Arc Flash Mitigation Technology by Siemens Low and Medium Voltage Equipment Unrestricted © Siemens 2016 usa.siemens.com/oil-and-gas Topics of Discussion Bolted Faults Vs Arcing Faults Applicable Industry Standards Arc Flash Hazards Terms and Definitions NFPA and NEC-2015 Changes Low and Medium Voltage Arc Flash Mitigating Techniques by Siemens Low Voltage Smart Switchgear Low and Medium Voltage Arc Resistant Switchgear Unrestricted © Siemens 2016 Page 2 So what causes Arc Flash?? Inadvertent Contact with Live Wires/Bus Loose connections Insulation Failure Poorly maintained equipment Voltage transients Unsuccessful Short Circuit Interruption Animals (squirrels, snakes, etc) Unrestricted © Siemens 2016 Page 3 Difference between Arcing Faults and short circuit fault? Unrestricted © Siemens 2016 Page 4 Unrestricted © Siemens 2016 Page 5 • Expanding plasma creates severe mechanical, thermal stresses in equipment • On a 3 ft x 4 ft door → 7 tons of force! • Can blow open doors • Can burn through enclosures Magnitude of Forces- Arc Flash Testing MV Unrestricted © Siemens 2016 Page 6 End effects of arc fault event… Temperature 1740F in 0.1 sec. – curable burn (2nd degree) 2030F in 0.1 sec. - incurable burn (3rd degree) Incident energy 1.2 cal/cm2 - onset of 2nd degree burn 10.7 cal/cm2 - onset of 3rd degree burn Electrical arc blast (explosion) “80% of electrically-related accidents & fatalities involving 'Qualified Workers' are caused by arc flash/ arc blast.” (OSHA) “2,000 workers are treated in specialized burn trauma centers each year as a result of arc flash injuries.” (ESFI – Electrical Safety Foundation International “5 to 10 arc flash explosions occur daily across US.” (NFPA 70E) Unrestricted © Siemens 2016 Page 7 Impacts Productivity! Arc Flash Mitigation- Applicable Standards Unrestricted © Siemens 2016 Page 8 NFPA 2015 Changes 130.1 Work Involving Electrical Hazards Normal Operation- Normal operation of electrical equipment shall be permitted when all of the following conditions are satisfied: a. The equipment is properly Installed; b. The equipment is properly maintained; c. All equipment doors are closed and secured; d. All equipment covers are in place and secured; and no evidence of imposing failure. Unrestricted © Siemens 2016 PagePage 9 NFPA 2015 Changes 130.1 Work Involving Electrical Hazards-Informational Notes: • The phrase “properly installed” means that the equipment is installed in accordance with applicable industry codes and standards and manufacturers recommendations. • The phrase “properly maintained” means the equipment has been maintained in accordance with manufacture recommendations and applicable industry codes and standards. • The phrase “evidence of impeding failure” means that there is evidence such as arcing, overheating, loose or bound equipment parts, visible damage or deterioration. Unrestricted © Siemens 2016 Page 10 NFPA 2015 Changes 130.2 (B) Energized Electrical Work Permit An energized electrical work permit shall not be required under any of the following: • Testing, troubleshooting and voltage measuring • Thermography and visual inspection if the restricted approach boundary is not crossed. • Access and egress to an area with electrical equipment if no electrical work is being performed and the restricted approach boundary is not crossed. • General housekeeping and miscellaneous non-electrical task if the restricted approach boundary is not crossed. • Where the employer’s arc flash risk assessment required by 130.5 identifies no arc-flash hazards Unrestricted © Siemens 2016 Page 11 Arc Flash Hazards Identification Table 130.7 (C)(15)(A) AC Equipment Section 130.