Electric Service and Metering Manual, Book 1

advertisement
TABLE OF CONTENTS
General:
Table of Contents/Introduction ............................................................................. G-1
Phone Numbers for We Energies ........................................................................ G-2
General Information/New Services ....................................................................... G-3
Secondary Voltages ............................................................................................. G-4
One Call Numbers for Location of Utility Facilities ............................................... G-4
Overhead Services - Secondary .............................................................................. O-1 to O-18
Underground Services - Secondary ........................................................................ U-1 to U-33
Metering - Secondary ................................................................................................. M-1 to M-26
Appendix - Choosing The Proper Meter Socket ...................................................... i to ii
Meter Mounting Devices - Book 2............................................................................. D-1 to D-21
INTRODUCTION
The purpose of this manual is to supply essential information to customers, contractors, builders,
architects, engineers, and others concerned with the planning of electrical installations.
All information given in this manual is to be used in conjunction with the Company's Electric Service
Rules and Regulations, on file with the Public Service Commissions of Wisconsin and Michigan. In
issuing this manual, the Company is in no way relieving the customer or contractor of his or her
responsibility to install the wiring in accordance with the applicable Wisconsin or Michigan State
Electrical Codes, as well as local ordinances, or to maintain the wiring and equipment in a safe
operating condition. The Company cannot accept any responsibility for the condition of the
customer's wiring and equipment.
The information contained herein is general and may not cover all conditions. For new or
special cases not specifically covered in this manual, the Company should be consulted.
This edition of the Electric Service and Metering Manual supersedes any and all previous editions.
HOW TO USE THIS MANUAL
This Manual is broken into five main sections. Each section has a Table of Contents and General
Requirements that apply to that section.




The section you are reading is the G (General) Section, which has the main Table of Contents,
phone numbers for We Energies, and provides general information.
Sections O & U (Overhead & Underground) provide the installation details of the equipment for
overhead and underground services respectively. They show the equipment layout, critical
dimensions and service drop or lateral terminations.
The M (Metering) Section should then be consulted for the wiring of the service equipment. This
section is organized by type of service, overhead or underground, 1Ø or 3Ø, and ampacity. The
metering sequence to be followed is given after the title block. This section references pages in
the D Section for that specific metering installation.
The D (Devices) Section lists all the approved termination and metering equipment and is
arranged similar to the M Section. Only equipment listed in the D Section is to be used.
G-1
WE ENERGIES SERVICE CENTER DIRECTORY
Winnebago Service Center
800 S. Lynndale Dr.
Appleton, WI 54914 or
P.O. Box 1699
Appleton, WI 54912
(920) 380-3490 or
1-800-972-8856
Fax: (920) 380-3507 or
1-800-932-6227
KR Service Center
201 First St. (CTH KR)
Racine, WI 53403
(262) 552-7500 or
1-800-223-3446
Fax: (262) 552-3460
Port Washington Service Center
700 Sunset Rd
Port Washington, WI 53074
(262) 268-3600 or
1-800-498-5111
Fax: (262) 268-3628
Burlington Service Center
700 S. Kane St.
Burlington, WI 53105
(262) 763-1099 or
1-800-558-3396
Fax: (262) 763-1077
Menomonee Falls Service Center
W140 N9100 Lilly Rd.
Menomonee Falls, WI 53051
(262) 253-4520 or
1-800-281-3888
Fax: (262) 253-4561
Watertown Service Center
315 William St
Watertown, WI 53094
(920) 261-6010 or
1-800-842-7628
Fax: (920) 262-6814
Delafield Service Center
S13 W33800 Highway 18
Delafield, WI 53018
(262) 968-2575 or
1-800-564-9113
Fax: (262) 968-5714
Metro North Service Center
3100 W. North Ave.
Milwaukee, WI 53208
(414) 449-3002 or
1-877-621-9140
Fax: (414) 449-3075
Waukesha Service Center
1830 S. West Ave
Waukesha, WI 53189
(262) 549-1100 or
1-800-878-8439
Fax: (262) 574-3109
Fort Atkinson Service Center
1300 Janesville Ave.
Fort Atkinson, WI 53538
(920) 563-2441 or
1-800-842-0813
Fax: (920) 563-1281
Metro South Service Center
500 S. 116th Street
West Allis, WI 53214
(414) 944-5772
Fax: (414) 944-5773
West Bend Service Center
245 Sand Drive
West Bend, WI 53095
(262) 338-7600 or
1-800-268-2060
Fax: (262) 338-7646
Headwaters Service Center
4222 County Road B
Land O' Lakes, WI 54540-9987
1-800-562-1050
Fax: (906) 779-2473
Oakbrook Service Center
4800 W. Rawson Ave
Franklin, WI 53132
(414) 423-6100 or
1-800-757-3777
Fax: (414) 423-5060
Wolverine Service Center
800 Industrial Park Dr.
Iron Mountain, MI 49801
(906) 779-2400 or
1-800-562-1050
Fax: (906) 779-2466
CUSTOMER CONTACT CENTER
● To Energize or De-energize a Service
● To Request Meter or Service Drop Removal
● To Apply for New Service or Rewiring
EMERGENCY SERVICE/LIGHTS OUT
1-800-662-4797
TO REPORT GAS LEAKS/GAS HAZARDS
1-800-261-5325
G-2
Phone ………………………..1-800-242-9137
Fax …………………………..1-800-354-3585
GENERAL INFORMATION
1. Unless otherwise indicated, all items shown on the sketches are to be furnished and installed by the
customer.
2. Meters and current transformers will be furnished and maintained by We Energies.
3. Only meter mounting devices and service termination equipment listed in Section D of this manual are
to be used. The listing of equipment in this manual is not an endorsement or indication of suitability, but
only that it is acceptable for installation of our metering equipment and termination of our service lateral
conductors as required. It is the responsibility of the customer or their electrical contractor to verify that
the equipment is suitable for the installation and that it is installed in accordance with all applicable codes.
4. Application of these standards must be made in accordance with the Company's Electric Service Rules
and Regulations.
5. Electrical contractors are expected to acquaint themselves with the plans of other trades on the premises
being wired so that the meter can be located in accordance with the requirements set forth in this manual.
6. For all new and rewired, one or two family, single-phase residential services rated at 200 amperes or less,
We Energies will not provide an outlet location letter with a Guaranteed Available Short Circuit Current
(GASCC) or service equipment location sketch. The customer and/or the electrical contractor
will be responsible for ensuring outlet locations and service entrance facilities comply with requirements
specified in this manual and in accordance with the applicable Wisconsin or Michigan State Electrical
Codes and local ordinances. A GASCC value of 10,000 amps is to be used for these services only.
7. Accepted service entrance cable may be used where permitted by the applicable Wisconsin or Michigan
State Electrical Codes and Local Ordinances.
8. Transfer equipment used with stand-by power plants or generators shall be suitable for intended use and
be so designed and installed as to prevent the inadvertent interconnection of normal and stand-by sources
of supply in any operation of the transfer equipment. Further, transfer equipment shall be installed such
that it is located electrically on the load side of the meter. All transfer schemes shall be submitted to the
local Company office for acceptance before installation.
9. The use of approved material, tested and listed by a nationally recognized testing laboratory, and approved
methods of installation are requirements of the Wisconsin State Electrical Code by the Wisconsin State
Electrical Code Section of the Department of Commerce, and by OSHA for employers, for customer owned
electrical service equipment.
10. This manual only covers secondary services. For Primary Services refer to the Electric Service and
Metering Manual Addendum Primary Rate Requirements for Customer Substations.
NEW SERVICES
1. Before any new electric service can be installed and energized :
 The electrical contractor, building owner or general contractor must be on site to take
responsibility for the newly energized service.
 Or We Energies crews must have safe access to the service’s main disconnect.
Please Note that these requirements are in addition to requirements or contingencies such as, but not
limited to, the City OK from the Local Municipal Electrical Inspector (or Affidavit in areas where they are
used in place of the City OK), grading, permits and payment of any charges.
2. If the above conditions are not met or the service is deemed unsafe the service lateral may be installed,
but the service will not be energized. Our crew will leave a tag on site with a telephone number to call to
arrange to have the service energized after the reason(s) for not energizing the service have been
corrected.
3. If a service is energized and there is no one on site authorized to take responsibility, the main disconnect
will be left in the off position and tagged to indicate that the electric service is energized.
G-3
SECONDARY VOLTAGES
The following secondary voltages are generally available from We Energies. It must be noted that all voltages
and ampacities may not be available in all areas. There may be a charge to extend the necessary facilities to
the customer. For some classes of service, especially three phase, availability is also dependent upon the
customer’s connected load. The local office must be contacted for cost and availability of service.
• 120 Volt, 1Ø, 2-Wire ..........................................................
30 Amperes maximum
• 120/240 Volt, 1Ø, 3-Wire ................................................... 800 Amperes maximum
• 208Y/120 Volt, 3Ø, 4-Wire, grounded-wye ........................ 4000 Amperes maximum
• 480Y/277 Volt, 3Ø, 4-Wire, grounded-wye ........................ 4000 Amperes maximum
• 208Y/120 Volt, 1Ø, 3-Wire Service .................................... 100 Amperes/Position maximum
(limited availability)
• 2400 Volt, 3Ø, 3-Wire Service ........................................... 800 kW load maximum
(generally used for municipal wells, contact
local office for requirements)
Secondary voltages no longer provided as new services:
• 240 Volt, 3Ø, 3-Wire Service, Grounded B Phase
• 480 Volt, 3Ø, 3-Wire Service
For services greater than 2000 Amperes and for services using 100% rated Breakers, the Percent Load Factor
needs to be calculated as follows:
% Load Factor 
Average Load of Daily Cycle
x 100
Daily Maximum 1 Hour Average
Where: The “Average Load of Daily Cycle” is equal to the sum of the average hourly current (in amperes) in a
24 hour period divided by 24.
The “Daily Maximum 1 Hour Average” is equal to the highest average hourly current (in amperes).
Once the % Load Factor has been determined, provide the % Load Factor with your service application.
ONE-CALL CENTERS FOR LOCATION OF UTILITY FACILITIES
1
1.
2.
3.
4.
5.
WISCONSIN - DIGGERS HOTLINE
Phone numbers include: From Milwaukee area
(414) 259-1181
Toll-free . . . . . . . . . . 1-800-242-8511 or 811
TTY . . . . . . . . . . . . . . 1-800-542-2289
All types of requests are accepted 24 hours a day, 7 days a week, 365 days a year.
Wisconsin law requires that a minimum of three working days notice be given for any excavation other than
emergencies.
Will accept calls for emergencies, planned excavation, planning information, appointments and overhead
information.
Visit http://www.diggershotline.com/ to file online requests.
1
MICHIGAN - MISS DIG
1. Phone number: toll-free 1-800-482-7171 or 811
2. Hours of operation 7:00 A.M. - 7:00 P.M. Monday thru Friday. Emergency calls accepted 24 hours a day
7 days a week.
3. Michigan law requires that a minimum of three working days notice be given for any excavation other than
emergencies.
4. Will accept calls for emergencies, planned excavation, appointments and overhead information.
5. Visit http://www.missdig.net/ to file online requests.
NOTE:1. These Services will only notify members to locate their facilities.
G-4
OVERHEAD SERVICES - SECONDARY
•
Contents - Overhead Services ................................................................................................. O-1
•
General Requirements for Overhead Service .......................................................................... O-2
•
Names of Parts for Overhead Service...................................................................................... O-3
•
Service Attachment on an Unguyed Service Mast ................................................................... O-4
•
Height of Service Head Above Support on an Unguyed Service Mast .................................... O-5
•
Service Attachment on a Guyed Service Mast......................................................................... O-6
Service Attachment on a Guyed Support Stud:
•
•
Pitched Roof............................................................................................................................. O-7
Flat Roof................................................................................................................................... O-8
Service Attachment on a Building with:
•
•
Brick or Stone Veneer .............................................................................................................. O-9
•
Service Attachment on a Brick or Metal Building
Wood, Aluminum, Stucco or Similar Siding (0-320 Amperes).................................................. O-10
with Single or Paralleled Service Entrances............................................................................. O-11
Service Attachment on a Building with Bus Duct Service Entrance and:
•
Indoor Metering ........................................................................................................................ O-12
•
Service Entrance on a Private Metering Pole (0-320 Amperes)............................................... O-13
•
Service Entrance on a Private Metering Pole with Outdoor Current Transformers
and Transfer Switch (1Ø, 201-800 Amperes) ........................................................................... O-14
•
Service Entrance to a Mobile Home (1Ø, 120/240 Volts, 0-200 Amperes, 1 Meter)................ O-15
•
Temporary Service for a Construction Site .............................................................................. O-16
•
Service to a Cable TV Power Supply (1Ø, 120 Volts, 0-30 Amperes) ..................................... O-17
•
Service to a Telephone Co. Pole Mounted Dryer (1Ø, 120 Volts, 0-30 Amperes) ................... O-18
O-1
GENERAL REQUIREMENTS FOR OVERHEAD SERVICE
Service Drops, Attachments, Supports, and Entrances
1. All service drops are furnished and installed by the Company.
2. In all installations except those stated in the Rules and Regulations for Electric Service, the customer
shall verify the proper location of the service head and service drop from the Company, which will furnish
this information in writing upon request.
3. In all cases, an adequate support for the service drop attachment and service drop shall be provided by the
customer. The Company furnishes attachments and will provide information as to the pounds of pull that the
service drop support must be designed for or withstand.
4. Typical installations for various service voltages and ampere capacities are shown in succeeding pages.
Unusual installations require special consideration and the Company shall be consulted in all cases.
5. The service head is to be located at a height such that the service drop conductors can be dead-ended below
the service head and still maintain proper clearance above ground, but they are not to be installed higher than
30' above ground.
6. When 1-phase and 3-phase secondary service is furnished to one building, the service heads shall be spaced
approximately 18" apart when installed at the same height. If installed vertically, they shall be
spaced approximately 3' apart with the 1-phase head located above the 3-phase head.
7. When a service mast is used to support the service drop, only the service drop is to be attached to it.
Other utilities such as telephone or cable TV shall not be attached to the service mast.
Grounding
1. Grounding shall be in accordance with all applicable codes.
2. Stainless steel (A.I.S.I. 302, 304, or 416) ground rods are recommended where ground rods must
be installed in the vicinity of buried galvanized rigid conduit, to minimize the possibility of corrosion.
3. The grounding electrode conductor shall not be run through the meter socket or transocket.
4. Bonding to other systems shall not be done on or within a metering enclosure unless a means of bonding,
intended for inter-system bonding, is furnished as part of the metering enclosure (PSC 114.099(C)).
Metering
1. This section details the requirements for overhead service drop attachments and connections. Refer
to the Metering Section of this manual for details of the metering requirements for each installation.
