TokiLuxTM Series 24 VDC or 24 VAC TOKISTAR LIGHTING

advertisement
T O K I S TA R L I G H T I N G
INSTRUCTION MANUAL
TokiLux Series
24 VDC or 24 VAC
TM
General Description
Tokistar’s TokiLux Series may be operated at 24 VDC or 24 VAC. Light Bars are installed end-to-end
within the TokiLux track. Each Light Bar contains five LEDs and consumes a total of 4 watts. An individual
run length may contain up to 24 Light Bars. Each track is labeled with wattage and operating voltage.
Light Bar
TokiLux Track
Multiple Length Assembly
Any run length exceeding 12 Light Bars will be
supplied as multiple lengths to be joined.
TokiLux Track
Light Bar
Retainer Clips
Maximum Run Length
Maximum 24 Light Bars
PRECAUTIONS
1. Read all instructions completely before beginning installation.
2. Turn off electricity before beginning installation.
3. All wiring is to be performed by a qualified electrician.
4. Installation must comply with the National Electrical Code, and all applicable codes.
5. Turn main supply to the Power Supply on only after all connections have been made and tested.
6. Use only LED Drivers or Transformers provided by Tokistar with the system.
TOKISTAR® LIGHTING
1015 E. Discovery Lane
Anaheim, CA 92801
TEL: 714 772 7005 FAX: 714 772 7014
email: info@tokistar.com Website: tokistar.com
Version 1.3
TokiLux Installation Instructions
Page 2
TM
Connectors
Feed Connector
Part#:TLX-CON
Feed Connectors bring power to one end of a
TokiLux run. Up to 24 Light Bars can be powered
from a single connector.
Flex Connector
Part#: TLX-FLC
Flex Connectors with 2" wires are
used to turn corners and enable
smaller sections of TokiLux to
conform to curves.
Do Not Snap Connectors in place
from above. Slide in place.
Retainer Clips
Retainer clips are included with Feed Connectors, Flex Connectors and fixtures exceeding 12 Light Bars.
These snap onto the fixture to provide a secure connection.
Feed Connector Assembled
A Retainer Clip is required
between the 4th and 5th
LED of the 1st Light Bar
Flex Connector Assembled
Retainer Clip
on Feed Connector
Retainer Clips snap in
place from above.
End Cap
Part #: TLX-ED
End Caps insulate the end
of a run of TokiLux.
Retainer Clips
Mounting Clamp
Part #: TLX-CP
Mounting clamps are attached
with screws and the Tokilux
fixture is snapped in place.
Recommended spacing is
Mounting Clamp
every 12".
TokiLux Installation Instructions
Page 3
TM
Secondary Circuit Wiring
A maximum of 24 Light Bars can be powered on one circuit from the power supply.
Secondary Circuit Limit
Do Not Exceed 4 Amps
(96 watts @ 24 VDC or 24 VAC)
Recommended Lead Wire Size
The distance from the power supply to the fixture, and the load of
the fixture, will determine the proper size of secondary wire. Feed
Connectors are provided with a 6' lead. If additional wire needs to
be attached to the Feed Connector, refer to the recommendations in
this chart.
Additional Secondary Lead
6' Factory Lead
Secondary Lead Wires
Wire Size
Wire Length
#16 AWG
50' (15 M)
#14 AWG
75' (23 M)
#12 AWG
100' (30 M)
#10 AWG
150' (46 M)
Power Supply
Splice
LED Driver Installation
LDR24-4A
This 96 Watt Class 2 LED Driver converts an AC input into a 24 VDC output. Refer to the manual provided
with the LED Driver for detailed installation instructions.
Part#
LDR24-4A
Input Volts
100~277
Output Volts
24 VDC
Output Ratings
1 @ 4 Amps
LDR24-192
Tokistar’s LDR24-192 has two independent 96 watt outputs. If the system is dimmed, each of the outputs
requires an independent dimmer pack. This unit has wiring compartments for splicing on input and output
leads, and can be connected directly to conduit. Refer to the manual provided with the LED Driver for detailed
installation instructions.
Part#
LDR24-192
Input Volts
100~277
Output Volts
24 VDC
Output Ratings
2 @ 4 Amps
TokiLux Installation Instructions
Page 4
TM
LC-1CH-MULTI Dimming System
Dimmer Pack - Part #: LC-1CH-MULTI
Each dimmer pack receives 24 VDC from an LED Driver.
The LDR24-192 LED Driver has two independent 96 watt
outputs. Each output requires an independent dimmer pack.
DMX Mode - Each unit is independently addressable.
Up to 36 dimmer packs may be connected in series. For
applications exceeding 36 dimmer packs, an additional feed
from the DMX dimmer is required. The additional feed(s)
can be sent directly from the dimmer, or you may use DMX
Splitters. Consult factory on details of DMX Splitters.
Analog Modes - For operation from devices using
0/1-10VDC protocol, up to 10 dimmer packs may be connected in series. For applications exceeding 10 dimmer
packs, an additional feed from the analog dimming device
is required.
Manual Mode - You may select a light intensity the fixtures
will operate at. In this case, no external dimming device is
required.
DMX Wiring Diagram
DMX Console
Fixture
Fixture
0-24 VDC
0-24 VDC
Dimmer Pack
Dimmer Pack
LED Driver
24 VDC
24 VDC
DMX Out
DMX In
LED Driver
DMX Out
Analog Dimmer
0/1-10 VDC Wiring Diagram
Fixture
Fixture
Analog Out
Analog Out
0-24 VDC
0-24 VDC
Dimmer Pack
24VDC
For further information, refer to the instruction manual
provided with the LC-1CH-MULTI.
Dimmer Pack
24VDC
LED Driver
LED Driver
Dual output LED drivers require a
dimmer pack for each output.
LC Dimming System
Wall Dimmer - Part #: LC-DMR
Power to the remote wall dimmer is provided from the LED
Driver powering the first Dimmer Pack. A 50 foot CAT5
cable is provided.
Dimmer Pack - Part #: LC-1CH-DP
Each dimmer pack receives 24 VDC from an LED Driver.
A CAT5 cable is provided with each unit. Up to 25 dimmer
packs may be connected in series if the total length of all
CAT5 cable does not exceed 165 feet from the wall dimmer
to the last dimmer pack.
For further information, refer to the instruction manual
provided with the LC-1CH-DP.
PRECAUTION
LC-DMR
Fixture
Fixture
0-24VDC
0-24VDC
Signal Out
Dimmer Pack
24VDC
LED Driver
Signal Out
Dimmer Pack
24VDC
LED Driver
All dimming components are rated for dry location only. They must be installed within an enclosure
suitable for the environment.
TokiLux Installation Instructions
TM
Page 5
24 VAC Magnetic Transformers
TokiLux may also be operated from Tokistar 24 VAC magnetic transformers. Transformers should be installed in an
accessible location. Magnetic transformers generate heat and must be installed in locations where there is free-air
circulation. Refer to the manual provided with the transformer for detailed installation instructions.
Dimming
Although Tokistar Transformers are fully dimmable on the primary input with phase control/triac dimming systems,
they may not show favorable results at all dim levels. Optimum dimming results are achieved with our 24 VDC Drivers
and our pulse-width modulation (PWM) dimming devices installed on the secondary output of drivers.
PRECAUTIONS
Do Not Exceed 4 Amps Per Circuit.
TOKISTAR® LIGHTING
1015 E. Discovery Lane
Anaheim, CA 92801
TEL: 714 772 7005 FAX: 714 772 7014
email: info@tokistar.com Website: tokistar.com
Version 1.3
Download