(7)(a) IN No. 2, “It is the collective experience of the Technical Committee on Electrical Safety in the Workplace that normal operation of enclosed electrical equipment, operating at 600 volts or less, that has been properly installed and maintained by qualified persons is not likely to expose the employee to an electrical hazard.” Unrestricted © Siemens 2016 Page 12 NFPA Section 130.4 Arc Flash Hazard Boundary Section 130.4(B) Eliminates the Prohibited Approach Boundary for the shock hazard. The Limited Approach Boundary is the closest an unqualified person can approach exposed energized conductors or circuit parts. The Restricted Approach Boundary is the point at which a qualified person must wear insulating rubber gloves or take other action to protect themselves from the shock hazard. Unrestricted © Siemens 2016 Page 13 NEC-2015 Arc Flash Requirements 240.87 Arc Energy Reduction Where the highest continuous current trip setting for which the actual over current device installed in a circuit breaker is rated or can be adjusted is 1200 A or higher, 240.87(A) and (B) shall apply. (A) Documentation. Documentation shall be available to those authorized to design, install, operate, or inspect the installation as to the location of the circuit breaker(s). (B) Method to Reduce Clearing Time. One of the following or approved equivalent means shall be provided: (1) Zone-selective interlocking (2) Differential relaying (3) Energy-reducing maintenance switching with local status indicator (4) Energy-reducing active arc flash mitigation system (5) An approved equivalent means Unrestricted © Siemens 2016 Page 14 Definitions of Arc-Flash Hazard Terms Arc current - NOT bolted fault current. In a typical 480V system, a bolted fault current of 50 kA available will result in an arc current of only 26 kA. • Arc current is used to determine the time for the overcurrent protective device to clear the circuit. • Since the time for the overcurrent protective device depends on the value of current flowing, it could be quite different for an arc than for a bolted fault. Incident energy-Energy impressed on a body surface by an arc, units in Calories/cm2. Determined by the three basic elements • Arc current • System voltage • Duration of the arc Incident Energy is used to determine the hazard category for selection of PPE (Personal Protective Equipment). Unrestricted © Siemens 2016 Page 15 So what is safe practice? Unrestricted © Siemens 2016 Page 16 Safest method to arc flash hazard.. People make mistakes, that’s why we call them accidents. Overcurrent Protective Devices can fail, PPE can fail and even enclosure can fail. Increasing working distance is the best, safest, most fool proof and in many cases the most cost effective mitigation method. Unrestricted © Siemens 2016 Page 17 Low and Medium Voltage Arc Flash Mitigation Techniques Unrestricted © Siemens 2016 usa.siemens.com/oil-and-gas Arc Flash Hazard Solutions Group into Four Categories Arc Flash Incident Prevention Arc Flash Incident Energy Reduction • Insulated bus bar • Dynamic Arc Flash Sentry • Isolation barriers • Zone selective interlock • Breaker shutters • High resistance grounding • Infrared viewport • Differential relaying • Breaker and cradle temperature monitoring • Crowbar systems Arc Flash Incident Energy Containment Arc resistant Switchgear Unrestricted © Siemens 2016 Page 19 • Arc flash light detection Enabling Personnel to Stay Outside the Arc Flash Hazard Boundary • Remote power monitoring, control & diagnostics • Remote breaker operator panel • Remote breaker racking device • Smart Switchgear with HMI Arc Flash Mitigation Insulated/Isolated Bus Bus bars are intimately covered with insulating material Unrestricted © Siemens 2016 Page 20 Arc Flash Mitigation Insulated/Isolated Bus Insulating barriers placed enclose each phase bus Unrestricted © Siemens 2016 Page 21 Arc Flash Mitigation Hot Spot/Loose Connections Monitoring IR Windows • IR Windows enable thermal, visual and corona inspection of live electrical equipment • IR Windows are a risk reduction tool, they cannot provide 100% protection against all eventualities but do provide significant reduction in risk of injury by reducing the triggers of explosions & providing a level of protection should an explosion occur Unrestricted © Siemens 2016 Page 22 Smart Switchgear- Digitalization Concept Cradle and Breaker Temperature Monitoring from Remote HMI Unrestricted © Siemens 2016 Page 23 Smart Switchgear- Digitalization Concept Bus Joints Monitoring