O-2
NAMES OF PARTS FOR OVERHEAD SERVICE
Customer furnishes and installs:
A - Service entrance conductors
B - Service head
C - Service mast
D - Company listed meter socket
E - Service equipment
Company furnishes and installs:
F - Service drop conductors
G - Watthour meter
H - Connectors
O-3
SERVICE ATTACHMENT ON AN UNGUYED SERVICE MAST
Customer furnishes and installs:
1. Service head.
2. Service mast, 2" minimum rigid metallic conduit (see Note 2).
3. Neoprene collar and flash plate.
4. Service entrance conductors (see Note 3).
5. Split ring type conduit supports.
6. Wood blocking.
Company furnishes and installs:
7. Service attachment
(clamp type wireholder).
8. Service connectors.
9. Service drop.
Notes:
1. Contact the Local Municipal Inspector for approval of service mast that extend more than 3' (914 mm) above
the roof.
2. That portion of service mast above uppermost conduit support shall be a continuous length without couplings.
Refer to Sheet O-5 for maximum height of service head above support.
3. Service entrance conductors shall extend at least 18" beyond the service head to permit proper connection to
the Company's conductors.
4. For rewires where it is not possible to install Item # 6 (wood blocking) a Heavy Duty Flash Plate is to be used.
5. Only the electric service drop shall be attached to the service mast.
O-4
HEIGHT OF SERVICE HEAD ABOVE SUPPORT
ON AN UNGUYED SERVICE MAST
Contact the local Company office if there is a need to extend the conduit beyond 8'.
Service
Drop
Length
#2 Aluminum
Triplex
(1Ø, 100 Amp. Service)
30'
40'
50'
60'
70'
80'
90-120'
8'- 0"
6'-11"
5'-10"
5'- 1"
4'- 7"
4'- 1"
3'- 2"
8'- 0"
8'- 0"
8'- 0"
8'- 0"
7'- 6"
6'- 8"
4'-11"
8'- 0"
8'- 0"
8'- 0"
8'- 0"
8'- 0"
8'- 0"
7'- 8"
#1/0 Aluminum
Triplex
(1Ø, 200 Amp. Service)
30'
40'
50'
60'
70'
80'
90-120'
7'- 8"
6'- 1"
5'- 0"
4'- 4"
3'-11"
3'- 7"
2'- 9"
8'- 0"
8'- 0"
8'- 0"
7'- 2"
6'- 4"
5'- 8"
4'- 2"
8'- 0"
8'- 0"
8'- 0"
8'- 0"
8'- 0"
8'- 0"
6'- 5"
#2 Aluminum
Triplex
(1Ø, 100 Amp. Service)
30'
40'
50'
60'
70'
80'
90-120'
4'- 1"
3'- 4"
2'-11"
2'- 7"
*
*
*
6'-10"
5'- 5"
4'- 8"
4'- 1"
3'- 8"
3'- 4"
2'- 7"
8'- 0"
8'- 0"
6'-11"
6'- 0"
5'- 4"
4'- 9"
3'- 8"
#1/0 Aluminum
Triplex
(1Ø, 200 Amp. Service)
30'
40'
50'
60'
70'
80'
90-120'
3'- 8"
3'- 0"
2'- 7"
*
*
*
*
6'- 0"
4'-10"
4'- 0"
3'- 6"
3'- 2"
2'-11"
*
8'- 0"
7'- 2"
5'-11"
5'- 1"
4'- 7"
4'- 2"
3'- 2"
#2 Aluminum
Triplex
(1Ø, 100 Amp. Service)
30'
40'
50'
60'
70'
80'
90-120'
6'- 0"
4'-10"
4'- 2"
3'- 8"
3'- 4"
3'- 0"
*
8'- 0"
8'- 0"
7'- 3"
6'- 4"
5'- 7"
5'- 0"
3'- 9"
8'- 0"
8'- 0"
8'- 0"
8'- 0"
8'- 0"
7'- 1"
5'- 3"
#1/0 Aluminum
Triplex
(1Ø, 200 Amp. Service)
30'
40'
50'
60'
70'
80'
90-120'
5'- 2"
4'- 4"
3'- 7"
3'- 2"
2'-11"
2'- 8"
*
8'- 0"
7'- 6"
6'- 2"
5'- 4"
4'- 9"
4'- 4"
3'- 3"
8'- 0"
8'- 0"
8'- 0"
7'- 7"
6'- 8"
6'- 1"
4'- 5"
Rigid Metal
Steel Conduit
Rigid Metal
Aluminum Conduit
Intermediate
Steel Conduit
Service
Drop
Length
Rigid Metal
Steel Conduit
Maximum Height of Service Head
2"
2-1/2"
3"
Conduit
Conduit
Conduit
#6 Aluminum
Duplex
30'
40'
50'
60'
70'
80'
90'
100'***
Dimensions Above Ground
2-1/2"
3"
Conduit
Conduit
20'- 4"
15'- 8"
12'-10"
11'- 1"
**
**
**
**
31'- 0"
25'- 9"
20'-10"
18'- 1"
15'- 7"
14'- 0"
12'- 9"
11'- 8"
* Conduit not adequate for 30" minimum requirement.
** Conduit not adequate for 10' minimum clearance.
*** Maximum allowable service drop length.
O-5
SERVICE ATTACHMENT ON A GUYED SERVICE MAST
Customer furnishes and installs:
1. Service head.
2. Service mast. 2" minimum rigid metallic conduit (see Note 1).
3. Service entrance conductors (see Note 2).
4. Neoprene collar and flash plate.
5. Split ring type conduit supports.
6. Galvanized guy wire and necessary attachments
(1/4" minimum, 3 or 7 strands).
Company furnishes and installs:
7. Service attachment
(clamp type wireholder).
8. Service connectors.
9. Service drop.
Notes:
1. That portion of service mast above uppermost conduit support shall be a continuous length without couplings.
2. Service entrance conductors shall extend at least 18" beyond the service head to permit proper connection to
the Company's conductors.
3. Only the electric service drop can be attached to the service mast.
O-6
SERVICE ATTACHMENT ON A GUYED SUPPORT STUD
PITCHED ROOF
Customer furnishes and installs:
1. Service head.
2. Service entrance conduit.
3. Service entrance conductors (see Note 2).
4. Steel channel or equivalent securely fastened to building wall
(see Note 1).
5. Galvanized guy wire and necessary attachments
(1/4" minimum, 3 or 7 strands).
Company furnishes and installs:
6. Service attachment.
7. Service connectors.
8. Service drop.
Notes:
1. Customer shall notch roof overhang to accommodate support stud. Stud to have sufficient strength to
withstand maximum loading. Install service entrance conduit close to building wall.
2. Service entrance conductors shall extend at least 18" beyond the service head to permit proper connection
to the Company's conductors.
3. Only the electric service drop can be attached to the service mast.
O-7
SERVICE ATTACHMENT ON A GUYED SUPPORT STUD
FLAT ROOF
Customer furnishes and installs:
1. Service head.
2. Service entrance conduit.
3. Service entrance conductors (see Note 1).
4. Steel channel or equivalent securely fastened to building wall.
5. Galvanized guy wire and necessary attachments
(1/4" minimum, 3 or 7 strands).
Company furnishes and installs:
6. Service attachment.
7. Service connectors.
8. Service drop.
Notes:
1. Service entrance conductors shall extend at least 18" beyond the service head to permit proper connection
to the Company's conductors.
2. Only the electric service drop can be attached to the service mast.
O-8
SERVICE ATTACHMENT ON A BUILDING
WITH BRICK OR STONE VENEER
Customer furnishes and installs:
1. Service head.
2. Service entrance conduit.
3. Service entrance conductors (see Note 2).
Company furnished and installs:
5. Service connectors.
6. Service drop (#2 & #1/0 triplex only).
Company furnishes and Customer installs:
4. Service attachment. "T" type bracket installed
with 3/8" x 4" lag screws (see Note 1).
Notes:
1. The customer may provide a bracket of the type shown below. Install a steel strap from the hole in the bracket
to an adjacent studding for service drops that pull off at an angle.
2. Service entrance conductors shall extend at least 18" beyond the service head to permit proper connection to
the Company's conductors.
O-9
SERVICE ATTACHMENT ON A BUILDING
WITH WOOD, ALUMINUM, STUCCO OR SIMILAR SIDING
0-320 AMPERES
Obtain acceptance for installations larger than 200 amperes from the local Company office.
Customer furnishes and installs:
1. Service head.
2. Service entrance conduit.
3. Service entrance conductors (see Note 2).
Company furnishes and installs:
4. Service attachment (see Note 1).
5. Service connectors.
6. Service drop.
Notes:
1. Customer shall mark location of studs on building.
2. Service entrance conductors shall extend at least 18" beyond the service head to permit proper connection
to the Company's conductors.
O-10
SERVICE ATTACHMENT ON A BRICK OR METAL BUILDING
WITH SINGLE OR PARALLELED SERVICE ENTRANCES
Customer furnishes and installs:
1. Service head (a maximum of 4).
2. Service entrance conduit.
3. Service entrance conductors (see Note 2).
4. Additional outlet for parallel services if required.
Company furnishes and installs:
6. Service attachment.
7. Service connectors.
8. Service drop.
9. Alternate service attachment
if required.
Company furnishes and Customer installs:
5. 5/8" spacer bolt with two 4" square flat washers. Washers
to be installed on both sides of building wall (see Note 1).
Notes:
1. It shall be the customer's responsibility to provide adequate wall strength to support service drop tensions as
provided by the Company.
2. Service entrance conductors shall extend at least 30" beyond the service head to permit proper connection to
the Company's conductors.
O-11
SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE
AND INDOOR METERING
Obtain acceptance and specific details from the local Company office.
Customer furnishes and installs:
1. Service entrance duct (see Note 1).
Company furnishes and installs:
3. Service drop and attachment.
4. Service connectors.
Company furnishes and Customer installs
2. 5/8" spacer bolt with two 4" square flat washers. Washers to be
installed on both sides of building wall (see Note 2).
Notes:
1. If the vertical dimension of the bus bars exceed 5-3/4”, the customer shall be responsible for taping the top of
the bus bars such that not more than 5-3/4" remain exposed.
2. It shall be the customer's responsibility to provide adequate wall strength to support service drop tensions as
provided by the Company.
O-12
SERVICE ENTRANCE ON A PRIVATE METERING POLE
0-320 AMPERES
Customer furnishes and installs:
1. Service heads.
2. Service entrance conduit. Provide mechanical protection
to a point 8' above grade.
3. Service entrance conductors (see Note 5).
4. Treated wood pole (see Notes 1 & 2).
5. Secondary pole rack or equivalent.
6. Sub-service conductors (see Notes 1 & 3).
7. Company listed 1-position meter socket (see Note 6).
8. Grounding electrode conductor.
9. Grounding electrode(s) per applicable codes
(see Sheet O-2).
10. Weatherproof disconnecting means (see Note 4).
Company furnishes and installs:
11. Service attachment.
12. Service connectors.
13. Service drop.
14. Watthour meter.
Notes:
1. It may be necessary to guy the meter pole. Customer shall
consult the Company to obtain such information as service
drop tension and direction so that adequate and effective
guying can be installed.
2. Customer shall consult the Company for the class, setting
depth and length of pole to be installed. Minimum
requirements are class 6, 5' setting depth and 25' length;
additional pole height may be required to maintain clearances
as specified in the NEC.
3. Other sub-services may be installed where necessary when
each is provided with proper service ground.
4. On meter poles where the disconnecting means is installed at
some other location, direct grounding of the meter socket is
permissible.
5. Service entrance conductors shall extend at least 18" beyond
the service head to permit proper connection to the
Company's conductors.
6. For farm installations the centerline of the meter shall be 5'
above grade. For all other installations, use standard meter
mounting height (see M-2).
O-13
SERVICE ENTRANCE ON A PRIVATE METERING POLE
WITH OUTDOOR CURRENT TRANSFORMERS AND A TRANSFER SWITCH
1-PHASE or 3-PHASE, 201-800 AMPERES
FOR FARM SERVICES ONLY
Obtain acceptance from the local Company office.
Customer furnishes and installs:
1. Transfer switch, UL listed or equivalent.
2. Weatherproof receptacle for generator.
3. Operating handle for transfer switch (grounded).
4. Service entrance conductors (see Note 1 & 2).
5. Service attachment (secondary wireholder
or equivalent).
6. Screw type insulator to support neutral conductor.
7. Treated wood pole (see Notes 3 & 4).
8. Grounding electrode(s) per applicable codes
(see Sheet O-2).
9. Grounding electrode conductor.
10. Company listed transformer rated meter socket
(see Sheet D-18).
11. Conduit (see Note 5).
12. Water-tight entrance connector with neoprene
bushing, or weatherhead.
Notes:
1. Service entrance conductors shall extend at least 36"
past the bottom of the pole top transfer switch to permit
proper connection to the Company's conductors.
2. Underground service entrance conductors and conduit
may be substituted for the overhead conductors. If this
is done the pole must be accessible by bucket truck
and mechanical protection 8' above and 18" below
grade, minimum, are required.
3. It may be necessary to guy meter pole. Customer
shall consult the Company to obtain such information
as service drop tensions and direction so that
adequate and effective guying can be installed.
4. Customer shall consult the Company for the class,
setting depth and length of pole to be installed.
Minimum requirements are class 6, 5' setting depth
and 25' height; additional pole height may be required
to maintain clearances as specified in the NEC.
5. 1-1/4" galvanized rigid, galvanized intermediate or
rigid nonmetallic schedule 40 PVC conduit per NEMA
Standard TC-2, and 1-1/4" coupling with 1-1/4" to 1"
reducer. Conduit to be securely fastened to pole with
standard conduit straps or clamps.
O-14
Company furnishes and installs:
13. Service attachment (secondary wireholder
or equivalent).
14. Service connectors.
15. Service drop.
16. Current transformers.
17. Metering cable.
18. Watthour meter.
SERVICE ENTRANCE TO A MOBILE HOME
1-PHASE, 120/240 VOLTS, 0-200 AMPERES, 1 METER
Customer furnishes and installs:
1. Service head.
2. Service entrance conduits. Provide mechanical
protection to a point 8' above grade.
3. Service entrance conductors (see Note 3).
4. Treated wood pole (see Notes 1 & 2).
5. Company listed 4-terminal meter socket.
6. Weatherproof panelboard (see Note 4).
7. Grounding electrode conductor.
8. Grounding electrode(s) per applicable codes
(see Sheet O-2).
Company furnishes and installs:
9. Service attachment.
10. Service connectors.
11. Service drop.
12. Watthour meter.
Notes:
1. It may be necessary to guy the meter pole. Customer
shall consult the Company to obtain such information
as service drop tension and direction so that adequate
and effective guying can be installed.
2. Customer shall consult the Company for the class,
setting depth and length of pole to be installed.
Minimum requirements are class 6, 5' setting depth
and 20' length; additional pole height may be required
to maintain clearances as specified in the NEC.
3. Service entrance conductors shall extend at least 18"
beyond the service head to permit proper connection to
the Company's conductors.
