SECTION 280500 - COMMON WORK RESULTS FOR

advertisement
SECTION 280500 - COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY
PART 1 - GENERAL
1.1
SUMMARY
A.
Section Includes:
1.
2.
3.
4.
1.2
Sleeves for raceways and cables.
Sleeve seals.
Grout.
Common electronic safety and security installation requirements.
SUBMITTALS
A.
Product Data: For sleeve seals.
PART 2 - PRODUCTS
2.1
SLEEVES FOR RACEWAYS AND CABLES
A.
Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain
ends.
B.
Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe,
with plain ends and integral waterstop, unless otherwise indicated.
C.
Sleeves for Rectangular Openings: Galvanized sheet steel.
1.
Minimum Metal Thickness:
a.
b.
2.2
For sleeve cross-section rectangle perimeter less than 50 inches and no side more
than 16 inches, thickness shall be 0.052 inch.
For sleeve cross-section rectangle perimeter equal to, or more than, 50 inches and
1 or more sides equal to, or more than, 16 inches, thickness shall be 0.138 inch.
SLEEVE SEALS
A.
Description: Modular sealing device, designed for field assembly, to fill annular space between
sleeve and raceway or cable.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Common Work Results for Electronic
Safety and Security
280500 -1
100% CD Submission – August 28, 2009
1.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following available manufacturers offering products that may be incorporated into the
Work include, but are not limited to, the following:
a.
b.
c.
d.
2.
3.
4.
2.3
Advance Products & Systems, Inc.
Calpico, Inc.
Metraflex Co.
Pipeline Seal and Insulator, Inc.
Sealing Elements: EPDM interlocking links shaped to fit surface of cable or conduit.
Include type and number required for material and size of raceway or cable.
Pressure Plates: Carbon steel. Include two for each sealing element.
Connecting Bolts and Nuts: Carbon steel with corrosion-resistant coating of length
required to secure pressure plates to sealing elements. Include one for each sealing
element.
GROUT
A.
Nonmetallic, Shrinkage-Resistant Grout:
ASTM C 1107, factory-packaged, nonmetallic
aggregate grout, noncorrosive, nonstaining, mixed with water to consistency suitable for
application and a 30-minute working time.
PART 3 - EXECUTION
3.1
COMMON REQUIREMENTS
INSTALLATION
FOR
ELECTRONIC
SAFETY
AND
SECURITY
A.
Comply with NECA 1.
B.
Measure indicated mounting heights to bottom of unit for suspended items and to center of unit
for wall-mounting items.
C.
Headroom Maintenance: If mounting heights or other location criteria are not indicated,
arrange and install components and equipment to provide maximum possible headroom
consistent with these requirements.
D.
Equipment: Install to facilitate service, maintenance, and repair or replacement of components
of both electronic safety and security equipment and other nearby installations. Connect in such
a way as to facilitate future disconnecting with minimum interference with other items in the
vicinity.
E.
Right of Way: Give to piping systems installed at a required slope.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Common Work Results for Electronic
Safety and Security
280500 -2
100% CD Submission – August 28, 2009
3.2
SLEEVE INSTALLATION
PENETRATIONS
FOR
ELECTRONIC
SAFETY
AND
SECURITY
A.
Electronic safety and security penetrations occur when raceways, pathways, cables, wireways,
or cable trays penetrate concrete slabs, concrete or masonry walls, or fire-rated floor and wall
assemblies.
B.
Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or formed
openings are used. Install sleeves during erection of slabs and walls.
C.
Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.
D.
Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies
unless openings compatible with firestop system used are fabricated during construction of floor
or wall.
E.
Cut sleeves to length for mounting flush with both surfaces of walls.
F.
Extend sleeves installed in floors 2 inches above finished floor level.
G.
Size pipe sleeves to provide 1/4-inch annular clear space between sleeve and raceway or cable,
unless indicated otherwise.
H.
Seal space outside of sleeves with grout for penetrations of concrete and masonry
1.
Promptly pack grout solidly between sleeve and wall so no voids remain. Tool exposed
surfaces smooth; protect grout while curing.
I.
Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve
and raceway or cable, using joint sealant appropriate for size, depth, and location of joint.
Comply with requirements in Division 0 Section "Joint Sealants.".
J.
Fire-Rated-Assembly Penetrations: Maintain indicated fire rating of walls, partitions, ceilings,
and floors at raceway and cable penetrations. Install sleeves and seal raceway and cable
penetration sleeves with firestop materials. Comply with requirements in Division 7 Section
“Firestopping."
K.
Roof-Penetration Sleeves: Seal penetration of individual raceways and cables with flexible
boot-type flashing units applied in coordination with roofing work.
L.
Aboveground, Exterior-Wall Penetrations: Seal penetrations using steel pipe sleeves and
mechanical sleeve seals. Select sleeve size to allow for 1-inch annular clear space between pipe
and sleeve for installing mechanical sleeve seals.
M.
Underground, Exterior-Wall Penetrations: Install cast-iron pipe sleeves. Size sleeves to allow
for 1-inch annular clear space between raceway or cable and sleeve for installing mechanical
sleeve seals.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Common Work Results for Electronic
Safety and Security
280500 -3
100% CD Submission – August 28, 2009
3.3
SLEEVE-SEAL INSTALLATION
A.
Install to seal exterior wall penetrations.
B.
Use type and number of sealing elements recommended by manufacturer for raceway or cable
material and size. Position raceway or cable in center of sleeve. Assemble mechanical sleeve
seals and install in annular space between raceway or cable and sleeve. Tighten bolts against
pressure plates that cause sealing elements to expand and make watertight seal.
3.4
FIRESTOPPING
A.
Apply firestopping to penetrations of fire-rated floor and wall assemblies for electronic safety
and security installations to restore original fire-resistance rating of assembly. Firestopping
materials and installation requirements are specified in Division 07 Section "Penetration
Firestopping."
END OF SECTION 280500
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Common Work Results for Electronic
Safety and Security
280500 -4
100% CD Submission – August 28, 2009
SECTION 280513 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY
PART 1 - GENERAL
1.1
SUMMARY
A.
Section Includes:
1.
2.
3.
4.
