TR ANSFORMER-BASED CENTR AL INVERTERS Product Name TR ANSFORMERLESS CENTR AL Inverters AE 35TX AE 50TX AE 75TX AE 100TX AE 250TX AE 260TX AE 500TX AE 250NX AE 333NX AE 500NX AE 500NX-HE AE 500NX-1kV AE 1000NX Continuous Output Power 35 kW 50 kW 75 kW 100 kW 249.5 kW 260 kW 500 kW 250 kW 333 kW 500 kW 500 kW 500 kW 1000 kW Weighted CEC Efficiency 95.5% (208 V) 96.0% (480 V) 95.5% (600 V) 96.0% (208 V) 96.0% (480 V) 96.0% (600 V) 95.5% (208 V) 95.5% (480 V) 96.0% (600 V) 95.5% (208 V) 96.0% (480 V) 96.0% (600 V) 96.5% (480 V) 96.5% (600 V) 97.0% 97.0% 97.5% 97.5% 97.5% 97.5% 97.5% (preliminary) Peak Efficiency 96.2% (208 V) 97.0% (480 V) 96.4% (600 V) 96.7% (208 V) 97.2% (480 V) 96.6% (600 V) 96.1% (208 V) 96.6% (480 V) 96.5% (600 V) 96.4% (208 V) 97.1% (480 V) 96.4% (600 V) 97.7% 97.7% 97.8% 98.1% 98.3% 98.6% 98.7% 98.0% 98% (preliminary) DC Max Input Voltage 600 VDC 600 VDC 600 VDC 600 VDC 600 VDC 600 VDC 600 VDC ± 600 VDC ± 600 VDC ± 600 VDC ± 600 VDC 1000 VDC ± 1000 VDC DC Voltage Operating Range 295 to 595 VDC 295 to 595 VDC 295 to 595 VDC 295 to 595 VDC 295 to 595 VDC 295 to 595 VDC 310 to 595 VDC ± 330 to ± 600 VDC ± 330 to ± 600 VDC ± 330 to ± 600 VDC ± 330 to ± 600 VDC 600 to 1000 VDC (± 300 to ± 500 VDC) ± 550 to ± 1000 VDC DC Max Operating Input Current 125 A 178 A 267 A 356 A 890 A 925 A 1600 A 375 A Imp, self limiting in operation 500 A Imp, self limiting in operation 750 A Imp, self limiting in operation 750 A Imp, self limiting in operation 850 A Imp, self limiting in operation 956 ADC Imp maximum, self limiting in operation AC Nominal Voltage 208 VAC 480 VAC 600 VAC 208 VAC 480 VAC 600 VAC 208 VAC 480 VAC 600 VAC 208 VAC 480 VAC 600 VAC 480 VAC 600 VAC 480 VAC 480 VAC 480 VAC 480 VAC 480 VAC 480 VAC 420 VAC 800 VAC ± 10% Phase Supply 3Φ 3Φ 3Φ 3Φ 3Φ 3Φ 3Φ 3Φ 3Φ 3Φ 3Φ 3Φ 3Φ Grid Frequency 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz AC Max Output Current 100 A (208 V) 43 A (480 V) 35 A (600 V) 141 A (208 V) 61 A (480 V) 49 A (600 V) 208 A (208 V) 91 A (480 V) 72 A (600 V) 278 A (208 V) 120 A (480 V) 96 A (600 V) 304 A (480 V) 243 A (600 V) 316 A 608 A 334 A (field adjustable) 445 A (field adjustable) 667 A (field adjustable) 667 A (field adjustable) 700 A 800 A Inverter Direct Data Monitoring Included Included Included Included Included Included Included Included Included Included Included Included Included Outdoor-Rated Enclosure NEMA 4 NEMA 4 NEMA 4 NEMA 4 NEMA 4 NEMA 4 NEMA 4 NEMA 3R with sealed electronics cabinet NEMA 3R with sealed electronics cabinet NEMA 3R with sealed electronics cabinet NEMA 3R with sealed electronics cabinet NEMA 3R with sealed electronics cabinet NEMA 3R with sealed electronics cabinet Dimensions with Integrated Disconnect (H x W x D ) 67 x 48.8 x 29.5 in (170 x 124 x 75 cm) 73.6 x 48.8 x 34.5 in (187 x 124 x 88 cm) 91.6 x 65.6 x 35.0 in (233 x 167 x 89 cm) 91.6 x 65.6 x 35.0 in (233 x 167 x 89 cm) 93.0 x 104.0 x 41.4 in (236 x 264 x 105 cm) 93.0 x 104.0 x 41.4 in (236 x 264 x 105 cm) 99.2 x 119.8 x 48.8 in (251.8 x 304.2 x 124 cm) 81.2 x 73.3 x 33.9 in (206.4 x 188.2 x 86.2 cm) 81.2 x 73.3 x 33.9 in (206.4 x 188.2 x 86.2 cm) 83.0 x 89.4 x 39.8 in (210.8 x 227 x 202.6 cm) 83.0 x 89.4 x 39.8 in (210.8 x 227 x 202.6 cm) 83.0 x 128.1 x 41.3 in (210.8 x 325.4 x 104.9 cm) 90.0 x 174.0 x 41.6 in (229 x 442 x 106 cm) Standard Warranty 10 Year 10 Year 10 Year 10 Year 10 Year 10 Year 10 Year 5 Year 5 Year 5 Year 5 Year 5 Year 5 years 20 Year Extended