting down Lights LED when short is detected SD505 – 6IB SLC Isolator Base Combines isolator module with a smoke detector Isolates both the input and the output of the SLC SD505 – 6IB Wiring Without SD500SD500-LIM Short anywhere across the SLC FACP communicates = SLC shorted All devices lose power Wiring with SD500SD500-LIM Short across SLC after LIM Rest of loop keeps operating Helps you find the short SD500--LIM Class A SD500 Class A style 6 designed to minimize loss of protection during a short SD500--LIM Class A SD500 Not protecting the FACP can lead to an SLC short SD500--LIM Class A SD500 Protect the FACP with a LIM on BOTH the SLC input and SLC output! SD500--LIM Class A Style 7 SD500 2 LIMs for each SLC device & 2 for the FACP Used in Government buildings Up to 256 Isolators SD505--6IB SD505 Works like style 7 without all the modules Smoke is truly isolated from the base SD505--6IB SD505 Smoke is truly isolated from the base SD500 – SDM 2 Wire Conventional Smoke Module Allows you to assign an address to a loop of conventional smoke detectors Can retrofit an existing building that utilize existing conventional devices Can put detectors and other devices on the same circuit SD500 – SDM Wiring Refer to install sheet part #151193 for compatible 2-wire smoke detectors SD500 – PS Addressable Pullstation Has MIM built-in Single action SD500 – PSDA A SD500 – PS can be upgraded to dual action by using a SD500 – LK upgrade kit SD500 – PS Wiring SD500 – LED LED driver Can drive up to 80 LEDs Up to 40 SD500-LED modules per SLC loop 100 per system Must supply aux power LED driver will supervise Sub-address for each output SD500 – LED Wiring To SLC Needs 24VDC constant power Supervised by SLC address SD500 – LED Wiring Eight 12-pin connectors used to connect LEDs All LED outputs use a common pin on each connector for LED power Current is limited through each output so no series resistor is required Dipswitch Addressing We only use 7 switches 1=1 2=2 3=4 4=8 5 = 16 6 = 32 7 = 64 8 = 128 (leave off) MUST set with no power! Add together to get address Addressing Heats and Smokes Use the hand-held programmer SD505-TCHB100 Or use the FACP as a programmer to program the address of each head 1 for Read address 2 for write address 3 for Seq Programming Addressing Heats and Smokes Using Write Programmer built into every FACP Connect detector base to terminals 45 & 46 Attach a smoke detector Enter Installer code 5820 Press 2 for Point Functions Press 3 for SLC Addressing Press arrow UP for YES Press “Silence” to silence trouble beep Press 2 for Write Enter new address and hit ENTER Left arrow to back out Addressing Heats and Smokes Addressing Heats and Smokes Using Write Connect detector base to terminals 45 & 46 Attach a smoke detector Enter Installer code 5820 Press 2 for Point Functions Press 3 for SLC Addressing Press arrow UP for YES Press “Silence” to silence trouble beep Press 2 for Write Enter new address and hit ENTER Left arrow to back out Addressing Heats and Smokes Using Sequential Connect detector base to terminals 45 & 46 Attach a smoke detector Enter Installer code 5820 Press 2 for Point Functions Press 3 for SLC Addressing Press arrow UP for YES Press “Silence” to silence trouble beep Press 3 for Sequential Enter first address and attach head Adds next address to each new head attached Left arrow to back out Objectives At the end of this section you will be able to: Explain the functions of each SLC device Explain the unique wiring considerations for each SLC device Describe how to calculate wiring distances for an SLC loop Demonstrate how to address SLC devices from the FACP Signaling Line Circuit - Hochiki Module 5B