5.
6.
7.
1.2
Coaxial cabling.
RS-232 cabling.
RS-485 cabling.
Low-voltage control cabling.
Control-circuit conductors.
Fire alarm wire and cable.
Identification products.
SUBMITTALS
A.
Product Data: For each type of product indicated.
1.
For coaxial cable, include the following installation data for each type used:
a.
b.
c.
Nominal OD.
Minimum bending radius.
Maximum pulling tension.
B.
Shop Drawings: Cable tray layout, showing cable tray route to scale, with relationship between
the tray and adjacent structural, electrical, and mechanical elements.
C.
Qualification Data: For qualified layout technician, installation supervisor, and field inspector.
D.
Source quality-control reports.
E.
Field quality-control reports.
F.
Maintenance data.
1.3
QUALITY ASSURANCE
A.
Surface-Burning Characteristics: As determined by testing identical products according to
ASTM E 84 by a qualified testing agency. Identify products with appropriate markings of
applicable testing agency.
1.
2.
Flame-Spread Index: 25 or less.
Smoke-Developed Index: 50 or less.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Conductors and Cables for
Electronic Safety and Security
280513 -1
100% CD Submission – August 28, 2009
B.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
PART 2 - PRODUCTS
2.1
PATHWAYS
A.
Support of Open Cabling: NRTL labeled for support of cabling, designed to prevent
degradation of cable performance and pinch points that could damage cable.
1.
2.
3.
B.
Support brackets with cable tie slots for fastening cable ties to brackets.
Lacing bars, spools, J-hooks, and D-rings.
Straps and other devices.
Cable Trays:
1.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following available manufacturers offering products that may be incorporated into the
Work include, but are not limited to, the following:
a.
b.
c.
d.
e.
2.
Cable Tray Materials: Metal, suitable for indoors, and protected against corrosion by
electroplated zinc galvanizing, complying with ASTM B 633, Type 1, not less than
0.000472 inch thick.
a.
C.
Basket Cable Trays: 6 inches wide and 2 inches deep. Wire mesh spacing shall
not exceed 2 by 4 inches.
Conduit and Boxes: Comply with requirements in Division 26 Section "Raceway and Boxes for
Electrical Systems."
1.
2.2
Cable Management Solutions, Inc.
Cablofil Inc.
Cooper B-Line, Inc.
Cope - Tyco/Allied Tube & Conduit.
GS Metals Corp.
Outlet boxes shall be no smaller than 2 inches wide, 3 inches high, and 2-1/2 inches deep.
BACKBOARDS
A.
Backboards: Plywood, fire-retardant treated, 3/4 by 48 by 96 inches. Comply with
requirements for plywood backing panels in Division 6 Section "Rough Carpentry".
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Conductors and Cables for
Electronic Safety and Security
280513 -2
100% CD Submission – August 28, 2009
2.3
COAXIAL CABLE
A.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following available manufacturers offering products that may be incorporated into the Work
include, but are not limited to, the following:
1.
2.
3.
4.
5.
Alpha Wire Company.
Belden CDT Inc.; Electronics Division.
Coleman Cable, Inc.
CommScope, Inc.
Draka USA.
B.
General Coaxial Cable Requirements: Broadband type, recommended by cable manufacturer
specifically for broadband data transmission applications. Coaxial cable and accessories shall
have 75-ohm nominal impedance with a return loss of 20 dB maximum from 7 to 806 MHz.
C.
RG-11/U: NFPA 70, Type CATV.
1.
2.
3.
4.
5.
D.
RG59/U: NFPA 70, Type CATVR.
1.
2.
3.
4.
E.
No. 16 AWG, solid, copper-covered steel conductor; gas-injected, foam-PE insulation.
Double shielded with 100 percent aluminum-foil shield and 60 percent aluminum braid.
Jacketed with black PVC or PE.
Suitable for indoor installations.
RG59/U: NFPA 70, Type CATV.
1.
2.
3.
G.
No. 20 AWG, solid, silver-plated, copper-covered steel conductor.
Gas-injected, foam-PE insulation.
Triple shielded with 100 percent aluminum polyester tape and 95 percent aluminum
braid; covered by aluminum foil with grounding strip.
Color-coded PVC jacket.
RG-6/U: NFPA 70, Type CATV or CM.
1.
2.
3.
4.
F.
No. 14 AWG, solid, copper-covered steel conductor.
Gas-injected, foam-PE insulation.
Double shielded with 100 percent aluminum polyester tape and 60 percent aluminum
braid.
Jacketed with sunlight-resistant, black PVC or PE.
Suitable for outdoor installations in ambient temperatures ranging from minus 40 to plus
85 deg C.
No. 20 AWG, solid, copper-covered steel conductor; gas-injected, foam-PE insulation.
Double shielded with 100 percent aluminum polyester tape and 40 percent aluminum
braid.
PVC jacket.
RG59/U (Plenum Rated): NFPA 70, Type CMP.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Conductors and Cables for
Electronic Safety and Security
280513 -3
100% CD Submission – August 28, 2009
1.
2.
3.
H.
NFPA and UL compliance, listed and labeled by an NRTL acceptable to authorities having
jurisdiction as complying with UL 1655, and with NFPA 70 "Radio and Television Equipment"
and "Community Antenna Television and Radio Distribution" Articles. Types are as follows:
1.
2.
3.
4.
2.4
No. 20 AWG, solid, copper-covered steel conductor; foam fluorinated ethylene
propylene insulation.
Double shielded with 100 percent aluminum-foil shield and 65 percent aluminum braid.
Copolymer jacket.
CATV Cable: Type CATV, or CATVP or CATVR.
CATV Plenum Rated: Type CATVP, complying with NFPA 262.
CATV Riser Rated: Type CATVR, complying with UL 1666.
CATV Limited Rating: Type CATVX.
COAXIAL CABLE HARDWARE
A.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following available manufacturers offering products that may be incorporated into the Work
include, but are not limited to, the following:
1.
2.
3.
B.
2.5
Aim Electronics; a brand of Emerson Electric Co.
Leviton Voice & Data Division.
Siemon Co. (The).
Coaxial-Cable Connectors: Type BNC, 75 ohms.