Unrestricted © Siemens 2016 Page 24 24 Page Smart Switchgear- Digitalization Concept Switchgear Bus Joints Monitoring from Remote HMI Unrestricted © Siemens 2016 Page 25 Smart Switchgear- Digitalization Concept Switchgear Bus Joints Monitoring from Remote HMI Unrestricted © Siemens 2016 Page 26 26 Page Rear view of LVS with rear doors open showing Exertherm IR sensor mounts in the main bus bar bolted joint Smart Switchgear- Digitalization Concept Cable Connections Monitoring from Remote HMI Unrestricted © Siemens 2016 PagePage 27 Arc Flash Energy Reduction- Maintenance Mode “REDUCING THE DANGEROUS ARC FLASH HAZARD IN INDUSTRIAL FACILITIES “ IEEE Denver Feb’05 Michael Hodder William Vilcheck Floyd Croyle David McCue Member, IEEE Sr. Member, IEEE Member, IEEE Member, IEEE Eaton Electrical Eaton Electrical Eaton Electrical Cytec Industries “Use a temporary “faster” trip time while work is performed. : A lockout tagout procedure can include the reduction of a protective device tripping time. The reduced time settings must be returned to the normal time setting after work is completed. . . . A lockable switch could be used to enable the faster setting.” Unrestricted © Siemens 2016 Page 28 Arc Flash Energy Reduction- Maintenance Mode Dynamic Arc Sentry (DAS) ETU776 Electronic Trip Unit in the WL Power Circuit Breaker Normal Operation Parameter A Maintenance Operation Parameter B Unrestricted © Siemens 2016 Page 29 Arc Flash Mitigation –Digitalization Concept Maintenance Mode from Remote HMI Unrestricted © Siemens 2016 Page 30 Arc Flash Mitigation –Passive Safety Design Arc Resistant Testing- 500ms Unrestricted © Siemens 2016 Page 31 07/200 Page Arc Resistant Testing- 100ms Unrestricted © Siemens 2016 Page 32 07/200 Page Arc Flash Energy Reduction High Resistance Grounding • Source (Wye) HRG limits ground current to 4-6A in low voltage system. AØ • • HRG allows continuous operation of the system with single phase to ground. Limits current to the arcing faults Unrestricted © Siemens 2016 Page 33 BØ N HRG CØ Arc Flash Mitigation- Digitalization Concept Dynamic Bus Differential using Smart Switchgear Typical Bus Differential Monitor total incoming currents in each phase and current going out from feeders. Sensing Each phase currents are monitored at incoming and at the load side of feeder breakers using Ragowski Coil sensors.. Analog signals from the sensors will be analyzed with logic developed in Smart IPC (CPU) Smart Concept Deviation in summation will be annunciated as a bus fault. Fastest Tripping Times- Reduction in Arc Flash Energy In such event, main breaker will be tripped within 70-80 ms Dynamic Bus Differential Automatically configured for the M-T-M with Benefits over ZSI • • Unrestricted © Siemens 2016 Page 34 Faster tripping times on bus faults Smart configured Arc Flash Mitigation- Digitalization Concept Dynamic Bus Differential using Smart Switchgear Unrestricted © Siemens 2016 Page 35 Arc Flash Detection Medium Voltage Switchgear Front and side view Optical sensors with wires Busbar compartment Breaker compartment Cable connection compartment Unrestricted © Siemens 2016 Page 36 31.03.201 Page Arc Flash Detection- Medium Voltage Switchgear Methods of Arc Flash Detection • Light only • Benefits: Extremely fast tripping, selective (only affected feeder is tripped if an arc appears in the cable connection compartment) • Disadvantages: risk of unwanted trips (from camera flash etc..) • Light and Current • Benefits: fast tripping, safety against unwanted trips • Disadvantages: more wiring required, limited to 4 feeders maximum (due to 15 sensor maximum per modular relay) • Light and Current with Communication (Binary signal /IEC 61850 GOOSE) • Benefits: fast tripping, safety against unwanted trips, no limit on number of feeders, one arc flash protection module per switchgear Unrestricted © Siemens 2016 Page 37 Light only trip time: ~3ms + contact Light + current trip time: ~4ms + contact Personal Safety- minimize equipment damage Arc Flash Detection- Medium Voltage Switchgear Light & Current (with communication) Binary signal / Goose