4. Article 550 of the National Electrical Code covers the
special requirements for mobile homes. A few of the
requirements are listed below. See the NEC for a
complete listing of the requirements.
z
Mobile home service equipment must have a
means for providing service to an auxiliary building
or electrical equipment located outside the mobile
home by a fixed wiring means.
z
It also permits additional 120 Volt, 15 or 20 Amp.,
GFI protected, receptacles to be installed for
equipment located outside of the mobile home.
z
The service or disconnecting means must be
with-in sight of and not more than 30' from an
exterior wall of the mobile home.
z
All wiring must be installed as per the NEC,
State and local ordinances.
O-15
TEMPORARY SERVICE FOR A CONSTRUCTION SITE
Customer furnishes and installs:
1. Service head.
2. Service entrance conduit.
3. Service entrance conductors (see Note 4).
4. Timber upright (4" x 4" or 6" x 6")
(see Notes 1 & 2).
5. Company listed meter socket (see Note 3).
6. Service switch and distribution panel
(see Note 3).
7. Brace or guy timbers to hold 1000 pounds
load each (see Note 1).
8. Grounding electrode conductor.
9. Grounding electrode(s) per applicable codes
(see Sheet O-2).
Notes:
1. For temporary service the customer shall
install this structure or other Company listed
equivalent structure: Utility Service
Manufacturing Company Miti-Mast, MM or
ML series with catalog numbers suffix "HDB"
(for heavy duty back stake). This approval
applies only to the meter socket and the
strength of the temporary mast, but does not
include approval of the disconnecting device
or the power outlet.
2. Consult the Company for the location and the
required height of the structure.
3. A Company listed temporary service assembly,
as listed on Sheet D-6, may be substituted for
the meter socket, service switch and distribution
panel.
4. Service entrance conductors shall extend at
least 30" beyond the service head to permit
proper connection to the Company's
conductors.
O-16
Company furnishes and installs:
10. Service attachment (secondary porcelain
screw bracket or equivalent wireholder).
11. Service connectors.
12. Service drop.
13. Watthour meter.
SERVICE TO A CABLE TV POWER SUPPLY
1-PHASE, 120 VOLTS, 0-30 AMPERES
Company furnishes and installs:
Customer furnishes and installs:
9. Service conductors and connectors from
1. Service head.
secondary to service entrance conductors.
2. Service entrance conduit (see Note 1).
10. Watthour meter.
3. Service entrance conductors (see Note 2).
4. Weatherproof, dead front, fuse or circuit
breaker (see Notes 3 & 4).
5. Cable TV power supply unit and mounting
hardware (see Notes 3, 4, 5, 6 & 7).
6. Grounding electrode conductor.
7. Grounding electrode(s) per applicable codes
(see Sheet O-2).
8. Company listed meter socket (see Notes 3 & 8).
Notes:
1. Non-metallic conduit, Schedule 80. If metallic
conduit is used, it shall be covered with a nonmetallic covering 40" above and 72" below any
communications attachments.
2. The service entrance conductors shall extend
at least 18" beyond the service head to permit
proper connection to the Company's
conductors.
3. The disconnect, power supply unit, meter socket
and TV cable shall be mounted on the same
quadrant of the pole.
4. When a unit contains both the service switch
and the power supply, installation height shall be
in accordance with applicable codes.
5. Unit may not be mounted on any pole on which
there are transformers, risers, vertical supply
conductors to aerial services, switch handles,
traffic signals, capacitor banks or similar fixtures.
Additionally, it may not be mounted
on a distribution system corner pole.
6. Where mounted on a pole on which a lighting
fixture is installed, a clearance of 20" is required
to an ungrounded fixture or 4" if fixture is
grounded and bonded to the power supply.
7. All installations must conform to the Wisconsin
or Michigan State Electrical Code for
clearances, climbing space and working space.
8. Where there is vehicle traffic, the Company may
refuse to allow service on a pole used by We
Energies, in this case, use a free standing
pedestal or customer owned service pole.
9. Not to be served from a transformer equipped
with neutral isolator.
O-17
SERVICE TO A TELEPHONE CO. POLE MOUNTED DRYER
1-PHASE, 120 VOLTS, 0-30 AMPERES
Customer furnishes and installs:
1. Air dryer (see Note 1).
2. Weatherproof dead front, fuse or circuit breaker
(see Note 2).
3. Service head, entrance conduit and minimum size #10
conductor (see Notes 3 & 4).
4. Company listed meter socket.
5. Air line covered with molding.
6. Alarm pair covered with molding.
7. Grounding electrode conductor covered with molding.
8. Grounding electrode(s) per applicable codes
(see Sheet O-2).
Company furnishes and installs:
9. Service conductors and connectors from
secondary to service entrance conductors.
10. Watthour meter.
Notes:
1. Unit may not be mounted on any pole on which there are risers, vertical supply conductors to aerial services,
switch handles, traffic signals, capacitor banks or similar fixtures. Air line, alarm pair and service conduit are
risers, and no more than 3 risers are permitted on a pole.
2. All installations must conform to the Wisconsin or Michigan State Electrical Code for clearances, climbing
space, working space.
3. Where mounted on a pole on which a lighting fixture is installed, a clearance of 20" is required to an
ungrounded fixture or 4" if fixture is grounded and bonded to the communication strand.
4. Non-metallic conduit, Schedule 80. If metallic conduit is used, it shall be covered with a non-metallic
covering 40" above and 72" below any communications attachments.
5. Not to be served from a transformer equipped with neutral isolator.
O-18
UNDERGROUND SERVICES - SECONDARY
• Contents - Underground Services ......................................................................................................... U-1
• General Requirements for Underground Service .................................................................................. U-2
• Names of Parts for Underground Service.............................................................................................. U-3
Service Termination in a Service Assembly for Mobile Home (1Ø, 120/240 Volts):
• 1 or 2 Meters, 0-200 Amperes per Meter .............................................................................................. U-4
Service Termination in a Meter Pedestal, Direct Buried Lateral (0-320 Amperes):
• Free Standing (1 meter) ........................................................................................................................ U-5
• Attached to a Building ........................................................................................................................... U-6
Service Termination in an Outdoor Meter Socket (0-200 Amperes):
• Concrete Encased Lateral..................................................................................................................... U-7
• Direct Buried Lateral ............................................................................................................................. U-8
Service Termination in a Multi-Position Meter Socket
(1Ø, 120/240 Volts, 0-400 Ampere Bus, 0-200 Amperes per Meter, 2-6 Meters):
• Concrete Encased Lateral..................................................................................................................... U-9
• Direct Buried Lateral ............................................................................................................................. U-10
• Temporary Service Termination in an Outdoor Meter Socket,
(1Ø, 120/240 Volts, 0-200 Amperes; 1Ø, 120/208 Volts, 0-200 Amperes) ............................................ U-11
Service Termination in a Free Standing Transocket:
• (1Ø, 120/240 Volts, 201-800 Amperes; 3Ø, 201-3000 Amperes).......................................................... U-12
• For farm service only, (1Ø, 120/240 Volts, 201-800 Amperes) ............................................................. U-13
Service Termination in an Outdoor Transocket:
• Concrete Encased Lateral,
(1Ø, 120/240 Volts, 201-800 Amperes; 3Ø, 201-3000 Amperes) .......................................................... U-14
• Direct Buried Lateral,
(1Ø, 120/240 Volts, 201-800 Amperes; 3Ø, 201-1200 Amperes) .......................................................... U-15
Service Termination in a Transocket, First Floor Installation:
• Concrete Encased Lateral,
(1Ø, 120/240 Volts, 201-800 Amperes; 3Ø, 201-3000 Amperes) .......................................................... U-16
• Direct Buried Lateral (1Ø, 120/240 Volts, 201-800 Amperes; 3Ø, 201-1200 Amperes) ........................ U-17
Service Termination in a Termination Compartment
• Direct Buried or Concrete Encased Lateral, above grade
(1Ø, 400-800 Amperes; 3Ø, 400-3000 Amperes) .................................................................................. U-18, U-19
• Direct Buried or Concrete Encased Lateral, above grade with all conduits exiting bottom of compartment
(1Ø, 400-800 Amperes; 3Ø, 400-3000 Amperes) .................................................................................. U-20, U-21
• Free Standing, Direct Buried or Concrete Encased Lateral
(1Ø, 400-800 Amperes; 3Ø, 400-3000 Amperes) .................................................................................. U-22, U-23
• Concrete Encased Lateral (1Ø, 400-800 Amperes; 3Ø, 400-3000 Amperes) ....................................... U-24
• Concrete Encased Lateral, Below Grade (1Ø, 400-800 Amperes; 3Ø, 400-3000 Amperes)................. U-25
• Building without a Basement, First Floor Installation, Direct Buried Lateral
or Concrete Encased Lateral, (1Ø, 400-800 Amperes; 3Ø, 400-3000 Amperes)................................... U-26, U-27
Service Termination in a Customer's Termination Compartment Free Standing Switchgear
(3Ø, 2000-4000 Amperes)
• Located Below Grade............................................................................................................................ U-28, U-29
• Located on First Floor or Above ............................................................................................................ U-30, U-31
Policy on Services for Communication Towers ...................................................................................................... U-32
Service Termination in a Multi-Position Meter Socket for Communication Tower .................................................. U-33
U-1
GENERAL REQUIREMENTS
FOR UNDERGROUND SERVICE
Space Requirements
1. The unobstructed space required in front of termination compartments, transockets and metering equipment
shall be as defined by the "Working Space About Electrical Equipment", Section 110.26, of the National
Electrical Code (as adopted by the states of Michigan and Wisconsin). This unobstructed space shall extend
from the floor or ground to a minimum height of 6'-6". For equipment higher than 6'-6" this space shall extend to
the top of the equipment.
Service Laterals and Entrances
1. Service laterals are furnished and installed by the Company.
2. Service laterals will generally be terminated in a meter pedestal, meter socket, transocket or termination
compartment. Customers shall obtain information from the Company relative to the proper location of the
service lateral and termination equipment. Such information will be furnished in writing upon request.
3. The preferred termination of service laterals is on the outside of a building (or structure). Service laterals that
terminate inside of a building shall terminate immediately upon entering as shown in this manual. The raceway
for service laterals under or thru a building shall not extend longer than 8' after penetrating the outside wall.
Services that terminate in a mezzanine are allowed a maximum length of 14' measured from grade.
4. For services, generally 2000 Amperes and larger, and with Company approval, the service lateral may be
terminated in the customer's switchgear or on the customer's bus duct. This type of installation is further
restricted by the following:
a. Customer shall provide all necessary plastic conduit encased in 3" of concrete for the extension of the cable
within his building (see Note 3 above).
b. Customer shall obtain Company acceptance of the switchgear terminal and C.T. compartment (if any)
design. Three copies of the switchgear plans shall be submitted to the local company office for acceptance.
The plans must show the general layout of the switchgear, the switchgear location within the building, and
the specific details of the termination compartment and any C.T. compartment(s). Specific details such as
compartment size, bus spacing and drilling dimensions, other clearances, bus & bus support configuration,
barrier location, sealing provisions, and materials used are to be included.
5. Only meter mounting devices and termination equipment approved and listed in Section D of this manual are
to be used. Additionally all equipment must be listed by a nationally recognized testing laboratory, e.g. UL,
installed and used as per the listing and the manufacturer's instructions.
6. Where metallic rigid conduit or IMC is used for the service lateral raceway the ends are to be threaded and
threaded couplings, connectors or locknuts are to be used. Slip type fittings shall not be used.
7. For outdoor service terminations with direct buried lateral, the horizontal portion of the conduit shall extend
through a minimum of 12" of undisturbed earth where practicable, defined as follows:
a. Undisturbed earth: The area not excavated for the construction of the building.(May be compacted fill.)
b. Fill area: The area between the building wall and the undisturbed earth.(May vary from a few inches to
several feet or more).
8. Services to individual dwelling units shall consist of one service lateral and one meter.
Grounding
1. Grounding shall be in accordance with all applicable codes.
2. Stainless steel (A.I.S.I. 302, 304 or 416) ground rods are recommended where ground rods must be installed in
the vicinity of buried galvanized rigid conduit to minimize the possibility of corrosion.
3. The grounding electrode conductor shall not be run through the meter pedestal, meter socket, transocket, or
termination compartment, unless a separate raceway is provided. The grounding electrode conductor may
terminate on the neutral bus of: the termination compartment for multi-metered installations provided it does not
interfere with the installation of the service lateral conductors, or a meter pedestal equipped with a main
disconnect and listed as Service Equipment.
4. Ground rods and grounding electrode conductors shall not be located in front of meter pedestals or wiring
troughs.
5. Bonding to other systems shall not be done on or within a metering enclosure unless a means of bonding,
intended for inter-system bonding, is furnished as part of the metering enclosure (PSC 114.099(C)).
Metering
1. This section details the requirements for underground service lateral terminations and connections.
Refer to the Metering Section of this manual for details of the metering requirements for each installation.
U-2
NAME OF PARTS FOR UNDERGROUND SERVICE
Customer furnishes and installs:
A - Metering Pedestal.
B - Service-Entrance Conduit and Conductors.
C - Distribution Panel, Main Fuse/Disconnect.
D - Meter Socket.
E - Service Lateral Conduit.
F - Transocket.
G - Transformer Rated Meter Socket.
H - Wiring Trough (1600 Amperes Maximum).
I - Termination Compartment, either wire or
bus connected type.
Customer furnishes and installs:
J - Metering or Main Disconnect/Fuse, wire
connected for use with wire type termination
compartment only.
K - Metering Equipment, bus connected for use with
bus connection type termination compartment
only and of same manufacturer.
Company furnishes and installs:
L - Underground Service Lateral.
M - Watthour Meter.
U-3
SERVICE TERMINATION IN A SERVICE ASSEMBLY
FOR MOBILE HOMES
1-PHASE, 120/240 VOLTS, 0-200 AMPERES PER METER, 1 OR 2 METERS
Customer furnishes and installs:
1. Company listed mobile home metering pedestal (see Sheet D-13).
2. Company listed pedestal supporting stake bolted to the pedestal
(see Sheet D-11) or equivalent (see Note 1).
3. Grounding electrode conductor in non-metallic conduit and
grounding electrodes(s) per applicable codes (Sheet U-2).
Company furnishes and installs:
4. Watthour meter.
5. Service lateral (radial feed, loop
thru installation).
Notes:
1. A 1-5/8" x 1-5/8" galvanized steel framing channel 80" long or a galvanized steel support of equal strength.
2. Article 550 of the National Electrical Code covers the special requirements for mobile homes. A few of the
requirements are listed below. See the NEC for a complete listing of the requirements.
•
Mobile home service equipment must have a means for providing service to an auxiliary building or
electrical equipment located outside the mobile home by a fixed wiring means.
•
Additional 120 Volt, 15 or 20 Amp., GFI protected, receptacles are permitted for equipment located
outside of the mobile home.
•
The service or disconnecting means must be with-in sight of and not more than 30 feet from an exterior
wall of the mobile home.
•
All wiring must be installed as per the NEC, State and local ordinances.
U-4
SERVICE TERMINATION IN A FREE STANDING METER PEDESTAL
DIRECT BURIED LATERAL
0-320 AMPERES, 1 METER
Not To Be Used for Mobile Homes
Customer furnishes and installs:
1. Company listed meter pedestal (see Notes 1 & 2).
2. Company listed supporting stake or concrete footing
(.75 cu. ft. min.) (see Notes 3 & 4 and Sheet D-11).