RS-232 CABLE
A.
Standard Cable: NFPA 70, Type CM.
1.
2.
3.
4.
5.
6.
B.
Paired, 2 pairs, No. 22 AWG, stranded (7x30) tinned copper conductors.
Polypropylene insulation.
Individual aluminum foil-polyester tape shielded pairs with 100 percent shield coverage.
PVC jacket.
Pairs are cabled on common axis with No. 24 AWG, stranded (7x32) tinned copper drain
wire.
Flame Resistance: Comply with UL 1581.
Plenum-Type Cable: NFPA 70, Type CMP.
1.
2.
3.
4.
5.
6.
Paired, 2 pairs, No. 22 AWG, stranded (7x30) tinned copper conductors.
Plastic insulation.
Individual aluminum foil-polyester tape shielded pairs with 100 percent shield coverage.
Plastic jacket.
Pairs are cabled on common axis with No. 24 AWG, stranded (7x32) tinned copper drain
wire.
Flame Resistance: Comply with NFPA 262.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Conductors and Cables for
Electronic Safety and Security
280513 -4
100% CD Submission – August 28, 2009
2.6
RS-485 CABLE
A.
Standard Cable: NFPA 70, Type CM or CMG.
1.
2.
3.
4.
5.
B.
Plenum-Type Cable: NFPA 70, Type CMP.
1.
2.
3.
4.
5.
2.7
Paired, 2 pairs, twisted, No. 22 AWG, stranded (7x30) tinned copper conductors.
PVC insulation.
Unshielded.
PVC jacket.
Flame Resistance: Comply with UL 1581.
Paired, 2 pairs, No. 22 AWG, stranded (7x30) tinned copper conductors.
Fluorinated ethylene propylene insulation.
Unshielded.
Fluorinated ethylene propylene jacket.
Flame Resistance: NFPA 262, Flame Test.
LOW-VOLTAGE CONTROL CABLE
A.
Paired Lock Cable: NFPA 70, Type CMG.
1.
2.
3.
4.
5.
B.
Plenum-Type, Paired Lock Cable: NFPA 70, Type CMP.
1.
2.
3.
4.
5.
C.
1 pair, twisted, No. 16 AWG, stranded (19x29) tinned copper conductors.
PVC insulation.
Unshielded.
PVC jacket.
Flame Resistance: Comply with NFPA 262.
Paired Lock Cable: NFPA 70, Type CMG.
1.
2.
3.
4.
5.
D.
1 pair, twisted, No. 16 AWG, stranded (19x29) tinned copper conductors.
PVC insulation.
Unshielded.
PVC jacket.
Flame Resistance: Comply with UL 1581.
1 pair, twisted, No. 18 AWG, stranded (19x30) tinned copper conductors.
PVC insulation.
Unshielded.
PVC jacket.
Flame Resistance: Comply with UL 1581.
Plenum-Type, Paired Lock Cable: NFPA 70, Type CMP.
1.
2.
3.
1 pair, twisted, No. 18 AWG, stranded (19x30) tinned copper conductors.
Fluorinated ethylene propylene insulation.
Unshielded.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Conductors and Cables for
Electronic Safety and Security
280513 -5
100% CD Submission – August 28, 2009
4.
5.
2.8
Plastic jacket.
Flame Resistance: NFPA 262, Flame Test.
CONTROL-CIRCUIT CONDUCTORS
A.
Class 1 Control Circuits: Stranded copper, Type THHN-THWN, in raceway complying with
UL 83.
B.
Class 2 Control Circuits: Stranded copper, Type THHN-THWN, in raceway complying with
UL 83.
C.
Class 3 Remote-Control and Signal Circuits: Stranded copper, Type TW or TF, complying with
UL 83.
2.9
FIRE ALARM WIRE AND CABLE
A.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following available manufacturers offering products that may be incorporated into the Work
include, but are not limited to, the following:
1.
2.
3.
4.
5.
Comtran Corp.
Draka USA.
Genesis Cable Products; Honeywell International, Inc.
Rockbestos-Suprenant Cable Corporation.
West Penn Wire/CDT; a division of Cable Design Technologies.
B.
General Wire and Cable Requirements: NRTL listed and labeled as complying with NFPA 70,
Article 760.
C.
Signaling Line Circuits: Twisted, shielded pair, not less than No. 18 AWG.
1.
D.
Circuit Integrity Cable: Twisted shielded pair, NFPA 70, Article 760, Classification CI,
for power-limited fire alarm signal service Type FPL. NRTL listed and labeled as
complying with UL 1424 and UL 2196 for a 2-hour rating.
Non-Power-Limited Circuits: Solid-copper conductors with 600-V rated, 75 deg C, color-coded
insulation.
1.
2.
3.
Low-Voltage Circuits: No. 16 AWG, minimum.
Line-Voltage Circuits: No. 12 AWG, minimum.
Multiconductor Armored Cable:
NFPA 70, Type MC, copper conductors,
Type TFN/THHN conductor insulation, copper drain wire, copper armor with red
identifier stripe, NTRL listed for fire alarm and cable tray installation, plenum rated, and
complying with requirements in UL 2196 for a 2-hour rating.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Conductors and Cables for
Electronic Safety and Security
280513 -6
100% CD Submission – August 28, 2009
2.10
A.
IDENTIFICATION PRODUCTS
Manufacturers: Subject to compliance with requirements, provide products by one of the
following available manufacturers offering products that may be incorporated into the Work
include, but are not limited to, the following:
1.
2.
3.
4.
Brady Corporation
HellermannTyton.
Kroy LLC.
Panduit Corp.
B.
Comply with UL 969 for a system of labeling materials, including label stocks, laminating
adhesives, and inks used by label printers.
C.
Comply with requirements in Division 26 Section "Identification for Electrical Systems."
2.11
SOURCE QUALITY CONTROL
A.
Factory sweep test coaxial cables at frequencies from 5 MHz to 1 GHz. Sweep test shall test
the frequency response, or attenuation over frequency, of a cable by generating a voltage whose
frequency is varied through the specified frequency range and graphing the results.
B.
Cable will be considered defective if it does not pass tests and inspections.
C.
