Compact Fire Pump Systems

advertisement
Compact Fire Pump Systems
At the heart of our systems you’ll find the
Aurora pumps you’ve relied on for over 80 years.
Aurora offers a complete system that has a small footprint and is ideal
for buildings with limited space. This built to order and pre-engineered
system is factory assembled and tested. Ready to set: only unit base
grouting, pipe and power connections need to be completed on site.
SYSTEM INCLUDES
n UL listed/FM approved Aurora fire pump
n Casing pressure relief valve
n UL listed/FM approved fire pump controller
n Hose header with valves, caps & chains
n Aurora jockey pump
n Suction and discharge piping per NFPA 20
n UL listed jockey pump controller
n All electrical components pre-wired at factory
n Pressure sensing lines complete per NFPA 20
n Complete system hydrostatically tested
n Listed OS & Y gate & butterfly valves
n All components are factory choice
n Suction and discharge pressure gauges
SYSTEM FEATURES
n Fits through a 36” doorway
n Capacities of 50-750 GPM
n ETL Listed System
n Pressures of 40-160 PSI
n Built to NFPA-20, NFPA-70 and NEC Standards
AVAILABLE OPTIONS
n Automatic Air Release Valve
n Transfer Switch
OPTIONAL
GPM
50
PSI
75 - 155
MODEL
2-383-9C
HP
10 - 25
100
43 - 70
3-383-7A
7.5 - 15
70 - 150
2-383-9C
10 - 25
41 - 60
3-383-7A
7.5 - 10
60 - 160
3-383-9A
15 - 50
40 - 55
3-383-7A
7.5 - 15
56 - 159
3-383-9A
15 - 50
40 - 65
3-383-7B
15 - 20
70 - 138
3-383-9
20 - 50
42 - 73
4-383-7B
15 - 30
74 - 90
4-383-9B
25 - 30
91 - 139
4-383-9
30 - 60
51 - 71
4-383-7B
20 - 30
70 - 85
4-383-9B
25 - 30
85 - 136
4-383-9
30 - 60
49 - 72
4-383-7B
20 - 30
82 - 135
4-383-9
30 - 60
96 - 131
4-383-9B
40 - 60
55 - 71
4-383-7B
25 - 30
72 - 92
4-383-9C
30 - 50
94 - 130
4-383-9B
40 - 60
54 - 84
4-383-13
40 - 75
86 - 143
4-383-10B
60 - 100
150
200
250
300
400
450
500
750
HB
66
(1676)
64
(1626)
66
(1676)
64
(1626)
72
(1829)
64
(1626)
72
(1829)
72
(1829)
72
(1829)
72
(1829)
72
(1829)
72
(1829)
72
(1829)
72
(1829)
72
(1829)
84
(2134)
72
(1829)
72
(1829)
84
(2134)
72
(1829)
72
(1829)
84
(2134)
84
(2134)
HF
64
(1626)
62
(1575)
64
(1626)
62
(1575)
70
(1778)
62
(1575)
70
(1778)
70
(1778)
70
(1778)
70
(1778)
70
(1778)
70
(1778)
70
(1778)
70
(1778)
70
(1778)
82
(2083)
70
(1778)
70
(1778)
82
(2083)
70
(1778)
70
(1778)
82
(2083)
82
(2083)
HD
13.25
(337)
14.25
(362)
13.25
(337)
14.25
(362)
14.25
(362)
14.25
(362)
14.25
(362)
14.25
(362)
13.88
(353)
15.25
(387)
15.00
(381)
15.00
(381)
15.25
(387)
15.00
(381)
15.00
(381)
15.25
(387)
15.00
(381)
15.00
(381)
15.25
(387)
15.00
(381)
15.00
(381)
17.81
(452)
17.06
(433)
HS
13.25
(337)
14.25
(362)
13.25
(337)
14.25
(362)
14.25
(362)
14.25
(362)
14.25
(362)
13.75
(349)
13.88
(353)
15.25
(387)
15.00
(381)
15.00
(381)
15.25
(387)
15.00
(381)
15.00
(381)
14.75
(375)
15.00
(381)
15.00
(381)
14.75
(375)
15.00
(381)
15.00
(381)
17.81
(452)
17.06
(433)
W
28.25
(718)
28.25
(718)
28.25
(718)
28.25
(718)
28.75
(730)
28.25
(718)
28.75
(730)
28.25
(718)
28.75
(730)
29.25
(743)
29.25
(743)
29.25
(743)
29.25
(743)
29.25
(743)
29.25
(743)
29.25
(743)
29.25
(743)
29.25
(743)
29.25
(743)
29.50
(749)
29.25
(743)
32.50
(826)
30.50
(775)
CP
65.75
(1670)
67.25
(1708)
65.75
(1670)
67.25
(1708)
70.25
(1784)
67.25
(1708)
70.25
(1784)
75.50
(1918)
71.25
(1810)
73.50
(1867)
74.50
(1892)
74.50
(1892)
73.50
(1867)
74.50
(1892)
74.50
(1892)
89.25
(2267)
81.00
(2057)
81.00
(2057)
89.25
(2267)
81.00
(2057)
81.00
(2057)
93.50
(2375)
89.50
(2273)
NOTES:
1. All dimensions are in inches(mm) and may vary ±3/8” (10).
2. Not for construction purposes, unless certified.
3. System suction and discharge flanges are ANSI class 125
flat face.