3. Service-entrance conductors (not shown, see Note 5).
4. Service-entrance conduit.
5. Ground conductor in non-metallic conduit, installed only
when the pedestal has a main disconnect.
6. Grounding electrode(s) per applicable codes (see Sheet U-2).
7. Accessory foot for concrete foundations.
Company furnishes and installs:
8. Service lateral.
9. Watthour meter.
Notes:
1. Unit shall have a main service switch and fuse, or circuit breaker either integral or attached to the pedestal.
2. Rodent covers for pedestal base, if included, shall be discarded.
3. Pedestal shall be set in firmly compacted soil up to the grade line of the pedestal.
4. A 1-5/8" x 1-5/8" galvanized steel framing channel 80" long or a galvanized steel support of equivalent strength.
5. Service-entrance conductors shall exit the pedestal below the lowest live part and above grade.
SIDE VIEW SHOWN WITH
SUPPORTING STAKE
FRONT VIEW SHOWN WITH
OPTIONAL CONCRETE FOOTING
U-5
SERVICE TERMINATION IN A METER PEDESTAL ATTACHED TO A BUILDING
DIRECT BURIED LATERAL
0-320 AMPERES
Customer furnishes and installs:
1. Company listed meter pedestal (see Notes 1,2 & 3).
2. Service-entrance conduit.
3. Service-entrance conductors (not shown, see Note 4).
Company furnishes and installs:
4. Service lateral.
5. Watthour meter.
Notes:
1. Pedestal shall set in firmly compacted soil up to the grade line of the pedestal.
2. Rodent covers for pedestal base, if included, shall be discarded.
3. It shall be the customer's responsibility to firmly secure the pedestal to the building.
4. Service-entrance conductors shall exit the pedestal below the lowest live part and above grade.
5. Allowance for the building wall, when the pedestal is mounted to the foundation.
6. When a two position meter pedestal is installed the positions must be labeled (see Note 7 on Page M–2).
SIDE VIEW
U-6
FRONT VIEW
SERVICE TERMINATION IN AN OUTDOOR METER SOCKET
CONCRETE ENCASED LATERAL
0-200 AMPERES
NOT TO BE USED WITHOUT PERMISSION FROM THE COMPANY (See Note 1)
Customer furnishes and installs:
1. Service-entrance conduit.
2. Service-entrance conductors.
3. Bonding. Metallic conduit shall be bonded.
4. Company listed meter socket.
5. Service lateral conduit (see Note 2).
6. Conduit supports.
Company furnishes and installs:
7. Service lateral conduit and concrete
envelope.
8. Service lateral.
9. Duct seal.
10. Watthour meter (not shown).
Note:
1. Not to be used for normal installation; requires permission from the company. See Page U-6 for
the standard installation.
2. Galvanized rigid or galvanized intermediate conduit with threaded ends and fittings at the meter socket.
1-phase, 0-100 amperes; one 2" conduit
1-phase, 101-200 amperes; one 2-1/2" conduit
3-phase, 0-100 amperes; one 2-1/2" conduit
3-phase, 101-200 amperes; one 3" conduit
U-7
SERVICE TERMINATION IN AN OUTDOOR METER SOCKET
DIRECT BURIED LATERAL
0-200 AMPERES
NOT TO BE USED WITHOUT PERMISSION FROM THE COMPANY (See Note 1)
Customer furnishes and installs:
1. Service-entrance conduit.
2. Service-entrance conductors.
3. Bonding. Metallic conduit shall be bonded.
4. Company listed meter socket.
5. Service lateral conduit (see Note 2).
6. Insulated conduit bushing (see Note 3).
7. Split ring type conduit supports or galvanized steel framing channel
brackets and conduit clamps. The lower conduit support shall be
attached to the building foundation.
8. Standard radius manufactured elbows or field bend conduit
(see Note 2).
Company furnishes and installs:
9. Service lateral.
10. Watthour meter (not shown).
Notes:
1. Not to be used for normal installations; requires permission from the Company.
See Page U-6 for the standard installation.
2. Galvanized rigid or galvanized intermediate conduit with threaded ends and fittings.
1-phase, 0-200 amperes; one 2" conduit with 12" bend radius
3-phase, 0-100 amperes; one 2" conduit with 12" bend radius
3-phase, 101-200 amperes; one 2-1/2" conduit with 15" bend radius
3. Service lateral conduit shall have a temporary waterproof end cap when installed to
prevent the accumulation of water, ice and other foreign matter inside the conduit.
U-8
SERVICE TERMINATION IN A MULTI-POSITION METER SOCKET
CONCRETE ENCASED LATERAL
1-PHASE, 120/240 VOLTS, 0-400 AMPERE BUS
0-200 AMPERES PER METER, 2-6 METERS
Customer furnishes and installs:
1. Service-entrance conduit.
2. Service-entrance conductors.
3. Bonding. Metallic conduit shall be bonded.
4. Company listed 2 to 6 position meter socket with or without
circuit breakers (see Notes 1, 2 & 4).
5. Service lateral conduit (see Note 3).
6. Conduit supports. The lower conduit support shall be
attached to the building foundation.
Company furnishes and installs:
7. Service lateral conduit and concrete
envelope.
8. Service lateral.
9. Duct seal.
10. Watthour meters (not shown).
Notes:
1. The Company will provide lugs for terminating incoming service lateral for all sockets rated 401 amperes
or more.
2. Separate cable compartments provided on some meter sockets are for the Company's service lateral
cable only.
3. Galvanized rigid or galvanized intermediate conduit with threaded ends and fittings. Consult the local
Company office for the proper size of the service lateral conduit.
4. Each meter position shall be marked on the outside of the socket or by the breaker (if available) with the
address of the unit served. If the marking is on the outside of the removable cover, it shall also be marked
on the inside of the meter socket in a visible location. This marking shall also be placed on the corresponding
distribution panel(s). The marking shall be a permanent label with 1/2" block letters and may consist of
individual self-stick letters or numbers, suitable for the location so as to be considered permanent.
U-9
SERVICE TERMINATION IN A MULTI-POSITION METER SOCKET
DIRECT BURIED LATERAL
1-PHASE, 120/240 VOLTS, 0-400 AMPERE BUS
0-200 AMPERES PER METER, 2-6 METERS
Customer furnishes and installs:
1. Service-entrance conduit.
2. Service-entrance conductors.
3. Metallic conduit shall be bonded.
4. Company listed 2 to 6 position meter socket
(see Notes 1, 2 & 5 and Sheets D-7 & D-10).
5. Service lateral conduit (see Note 3).
6. Split ring type conduit supports or galvanized steel framing
channel brackets and conduit clamps. The lower conduit
support shall be attached to the building foundation.
7. Insulated conduit bushing (see Note 4).
8. Standard radius manufactured elbows or field bend radius.
(Not shown, see Note 6).
Company furnishes and installs:
9. Service lateral.
10. Watthour meters (not shown).
Notes:
1. The Company will provide lugs for terminating incoming service lateral for all sockets rated 401 amperes
or more.
2. Separate cable compartments provided on some meter sockets are for the Company's service lateral
cable only.
3. Galvanized rigid or galvanized intermediate conduit with threaded ends and fittings. Consult the Company
office for the proper size of the service lateral conduit. A Company listed wireway may be substituted for the
service lateral conduit as shown in dashed lines (preferred method).
4. Service lateral conduits shall have a temporary waterproof end cap to prevent the accumulation of water, ice
and other foreign matter inside the conduit.
5. Each meter position shall be marked on the outside of the socket or by the breaker (if available) with the
address of the unit served. If the marking is on the outside of the removable cover, it shall also be marked on
the inside of the meter socket in a visible location. This marking shall also be placed on the corresponding
distribution panel(s). The marking shall be a permanent label with 1/2" block letters and may consist of individual
self-stick letters or numbers, suitable for the location so as to be considered permanent.
6. Conduit
2-1/2"
3"
3-1/2"
Min. Bend Radius
15"
18"
21"
WITHOUT BREAKER
U-10
WITH BREAKER
TEMPORARY SERVICE TERMINATION IN AN OUTDOOR METER SOCKET
1-PHASE, 120/240 VOLTS, 0-200 AMPERES
1-PHASE, 120/208 VOLTS, 0-200 AMPERES
Customer furnishes and installs:
1. Treated 4" x 4" wood post or equivalent (see Note 1).
2. Painted 3/4" weatherproof plywood to extend a minimum
of 1" beyond the meter socket on all 4 sides.
3. 200 Amp., Company listed meter socket (see D-7 & D-8).
4. Bonding. Metallic conduit shall be bonded.
5. Service-entrance conductors.
6. Service-entrance conduit.
7. Weatherproof disconnecting means (see Note 2).
8. Ground conductor in conduit.
9. Grounding electrode(s) per applicable codes (see Sheet U-2).
10. Service lateral conduit (see Note 3).
11. Split ring type conduit supports or galvanized steel 2-hole
conduit straps.
Company furnishes and installs:
12. Service lateral.
13. Flexible polyethylene conduit.
14. Coupling.
15. Watthour meter (not shown).
Notes:
1. The temporary service assembly shall be located 6' from the Company service pedestal or
padmounted transformer.
2. Consult the local Company office for alternate locations for mounting the disconnect.
3. 2" galvanized rigid, galvanized intermediate, or rigid nonmetallic schedule 80 PVC conduit
per NEMA Standard TC-2.
U-11
SERVICE TERMINATION IN A FREE STANDING TRANSOCKET
1-PHASE, 120/240 VOLTS, 201-800 AMPERES
ALL 3-PHASE VOLTAGES, 201-3000 AMPERES
Obtain acceptance for 1-phase installations larger than 400 amperes from the Company
Customer furnishes and installs:
1. Company listed transocket (see M-21 & D-17).
2. Company listed transformer rated meter socket, usually
supplied with transocket (see D-18).
3. Service lateral conduit (see Notes 1, 2 & 3).
4. 4" Galvanized rigid or IMC 90° elbow with 24" radius.
5. Insulated conduit bushing (see Note 4).
6. Service entrance conduit.
7. Galvanized steel framing channel, 1-5/8" x 1-5/8" x 12 Ga.
8. Conduit clamps.
9. 3" galvanized rigid with galvanized end cap (see Note 5).
10. Concrete footing (12" min. hole size).
Company furnishes and installs:
11. Service lateral.
12. Watthour meter, current
transformers and associated
meter wiring.
Notes:
1. Galvanized rigid or IMC with threaded ends and fittings. Metallic conduit shall be bonded. For services
201-400 amperes, one 4" conduit with 24" bend radius is required. For services larger than 400 Amperes
consult the local Company office for number and size of the service lateral conduits.
2. Conduits to be grouped at end furthest from the termination compartment to allow for service lateral bending.
See pages U-26 & U-28 for conduit details.
3. For 201-1600 ampere services, a Company listed wireway may be used for Item 3 (see D-18).
4. Service lateral conduit shall have a temporary waterproof end cap to prevent the accumulation of water, ice
and other foreign matter from inside the conduit.
5. As an alternative to Item 9 above; 4" x 4" x 3/8" galvanized steel angle may be used.
6. For concrete encased service lateral refer to U-14, U-22 and U-23.
FRONT VIEW
U-12
SIDE VIEW
SERVICE TERMINATION IN A FREE STANDING TRANSOCKET
1-PHASE, 120/240 VOLTS, 201-800 AMPERES
FOR FARM SERVICE ONLY
Obtain acceptance for installations larger than 400 amperes from the Company
Customer furnishes and installs:
1. Company listed transocket (see M-21 & D-17).
2. Company listed transformer rated meter socket, usually
supplied with transocket (see D-18).
3. Service lateral conduit (see Notes 1, 2 & 3).
4. 4" Galvanized rigid or IMC 90° elbow with 24" radius.
5. Insulated conduit bushing (see Note 4).
6. Service-entrance conduit.
7. Galvanized steel framing channel, 1-5/8" x 1-5/8" x 12 Ga.
8. Conduit clamps.
9. Post, 6" x 6", pressure treated for Ground Contact
(preservative retention of .60 # per cu. ft.).
10. Wood, 2X, pressure treated for aboveground use
(preservative retention of .40 # per cu. ft.).
11. Concrete footing (12" min. hole size).
Company furnishes and installs:
12. Service lateral.
13. Watthour meter, current
transformers and associated
meter wiring.
Notes:
1. Galvanized rigid or IMC with threaded ends and fittings. Metallic conduit shall be bonded. For services
201-400 amperes, one 4" conduit with 24" bend radius is required. For services larger than 400 Amperes
consult the local Company office for number and size of the service lateral conduits.
2. Conduits to be grouped at end furthest from the termination compartment to allow for service lateral bending.
3. For 201-800 ampere services, a Company listed wireway may be used for Item 3 (see D-18).
4. Service lateral conduit shall have a temporary waterproof end cap to prevent the accumulation of water, ice
and other foreign matter from inside the conduit.
FRONT VIEW
SIDE VIEW
U-13
SERVICE TERMINATION IN AN OUTDOOR TRANSOCKET
CONCRETE ENCASED LATERAL
1-PHASE, 120/240 VOLTS, 201-800 AMPERES
ALL 3-PHASE VOLTAGES, 201-3000 AMPERES
(NOT FOR AC NETWORK)
Obtain acceptance for 1-phase installations larger than 400 amperes from the Company
Customer furnishes and installs:
1. Company listed transocket with transformer rated
meter socket mounted on cover (see Note 1).
2. Service-entrance conduit and conductors.
3. Metallic conduit shall be bonded.
4. Service lateral conduit (see Notes 2 & 3).
5. Conduit supports solidly attached to building.
6. Solid bar.
Company furnishes and installs:
7. Service lateral conduit and concrete envelope.
8. Service lateral with compression lug
terminations.
9. Watthour meter, current transformers and
associated meter wiring (not shown, see
Metering Section M-21).
Notes:
1. The cable trough compartment (for 401-3000 ampere services) is for the Company's service lateral
cables only. This compartment may be on the left side, contact your distributor or manufacturer.
2. Galvanized rigid or galvanized intermediate conduit with threaded ends and threaded fittings at the
transocket. Service sizes 201-400 amperes require one 4" conduit. For larger services consult the
local Company office for the proper number and size of the conduits. For services 1200-1600 amperes
with concrete encased service laterals, a 1600 ampere wireway may be substitured for the conduits.
See sheet D-18, Note (1) for correct burial depth.
3. Conduits to be grouped at the end furthest from the termination compartment to allow for service lateral
bending, (see Note 1). See pages U-26 & U-28 for conduit details.
U-14
SERVICE TERMINATION IN AN OUTDOOR TRANSOCKET
DIRECT BURIED LATERAL
1-PHASE, 120/240 VOLTS, 201-800 AMPERES
ALL 3-PHASE VOLTAGES, 201-1200 AMPERES
Obtain acceptance for 1-phase installations larger than 400 amperes from the Company
Customer furnishes and installs:
1. Company listed transocket with transformer rated
meter socket mounted on cover (see Note 1).