Prepare test and inspection reports.
PART 3 - EXECUTION
3.1
INSTALLATION OF PATHWAYS
A.
Cable Trays: Comply with NEMA VE 2 and TIA/EIA-569-A-7.
B.
Comply with TIA/EIA-569-A for pull-box sizing and length of conduit and number of bends
between pull points.
C.
Comply with requirements in Division 26 Section "Raceway and Boxes for Electrical Systems."
for installation of conduits and wireways.
D.
Install manufactured conduit sweeps and long-radius elbows whenever possible.
E.
Pathway Installation in Equipment Rooms:
1.
2.
3.
Position conduit ends adjacent to a corner on backboard where a single piece of plywood
is installed or in the corner of room where multiple sheets of plywood are installed
around perimeter walls of room.
Install cable trays to route cables if conduits cannot be located in these positions.
Secure conduits to backboard when entering room from overhead.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Conductors and Cables for
Electronic Safety and Security
280513 -7
100% CD Submission – August 28, 2009
4.
5.
F.
3.2
Extend conduits 3 inches above finished floor.
Install metal conduits with grounding bushings and connect with grounding conductor to
grounding system.
Backboards: Install backboards with 96-inch dimension vertical. Butt adjacent sheets tightly,
and form smooth gap-free corners and joints.
INSTALLATION OF CONDUCTORS AND CABLES
A.
Comply with NECA 1.
B.
General Requirements for Cabling:
1.
2.
3.
4.
5.
6.
C.
Open-Cable Installation:
1.
2.
3.
D.
Install cabling with horizontal and vertical cable guides in telecommunications spaces
with terminating hardware and interconnection equipment.
Suspend copper cable not in a wireway or pathway a minimum of 8 inches above ceilings
by cable supports not more than 60 inches apart.
Cable shall not be run through structural members or in contact with pipes, ducts, or other
potentially damaging items.
Installation of Cable Routed Exposed under Raised Floors:
1.
2.
3.
E.
Terminate all conductors; no cable shall contain unterminated elements. Make
terminations only at indicated outlets or terminals.
Cables may not be spliced. Secure and support cables at intervals not exceeding 30
inches and not more than 6 inches from cabinets, boxes, fittings, outlets, and terminals.
Bundle, lace, and train conductors to terminal points without exceeding manufacturer's
limitations on bending radii. Install lacing bars and distribution spools.
Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable
between termination, tap, or junction points. Remove and discard cable if damaged
during installation and replace it with new cable.
Cold-Weather Installation: Bring cable to room temperature before dereeling. Heat
lamps shall not be used for heating.
Pulling Cable: Do not exceed manufacturer's instructions as to allowable pulling tension.
Monitor cable pull tensions.
Install plenum-rated cable only.
Install cabling after the flooring system has been installed in raised floor areas.
Coil cable 72 inches long shall be neatly coiled not less than 12 inches in diameter below
each feed point.
Outdoor Coaxial Cable Installation:
1.
2.
Install outdoor connections in enclosures complying with NEMA 250, Type 4X. Install
corrosion-resistant connectors with properly designed O-rings to keep out moisture.
Attach antenna lead-in cable to support structure at intervals not exceeding 36 inches.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Conductors and Cables for
Electronic Safety and Security
280513 -8
100% CD Submission – August 28, 2009
3.3
FIRE ALARM WIRING INSTALLATION
A.
Comply with NECA 1 and NFPA 72.
B.
Wiring Method: Install wiring in metal raceway according to Division 26 Section "Raceway
and Boxes for Electrical Systems."
1.
2.
Install plenum cable in environmental air spaces, including plenum ceilings.
Fire alarm circuits and equipment control wiring associated with the fire alarm system
shall be installed in a dedicated raceway system. This system shall not be used for any
other wire or cable.
C.
Wiring within Enclosures: Separate power-limited and non-power-limited conductors as
recommended by manufacturer. Install conductors parallel with or at right angles to sides and
back of the enclosure. Bundle, lace, and train conductors to terminal points with no excess.
Connect conductors that are terminated, spliced, or interrupted in any enclosure associated with
the fire alarm system to terminal blocks. Mark each terminal according to the system's wiring
diagrams. Make all connections with approved crimp-on terminal spade lugs, pressure-type
terminal blocks, or plug connectors.
D.
Cable Taps: Use numbered terminal strips in junction, pull, and outlet boxes, cabinets, or
equipment enclosures where circuit connections are made.
E.
Color-Coding: Color-code fire alarm conductors differently from the normal building power
wiring. Use one color-code for alarm circuit wiring and another for supervisory circuits. Colorcode audible alarm-indicating circuits differently from alarm-initiating circuits. Use different
colors for visible alarm-indicating devices. Paint fire alarm system junction boxes and covers
red.
F.
Risers: Install at least two vertical cable risers to serve the fire alarm system. Separate risers in
close proximity to each other with a minimum one-hour-rated wall, so the loss of one riser does
not prevent the receipt or transmission of signals from other floors or zones.
G.
Wiring to Remote Alarm Transmitting Device: 1-inch conduit between the fire alarm control
panel and the transmitter. Install number of conductors and electrical supervision for
connecting wiring as needed to suit monitoring function.
3.4
CONTROL-CIRCUIT CONDUCTORS
A.
Minimum Conductor Sizes:
1.
2.
3.
3.5
Class 1 remote-control and signal circuits, No. 14 AWG.
Class 2 low-energy, remote-control and signal circuits, No. 16 AWG.
Class 3 low-energy, remote-control, alarm and signal circuits, No. 12 AWG.
FIRESTOPPING
A.
Comply with requirements in Division 7 Section "Firestopping."
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Conductors and Cables for
Electronic Safety and Security
280513 -9
100% CD Submission – August 28, 2009
3.6
GROUNDING
A.
3.7
For low-voltage wiring and cabling, comply with requirements in Division 26 Section
"Grounding and Bonding for Electrical Systems."
IDENTIFICATION
A.
3.8
Comply with requirements for identification specified in Division 26 Section "Identification for
Electrical Systems."
FIELD QUALITY CONTROL
A.
Tests and Inspections:
1.
2.
B.