Warranty Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional Sub-Combiner Optional (fuse) Optional (fuse) Optional (fuse) Optional (fuse) Optional (fuse or breaker) Optional (fuse or breaker) Optional (breakers) – – Optional Optional Optional – Installation Mounting Type Pad or skid-mounted Pad or skid-mounted Pad or skid-mounted Pad or skid-mounted Pad or skid-mounted Pad or skid-mounted Pad or skid-mounted Pad or skid-mounted Pad or skid-mounted Pad or skid-mounted Pad or skid-mounted Pad or skid-mounted Pad or skid-mounted Unit Weight 1200 lb (544 kg) 1500 lb (680 kg) 2750 lb (1247 kg) 3000 lb (1361 kg) 5000 lb (2268 kg) 5000 lb (2268 kg) 8750 lb (3969 kg) 2045 lb (927.5 kg) 2045 lb (927.5 kg) 3760 lb (1705.5 kg) 3760 lb (1705.5 kg) 3600 lb (1633 kg) 5300 lb (2404 kg) Cooling System Forced convection Forced convection Forced convection Forced convection Forced convection Forced convection Forced Convection Combo air and liquid (selfcontained system) Combo air and liquid (self-contained system) Combo air and liquid (self-contained system) Combo air and liquid (self-contained system) Combo air and liquid (self-contained system) Combo air and liquid (self contained system) Operating Temperature Range -22 °F to 122 °F (-30 °C to 50 °C) -22 °F to 122 °F (-30 °C to 50 °C) -22 °F to 122 °F (-30 °C to 50 °C) -22 °F to 122 °F (-30 °C to 50 °C) -22 °F to 122 °F (-30 °C to 50 °C) -22 °F to 122 °F (-30 °C to 50 °C) -22 °F to 131 °F (-30 °C to 55 °C) -4 °F to 122 °F (-20 °C to 50 °C) -4 °F to 122 °F (-20 °C to 50 °C) -4 °F to 122 °F (-20 °C to 50 °C) Cold weather option to -31 °F (-35 °C) -4 °F to 122 °F (-20 °C to 50 °C) Cold weather option to -31 °F (-35 °C) -4 °F to 122 °F (-20 °C to 50 °C) -4 °F to 122 °F (-20 °C to 50 °C) Storage Temperature Range -40 ªF to 140 ªF (-40 ªC to 60 ªC) -40 ªF to 140 ªF (-40 ªC to 60 ªC) -40 ªF to 140 ªF (-40 ªC to 60 ªC) -40 ªF to 140 ªF (-40 ªC to 60 ªC) -40 ªF to 140 ªF (-40 ªC to 60 ªC) -40 ªF to 140 ªF (-40 ªC to 60 ªC) -40 ªF to 140 ªF (-40 ªC to 60 ªC) -22 ªF to 158 ªF (-30 ªC to 70 ªC) -2 2ªF to 158 ªF (-30 ªC to 70 ªC) -22 ªF to 158 ªF (-30 ªC to 70 ªC) -22 ªF to 158 ªF (-30 ªC to 70 ªC) -22 ªF to 158 ªF (-30 °C to 70 °C) -22 °F to 158 °F (-30 °C to 70 °C) Compliance UL 1741 IEEE 1547 UL 1741 IEEE 1547 UL 1741 IEEE 1547 UL 1741 IEEE 1547 UL 1741 IEEE 1547 UL 1741 IEEE 1547 UL 1741 IEEE 1547 UL 1741 IEEE 1547 UL 1741 IEEE 1547 UL 1741 IEEE 1547 UL 1741 IEEE 1547 UL 1741 † Pending UL 1741 98.0% † UL 1741-2010, though not all utility interactive controls are included in the listing. AE Solar Energy Services Leverage AE’s decades of worldwide service experience to ensure optimal LCOE performance for the next 20+ years. Proven Performance World Class Inverter Support PV System Lifecycle Services Decades supporting mission-critical components in semiconductor, solar, and flat panel display industries Precise, scheduled maintenance and advanced service programs for higher system performance Whole-site O&M agreements to help lower LCOE • Helpful and responsive technical phone support • Global footprint • Dedicated AE Staff • Proven MTTR Performance •SafeGuard ® Ensure inverter reliability through product life •SafeGuard ® Plus Ensure higher level of service for maximum inverter uptime Uptime guarantees and warranties from 5-20 years SM •SiteGuard ® O&M Rely on one source to simplify site operations • Performance Optimization • System Design Expertise • Commissioning