2. Service-entrance conduit and conductors.
3. Bonding. Metallic conduit shall be bonded.
4. Wireway, preferred, 1600 Ampere Maximum (see D-18).
5. Service lateral conduit (see Notes 2, 3 & 4).
6. Conduit supports solidly attached to building.
7. Solid bar.
Company furnishes and installs:
8. Service lateral with compression lug
terminations.
9. Watthour meter, current transformers
and associated meter wiring (not
shown, see Metering Section M-21).
Notes:
1. The cable trough compartment (for 401-1200 ampere services) is for the Company's service lateral
cables only. This compartment may be on the left side, contact your distributor or manufacturer.
2. Service lateral conduit shall have a temporary waterproof end cap when installed to prevent the
accumulation of water, ice and other foreign matter inside the conduit.
3. Galvanized rigid or galvanized intermediate conduit with threaded ends and threaded fittings. For
services 201-400 amperes, one 4" conduit with 24" bend radius is required. For larger services
consult the local Company office for the proper number and size of the conduits.
4. Conduits to be grouped at the end furthest from the termination compartment to allow for service lateral
bending, (see Note 1). See pages U-26 & U-28 for conduit details.
U-15
SERVICE TERMINATION IN A TRANSOCKET FIRST FLOOR INSTALLATION
CONCRETE ENCASED LATERAL
1-PHASE, 120/240 VOLTS, 201-800 AMPERES
ALL 3-PHASE VOLTAGES, 201-3000 AMPERES
Obtain acceptance from the Company
Customer furnishes and installs:
1. Company listed transocket (see M-21 & D-17).
2. Transformer rated meter socket, usually supplied with transocket
(see D-18).
3. Service lateral conduit (see Note 1).
4. Continuous concrete envelope with 3" of concrete on all sides
(see Note 1).
5. 4" I.D. 90° bend with 36" minimum radius (see Note 1).
6. Steel reinforcing rods, 5/8" x 2'.
7. Insulated bushing & temporary watertight end cap.
Company furnishes and installs:
8. Service lateral, conduit, coupling and
concrete envelope.
9. Watthour meter, current transformers
and associated meter wiring.
Notes:
1. Galvanized rigid or galvanized intermediate with threaded ends, or rigid nonmetallic schedule 40 PVC. For
services 201- 400 Amperes, one 4" conduit and 90° elbow with 24" bend radius is required. For larger services
consult the Local Company Office. See pages U-26 & U-28 for conduit details.
2. The cable trough compartment (for 401-3000 ampere services) is for the Company's service lateral cables only.
This compartment may be on the left side, contact your distributor or manufacturer.
U-16
SERVICE TERMINATION IN A TRANSOCKET FIRST FLOOR INSTALLATION
DIRECT BURIED LATERAL
1-PHASE, 120/240 VOLTS, 201-800 AMPERES
ALL 3-PHASE VOLTAGES, 201-1200 AMPERES
Obtain acceptance from the Company
Customer furnishes and installs:
1. Company listed transocket (see M-21 & D-17).
2. Transformer rated meter socket, usually supplied with Transocket
(see D-18).
3. Service lateral conduit (see Note 1).
4. Continuous concrete envelope with 3" of concrete on all sides
(see Note 1).
5. 4" I.D. 90° bend with 36" minimum radius (see Note 1).
6. Insulated bushing & temporary watertight end cap.
Company furnishes and installs:
7. Watthour meter, current transformers
and associated meter wiring.
8. Service lateral (not shown).
Notes:
1. Galvanized rigid or galvanized intermediate with threaded ends, or rigid nonmetallic schedule 40 PVC. For
services 201 - 400 Amperes, one 4" conduit and 90° elbow with 24" bend radius is required. For larger services
consult the Local Company Office. See pages U-26 & U-28 for conduit details.
2. The cable trough compartment (for 401-1200 ampere services) is for the Company's service lateral cables only.
This compartment may be on the left side, contact your distributor or manufacturer.
U-17
SERVICE TERMINATION IN A TERMINATION COMPARTMENT
DIRECT BURIED OR CONCRETE ENCASED LATERAL
ALL 1-PHASE VOLTAGES, 400-800 AMPERES
ALL 3-PHASE VOLTAGES, 400-3000 AMPERES ONLY
Obtain acceptance for 1-phase installations larger than 400 amperes from the Company
Customer furnishes and installs:
1. Company listed termination compartment (see Note 1 and D-19).
2. Wireway, 400-1600 Amperes Max.(see Note 2 & D-18).
3. Service lateral conduit 400-3000 Amperes (see Note 3).
4. Conduit supports.
5. Service-entrance conduit (see Note 4).
6. Service-entrance conductors (see Note 5).
7. Bonding. Metallic conduit shall be bonded.
8. 90{ metallic elbow (see Note 6).
9. Insulated conduit bushing.
Company furnishes and installs:
10. Service lateral and connectors.
11. Conduit package, 801-3000
Amperes.
Notes:
1. The termination compartment may be bonded to the neutral termination pad.
2. For services 1600 Amperes or less the wireway is preferred. If the wireway cannot be used, such as where the
termination compartment is located in a paved area, conduit may be used. Contact the local office for approval
and number of conduits required.
3. 4" galvanized rigid or IMC shall have threaded ends and locknuts at the termination compartment. Set screw or
threadless fittings shall not be used. For concrete encased laterals the lower ends are not required to be
threaded. Conduits are to be located on 6" centers and extend to grade level. Contact the local office for
approval and number of conduits required. See page U-26 for conduit details. For services 1200-1600 amperes
with concrete encased service laterals, a 1600 ampere wireway may be substituted for the conduits. See sheet
D-18, Note (1) for correct burial depth.
4. If the service-entrance conduits are located above the termination pads, watertight hubs or sealing locknuts are
required. When the service-entrance conduit enters box at the top watertight hubs are required.
5. The customer's service-entrance conductors shall leave the termination compartment as a maximum of two
circuits regardless of the number of conductors per phase.
6. Galvanized rigid or galvanized intermediate 90{ metallic elbows. The ends shall be threaded and threaded
couplings are to be used.
• 201-400 amperes, one 4" conduit with 36" radius elbow.
• 401-800 amperes, two 4" conduits with 36" radius elbows.
U-18
WITH SERVICE LATERAL DIRECT BURIED IN EARTH
WITH SERVICE LATERAL IN CONDUIT
U-19
SERVICE TERMINATION IN A TERMINATION COMPARTMENT ABOVE GRADE
DIRECT BURIED OR CONCRETE ENCASED SERVICE LATERAL CONDUITS
AND SERVICE ENTRANCE CONDUITS EXITING THE BOTTOM
ALL 1-PHASE VOLTAGES, 400-800 AMPERES
ALL 3-PHASE VOLTAGES, 400-3000 AMPERES ONLY
Obtain acceptance for 1-phase installations larger than 400 amperes from the Company
Customer furnishes and installs:
1. Company listed termination compartment (see Note 1 & D-19).
2. Termination pads, see Note 2.
3. Service lateral conduit 801-3000 Amperes (see Note 3).
4. Conduit supports, 2 minimum.
5. Service-entrance conduit (see Note 4).
6. Service-entrance conductors (see Note 5 & 6).
7. Bonding. Metallic conduit shall be bonded.
8. 90{ metallic elbow (see Note 7).
9. Insulated conduit bushing.
Company furnishes and installs:
10. Service lateral and connectors
(see Note 8).
11. Conduit package.
Notes:
1. The termination compartment may be bonded to the neutral termination pad.
2. The termination pads are to be raised to their highest position.
3. The service lateral conduits are to be 4" galvanized rigid or IMC with threaded ends and locknuts at the
termination compartment and installed in a row, on 6" centers, in the front of the compartment. Set screw
or threadless fittings shall not to be used. If the service lateral is to be installed in a concrete encased duct
package the lower ends are not required to be threaded and shall extend to grade level. Contact the Company
for approval and number of conduits required.
4. The service-entrance conduits are to be located at the back of the termination compartment and in a row.
5. The customer's service-entrance conductors are to terminate on the back of the termination pads and shall
leave the termination compartment as a maximum of two circuits regardless of the number of conductors per
phase. They shall not share bolts with the service lateral.
6. The service entrance conductors are to be trained so to leave the front of the compartment available for training
the service lateral conductors.
7. Galvanized rigid or galvanized intermediate 90{ metallic elbows. The ends shall be threaded and threaded
couplings are to be used.
8. The service lateral conductors will terminate on the front of termination pads.
U-20
U-21
SERVICE TERMINATION IN A FREE STANDING TERMINATION COMPARTMENT
ALL 1-PHASE VOLTAGES, 400 - 800 AMPERES
ALL 3-PHASE VOLTAGES, 400 - 3000 AMPERES
Obtain acceptance for 1-phase installations larger than 400 amperes from the Company
Customer furnishes and installs:
Company furnishes and installs:
1. Company listed termination compartment
13. Service lateral and connectors (see Note 8)
(see Note 1 & D-19).
14. Conduit package.
2. Termination pads (see Note 2).
3. Service lateral conduit (see Note 3).
4. Conduit supports, 2 min.
5. 90 metallic elbow, 36" radius (see Note 4).
6. Service-entrance conduit (see Note 5).
7. Service-entrance conductors (see Note 6 & 7).
8. Bonding (not shown). Metallic conduit shall be bonded.
9. Insulated conduit bushing.
10. Structure supports (see Note 9 & 10).
400 – 1600 Amperes - 3" Galvanized rigid conduit.
1601 – 3000 Amperes - 4" Galvanized rigid conduit.
11. Concrete footing, 12" min. diameter.
12. Galvanized steel framing channel, 1-5/8" x 1-5/8" x 12 Ga.
Notes:
1. The termination compartment may be bonded to the neutral termination pad.
2. The termination pads are to be raised to their highest position.
3. The service lateral conduits are to be 4" galvanized rigid or IMC with threaded ends and locknuts at the
termination compartment and installed in a row, on 6" centers, in the front of the compartment. Set screw
or threadless fittings shall not to be used. If the service lateral is to be installed in a concrete encased duct
package the lower ends are not required to be threaded and shall extend to grade level. Contact the
Company for approval and number of conduits required.
4. Galvanized rigid or galvanized intermediate 90º, 36" radius, metallic elbows. The ends shall be threaded and
threaded couplings are to be used.
5. The service-entrance conduits are to be located at the back of the termination compartment and in a row.
6. The customer's service-entrance conductors shall leave the termination compartment as a maximum of two
circuits regardless of the number of conductors per phase. They shall not share bolts with the service lateral.
7. The service entrance conductors are to terminate on the back of the termination pads and be trained so to
leave the front of the compartment available for training the service lateral conductors.
8. The service lateral conductors will terminate on the front of termination pads.
9. To prevent water from entering the supports they must be either capped or filled with concrete.
10. The supports must be spaced far enough apart to allow the service entrance conduits to pass between
them. To calculate the minimum distance needed between the supports (center to center) use the formula;
(6 x n) + d. Where “n” is the number of conduits and “d” is the diameter of the footings.
U-22
U-23
SERVICE TERMINATION IN A TERMINATION COMPARTMENT
CONCRETE ENCASED SERVICE LATERAL
ALL 1-PHASE VOLTAGES, 400-800 AMPERES
ALL 3-PHASE VOLTAGES, 400-3000 AMPERES ONLY
AC NETWORK, 0-800 AMPERES ONLY
MULTI-METERED INSTALLATIONS
Obtain acceptance for 1-phase installations larger than 400 amperes from the Company
Customer furnishes and installs:
1. Company listed termination compartment (see Note 1 and D-19).
2. Service lateral conduit 400-3000 Amperes (see Note 2).
3. Conduit supports.
4. Service-entrance conduit (see Note 3).
5. Service-entrance conductors (see Note 4).
6. Bonding. Metallic conduit shall be bonded.
Company furnishes and installs:
7. Service lateral and connectors.
8. Conduit package.
Notes:
1. The termination compartment may be bonded to the neutral termination pad.
2. 4" galvanized rigid or IMC with threaded ends and locknuts at the termination compartment, the lower ends
are not required to be threaded. Set screw or threadless fittings shall not be used. Conduits are to be located
on 6" centers and extend to grade level. Contact the local office for approval and number of conduits required.
See pages U-26 & U-28 for conduit details. For services 1200-1600 amperes with concrete encased service
laterals, a 1600 ampere wireway may be substituted for the conduits. See sheet D-18, Note (1) for correct burial
depth.
3. If the service-entrance conduits are located above the termination pads, watertight hubs or sealing locknuts
are required. When the service-entrance conduit enters box at the top watertight hubs are required.
4. The customer's service-entrance conductors shall leave the termination compartment as a maximum
of two circuits regardless of the number of conductors per phase.
Side View
U-24
Front View
SERVICE TERMINATION IN A TERMINATION COMPARTMENT
LOCATED BELOW GRADE CONCRETE ENCASED LATERAL
ALL 1-PHASE VOLTAGES, 400-800 AMPERES
ALL 3-PHASE VOLTAGES, 400-3000 AMPERES
(AC NETWORK, 0-800 AMPERES ONLY)
FOR MANHOLE AND NETWORK AREAS ONLY (SUCH AS DOWNTOWN MILWAUKEE)
Customer provides:
1. Company listed termination compartment (see Note 1 and D-19a).
2. Service lateral conduit (see Note 2).
3. Terminal adapter with locknuts and insulated bushing.
4. Steel reinforcing rods, 5/8" x 6'.
5. Continuous concrete envelope with a minimum of 3" of concrete
on all sides.
6. Service-entrance conduit. Metallic conduit shall be bonded.
7. Service-entrance conductors (see Note 3).
8. Temporary watertight end cap.
Company furnishes and installs:
9. Service lateral conduit, concrete
encased.
10. Service lateral and connectors.
Notes:
1. The termination compartment may be bonded to the neutral termination pad. Only termination compartments
listed on Page D-19a as for use below grade are to be used. These units have termination pads that are
adjustable to obtain the 24" min. from the top of the pad to the bottom of the conduits.
2. 4" Rigid nonmetallic schedule 40 PVC conduit per NEMA standard TC-2. Conduits are to be arranged
horizontally and on 6" centers as shown. Contact the local office for number of conduits required.
3. The customer's service-entrance conductors shall leave the termination compartment as a maximum
of two circuits regardless of the number of conductors per phase.
U-25
SERVICE TERMINATION IN A TERMINATION COMPARTMENT
BUILDING WITHOUT A BASEMENT, FIRST FLOOR INSTALLATION
ALL 1-PHASE VOLTAGES, 400-800 AMPERES
ALL 3-PHASE VOLTAGES, 400-3000 AMPERES
(AC NETWORK, 0-800 AMPERES ONLY)
MULTI-METERED INSTALLATIONS
Obtain acceptance for 1-phase installations larger than 400 amperes from the Company
Customer furnishes and installs:
1. Company listed termination compartment (see Note 1 and D-19).
2. Service lateral conduit (see Note 2).
3. 4" I.D. 90{ elbow (see Note 2).