Visually inspect cable jacket materials for UL or third-party certification markings.
Inspect cabling terminations to confirm color-coding.
Visually inspect cable placement, cable termination, grounding, and bonding.
Prepare test and inspection reports.
END OF SECTION 280513
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Conductors and Cables for
Electronic Safety and Security
280513 -10
100% CD Submission – August 28, 2009
SECTION 283111 - FIRE ALARM
PART 1 - GENERAL
1.1
SUMMARY
A.
This Section includes fire alarm systems with manual stations, detectors, signal equipment,
controls, and devices.
B.
Related Sections include the following:
1.
1.2
Division 8 Section "Hardware" for door closers/holders/smoke detectors, electric door
locks, and release devices that interface with fire alarm systems.
DEFINITIONS
A.
FACP: Fire alarm control panel.
B.
LED: Light-emitting diode.
C.
Definitions in NFPA 72 apply to fire alarm terms used in this Section.
1.3
SYSTEM DESCRIPTION
A.
Furnish and install all labor, materials and equipment required for modifications to existing non
addressable fire alarm system as shown on the plans and covered by these specifications. All
equipment shall be wired, connected and left in first class operating condition. All equipment
shall conform to NFPA 13, 72 and formal interpretations of these codes. All equipment shall be
U.L. listed and shall meet the requirements of the authorities having jurisdiction. All equipment
shall be ADA compliant. The scope includes but shall not be limited to the following.
1.
Utilize existing fire alarm control panel to accommodate the devices indicated. Provide
contacts, monitor and control modules, additional power supplies and all other
accessories for a complete and operational system.
2.
Fire Alarm System Shall Include (But Not Limited To):
a.
Alarm signals: audio visual devices (combination horn/strobe) ADA compliant
to match existing.
b.
Alarm signals:
c.
Notification appliance circuit power extender.
d.
All wiring and installation work shall be in accordance with the system
manufacturers written installation instructions and requirements.
visual devices (strobe light) ADA compliant to match existing.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Fire Alarm
283111 -1
100% CD Submission – August 28, 2009
1.4
e.
All fire alarm devices shall be ADA compliant and as required by the local
authority having jurisdiction. Any additional devices required for the audio visual
compliance shall be the responsibility of the contractor.
f.
The electrical contractor shall test all the fire alarm equipment or devices serving
the area in the contract. Testing shall be in the presence of the local fire official
having jurisdiction and the Owners designated representatives.
3.
All existing zones which have been modified due to deletion of existing devices or
installation of any additional devices shall require all devices within the affected alarm
and detection zones to be cleaned. The affected zone (s) shall be tested for verification of
proper alarm and/or detection function.
4.
Refer to electrical drawings for fire alarm diagram and additional information.
5.
Existing Fire Alarm Audio/Visual devices shall be synchronized with the new devices
being installed.
6.
All work associated with modification to the existing fire alarm shall be in full
compliance with the written requirements of the 2006 IBC-NJ, Section 907, GSA PBS
and the referenced Standard, NFPA72-2007 Edition.
7.
Section 907-2006-IBC-NJ Fire Alarm Detection Systems
SUBMITTALS
A.
Product Data: For each type of product indicated.
B.
Shop Drawings:
1.
2.
3.
4.
5.
C.
Wiring Diagrams: Detail wiring and differentiate between manufacturer-installed and
field-installed wiring. Include diagrams for equipment and for system with all terminals
and interconnections identified.
Battery: Sizing calculations.
Floor Plans: Indicate final device locations and routings of raceway connections.
Device Address List: Coordinate with final system programming.
System Operation Description: Detailed description for this Project, including method of
operation and supervision of each type of circuit and sequence of operations for manually
and automatically initiated system inputs and outputs. Manufacturer's standard
descriptions for generic systems are not acceptable.
Coordination Drawings: Plans, sections, and elevations drawn to scale and coordinating
installation of devices.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Fire Alarm
283111 -2
100% CD Submission – August 28, 2009
D.
Product Certificates: Signed by manufacturers of system components certifying that products
furnished comply with requirements.
E.
Installer Certificates: Signed by manufacturer certifying that installers comply with
requirements.
F.
Field Test Reports: Indicate and interpret test results for compliance with performance
requirements. Comply with NFPA 72.
G.
Maintenance Data: For fire alarm systems to include in maintenance manuals specified in
Division 1. Comply with NFPA 72.
H.
Submissions to Authorities Having Jurisdiction: In addition to distribution requirements for
Submittals specified in Division 1 Section "Submittals," make an identical submission to
authorities having jurisdiction. Include copies of annotated Contract Drawings as needed to
depict component locations to facilitate review.
1.
Complete submittal shall be signed and sealed by an independent professional engineer
licensed in the State of New Jersey.
2.
Resubmit if required to make clarifications or revisions to obtain approval. On receipt of
comments from authorities having jurisdiction, submit them to Architect for review.
I.
Certificate of Completion: Comply with NFPA 72.
QUALIFICATIONS
1.5
A.
Because of the essential life safety aspects of this contract, bidders shall meet all of the
following criteria and submit proof of same with bid:
B.
Manufacturer:
1.
Company specializing in manufacturing the products specified in this Section with a
minimum of five (5) years documented experience, and with service facilities within 100
miles of the project.
C.
Installer shall be a licensed New Jersey Electrical Contractor and business permittee. Licenses
held by employees or subcontractors to bidder will not be considered unless they form the basis
for the bidder’s electrical business permit.
D.
Installer shall be listed by UL or other nationally recognized testing laboratory as a protective
signaling services company and shall issue a certificate for the fire alarm systems required by
these specifications. The UL Certificate issued by a UL listed company provides a means of
verifying the specific NFPA standard that the system has been installed to comply with and
extent of coverage provided. The listed protective signaling services company bears the
responsibility for the correctness of the installation and documentation and service. Listing is
most often provided by UL (Underwriters Laboratories) but may be provided by any nationally
recognized testing laboratory which provides equivalent services. A bidder offering such
alternative listing shall fully document the equivalency with his bid.
E.