Support AE Solar Energy products built in Ontario meet the requirement for local content by the Ontario government's feed-in-tariff (FiT) program under the Green Energy Act. Specifications subject to change without notice. Contact Advanced Energy for specifications in your region. AE Solar Energy 115 Nicholson Lane San Jose, CA 95134 877.312.3832 www.advanced-energy.com/solarenergy sales.support@aei.com invertersupport@aei.com Please see www.advanced-energy.com for worldwide contact information © Advanced Energy Industries, Inc. 2013 All rights reserved. Printed in U.S.A. ENG-ProductPoster-200-07 6/13 PowerStation™, SafeGuard ® and SiteGuard ® are U.S. trademarks of Advanced Energy Industries, Inc. SafeGuard ® Plus is a U.S. service mark of Advanced Energy Industries, Inc. STRING Inverters Product Name AE 3TL-12kW about ae solar energy integrated solutions AE 3TL-16kW AE 3TL-20kW AE 3TL-24kW AE PowerStation™ TX* AE PowerStation™ NX* AE Solar Energy - An Industry Leader You Can Bank On For over 30 years, AESE has delivered outstanding power conversion products and a Continuous Output Power 12 kW 16 kW 20 kW 23.2 kW TX: Configurable up to 1040 kW NX: Configurable up to 2 MW Weighted CEC Efficiency 97.5% 97.5% 97.5% 98.0% Up to 97.0%, excluding MV transformer 97.5%, excluding MV transformer projects, maximize their financial return, and grow their businesses. With our rich Peak Efficiency 98.2% 98.2% 98.2% 98.2% Up to 97.8%, excluding MV transformer Up to 98.6%, excluding MV transformer heritage of leadership in inverter technology, we’re deeply rooted in the international DC Max Input Voltage 500 V 500 V 500 V 500 V 600 VDC ± 600 VDC / 1000 VDC DC Voltage Operating Range 125 to 450 VDC 125 to 450 VDC 125 to 450 VDC 125 to 450 VDC 295 to 595 VDC ± 330 to ± 600 VDC DC Max Operating Input Current 2 X 27.5 A 2 X 33 A 2 X 37.5 A 2 X 40 A 295 / 310 to 595 VDC See inverter information AC Nominal Voltage 480 V 480 V 480 V 480 V Up to 38 kV Up to 38 kV Phase Supply 3Φ 3Φ 3Φ 3Φ 3Φ 3Φ Grid Frequency 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz AC Max Output Current 14.5 A 19.35 A 24.1 A 27.9 A 47 A @ 12.47 kV 51 A @ 12.47 kV Inverter Direct Data Monitoring Included Included Included Included Included Included NEMA 4 NEMA 3R with sealed electronics cabinet - SafeGuard® PM Services • BALANCE OF SYSTEM SOLUTIONS Outdoor-Rated Enclosure solutions oriented approach for our customers, enabling them to secure more solar solar community and combine extensive industry-wide expertise with in-depth local knowledge to provide efficient and effective solutions – backed up by outstanding support and consulting services. Whatever size and project requirement, we've got the inverter and energy management solution you need: • AE TL STRING INVERTERS - Transformerless three-phase string inverters • AE TX INVERTERS - Transformer based central inverters • AE NX INVERTERS - Transformerless bipolar inverters • AE SOLAR ENERGY SERVICES - Installation and PV system commissioning NEMA 3R/4 NEMA 3R/4 NEMA 3R/4 NEMA 3R/4 - SiteGuard® O&M Services Dimensions with Integrated Disconnect (H x W x D ) 35 X 21 X 11 in (895 x 535 x 280 mm) 35 X 21 X 11 in (895 x 535 x 280 mm) 35 X 21 X 11 in (895 x 535 x 280 mm) 35 X 21 X 11 in (895 x 535 x 280 mm) 119 x 368 x 148 in (302 x 934 x 376 cm) Open Station: 91 x 282 x 137 in (231.1 x 716.3 x 348 cm) Standard Warranty 5 Year 5 Year 5 Year 5 Year PowerStation TX: 1 year Inverter: 10 year PowerStation NX: 1 year Inverter: 5 year - Combiner level PV Tie (CPT) 20 Year Extended Warranty Optional Optional Optional Optional Optional Optional - Turn-key PowerStation Solutions Sub-Combiner Fusing Yes Yes Yes Yes Optional Optional • ADVANCED UTILITY CONTROLS Installation Mounting Type Wall or Pole Mount Wall or Pole Mount Wall or Pole Mount Wall or Pole Mount Pad or pier-mounted Pad or pier-mounted Open 1 MW PowerStation: Approx. 