4. Refer to selection tables in section 911 for selection of
pump sizes and motor horsepower for specific applications.
5. Standard controller is across-the-line. Refer to factory for
the availability of optional controller starting methods.
6. Dimensions and specifications subject to change without
notice.
FIRE PUMP SPEC
JOCKEY PUMP CONTROLLER
FIRE PUMP
A Metron model_________ UL listed, jockey pump controller
The pump shall be an Aurora model 383 vertical in-line centrifugal
shall be supplied. The jockey pump controller shall come complete
pump. The pump shall be rated for ________GPM @ _______PSI. with a fusible disconnect, prepiped pressure switch, front mounted
The pump shall be listed by the Underwriters' Laboratory and/or be hand-off-auto selector switch and overload relays. The controller
approved by Factory Mutual. The pump shall have a bronze impeller, enclosure shall be of Nema 2 type.
bronze case wear ring, packing gland and shaft sleeve. The pump
shall deliver no less than 65% of rated pressure at 150% of rated flow. ACCESSORIES
Systems shall include:
The shut-off pressure shall not exceed 140% of rated pressure.
• Suction and discharge pressure gauges on fire pump.
ELECTRIC DRIVER
• Isolating gate valve at suction for both fire pump and jockey pump.
The motor shall be listed by Underwriters' Laboratories and have a
• Isolation valve at discharge for both fire pump and jockey pump.
maximum of ___horsepower, 3-phase, ______hertz, ______volts. • Discharge check valve for fire pump and jockey pump.
It shall be open drip proof with a 1.15 service factor and shall
comply with the provisions of N.F.P.A 70, National Electric Code as
FACTORY PREFABRICATION AND TESTING
described in N.F.P.A 20.
All of the above equipment (except the test header and hose valves)
shall be mounted on a common base. All pipes, piping components,
CONTROLLER
and the pressure sensing lines shall be firmly anchored to the steel
The motor controller shall be a Metron model _____, listed by
base by means of structural steel supports. All electrical wiring
Underwriters Laboratories and approved by Factory Mutual for fire
between controllers and motors shall be completed and tested at the
pump service. It shall be compatible with the motor horsepower and factory. The entire packaged system will be hydrostatically tested at
voltage. It shall be of the full voltage type with a withstand rating of the factory prior to shipment. Additionally, all equipment will be tested
________42 AIC RMS symmetrical. The controller enclosure shall in accordance with the requirements of NFPA 20, U.L. and F.M.
be of Nema 2 type. The controller shall be completely assembled,
wired and tested prior to shipment.
NOTE: Aurora Pump reserves the right to make revisions to its products and their specifications, and to this bulletin and related information, without notice.
— Your Authorized Local Distributor —
AURORA PUMPS ARE
R
LISTED
FM
APPROVED
MARKETING & SALES:
800 AIRPORT ROAD • NORTH AURORA, ILLINOIS U.S.A. • 60542
PHONE: (630) 859-7000 U.S.A./CANADA FAX: (630) 859-7060
WORLDWIDE FAX: (630) 859-1226
AURORA MFG. PLANT:
800 AIRPORT ROAD • NORTH AURORA, ILLINOIS U.S.A. • 60542
SALES OFFICES IN ALL MAJOR CITIES AND COUNTRIES
Refer to “Pumps” in yellow pages of your phone directory
for your local Distributor
PRINTED IN U.S.A.
JOCKEY PUMP
The jockey pump shall be an Aurora model________, size_______.
The pump shall be rated for_______GPM @ _________PSI.
The jockey pump will be close coupled to a ODP motor. The motor
will operate at ________HP, ______RPM,________v,
_______Hertz.
AP-CFPS 10/06
The contractor shall provide and install an Aurora model 383 packaged
fire pump system designed in accordance with NFPA 20. The system
shall be rated for a flow of ________GPM @ ______PSIG.
The system shall be mounted on a common base plate and include
all necessary components such that the customer only needs to run
piping to and from the system and connect incoming power. The
packaged fire pump system shall include the following equipment:
Download