Installer shall directly employ at least two (2) technicians certified to Level 2 by the National
Institute for Certification in Engineering Technologies (NICET). NICET is an independent
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Fire Alarm
283111 -3
100% CD Submission – August 28, 2009
third party certification institute sponsored by the National Society of Professional Engineers
and located at 1420 King Street, Alexandria, VA 22314-2715.
F.
1.6
Installer shall provide a letter of certification from the manufacturer of the equipment proposed
for this project certifying that he is authorized to provide installation and service and that there
is at least one (1) additional unrelated service facility authorized to provide service for the
equipment involved.
QUALITY ASSURANCE
A.
Installer Qualifications: An experienced installer who is an authorized representative of the
FACP manufacturer for both installation and maintenance of units required for this Project.
B.
Manufacturer Qualifications: A firm experienced in manufacturing systems similar to those
indicated for this Project and with a record of successful in-service performance.
C.
Source Limitations: Obtain fire alarm system components through one source from Simplex.
D.
Compliance with Local Requirements: Comply with applicable building code, local ordinances
and regulations, and requirements of authorities having jurisdiction.
E.
Comply with NFPA 72.
1.7
EXTRA MATERIALS
A.
Furnish extra materials described below that match products installed and that are packaged
with protective covering for storage and identified with labels describing contents.
1.
Lamps for Strobe Units: Quantity equal to 10 percent of amount installed, but not less
than one unit.
2.
Keys and Tools: One extra set for access to locked and tamperproofed components.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
Manufacturers: Subject to compliance with requirements, provide products by Simplex
Grinnell.
FUNCTIONAL DESCRIPTION OF SYSTEM
A.
Control of System: By the FACP.
B.
System Supervision: Automatically detect and report open circuits, shorts, and grounds of
wiring for initiating device, signaling line, and notification-appliance circuits.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Fire Alarm
283111 -4
100% CD Submission – August 28, 2009
C.
Priority of Signals: Automatic alarm response functions resulting from an alarm signal from
one device are not altered by subsequent alarm, supervisory, or trouble signals. An alarm signal
is the highest priority. Supervisory and trouble signals have second- and third-level priority.
Higher-priority signals take precedence over signals of lower priority, even when the lowerpriority condition occurs first. Annunciate and display all alarm, supervisory, and trouble
signals regardless of priority or order received.
D.
System Reset: System is manually resettable from the FACP after initiating devices are
restored to normal.
E.
Transmission to Remote Alarm Receiving Station: Automatically route alarm, supervisory, and
trouble signals to a remote alarm station by means of a digital alarm communicator transmitter
and fiber-optic lines.
F.
Loss of primary power at the FACP initiates a trouble signal at the FACP and the annunciator.
An emergency power light is illuminated at both locations when the system is operating on the
secondary power supply.
1.
2.
3.
4.
5.
G.
Alarm Silencing, System Reset and Indication: Controlled by switches in the FACP and the
remote annunciator.
1.
2.
3.
H.
2.3
Notification-appliance operation.
Identification at the FACP and the remote annunciator of the device originating the
alarm.
Transmission of an alarm signal to the remote alarm receiving station.
Recording of the event in the system memory.
Recording of the event by the system printer.
Silencing-switch operation halts alarm operation of notification appliances and activates
an "alarm silence" light. Display of identity of the alarm zone or device is retained.
Subsequent alarm signals from other devices or zones reactivate notification appliances
until silencing switch is operated again.
When alarm-initiating devices return to normal and system reset switch is operated,
notification appliances operate again until alarm silence switch is reset.
FACP Alphanumeric Display: Plain-English-language descriptions of alarm, supervisory, and
trouble events; and addresses and locations of alarm-initiating or supervisory devices
originating the report. Display monitoring actions, system and component status, system
commands, programming information, and data from the system's historical memory.
MANUAL PULL STATIONS
A.
Description: Fabricated of metal or plastic, and finished in red with molded, raised-letter
operating instructions of contrasting color.
1.
2.
3.
Double-action mechanism initiates an alarm.
Double-action mechanism requires two actions, such as a push and a pull, to initiate an
alarm.
Station Reset: Key or wrench operated; double pole, double throw; switch rated for the
voltage and current at which it operates.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Fire Alarm
283111 -5
100% CD Submission – August 28, 2009
4.
5.
6.
2.4
Indoor Protective Shield: Factory-fabricated clear plastic enclosure, hinged at the top to
permit lifting for access to initiate an alarm. Lifting the cover actuates an integral
battery-powered audible horn intended to discourage false alarm operation.
Weatherproof Protective Shield: Factory-fabricated clear plastic enclosure, hinged at the
top to permit lifting for access to initiate an alarm.
Integral Addressable Module: Arranged to communicate manual-station status (normal,
alarm, or trouble) to the FACP.
NOTIFICATION APPLIANCES
A.
Description: Equip for mounting as indicated and have screw terminals for system connections.
1.
Combination Devices: Factory-integrated audible and visible devices in a singlemounting assembly.
B.
Horns: Electric-vibrating-polarized type, 24-V dc; with provision for housing the operating
mechanism behind a grille. Horns produce a sound-pressure level of 90 dB, measured 10 feet (3
m) from the horn.
C.
Visible Alarm Devices: Xenon strobe lights listed under UL 1971 with clear or nominal white
polycarbonate lens. Mount lens on an aluminum faceplate. The word "FIRE" is engraved in
minimum 1-inch- (25-mm-) high letters on the lens.
1.
2.
3.
2.5
Rated Light Output: 30 and 75 candela in corridors, 30 feet on centers or in rooms no
greater than 20’x20’, 75 candela for rooms greater that 20’x20’ but less than 55’x55’ and
110 candela for larger spaces.
Strobe Leads: Factory connected to screw terminals.
All strobes shall be synchronized together.
GUARDS FOR PHYSICAL PROTECTION
A.
Description: Welded wire mesh of size and shape for the manual station, smoke detector, gong,
or other device requiring protection.
1.
2.
2.6
Factory fabricated and furnished by the manufacturer of the device.
Finish: Paint of color to match the protected device.
WIRE
A.
Non-Power-Limited Circuits: Solid-copper conductors with 600-V rated, 75 deg C, color-coded
insulation.
1.
2.
B.