41,000 lb (18,600 kg) Open 2 MW PowerStation: Approx. 48,000 lb (21,772 kg) Enclosed 1 MW PowerStation: Approx. 47,000 lb (21,318 kg) Enclosed 2 MW PowerStation: Approx. 57,000 lb (25,854 kg) Unit Weight 108 lb (49 kg) 108 lb (49 kg) 108 lb (49 kg) 108 lb (49 kg) - Inverter Integrated subcombiners, DC breakers, subarray monitoring and AC/DC switchgear cabinets - Remote PV Tie (RPT) - Utility Interactive Controls Monitoring Solutions • Inverter Direct Data Monitoring • Premium Integrated Data Monitoring Cooling System Passive Passive Passive Passive Forced convection – Operating Temperature Range -13 °F to 131 °F (-25 °C to 55 °C) -13 °F to 131 °F (-25 °C to 55 °C) -13 °F to 131 °F (-25 °C to 55 °C) -13 °F to 131 °F (-25 °C to 55 °C) -22 °F to 131 °F (-30 °C to 55 °C) -4 °F to 122 °F (-20 °C to 50 °C) Cold weather option to -31 °F (-35 °C) Storage Temperature Range -13 °F to 158 °F (-25 °C to 70 °C) -13 °F to 158 °F (-25 °C to 70 °C) -13 °F to 158 °F (-25 °C to 70 °C) -13 °F to 158 °F (-25 °C to 70 °C) -40 ªF to 140 ªF (-40 °C to 60 °C) -22 ªF to 158 ªF (-30 °C to 70 °C) Compliance UL 1741 UL 1741 UL 1741 UL 1741 Refer to equipment specs for individual component compliance Refer to equipment specs for individual component compliance *PowerStations are custom configurable. Contact AE Sales to verify specifications. AE Solar Energy Services Leverage AE’s decades of worldwide service experience to ensure optimal LCOE performance for the next 20+ years. Proven Performance World Class Inverter Support PV System Lifecycle Services Decades supporting mission-critical components in semiconductor, solar, and flat panel display industries Precise, scheduled maintenance and advanced service programs for higher system performance Whole-site O&M agreements to help lower LCOE • Helpful and responsive technical phone support • Global footprint • Dedicated AE Staff • Proven MTTR Performance •SafeGuard ® Ensure inverter reliability through product life •SafeGuard ® Plus Ensure higher level of service for maximum inverter uptime Uptime guarantees and warranties from 5-20 years SM •SiteGuard ® O&M Rely on one source to simplify site operations • Performance Optimization • System Design Expertise • Commissioning Support AE Solar Energy products built in Ontario meet the requirement for local content by the Ontario government's feed-in-tariff (FiT) program under the Green Energy Act. Specifications subject to change without notice. Contact Advanced Energy for specifications in your region. AE Solar Energy 115 Nicholson Lane San Jose, CA 95134 877.312.3832 www.advanced-energy.com/solarenergy sales.support@aei.com invertersupport@aei.com Please see www.advanced-energy.com for worldwide contact information © Advanced Energy Industries, Inc. 2013 All rights reserved. Printed in U.S.A. ENG-ProductPoster-200-07 6/13 PowerStation™, SafeGuard ® and SiteGuard ® are U.S. trademarks of Advanced Energy Industries, Inc. SafeGuard ® Plus is a U.S. service mark of Advanced Energy Industries, Inc.