Busbar compartment Breaker compartment Cable connection compartment Unrestricted © Siemens 2016 Page 38 Feeder 1 Feeder 2 Incoming Arc Flash Detection- Low Voltage Swtichgear OPTIONAL SPOT SENSOR Unrestricted © Siemens 2016 Page 39 Arc Flash Detection- Low Voltage Switchgear Fiber Loop- Current and Flash Detection Unrestricted © Siemens 2016 Page Page 40 Arc Flash Avoidance – WL Remote Breaker Racking Device Unrestricted © Siemens 2016 Page 41 Arc Flash Avoidance – Digitalization Concept Remote Breaker Racking from Smart HMI Unrestricted © Siemens 2016 Page 42 Arc Flash Mitigation Siemens Integrated Electrical-Racking System Placement of SIERS components in switchgear cell B Control module mounted in low-voltage area C C A Electrical racking mechanism A Power supply module Unrestricted © Siemens 2016 Page 43 B Control pendant Medium Voltage Switchgear External Mounted Remote Racking Device • Motor drive accessory: • Installs without tools on mounting brackets on front door of circuit breaker compartment • Secured to mounting brackets with pins that are attached to motor drive assembly with lanyards to prevent loss of pins • Power cord for connection to user’s 120 Vac duplex receptacle • Control cable with pushbutton • Allows operator to control racking from a distance Unrestricted © Siemens 2016 Page 44 Siemens Digitalization Concept Low Voltage Smart Switchgear Unrestricted © Siemens 2016 Enabling Personnel to Stay Outside the Arc Flash Hazard Boundary – Remote Operation Panel Traditional Remote Control Panel Unrestricted © Siemens 2016 Page Page 46 3/31/20 Smart LVS Remote Control Panel Arc Flash Mitigation – Smart Switchgear Remote HMI Panel Unrestricted © Siemens 2016 Page 47 Arc Flash Mitigation- Smart Switchgear Benefits Safety • • • Arc Flash Hazard Data and Calculations Keeping personnel outside for Fire Hazard Boundary Remote Control, Configuration and Monitoring Reliability/Productivity • • • • • • • • Fault Trends and Reporting Harmonics Monitoring Min/Max Power Metering Monthly/Daily Maintenance Reports Transformer Monitoring Fault Annunciation and Diagnostics Predictive/Preventive Maintenance Self Diagnostic Data- Breaker Contact Wear Indication/Temperature/Type of Fault Alarms Flexibility • • Easy Integration into Upper Level System One Power System Solution- Potentially integrate with MV and Motor Control Centers Unrestricted © Siemens 2016 Page 48 The user has the option to use the elevation view (shown here) or the one-line view (next slide) as their home page where they can drill down to the embedded intelligent devices. Unrestricted © Siemens 2016 Page Page 49 49 Page 3/31/20 Smart Switchgear Topology Unrestricted © Siemens 2016 Page 50 Breaker configuration support screens are shown below. Unrestricted © Siemens 2016 Page 51 51 Page 3/31/20 Page Unrestricted © Siemens 2016 Page 52 Unrestricted © Siemens 2016 Page 53 53 Page 3/31/20 Page Siemens Digitalization Concept SMART Low Voltage Switchboards Expanding the platform, same great features now available in a switchboard SMART LVS Unrestricted © Siemens 2016 Page 54 SMART SB Switchboards Siemens Digitalization Concept SMART Low Voltage Switchboards New HMI for Switchboards Maintain same offering: WL circuit breakers Power Meters Expand offering: VL electronic circuit breakers 150A-1200A New modular metering system SEM3 Upstream PMCS, DCS, PCS, or SCADA systems HMI PLC Murray Load Centers Low Voltage Power Meter Power breaker Unrestricted © Siemens 2016 Page 55 SEM3 VL Switchboard Branch Circuit Monitoring MCCB (Temp, Humidity, etc.) Low Voltage Arc Resistant Switchgear Unrestricted © Siemens 2016 www.usa.siemens.com/lowvoltage Arc Flash Mitigation –Passive Safety Design Arc Resistant Low Voltage Switchgear UL Listed performance tested and classified as arc resistant in accordance with ANSI C37.20.7-2007 10 ft ceiling height requirement No outside venting is needed in accordance with performance testing. Unrestricted © Siemens 2016 Page 57 Arc Flash Mitigation –Passive Safety Design Room & Personnel Simulation Switchgear Side View Working Space Indicators