4. Steel reinforcing rods, 5/8" x 6'.
5. Conduit spacers.
6. Continuous concrete envelope with a minimum of 3" of concrete
on all sides.
7. Bonding. Metallic conduit shall be bonded.
8. Service-entrance conduit.
9. Service-entrance conductors (see Note 3).
10. Temporary watertight end cap.
Company furnishes and installs:
11. Service lateral conduit, coupling
and concrete envelope.
12. Service lateral and connectors.
Notes:
1. The termination compartment may be bonded to the neutral termination pad.
2. 4" Galvanized rigid, galvanized intermediate or rigid nonmetallic schedule 40 PVC conduit. If metallic
conduit is used, the ends shall be threaded and threaded connectors and couplings are to be used.
• 201-400 amperes, one 4" conduit with 36" radius elbow.
• 401-800 amperes, two 4" conduits with 36" radius elbows.
• 801-1200 amperes, three 4" conduits with 36" radius elbows.
• 1201-1600 amperes, four 4" conduits with 36" radius elbows.
• For services larger than 1600 amperes contact local office for number of conduits required.
3. The customer's service-entrance conductors shall leave the termination compartment as a maximum
of two circuits regardless of the number of conductors per phase.
4. Conduit for direct buried installations shall extend a minimum of 12" into undisturbed earth.
CONDUIT DETAILS FOR CONCRETE ENCASED SERVICE LATERALS
U-26
WITH DIRECT BURIED SERVICE LATERAL
WITH CONCRETE ENCASED SERVICE LATERAL
U-27
SERVICE TERMINATION IN A CUSTOMER'S TERMINATION COMPARTMENT
FREE STANDING SWITCHGEAR LOCATED BELOW GRADE
FOR AREAS SERVED BY CONDUIT AND CABLE ONLY
FOR ALL 3-PHASE VOLTAGES, 2000 - 4000 AMPERES (see Note 3).
NOT FOR AC NETWORK (DOWNTOWN MILWAUKEE)
REQUIRES COMPANY APPROVAL
Customer furnishes and installs:
1. Completely enclosed termination compartment with rigidly supported
bus bars, located and drilled as shown (see Notes 1 & 2).
2. 4" Schedule 40 PVC conduit, concrete encased. See table for the
minimum number of conduits required.
3. Temporary watertight end caps.
4. Reinforcing rods (epoxy coated re-bar).
Company furnishes and installs:
5. Service lateral conduit and concrete
envelope (not shown). We Energies
does not lace cables.
6. Service lateral conductors with
compression lug terminations
(not shown).
Notes:
1. • Rigidly supported Barriers shall separate the termination compartment from other compartments.
• Front panels are to be removable and sealable; and when removed shall leave a clear and unobstructed
opening exposing only the service lateral termination area.
• Minimum live part clearances: 2" phase-to-phase, 1" phase-to-ground.
2. Only the service lateral conductors are allowed in this termination compartment. The grounding electrode
conductor shall not pass-thru or terminate in this compartment, nor shall bonding of the neutral and grounding
buses be done in this compartment.
3. Three sets of prints for the switchgear termination and metering compartments are to be sent to the local district
office for acceptance prior to any construction.
4. The dimension shown is from the bottom of the conduit to the top hole in the bus bar. For 3Ø, 3 wire
installations omit the neutral bus and use the 40" dimension.
5. See Pages M-24 & 25 for metering details.
U-28
SWITCHGEAR REQUIREMENTS 2000, 3000 AND 4000 AMPERES
SWITCHGEAR
AMPERAGE
MINIMUM WIDTH
OF TERMINATION
COMPARTMENT
SETS OF
HOLES
REQUIRED
MINIMUM
NUMBER
OF DUCTS
WIDTH OF
CONDUIT
PACKAGE
2000
24 Inches
6
6
24 Inches
3000
30 Inches
8
8
30 Inches
4000
36 Inches
10
10
36 Inches
Note: The dimensions shown above are minimums and should not be used for design purposes.
For actual dimensions contact the switchgear manufacturer.
U-29
SERVICE TERMINATION IN A CUSTOMER'S TERMINATION COMPARTMENT
FREE STANDING SWITCHGEAR LOCATED ON FIRST FLOOR OR ABOVE
ALL 3-PHASE VOLTAGES, 2000 - 4000 AMPERES (see Note 3).
NOT FOR AC NETWORK (DOWNTOWN MILWAUKEE)
Customer furnishes and installs:
1. Completely enclosed termination compartment with rigidly supported
bus bars located and drilled as shown (see Notes 1 & 2).
2. 4" Schedule 40 PVC conduit, concrete encased. See table for
minimum number of conduits required. All metallic conduit must
be bonded.
3. Temporary watertight end caps.
4. Reinforcing rods (epoxy coated re-bar).
5. 4" Schedule 40 PVC, 90° elbows with 36" radius
Company furnishes and installs:
6. Service lateral conduit and concrete
envelope (not shown). We Energies
does not lace cables.
7. Service lateral conductors with
compression lug terminations
(not shown).
Notes:
1. • Rigidly supported barriers shall separate the termination compartment from other compartments.
• Front panels are to be removable and sealable; and when removed shall leave a clear and unobstructed
opening exposing only the service lateral termination area.
• Minimum live part clearances: 2" phase-to-phase, 1" phase-to-ground.
2. Only the service lateral conductors are allowed in this termination compartment. The grounding electrode
conductor shall not pass-thru or terminate in this compartment, nor shall bonding of the neutral and grounding
buses be done in this compartment.
3. Three sets of prints for the switchgear, termination and metering compartments are to be sent to the local
district office for acceptance prior to any construction.
4. The dimension shown is from the top of the conduit to the lower hole in the bus bar. For 3Ø, 3 wire installations
omit the neutral bus and use the 40" dimension.
5. The preferred termination of service laterals is on the outside of a building (or structure). Service laterals that
terminate inside of a building shall terminate immediately upon entering as shown in this manual. The raceway
for service laterals under or thru a building shall not extend longer than 8’ after penetrating the outside wall.
6. Where the termination compartment is located on a mezzanine, a continuous duct package must be installed
with a maximum distance of 14’ from final grade to the bottom of the termination compartment.
7. See Pages M-24 & 25 for metering details.
U-30
SWITCHGEAR REQUIREMENTS 2000, 3000 AND 4000 AMPERES
SWITCHGEAR
AMPERAGE
MINIMUM WIDTH
OF TERMINATION
COMPARTMENT
SETS OF
HOLES
REQUIRED
MINIMUM
NUMBER
OF DUCTS
WIDTH OF
CONDUIT
PACKAGE
2000
24 Inches
6
6
24 Inches
3000
30 Inches
8
8
30 Inches
4000
36 Inches
10
10
36 Inches
Note: The shown above are minimums and should not be used for design purposes.
For actual dimensions contact the switchgear manufacturer.
U-31
POLICY ON SERVICES FOR COMMUNICATION TOWERS
1.0 NEW SERVICES
We Energies policy is to provide one electric service to each tower site. This service must be sized
to accommodate present and future carriers that may have space on the tower with a meter position for
each carrier. Applications for service to tower sites shall include information on each tower's capacity
(i.e. total number of carriers the tower will accommodate). This information is a requirement for electric
service to the tower site.
If additional carriers are allowed space on the tower and the size of the service or number of meter
sockets need to be increased, the owner shall be responsible for increasing the size of the service and/or
the number of meter sockets. Additional services are not permitted.
2.0 EXISTING SERVICES
For existing towers the owner will be required to install a multi-position metering bank to serve the number
of additional tenants that may attach to the tower in the future.
Existing services installed prior to Friday, January 19, 2001 will be allowed to remain and after this date
additional service to a tower site must meet the requirements of Rule 1.0 above.
U-32
FREE STANDING SERVICE FOR COMMUNICATION TOWER
SERVICE TERMINATION IN A MULTI-POSITION METER SOCKET
DIRECT BURIED LATERAL
1-PHASE, 120/240 VOLTS, 0-800 AMPERE
0-200 AMPERES PER METER, 2-6 METERS
Customer furnishes and installs:
1. Service-entrance conduit.
2. Service-entrance conductors.
3. Metallic conduit shall be bonded.
4. Company listed 2 to 6 position meter socket
(see Notes 1 & 4 and Sheet D-10).
5. Service lateral conduit (see Note 2).
6. Insulated conduit bushings (see Note 3).
7. 4” galvanized rigid or IMC 90º elbow with 24” radius.
8. Galvanized steel framing channel, 1 5/8” x 1 5/8” x 12 ga.
9. Conduit clamps.
10. 3” galvanized rigid with galvanized end cap (see Note 5).
11. Concrete footing (12” min. hole size).
Company furnishes and installs:
12. Service lateral.
13. Watthour meters.
Notes:
1. Separate cable compartment is provided for the Company’s service lateral cable only.
2. 4” galvanized rigid or galvanized intermediate conduit with threaded ends and fittings. Consult the Company
office for the proper number of service lateral conduits.
3. Service lateral conduits shall extend underground to a point outside of fenced area and have temporary
waterproof end caps to prevent the accumulation of water, ice and other foreign matter inside the conduits.
4. Each meter position shall be marked on the outside of the socket or by the breaker (if available) with the
address of the unit served. If the marking is on the outside of a removable cover, it shall also be marked on
the inside of the meter socket in a visible location. This marking shall also be placed on the corresponding
distribution panel(s). The marking shall be a permanent label with 1/2" block letters and may consist of
individual self-stick letters or numbers, suitable for the location so as to be considered permanent.
5. As an alternative to Item 10 above; 4” x 4” x 3/8” galvanized steel angle may be used.
U-33
METERING - SECONDARY
• Contents - Metering ............................................................................................................... M-1
• General Requirements for Metering ...................................................................................... M-2, M-3
• Meter Socket Mounting.......................................................................................................... M-4
• Guards for Outdoor Installations............................................................................................ M-5
Metering Installations For Secondary Services:
Meter Socket with Overhead Service Entrance:
• 1Ø, 2-Wire Service, all voltages, 0-100 Amperes.................................................................. M-6
• 1Ø, 3-Wire Service, 120/240 Volts, 0-320 Amperes.............................................................. M-7
208Y/120 Volts, 0-100 Amperes ........................................................... M-8
•
3Ø, 3-Wire Service, 240 Volts, 0-200 Amperes..................................................................... M-8
480 Volts, 0-200 Amperes .................................................................... M-9
3Ø,
4-Wire
Service,
208Y/120
Volts, 480Y/277 Volts, 0-200 Amperes ................................. M-10
•
Meter Socket for Customer Owned Street Lighting:
• 1Ø, 3-Wire Service, 120/240 or 240/480 Volts, 0-200 Amperes............................................ M-11
Meter Pedestal with Underground Service Lateral:
• 1Ø, 2-Wire Service, 120 Volts, 0-30 Amperes....................................................................... M-12
• 1Ø, 3-Wire Service, 120/240 or 240/480 Volts, 0-200 Amperes............................................ M-13
120/240 Volts, 201-320 Amperes.......................................................... M-14
208Y/120 Volts, 0-100 Amperes ........................................................... M-15
• 3Ø, 3-Wire Service, 240 or 480 Volts, 0-200 Amperes.......................................................... M-15
• 3Ø, 4-Wire Service, 208Y/120 Volts or 480Y/277 Volts, 0-200 Amperes.............................. M-16
Meter Socket with Underground Service Lateral:
• 1Ø, 3-Wire Service, 120/240 Volts, 0-200 Amperes.............................................................. M-17
208Y/120 Volts, 0-100 Amperes ........................................................... M-18
• 3Ø, 3-Wire Service, 240 or 480 Volts, 0-200 Amperes.......................................................... M-18
• 3Ø, 4-Wire Service, 208Y/120 Volts or 480Y/277 Volts, 0-200 Amperes.............................. M-19
Transocket with Overhead Service Entrance:
• 1Ø, 3-Wire, 120/240 Volts, 201-800 Amperes, All 3Ø Voltages, 201-2000 Amperes ........... M-20
Transocket with Underground Service Lateral:
• 1Ø, 3-Wire, 120/240 Volts, 201-800 Amperes, All 3Ø Voltages, 201-2000 Amperes
• 3Ø, 4-Wire, 208Y/120 Volts or 480Y/277 Volts, 201-3000 Amperes..................................... M-21
Outdoor Current Transformer Metering (Transocket) with Customer Disconnect
• 1Ø, 3 Wire, 120/240 Volts, 201-800 Amperes, All 3Ø Voltages, 201-1200 Amperes............ M-22
Meter Stack Socket Breaker Installation:
• All Voltages, 0-200 Amperes per Meter................................................................................. M-23
Current Transformer Metering in Free Standing Switchgear (Indoor):
• All Voltages ........................................................................................................................ M-24, M-25
Modular Metering (Indoor):
• 1Ø, 3-Wire, 120/240 Volts, 208Y/120 Volts, All 3Ø Voltages, 0-200 Amperes per Meter ..... M-26
M-1
GENERAL REQUIREMENTS FOR METERING
General
The information covered in this section is applicable to overhead, underground, substation, and AC network
sources of supply covered in the foregoing sections of the manual.
Location of Meters and Metering Equipment
1. Outdoor metering is required for residential, one or two customer, and farm installations with 1-phase service
of 200 amperes or less.
2. Meters shall be installed outdoors in cases such as summer dwellings and other premises not occupied during
the entire year or not accessible during regular working hours of Company personnel.
3. For outdoor installations with an OH service drop, the centerline of all meters shall be between 4 and 6 feet
from the finished grade.
4. For outdoor installations with an UG service lateral, the centerline of all meters shall be between 3 and 6 feet
from the finished grade.
5. For indoor installations, locate meters in the basement or other suitable and readily accessible place as near
as possible to the point where the service enters the building. The centerline of all meters shall be between 4
and 6 feet above the floor (not applicable to ganged or grouped installations of more than 2 units as covered
in 6 below).
6. For indoor group installations the centerline of all meters shall be between 2 and 6 feet above the floor. For
apartment, commercial and other appropriate buildings of more than 2 floors, meters may be located on the
different floors of the building provided they are grouped in enclosures as near as practicable to the risers
serving the floors and the wiring and metering layout for the building is accepted by the Company.
7. For multiple unit buildings (two or more), each meter position shall be marked on the outside of the socket or
by the breaker (if available) with the address of the unit served. If the marking is on outside of the removable
cover, it shall also be marked on the inside of the meter socket in a visible location. This marking shall also
be placed on the corresponding distribution panel(s). The marking shall be a permanent label with 1/2" block
letters and may consist of individual self-stick letters or numbers, suitable for the location so as to be
considered permanent.
8. There shall be a 3' minimum of unobstructed working space, measured from the meter face, in front of all
meters. This space shall extend from the floor or grade to a height of 6'-6". At least one entrance of sufficient
area shall be provided to give access to this working space.
