TO LUMINAIRE 5 #12 WHITE #12 BLACK #14 BARE 12 ENCLOSURE 229 mm X 58 mm X 102 mm CIRCUIT BREAKER (9" H X 2‚ " W X 4" D) HANDHOLE PRE-WIRED CIRCUIT BREAKER 3 BOTTOM HANDHOLE #6 BARE (POLE GROUND) 1 2 POLE GROUND LUG GREY 2 #14 BLACK HANDHOLE COVER (SUPPLIED WITH POLE) BLACK #6 GREEN #6 GREEN (GROUND ROD) 4 BLACK WHITE RED 2 WHITE 6 2 7 WHITE SEE NOTE 3 FINISHED GRADE x OUT BLACK 120 V TO SECOND POLE LUMINAIRE IN WHITE 8 10 A GROUND GREEN BOTTOM APERTURES CIRCUIT BREAKER HANDHOLE 15 A OR 50 A 9 10 SEE NOTE 2 120 V FROM BLACK TO RED SUPPLY SOURCE WHITE 2 POLE GROUND GROUND ROD SERVICE ENTRANCE BREAKER SCHEM ATI C DI AGRAM NOTES: 1) FLEXIBLE BREAKER LEADS SHALL BE LONGER THAN CABLE TAILS FOR EASIER BREAKER INSTALLATION IN HANDHOLE. 2 2) NEUTRAL AND GROUND CONDUCTOR SHALL BE BONDED TOGETHER AT THE FIRST POLE ONLY IN THE STREET LIGHT CIRCUIT. 3) USE 15 A CIRCUIT BREAKER FOR COMBINED LOAD EQUAL OR LESS THAN 1200 W. 4) USE 50 A CIRCUIT BREAKER FOR COMBINED LOAD OF GREATER THAN 1200 W. DI STRI BUTI ON CONSTRUCTI ON STANDARD 120 V SERVI CE ENTRANCE St r eetLi ght i ng I.S. TORONTO HYDRO 2 CI RCUI T BREAKER Appr oved By: 2012-06-08 Dr af t ed By: Desi gned By: L.Z. I.E. 1PHASE PREWI RED I NPOLE TYPE AT THE FI RST POLE Or i gi nalI ssue: C.P. 2006-02-21 Scal e: N.T.S. Rev: 2 303700 1/ 3 2 STREET LI GHTI NG POW ER SUPPLY SCHEM ATI CWI TH CI RCUI T BREAKER L1, L2, N REFER TO SHEET 1 OF 3 REFER TO STD. 30-3800 BREAKER #6 BLACK L1, L2 #6 BLACK ... 15 A #14 BLACK OR #14 BLACK #14 BLACK F1 F2 FL 50 A #12 BLACK #12 BLACK PC1 #12 BLACK PCL PC2 120 V SUPPLY SL1 X SEE NOTE 1 X #12 WHITE SL2 SLL X #12 WHITE #12 WHITE NEUTRAL #6 WHITE N #6 WHITE ... #14 BARE PG OR TAP BOX #14 BARE PG PG LAST POLE POLE #2 POLE #1 CABLE CHAMBER #14 BARE #6 GREEN ... GROUND CONDUCTOR SEE NOTE 3 LEGEND: F = 10 A IN-LINE FUSE L = LAST POLE PC = PHOTOCELL CONTROLLER SL = STREET LIGHT PG = POLE GROUND = GROUND ROD NOTES: 1) NEUTRAL AND GROUND CONDUCTOR SHALL BE BONDED TOGETHER AT THE FIRST POLE ONLY IN THE STREET LIGHT CIRCUIT. 2) NEUTRAL AND GROUND CONDUCTOR SHALL BE SEPARATED FROM THE SECOND POLE ONWARDS. 3) INSTALL GROUND ROD AT FIRST POLE, LAST POLE AND EVERY 300 METERS. 4) IF AN IN-POLE CIRCUIT BREAKER CAN NOT BE INSTALLED REFER TO STD. 30-3730. DI STRI BUTI ON CONSTRUCTI ON STANDARD 120 V SERVI CE ENTRANCE St r eetLi ght i ng 2 CI RCUI T BREAKER Appr oved By: I.S. TORONTO HYDRO 2012-06-08 Dr af t ed By: Desi gned By: L.Z. I.E. 1PHASE PREWI RED I NPOLE TYPE AT THE FI RST POLE Or i gi nalI ssue: C.P. 2006-02-21 Scal e: N.T.S. Rev: 2 303700 2/ 3 BOM LEGEND A 15 A 1-PHASE CIRCUIT BREAKER 2 B 50 A 1-PHASE CIRCUIT BREAKER 2 BILL OF MATERIALS FOR 30-3700 ITEM ITEM DESCRIPTION NO. QTY I.D. A B 1 CIRCUIT BREAKER 15A 1-PHASE PRE-WIRED IN-POLE TYPE 9662036 1 - 2 CIRCUIT BREAKER 50A 1-PHASE PRE-WIRED IN-POLE TYPE 9662037 - 1 3 CONNECTOR AL KIT #14 STR - 2/0 STR 7214022 2 2 2 4 CONNECTOR CU SPLIT BOLT #8 STR - #6 SOL 7213004 2 2 2 5 CABLE 2/C #12 SOL CU WITH #14 SOL CU 7155155 6 CABLE #6 7STR CU 600V RW90 XLPE/PVCJ BLACK 9663416 3 3 2 7 CABLE #6 7STR CU 600V RW90 XLPE/PVCJ WHITE 9663417 3 3 2 8 CABLE #6 7STR CU 600V RW90 XLPE/PVCJ GREEN 7150128 3 3 2 9 CONNECTOR GROUND ROD AMPACT WRENCH LOCK ƒ " ROD 7214201 1 1 ROD ƒ " X 10' GROUND STEEL GALVANIZED 2470102 1 1 10 13 13 ASSOCIATED STANDARDS 11 120 V TYPICAL STREET LIGHT SUPPLY STD.30-3800 1 1 2 12 LUMINAIRE FUSE ASSEMBLY STD.30-3200 1 1 2 2 DI STRI BUTI ON CONSTRUCTI ON STANDARD 120 V SERVI CE ENTRANCE St r eetLi ght i ng 2 CI RCUI T BREAKER Appr oved By: I.S. TORONTO HYDRO 2012-06-08 Dr af t ed By: Desi gned By: L.Z. I.E. 1PHASE PREWI RED I NPOLE TYPE AT THE FI RST POLE Or i gi nalI ssue: C.P. 2006-02-21 Scal e: N.T.S. Rev: 2 303700 3/ 3