Unrestricted © Siemens 2016 Page 58 Arc Flash Mitigation –Passive Safety Design Design Enhancements Door Gaskets and Sealing Trims Extra Hinges Thumb Screw latches added One Piece Breaker Door Enhanced SillChannel Unrestricted © Siemens 2016 PagePage 59 FRONT VIEW Arc Flash Mitigation –Passive Safety Design Design Enhancements REAR VIEW Pressure vent in rear top cover Extra bolts and pressure dams in rear covers/doors Rear vent covers extended for vent flaps Extra bolts on end trim sheets Unrestricted © Siemens 2016 PagePage 60 Sill channel with internal plenum for arc venting Arc Resistant Low Voltage Switchgear Design Enhancements Type 2A Unrestricted © Siemens 2016 Page 61 Type 2B Arc Flash Mitigation –Passive Safety Design Optional Plenum Venting Design Front Top Exhaust Unrestricted © Siemens 2016 Page 62 Arc Resistant Low Voltage Switchgear Industry Recognitions • Type 2B Arc Resistant WL Low Voltage Switchgear • Maximum Arcing Short-Circuit Current Rating – 100kA @ 508VAC and 85kA @ 635VAC • Maximum Arcing Short-Circuit Current Rating – 100kA @ 508VAC with Plenum Venting Unrestricted © Siemens 2016 Page 63 • 500 ms arcing duration • Compliant with IEEE C37.20.7 with UL Witnessed • Maximum Amperage – 5000 amps Medium-Voltage Arc-Resistant GM-SG-AR Unrestricted © Siemens 2016 www.usa.siemens.com/mediumvoltage Arc Flash Mitigation –Passive Safety Design Medium Voltage and Systems Air-insulated Switchgear – Type GM-SG-AR IEEE C37.20.7-2007, type 2B 5 kV, 7.2 kV and 15 kV Up to 63KA Circuit breakers up to 3,000 A self-cooled, 4,000 A fan-cooled One- or two-high construction Three-cycle interrupting time (optional) UL or C-UL Listing available Meets ANSI, IEEE and NEMA standards Unrestricted © Siemens 2016 Page 65 GM-SG-AR Arc-Resistant Switchgear Venting of Hot Gases & Arcing Byproducts Arc venting Unrestricted © Siemens 2016 Page 66 GM-SG-AR Arc-Resistant Switchgear Exhaust To Safe Location Shared Plenum SIMOVAC-AR Medium-Voltage Controller, Transition Section & GM-SG-AR Medium-Voltage Switchgear • Exhaust duct (plenum) must be extended to a safe location • Local building codes to define safe location Unrestricted © Siemens 2016 Page 67 Siemens recommendations: • Outside the building • Safe location outside the room • Safe location inside the room & closed to personnel for at least 10’ x 10’ area around outlet Arc Flash Mitigation –Passive Safety Design Medium Voltage and Systems Motor Control – SIMOVAC-AR 2.3 kV to 7.65 kV Ratings NEMA Class E2 controllers Vacuum contactors 400 A and 720 A Optional plug-in contactor (400 A) Up to 3000 A main bus Up to 50 kA NEMA 1, NEMA 1A, NEMA 12 and NEMA 3R Arc resistant type 2B option Wide variety of applications: • Full-voltage non-reversing (FVNR) • Reduced-voltage solid state (SSRV) • Two-speed two-winding (2S2W) • Two-speed one-winding (2S1W) • Reversing Unrestricted © Siemens 2016 Page 68 SIMOVAC-AR arc-resistant SIMOVAC non-arc-resistant Arc Flash Mitigation –Passive Safety Design Medium Voltage and Systems Motor Control – SIMOVAC-AR Arc-Plenum (Exhaust Duct) Exhaust System: Can be connected to front, rear, side or top Exhaust duct required to vent gases outside of the equipment room. Unrestricted © Siemens 2016 Page 69 SIMOVAC-AR arc-resistant PRC Exhaust duct (or plenum) Arc Flash Mitigation –Passive Safety Design Medium Voltage and Systems Motor Control – SIMOVAC-AR Arc-Plenum Exhaust System With GM-SG-AR Arc-Resistant Switchgear: PRCs coordinated between GM-SG-AR and SIMOVAC-AR GM-SG-AR arc-resistant switchgear & SIMOVAC-AR arc-resistant motor control Exhaust duct (or plenum) Single plenum Can be connected to front, rear, side or top GM-SG-AR Exhaust duct required to vent gases outside of equipment room. Transition section SIMOVAC-AR Unrestricted © Siemens 2016 Page 70 Arc Flash Mitigation –Passive Safety Design Medium Voltage and Systems Motor Control – SIMOVAC-AR SIMOVAC-AR With Transition Section To GM-SG-AR Arc-Resistant Switchgear Installed In A Power Equipment Center Common PRC for SIMOVAC-AR and GM-SG-AR & single exhaust duct (plenum) Unrestricted © Siemens 2016 Page 71