9. The unobstructed space required in front of meter cabinets, current transformer compartments, and
transformer loss compensation cabinets shall be as defined by the "Working Space About Electrical
Equipment" section 110.26 of the National Electrical Code (latest revision as adopted by the states
of Michigan and Wisconsin). This unobstructed space shall extend from the floor or ground to a height
of 6'-6". Equipment doors are required by the NEC to open a minimum of 90°.
10. Ample space shall be provided for all meters, metering equipment, and other apparatus so that they can
be safely read, inspected, and tested. Meter equipment shall not be located:
a. In animal enclosures, attics, closets, elevator or ventilating shafts, hallways, living quarters, stairways,
or rooms containing corrosive or explosive vapors (battery rooms).
b. Near stoves, radiators, steam or hot water pipes, or within 5' of moving machinery.
c. Above laundry equipment, plumbing fixtures or other bulky equipment.
d. Behind shrubbery or swinging doors, or over alleys, driveways, decks or porches (or over sidewalks
where practicable), or where it is necessary to trespass on adjacent property.
e. In hazardous locations as defined in articles 500 to 516 of the National Electric Code as amended
in Michigan by the Michigan Administrative Code and as amended in Wisconsin by the Wisconsin
Administrative Code.
f. Where subject to damage from falling ice, snow or other debris. If the metering equipment cannot be
moved to an area free of these hazards the necessary protection may be provided by a roof overhang or
gutter that extends a minimum of 12" past the face of the meter socket. In place of the roof overhang the
customer shall provide and install a deflector that shall extend 12" past the face of the meter socket and
be installed at a height greater than 6'-6" to comply with Notes 8 & 9 above.
11. Meter locations shall be free from excessive moisture, vibrations, and heat. Meters shall not be placed on
partitions, insecure walls or over doorways. Meters shall be shielded from magnetic disturbances and
protected from mechanical damage, moving machinery and belts by means of a suitable protecting cabinet.
12. 3' horizontal clearance between gas and electric metering equipment should be provided.
M-2
Methods of Mounting Metering Equipment
1. Socket-type meter mounting devices installed on concrete or masonry walls shall be fastened by
non-corrosive metal machine screws in lead sleeve, wedge-type expansion anchors.
2. All mounting devices for metering equipment shall be plumb.
Methods of Wiring Service Equipment and Meters
1. On outdoor installations, the knockouts of meter sockets, transockets, or meter pedestals shall not be used for
service entrance conductors unless the knockouts are located entirely below the lowest live parts.
2. Metered and unmetered conductors shall not be installed in the same conduit, wiring trough, channel, gutter
or similar enclosure.
3. Where a group of meters is supplied from a service raceway, the covers of the raceway must be provided with
a means for sealing where individual service taps are made into the raceway.
4. Termination compartments, meter mounting devices or current transformer compartments shall not be used
as junction boxes for additional customer circuit connections.
a. This includes taps for emergency circuits or fire alarms.
b. At single metered installations where 2 to 6 disconnects are used in place of a single main disconnect, a
customer owned junction box or switchboard section shall be installed on the load side of all Company
facilities for the purpose of making taps to the individual disconnects.
c. Customer provided termination compartments and transockets are permitted to have up to 2 circuits exiting
them.
5. Sockets shall be equipped with blank covers furnished by the customer at the time of installation.
6. The rating of a single service switch or the combined rating of all service switches connected to a
1-phase 120/240 volt service shall not exceed 400 amperes unless accepted by the Company.
7. A common grounding conductor shall be used to ground the service entrance equipment and the grounded
circuit conductor. A grounding conductor shall not be run from the meter socket to ground or through the
meter socket, termination compartment or transocket in going from the customer's main service switch or
disconnect means to ground. Direct grounding of meter sockets is permissible, only on meter poles where
the disconnecting means is installed at some other location. For multi-metered installations the grounding
electrode conductor may be bonded to the neutral in a termination compartment.
8. Service switches or service breakers shall be installed so that any one service switch or breaker, when
disconnected, shall not interrupt continuity of service to any other separately metered customer on the
premises.
9. All large installations not covered by this Metering Section require special consideration and the Company
shall be consulted in all cases. The customer shall submit 3 drawings of the proposed service equipment
and metering arrangement to the local Company office for acceptance.
10. Any service entrance that serves a 24-hour load, 30 days each month of 150 amperes or more, shall have
a current transformer metering installation.
11. Any fire pump service where the Full Load Running Amperage (FLRA) of the pump(s) exceeds 125 Amperes
shall have a current transformer metering installation.
12. On outdoor current transformer installations the meter cabinet and conduit shall be grounded, either by
bonding to the service entrance conduit or bus duct.
13. The Company shall meter only those voltages supplied to the customer by the Company; there will be no
Company metering after a customer-owned stepdown transformer.
14. On new installations it is the customer’s responsibility to ensure that the meter stops or grounding brackets
are clean and provide for a good electrical contact with the meter base.
15. Multi-metered installations shall be installed so as to balance the load on the service.
16. For Communication Tower Policy and Service Termination see pages U-32 and U-33.
M-3
METER SOCKET MOUNTING
Customer furnishes and installs:
1. Company listed meter socket.
2. Galvanized bolts, nuts and washers for mounting meter socket.
3. Galvanized thinwall spacers. They must be as long as the thickness
of the finished wall, such as siding, brick or stone (see Note 1).
4. Horizontally mounted 2"x 4" wood supports or #11 gauge minimum
thickness steel plates.
5. Studding for the building wall.
Company furnishes and installs:
6. Watthour meter.
Note:
1. The meter socket is to be so installed that it will be securely and permanently mounted both before
and after the finished wall is installed. The meter will not be installed until the socket is so mounted.
TOP VIEW
M-4
SIDE VIEW
GUARDS FOR OUTDOOR INSTALLATIONS
Customer furnishes and installs:
1. Galvanized steel pipe, schedule 40, 3-1/2" diameter by 6'-6" minimum length and filled with concrete.
Approximately 3.4 cu. ft. of concrete is required for the foundation and filling the pipe (see Note 1).
2. Galvanized steel pipe, schedule 40, 6" diameter by 8' minimum length and filled with concrete.
Approximately 4 cu. ft. of concrete is required for the foundation and filling the pipe (see Note 1).
3. Concrete footing. A Sono tube is recommended to prevent heaving due to frost.
Notes:
1. The Company shall be consulted concerning the type, placement and number of guards required.
LIGHT DUTY GUARD
HEAVY DUTY GUARD
M-5
METER SOCKET WITH OVERHEAD SERVICE ENTRANCE
1-PHASE, 2-WIRE, 120 VOLTS, 0-30 AMPERES 2
1-PHASE, 2-WIRE, 277 VOLTS, 0-60 AMPERES
1-PHASE, 2-WIRE, 240 3, 4 OR 480 VOLTS (UNGROUNDED) 4, 0-100 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE
Customer furnishes and installs:
1.Conduit and conductors.
2. Water-tight hub.
3. Company listed 4-terminal meter socket
(see Note 1 and Sheets D-3 & D-5).
4. Metallic conduit shall be bonded to the meter socket.
Company furnishes and installs the
Watthour meter.
Note:
1. Provide 4" clearance around meter from all foreign objects.
2. When supplied from a 1-phase, 3-wire, 120/240 volt grounded system
or a 3-phase, 4-wire, 208Y/120 volt grounded radial system.
3. When supplied from a 3-phase, 3-wire, 240 volt grounded system.
4. For maintenance only.
120, 240 or 277 VOLTS
M-6
480 (UNGROUNDED)
METER SOCKET WITH OVERHEAD SERVICE ENTRANCE
1-PHASE, 3-WIRE, 120/240 VOLTS, 0-320 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE
Customer furnishes and installs:
1. Conduit and conductors.
2. Water-tight hub.
3. Company listed 4-terminal meter socket
(see Note 1 and Sheets D-3 & D-5).
4. Metallic conduit shall be bonded to the meter socket.
Company furnishes and installs the
Watthour meter.
Note:
1. Provide 4" clearance around meter from all foreign objects.
M-7
METER SOCKET WITH OVERHEAD SERVICE ENTRANCE
1-PHASE, 3-WIRE, 208Y/120 VOLTS, 0-100 AMPERES*
3-PHASE, 3-WIRE, 240 VOLTS, 0-200 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE (See Note 3)
Customer furnishes and installs:
1. Conduit and conductors.
2. Water-tight hub.
3. Company listed 5-terminal meter socket (see Note 1 and Sheet D-4).
4. Metallic conduit shall be bonded to the meter socket.
5. 5th terminal. May be in the 6 or 9 o'clock position (see Note 2).
Company furnishes and installs the
Watthour meter.
Notes:
1. Provide 4" clearance around meter from all foreign objects.
2. If the potential tap from the neutral conductor to the 5th terminal is not supplied by the manufacturer it shall be
a #14 white insulated wire.
3. SW-F-M sequence is required for 208Y/120 Volt, AC network (downtown Milwaukee area), services located
indoors.
*2 phase wires and a neutral supplied from a 3-phase, 4-wire, 208Y/120 volt grounded system.
M-8
METER SOCKET WITH OVERHEAD SERVICE ENTRANCE
3-PHASE, 3-WIRE, 480 VOLTS (UNGROUNDED), 0-200 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE
Customer furnishes and installs:
1. Company listed 5-terminal meter socket with center
phase sliding link disconnect (see Note 1 and Sheet D-4).
2. Conduit and service entrance conductors.
3. Water-tight hub.
4. Metallic conduit shall be bonded to the meter socket.
5. 5th terminal. May be in the 6 or 9 o'clock position
(6 o’clock shown, see Note 2).
Company furnishes and installs the
Watthour meter.
Notes:
1. Provide 4" clearance around meter from all foreign objects.
2. When the 5th terminal is in the 9 o'clock position and the potential tap wire from the center phase
to the 5th terminal is not provided by the manufacturer a #14 black insulated wire shall be installed.
M-9
METER SOCKET WITH OVERHEAD SERVICE ENTRANCE
3-PHASE, 4-WIRE, 208Y/120 OR 480Y/277 VOLTS, 0-200 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE (See Note 3)
Customer furnishes and installs:
1. Conduit and conductors.
2. Water-tight hub.
3. Company listed 7-terminal meter socket (see Note 1 and Sheet D-4).
4. 7th terminal with potential tap (see Note 2).
5. Metallic conduit shall be bonded to the meter socket.
Company furnishes and installs the
Watthour meter.
Notes:
1. Provide 4" clearance around meter from all foreign objects.
2. If the potential tap from the neutral conductor to the 7th terminal is not provided by the manufacturer it
shall be a #14 white insulated wire.
3. SW-F-M sequence is required for indoor, 208Y/120 Volt, AC network (downtown Milwaukee), services.
M-10
METER SOCKET FOR CUSTOMER OWNED STREET LIGHTING
1-PHASE, 3-WIRE, 240/480 VOLTS (GROUNDED), 0-200 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE
Customer furnishes and installs:
1. Conduit and conductors.
2. Water-tight hub.
3. Company listed 4-terminal meter socket
(see Note 1 and Sheet D-6).
4. Metallic conduit shall be bonded to the meter socket.
Company furnishes and installs the
Watthour meter.
Notes:
1. Provide 4" clearance around meter from all foreign objects.
M-11
METER PEDESTAL WITH UNDERGROUND SERVICE LATERAL
1-PHASE, 2-WIRE, 120 VOLTS, 0-30 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE
Customer furnishes and installs:
1. Service-entrance conduit and conductors (see Note 1).
2. Company listed 4-terminal meter pedestal
(see Note 2 and Sheets D-11 & D-12).
3. Metallic conduit shall be bonded to the meter pedestal.
4. Service-entrance conductor, neutral.
5. Service-entrance conductor, phase or hot wire.
Company furnishes and installs:
6. Service lateral.
7. Watthour meter (not shown).
Notes:
1. Service-entrance conductors must exit the pedestal below the lowest live part and above grade.
2. Provide 4" clearance around meter from all foreign objects.
M-12
METER PEDESTAL WITH UNDERGROUND SERVICE LATERAL
1-PHASE, 3-WIRE, 120/240 or 240/4803 VOLTS, 0-200 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE
Customer furnishes and installs:
1. Service entrance conduit and conductors (see Note 1).
2. Company listed 4-terminal meter pedestal
(see Note 2 and Sheets D-11 & 12).
3. Metallic conduit shall be bonded.
Company furnishes and installs:
4 Service lateral.
5. Watthour meter (not shown).
Notes:
1. Service entrance conductors must exit the pedestal below the lowest live part and above grade.
2. Provide 4" clearance around meter from all foreign objects.
3. For use with 240/480 Volt, 1Ø, 3 Wire service, the pedestal must be rated for 480 Volts or above.
M-13
METER PEDESTAL WITH UNDERGROUND SERVICE LATERAL
1-PHASE, 3-WIRE, 120/240 VOLTS, 201-320 AMPERES (see Note 3)
METERING SEQUENCE: METER-SWITCH-FUSE
Customer furnishes and installs:
1. Company listed 4-terminal meter pedestal
(see Note 1 and Sheet D-11).
2. Service entrance conduit and conductors (see Note 2).
3. Bonding. Metallic conduit shall be bonded to the meter pedestal.
Company furnishes and installs:
4. Service lateral.
5. Watthour meter (not shown).
Notes:
1. Provide 4" clearance around meter from all foreign objects.
2. Service entrance conductors are allowed to leave as two circuits and must exit the pedestal
below the lowest live part and above grade.
3. This equipment is rated at 320 Amperes for continuous duty, which must not be exceeded.
4. Requires anti-inversion clip.
M-14
METER PEDESTAL WITH UNDERGROUND SERVICE LATERAL
1-PHASE, 3-WIRE, 208Y/120 VOLTS, 0-100 AMPERES*
3-PHASE, 3-WIRE, 240 OR 480 VOLTS (UNGROUNDED), 0-200 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE
Customer furnishes and installs:
1. Service entrance conduit and conductors (see Note 1).
2. Company listed 5-terminal meter pedestal
(see Notes 2 & 3 and Sheet D-12).
3. Metallic conduit shall be bonded to the meter pedestal.
4. 5th terminal. 6 o’clock position for 480 Volt, all others to
be in the 9 o'clock or (see Note 4).
Company furnishes and installs:
5. Service lateral.
6. Watthour meter (not shown).
Notes:
1. Service entrance conductors must exit the pedestal below the lowest live part and above grade.
2. Provide 4" clearance around meter from all foreign objects.
3. Meter pedestals used in 480 volt applications must be equipped with a center phase sliding link disconnect.
4. If the potential tap from the neutral conductor to the 5th terminal is not provided by the manufacturer it shall
be a #14 white insulated wire for 208Y/120 Volts or a #14 black insulated wire for 480 Volts (ungrounded).
208/120 or 240 VOLTS
480 VOLTS (UNGROUNDED)
* 2 phase wires and a neutral supplied from a 3-phase,4-wire, 208Y/120 volt grounded system.
M-15
METER PEDESTAL WITH UNDERGROUND SERVICE LATERAL
3-PHASE, 4-WIRE, 208Y/120 OR 480Y/277 VOLTS, 0-200 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE (See Note 4)
Customer furnishes and installs:
1. Service entrance conduit and conductors (see Note 1).
2. Company listed 7-terminal meter pedestal
(see Note 2 and Sheet D-12).