Low-Voltage Circuits: No. 16 AWG, minimum.
Line-Voltage Circuits: No. 12 AWG, minimum.
Power-Limited Circuits: NFPA 70, Types FPL, FPLR, or FPLP, as recommended by
manufacturer.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Fire Alarm
283111 -6
100% CD Submission – August 28, 2009
PART 3 - EXECUTION
3.1
EQUIPMENT INSTALLATION
A.
Manual Pull Stations: Mount semiflush in recessed back boxes.
B.
Audible Alarm-Indicating Devices: Install not less than 80” AFF to bottom of device or 6
inches (150 mm) below the ceiling. Install bells and horns on flush-mounted back boxes with
the device-operating mechanism concealed behind a grille. Combine audible and visible alarms
at the same location into a single unit.
C.
Visible Alarm-Indicating Devices: Install adjacent to each alarm bell or alarm horn and at least
6 inches (150 mm) below the ceiling.
D.
Device Location-Indicating Lights: Locate in public space near the device they monitor.
3.2
WIRING INSTALLATION
A.
Wiring Method: Install wiring in conduit according to Division 16 Section "Raceways and
Boxes." Conceal raceway except in unfinished spaces and as indicated.
B.
Wiring within Enclosures: Separate power-limited and non-power-limited conductors as
recommended by the manufacturer. Install conductors parallel with or at right angles to sides
and back of the enclosure. Bundle, lace, and train conductors to terminal points with no excess.
Connect conductors that are terminated, spliced, or interrupted in any enclosure associated with
the fire alarm system to terminal blocks. Mark each terminal according to the system's wiring
diagrams. Make all connections with approved crimp-on terminal spade lugs, pressure-type
terminal blocks, or plug connectors.
C.
Cable Taps: Use numbered terminal strips in junction, pull and outlet boxes, cabinets, or
equipment enclosures where circuit connections are made.
D.
Color-Coding: Color-code fire alarm conductors differently from the normal building power
wiring. Use one color-code for alarm circuit wiring and a different color-code for supervisory
circuits. Color-code audible alarm-indicating circuits differently from alarm-initiating circuits.
Use different colors for visible alarm-indicating devices. Paint fire alarm system junction boxes
and covers red.
3.3
IDENTIFICATION
A.
Identify system components, wiring, cabling, and terminals according to Division 16 Section
"Electrical Identification."
B.
Install instructions frame in a location visible from the FACP.
C.
Paint power-supply disconnect switch red and label "FIRE ALARM."
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Fire Alarm
283111 -7
100% CD Submission – August 28, 2009
3.4
GROUNDING
A.
Ground cable shields and equipment according to system manufacturer's written instructions to
eliminate shock hazard and to minimize, to the greatest extent possible, ground loops, commonmode returns, noise pickup, cross talk, and other impairments.
B.
Signal Ground Terminal: Locate at main equipment rack or cabinet. Isolate from power system
and equipment grounding.
C.
Install grounding electrodes of type, size, location, and quantity as indicated. Comply with
installation requirements in Division 16 Section "Grounding."
D.
Ground equipment and conductor and cable shields. For audio circuits, minimize, to the
greatest extent possible, ground loops, common-mode returns, noise pickup, cross talk, and
other impairments. Provide 5-ohm ground at main equipment location. Measure, record, and
report ground resistance.
3.5
FIELD QUALITY CONTROL
A.
Manufacturer's Field Service: Engage a factory-authorized service representative to inspect
field-assembled components and connections and to supervise pretesting, testing, and
adjustment of the system. Report results in writing.
B.
Pretesting: After installation, align, adjust, and balance the system and perform complete
pretesting. Determine, through pretesting, the compliance of the system with requirements of
Drawings and Specifications. Correct deficiencies observed in pretesting. Replace
malfunctioning or damaged items with new ones, and retest until satisfactory performance and
conditions are achieved. Prepare forms for systematic recording of acceptance test results.
C.
Report of Pretesting: After pretesting is complete, provide a letter certifying the installation is
complete and fully operable, including the names and titles of witnesses to preliminary tests.
D.
Final Test Notice: Provide a minimum of 10 days' notice in writing when the system is ready
for final acceptance testing.
E.
Minimum System Tests: Test the system according to procedures outlined in NFPA 72.
Minimum required tests are as follows:
1.
2.
3.
4.
5.
Verify the absence of unwanted voltages between circuit conductors and ground.
Test all conductors for short circuits using an insulation-testing device.
With each circuit pair, short circuit at the far end of the circuit and measure the circuit
resistance with an ohmmeter. Record the circuit resistance of each circuit on record
drawings.
Verify that the control unit is in the normal condition as detailed in the manufacturer's
operation and maintenance manual.
Test initiating and indicating circuits for proper signal transmission under open circuit
conditions. One connection each should be opened at not less than 10 percent of
initiating and indicating devices. Observe proper signal transmission according to class
of wiring used.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Fire Alarm
283111 -8
100% CD Submission – August 28, 2009
6.
7.
8.
Test each initiating and indicating device for alarm operation and proper response at the
control unit. Test smoke detectors with actual products of combustion.
Test the system for all specified functions according to the approved operation and
maintenance manual. Systematically initiate specified functional performance items at
each station, including making all possible alarm and monitoring initiations and using all
communications options. For each item, observe related performance at all devices
required to be affected by the item under all system sequences. Observe indicating lights,
displays, signal tones, and annunciator indications. Observe all voice audio for routing,
clarity, quality, freedom from noise and distortion, and proper volume level.
Test Both Primary and Secondary Power: Verify by test that the secondary power system
is capable of operating the system for the period and in the manner specified.
F.
Retesting: Correct deficiencies indicated by tests and completely retest work affected by such
deficiencies. Verify by the system test that the total system meets Specifications and complies
with applicable standards.
G.
Report of Tests and Inspections: Provide a written record of inspections, tests, and detailed test
results in the form of a test log. Submit log on the satisfactory completion of tests.
H.
Tag all equipment, stations, and other components at which tests have been satisfactorily
completed.
3.6
CLEANING AND ADJUSTING
A.