3. Metallic conduit shall be bonded to the meter pedestal.
4. 7th terminal with potential tap (see Note 3).
Company furnishes and installs:
5. Service lateral.
6. Watthour meter (not shown).
Notes:
1. Service entrance conductors must exit the pedestal below the lowest live part and above grade.
2. Provide 4" clearance around meter from all foreign objects.
3. If the potential tap from the neutral conductor to the 7th terminal is not provided by the manufacturer
it shall be a #14 white insulated wire.
4. SW-F-M sequence is required for 208Y/120 Volt, AC network (downtown Milwaukee area), services
located indoors.
M-16
METER SOCKET WITH UNDERGROUND SERVICE LATERAL
1-PHASE, 3-WIRE, 120/240 VOLTS, 0-200 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE
Obtain acceptance for 1-phase installations from the Company.
Customer furnishes and installs:
1. Service entrance conduit and conductors (see Note 1).
2. Company listed 4-terminal meter socket
(see Note 2 and Sheets D-7 & D-9).
3. Service lateral conduit.
4. Metallic conduit shall be bonded to the meter socket.
Company furnishes and installs:
5. Service lateral.
6. Watthour meter (not shown).
Notes:
1. For a 120 volt, 2-wire service, the service entrance conductors
consist of the neutral conductor and one of the phase conductors.
2. Provide 4" clearance around meter from all foreign objects.
M-17
METER SOCKET WITH UNDERGROUND SERVICE LATERAL
1-PHASE, 3-WIRE, 208Y/120 VOLTS, 0-100 AMPERES*
3-PHASE, 3-WIRE, 240 VOLTS OR 480 VOLTS (UNGROUNDED), 0-200 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE (See Note 3)
Customer furnishes and installs:
1. Company listed 5-terminal meter socket (see Note 1 and sheets D-8
& D-9). Center phase disconnect is required for 480 volt applications.
2. Service entrance conduit and conductors.
3. Service lateral conduit.
4. 5th terminal (see Note 2).
5. Metallic conduit shall be bonded.
Company furnishes and installs:
6. Service lateral.
7. Watthour meter (not shown).
Notes:
1. Provide 4" clearance around meter from all foreign objects.
2. For 1-phase, 208Y/120 volt and 3-phase, 240 volt the 5th terminal shall be in the 9 o’clock position. If the
potential tap from the 5th terminal to the grounded conductor is not provided by the manufacturer it shall be
a #14 white insulated wire. For 480 volt the 5th terminal shall be in the 6 o’clock position. If the potential tap
from the 5th terminal to the center phase conductor is not provided by the manufacturer it shall be a #14 black
insulated wire.
3. SW-F-M sequence is required for indoor, 208Y/120 Volt, AC network (downtown Milwaukee), services.
208Y/120* or 240 VOLTS
480 VOLTS (UNGROUNDED)
* 2 phase wires and a neutral supplied from a 3-phase, 4-wire, 208Y/120 volt grounded system.
M-18
METER SOCKET WITH UNDERGROUND SERVICE LATERAL
3-PHASE, 4-WIRE, 208Y/120 OR 480Y/277 VOLTS, 0-200 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE (See Note 3)
Customer furnishes and installs:
1. Service entrance conduit and conductors.
2. Company listed 7-terminal meter socket
(see Note 1 and Sheet D-8).
3. 7th terminal with potential tap (see Note 2).
4. Service lateral conduit.
5. Metallic conduit shall be bonded to the meter socket.
Company furnishes and installs:
6. Service lateral.
7. Watthour meter (not shown).
Notes:
1. Provide 4" clearance around meter from all foreign objects.
2. If the potential tap from the neutral conductor to the 7th terminal is not provided by the manufacturer it
shall be a #14 white insulated wire.
3. SW-F-M sequence is required for indoor, 208Y/120 Volt, AC network services (downtown Milwaukee).
M-19
TRANSOCKET WITH OVERHEAD SERVICE ENTRANCE
1-PHASE, 3-WIRE, 120/240 VOLTS, 201-800 AMPERES
ALL 3-PHASE VOLTAGES, 201-2000 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE (See Note 3)
Obtain acceptance for 1-phase installations larger than 400 amperes from the Company.
Customer furnishes and installs:
1. Company listed transocket with transformer rated
meter socket (see Note 1 and Sheets D-16 & D-18).
2. Service entrance conduit(s) and conductors.
3. Metallic conduit shall be bonded.
4. Solid bar (see Note 2).
Company furnishes and installs:
5. Current transformers.
6. Watthour meter and wiring (not shown).
Note:
1. A 6-terminal socket is required for a 1-phase, 3-wire service; an 8-terminal socket is required for a 3-phase,
3-wire service; a 13-terminal socket is required for a 3-phase, 4-wire service.
2. For 480 volt ungrounded applications the center phase bar (required) shall be removable.
3. SW-F-M sequence is required for, 208Y/120 Volt, AC network services (downtown Milwaukee area).
M-20
TRANSOCKET WITH UNDERGROUND SERVICE LATERAL
1-PHASE, 3-WIRE, 120/240 VOLTS, 201-800 AMPERES
ALL 3-PHASE VOLTAGES, 201-2000 AMPERES
3-PHASE, 4-WIRE, 208Y/120 VOLTS or 480Y/277 VOLTS, 201-3000 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE (See Note 3)
Obtain acceptance for 1-phase installations larger than 400 amperes from the Company.
Customer furnishes and installs:
1. Company listed transocket with transformer rated
meter socket (see Note 1 and Sheets D-17 & D-18).
2. Service lateral conduit (800 A. wireway shown).
3. Service entrance conduit and conductors.
4. Metallic conduit shall be bonded.
5. Solid bar (see Note 2).
Company furnishes and installs:
6. Service lateral and lug type
terminations.
7. Current transformers.
8. Watthour meter and wiring (not shown).
Note:
1. A 6-terminal socket is required for a 1-phase, 3-wire service; an 8-terminal socket is required for a 3-phase,
3-wire service; a 13-terminal socket is required for a 3-phase, 4-wire service.
2. For 480 volt ungrounded applications the center phase bar (required) shall be removable.
3. SW-F-M sequence is required for, 208Y/120 Volt, AC network services (downtown Milwaukee area).
4. This wiring gutter is for the service lateral (Item 6) only. No other conductors are to pass through it.
The transocket shown has the wiring space on the right, units with the space on the left are also available.
M-21
OUTDOOR CURRENT TRANSFORMER METERING WITH
CUSTOMER DISCONNECT
1-PHASE, 3-WIRE, 120/240 VOLTS, 201-800 AMPERES
ALL 3-PHASE VOLTAGES, 201-1200 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE (See Note 3)
Customer furnishes and installs:
1. Company listed combination metering transformer section
and disconnect with transformer rated meter socket
(see Note 1 and Sheet D-17).
2. Service entrance conduit and conductors, metallic conduit
shall be bonded.
3. Wireway, 1600A. maximum.
4. Wiring Gutter for Service Lateral (Item 7) only (see Note 4).
5. Solid bar (see Note 2).
Company furnishes and installs:
6. Current transformers.
7. Service lateral and lug type terminations.
8. Watthour meter and wiring (not shown).
Note:
1. A 6-terminal socket is required for a 1-phase, 3-wire service; an 8-terminal socket is required for a
3-phase, 3-wire service; a 13-terminal socket is required for a 3-phase, 4-wire service.
2. For 480 volt ungrounded applications the center phase bar (required) shall be removable.
3. SW-F-M sequence is required for, 208Y/120 Volt, AC network services (downtown Milwaukee area).
4. The unit shown has the wiring space on the right, units with the space on the left are also available.
M-22
METER STACK SOCKET BREAKER INSTALLATION
All 1-PHASE, 3-WIRE, AND ALL 3-PHASE VOLTAGES
0-200 AMPERES PER METER
METERING SEQUENCE: METER-SWITCH-FUSE (See Note 4)
Customer furnishes and installs:
1. Company listed termination compartment, breaker/disconnect,
switch/fuse combination (see Sheet D-20).
2. Company listed meter stacks
(see Notes 1, 2, & 3 and Sheets D-13 thru D-16).
3. Wireway (1600 Amp. max., see Sheet D-18) for service lateral.
For outdoor use only.
4. Conduit, 4"(Rigid or IMC if used outdoors) for service lateral.
(See pages U-18 to U-23 for details).
5. Spacer, (see Note 1 for requirements).
6. Label identifying the individual unit served by the meter position.
(See Note 5).
Company furnishes and installs:
7. Watthour meters.
8. Service Lateral.
Notes:
1. 4" of clearance around meter is required. Where the termination/switch/fuse compartment or switch handles
have less than the 4" clearance a spacer is required(Item 5).
2. All panels shall be removable for inspection or wiring. Each meter socket shall be individually sealable.
3. Before ordering and installing meter stacks, verify that the stack will meet the minimum and maximum
meter height requirements when installed.
4. SW-F-M is required for each meter for 208Y/120 Volt, AC network (downtown Milwaukee), multi-meter
services without a main disconnect.
5. Each meter position shall be marked on the outside of the socket or by the breaker (if available) with the
address of the unit served. If the marking is on the outside of the removable cover, it shall also be marked on
the inside of the meter socket in a visible location. This marking shall also be placed on the corresponding
distribution panel(s). The marking shall be a permanent label with 1/2" block letters and may consist of
individual self-stick letters or numbers, suitable for the location so as to be considered permanent.
M-23
INDOOR CURRENT TRANSFORMER METERING
IN FREE STANDING SWITCHGEAR
1-PHASE, 3-WIRE, 120/240 VOLTS, 201-800 AMPERES
ALL 3 PHASE VOLTAGES, 201-4000 AMPERES
METERING SEQUENCE: METER-SWITCH-FUSE (See Note 15)
Customer furnishes and installs:
1. Company listed transformer rated meter socket
(see Note 1 and Sheet D-18).
2. Conduit (see Note 2).
3. Current transformer (CT) compartment as part of
the main switchboard (see Notes 3 to 14).
4. Main breaker compartment.
5. Distribution equipment.
6. Service entrance (see Overhead or Underground
Sections for installation details).
7. Alternate location of the line and load side bus bar.
8. Alternate location for insulating barrier when alternate
load bus is used.
Company furnishes and installs:
9. Meter test switch (not shown).
10. Watthour meter (not shown).
11. Meter wire from the secondary side
of current transformers to meter
(not shown).
12. Indoor current transformers and
the necessary mounting bolts
(not shown, see Note 12).
Notes:
1. Meter socket shall be installed within sight of or attached to the CT compartment with the following limitations:
a. Meter must be installed in a suitable location as outlined in the preceding General Requirements.
b. Meter conduit shall be run exposed where practicable.
c. Consult the Company if the distance between the CT compartment and meter location exceeds 40'.
2. 1-1/4" Galvanized rigid, galvanized intermediate or rigid nonmetallic Schedule 40 PVC conduit per NEMA
Standard TC-2, to extend between the CT compartment and meter cabinet. If nonmetallic conduit is used,
a #12 copper conductor or equivalent must be installed in the conduit to maintain continuity of equipment
ground. This conductor must be bare or green covered with one or more yellow stripes.
3. The CT compartment shall be completely enclosed; barriers between compartments shall be rigidly supported.
4. No transition bus is allowed within the CT compartment with the bus configuration shown.
5. Front of CT compartment shall be enclosed using one of the following methods:
a. Double hinged door with sealable hasp and double bolt type latch (preferred).
b. Single hinged door with sealable hasp and double bolt type latch.
6. The following live part clearances must be maintained: 2" phase-to-phase, 1" phase-to-ground.
7. The CT bar will be drilled to conform to EEI Pub. MSJ-11.
8. For 1-phase and 3-phase services less than 1200 amperes, provide a threaded hole in neutral bar for a
potential tap (Tap hole for No. 10-24 brass screw). For 3-phase services, 1201 - 4000 amperes, provide
a threaded hole in the bus bars of each phase and the neutral for the potential tap as shown in the bus bar
drilling detail.
9. Bus supports shall have a minimum separation of 15" and shall consist of an insulating material such as
Benelex or equivalent, or porcelain insulators mounted on a steel channel.
10. Neutral bus bar must either run through or be extended back into the CT cabinet so that it is accessible for
the potential tap. Working clearance between neutral bus and any live bus in the vicinity of the CT mounting
must be 6" minimum. Neutral bus must not be located closer to the front of the enclosure than any live bus.
11. The compartment detail shown is for use with a 3-phase, 4-wire system. For 3-wire systems, the center phase
bar is to be continuous, and the neutral bar is omitted.
12. The customer may consult the Company and make arrangements to pick up and install the CTs.
13. For services less than 1200 amperes, refer to Sheet D-18 for listed CT compartments.
14. Submit 3 drawings of the proposed CT compartment details to the local Company office for acceptance.
15. SW-F-M sequence is required for, 208Y/120 Volt, AC network services (downtown Milwaukee area).
M-24
1-PHASE, 120/240 VOLTS, 201-800 AMPERES
ALL 3-PHASE VOLTAGES, 201-1200 AMPERES
ALL 3-PHASE VOLTAGES, 1201-4000 AMPERES
M-25
INDOOR MODULAR METERING
1-PHASE, 3-WIRE, 120/240 OR 208Y/120 VOLTS, 0-200 AMPERES PER METER
ALL 3-PHASE VOLTAGES, 0-200 AMPERES PER METER
Obtain acceptance from the Company.
Customer furnishes and installs:
1. Provisions for sealing (see Note 1).
2. Sealable cover. Double covers must be equipped with handles.
3. Benelex or polyester barrier (see Note 2).
4. Main disconnect when required (see Note 3).
5. Individual tenant disconnects.
6. Load conductor wireway.
7. Modular meter units (see Notes 4, 5, 6, 7 & Sheet D-16).
Company furnishes and installs:
8. Watthour meters.
NOTES:
1. All covers which could expose unmetered bus shall have provisions for sealing.
2. All load wireways and lugs for connection of load conductors shall be separated by barriers from
the meter area, and from unmetered bus.
3. This device as shown is not suitable for the direct termination of Company service conductors.
See Overhead or Underground Sections of the manual for the appropriate termination methods.
4. For a 3-phase, 3-wire, 480 volt meter socket, there must be a center phase disconnecting link.
5. Provide 4" clearance around meter from all foreign objects.
6. The meter disconnect combination may consist of a preassembled module designed to be inserted
into a bussed enclosure.
7. Each meter position shall be marked on the outside of the socket or by the breaker (if available) with the
address of the unit served. If the marking is on the outside of the removable cover, it shall also be marked on
the inside of the meter socket in a visible location. This marking shall also be placed on the corresponding
distribution panel(s). The marking shall be a permanent label with 1/2" block letters and may consist of
individual self-stick letters or numbers, suitable for the location so as to be considered permanent.
FULLY ASSEMBLED METERING SWITCHBOARD
M-26
Download