3.7
Cleaning: Remove paint splatters and other spots, dirt, and debris. Touch up scratches and
marred finish to match original finish. Clean unit internally using methods and materials
recommended by manufacturer.
DEMONSTRATION
A.
Engage a factory-authorized service representative to train Owner's maintenance personnel as
specified below:
1.
2.
3.
3.8
Train Owner's maintenance personnel on procedures and schedules for starting and
stopping, troubleshooting, servicing, adjusting, and maintaining equipment and
schedules. Provide a minimum of 8 hours' training.
Training Aid: Use the approved final version of the operation and maintenance manual
as a training aid.
Schedule training with Owner, through Architect, with at least seven days' advance
notice.
WARRANTY
A.
Manufacturer shall guarantee the system equipment for a period of one (1) year from date of
final acceptance of the system.
B.
The contractor shall guarantee all wiring and raceways to be free from inherent mechanical or
electrical defects for one (1) year from date of final acceptance of the system.
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Fire Alarm
283111 -9
100% CD Submission – August 28, 2009
C.
3.9
Upon completion of the installation of the fire alarm system equipment, the electrical contractor
shall provide to the architect a signed written statement, substantially in form as follows: “The
undersigned, having engaged as the Contractor for this project, confirms that the fire alarm
system equipment was installed in accordance with the wiring diagrams, instructions and
directions provided to us by the manufacturer.”
ON-SITE ASSISTANCE
A.
Occupancy Adjustments: When requested within one year of date of Substantial Completion,
provide on-site assistance in adjusting sound levels, controls, and sensitivities to suit actual
occupied conditions. Provide up to three requested visits to Project site for this purpose.
END OF SECTION 13851
Monmouth County Courthouse –East Wing Alterations
Freehold, NJ
F08-5504
Fire Alarm
283111 -10
100% CD Submission – August 28, 2009
MCCI – Facility Generator and Electrical Panel Replacement
Monmouth County Correctional Institution
1 Waterworks Road, Freehold, NJ 07728
MCCI - GENERAL SECURITY REQUIREMENTS
1
Two weeks prior to beginning work, provide the Facility with a list of all of the
Contractor's and Subcontractor's personnel who will be engaged on the Project so that the
Facility can perform a security check (See form at end of this Division). Include date of
birth and Social Security number. Only those personnel who have been issued clearances
will be permitted to pass through the designated check point to work on the site.
2
Personnel will be issued passes no earlier than 5pm by a Sheriff Officer. Passes will be
collected at the end of each day (work shift).
3
Routes of ingress and egress within the Facility to the location of the Work shall be as
directed by the Facility's Representative. All of the Contractor’s employees shall enter and
exit the site through Gate 1 or as designated by the Facility.
4
Store materials and perform the Work so that pedestrian and vehicular traffic is not
obstructed.
5
Be responsible and accountable for employees, suppliers, subcontractors and their
employees, with regard to their use of the premises and their equipment. Direct them to
comply with the Facility Regulations and with the security and traffic regulations attached
at the end of this Division. All of the Contractor’s employees, his subcontractors and other
personnel engaged by the Contractor will be required to sign an affidavit certifying that
they have read and understand these Regulations.
6
Furnish Facility authorities with a 24 hour telephone number or method to contact the
Contractor's Superintendent, Foreman or designated representative in case of an emergency
after work hours, including weekends and holidays.
7
Direct employees to be watchful for people in or near the work area where safety hazards
may be present. Notify the Facility, if necessary, to remove them from the work area or
Site.
8
Report fire and other emergency situations to the Facility immediately.
9
The following items are not allowed on the Site or on Facility premises:
•
•
•
•
10
Firearms, ammunition, weapons, and dangerous instruments (other than tools required
for the Work).
Alcoholic beverages and persons under the influence of same.
Illegal controlled substances and persons under the influence of same.
Cameras (except with written permission from the Facility's Representative).
Comply with Facility policies relating to smoking at the Site.
General Security Requirements
GSR-1
11
MCCI – Facility Generator and Electrical Panel Replacement
Monmouth County Correctional Institution
1 Waterworks Road, Freehold, NJ 07728
Do not physically, verbally, or psychologically mistreat inmates, personnel, and other
persons at the Facility.
12
Do not talk to, address or respond to any inmate.
13
Do not receive from or give to inmates, visitors, or other persons at the Facility, any items
(food, cigarettes, money, matches, mail, etc.)
14
Do not diminish the level of life safety during performance of the Work.
15
Obtain location of underground tanks and tunnels from the Facility Representative prior to
bringing heavy equipment on site. Avoid these locations for parking or moving heavy
vehicles.
16
Coordinate with the Facility for any additional requirements that may be in affect at the
time of construction.
General Security Requirements
GSR-2
Please print or type all entries.
Date of Application
CONTRACTOR'S SECURITY CLEARANCE APPLICATION
To Office of the Monmouth County Sheriff
Fax to 732-431-7435
Contractor's Name (Firm)
Project:
East Wing Renovation
Monmouth County Courthouse
71 Monument Park, Freehold, NJ 07728
Contractor's Contact Person (Name)
Phone Number: (
)
/
Last Name
First Name
M.I.
Social Security Number
Driver License Number
State
Home Address - Street
City
State
/
Date of Birth
Month
Day
Year
Race
Sex
Hair Color
Eye Color
Zip
For Office Use Only (enter date)
Cleared/Denied:
By:
/
Last Name
First Name
M.I.
Social Security Number
Driver License Number
State
Home Address - Street
City
State
/
Date of Birth
Month
Day
Year
Race
Sex
Hair Color
Eye Color
Zip
For Office Use Only (enter date)
Cleared/Denied:
By:
/
Last Name
First Name
M.I.
Social Security Number
Driver License Number
State
/
Date of Birth
Month
Day
Year
Race
Sex
Hair Color
Eye Color
For Office Use Only (enter date)
Cleared/Denied:
By:
Home Address - Street
City
State
Zip
Last Name
First Name
M.I.
Date of Birth
Month
Day
Year
Race
Sex
Hair Color
Eye Color
Social Security Number
Driver License Number
State
/
Home Address - Street
City
State
Zip
/
For Office Use Only (enter date)
Cleared/Denied:
By:
GSR-3
Download