9200 Power Meter 9200 Features Guide Table of Contents Table of Contents ◆ 9200 Meter Features Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 ◆ The Megawatt Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Before You Use the Megawatt Option . . . . . . . . . . . . . . . . . . . . . . 6 ◆ Basic Setup for the Megawatt Option . . . . . . . . . . . . . . . . . . . . . . . 7 ◆ Megawatt Option Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Display Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Configuration Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 ◆ Appendix A: Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modbus Address Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Read-Write Configuration Map . . . . . . . . . . . . . . . . . . . . . . . . . . Read-Write Control Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modbus Data Formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Exception Responses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ◆ Appendix B: Configuration Reference Tables . . . . . . . . . . . . . . . 20 Standard Measurements and Enhanced Packages 1 & 2 . . . . . 20 Meter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 13 13 16 18 19 19 3 Table of Contents 4 9200 Meter Features Guide 9200 Meter Features Guide This guide describes the 9200 meter features that are ordering options— this edition includes meter operation of the Megawatt option. 9200 Technical Documentation Comprehensive technical documentation for the 9200 meter is shipped with the meter and is available online at www.sea.siemens.com/access. The 9200 Installation and Basic Setup Instructions manual provides operational details for your 9200 meter, and can be referenced in addition to this Features Guide. DANGER Installation and maintenance of Access meters and meter options should only be performed by qualified personnel that have appropriate training and experience with high voltage/ current devices. In the 9200 Installation and Basic Setup Instructions, refer to Installation Considerations, and the Danger, Warning, and Limitation of Liability notices. 5 9200 Features Guide The Megawatt Option The Megawatt option displays all power and energy values in millions (e.g. megawatts) and volts in thousands (kilovolts). The Megawatt option has a different front panel faceplate than the standard meter, with labels for kV, MW, MVA, MVAR, MWh, MVAh, and MVARh. Before You Use the Megawatt Option In addition to setting up the PT1 and PT2 registers on your Megawatt option, you must set the PTS (PT Scaling) register to “x1000.” This allows communications software to correctly interpret megawatt and kilovolt quantities, and enables meaningful measurements through the meter front panel. You must set the PTS register to “x1000” for the Megawatt option to operate correctly. Pt1 PtS Pt2 PT1 (Primary) PTS (Scaling) PT2 (Secondary) To learn about meter configuration, refer to the 9200 Installation and Basic Setup Instructions section “Front Panel Navigation”—”Configuration Mode.” What Does the PT Scaling (PTS) Setup Register Do? The PT Scaling setup register provides an additional PT primary register to accommodate a larger PT ratio. PTS offers a “x1000” quantity for the PT primary register. (The standard meter model uses the “x1” default scaling.) How PT Scaling Defines the PT Ratio Suppose that a meter with the Megawatt option is applied to measure power on a 500 kV system, the voltage applied to the PT primary is 288 kV, and the expected voltage on the PT secondary is 120 V. The formula below shows how these values are used with the PT Scaling register set at “x1000” to define the overall PT ratio. PT Ratio = PT Primary PT Secondary PT Ratio = 288,000 120 PT1 x PTS PT2 288 x 1000 120 The formula shows that the meter correctly measures 288.0 kV when PTS is set to “x1000,” PT1 is set to 288, and PT2 is set to 120. 6 Basic Setup for the Megawatt Option Basic Setup for the Megawatt Option Basic setup determines how the meter interprets the power system it is connected to, as well as how the meter communicates with connected networks or workstations. You can use the meter front panel or software to perform basic setup (e.g. PT Primary, PT Secondary, and PT Scaling set up) on a meter with the Megawatt option. For parameter configuration through the front panel, the meter must be in Configuration mode. Refer to “Configuration Mode” in the 9200 Installation and Basic Setup Instructions. For meter setting defaults and values refer to “Meter Settings” on page 21. Using configuration software, you can access the networked meter from your workstation. Refer to “Appendix A: Communications” on page 13. Megawatt Option Front Panel Infrared (IR) Port Phase measurements Phase A Negative value indicator System measurements A B Phase B x 1000 indicator C Phase C Demand / Peak Demand measurements Energy readings Down button Up button Enter button 7 9200 Features Guide With the meter front panel, you can view parameter values; configure parameters; perform demand resets; perform LED checks; and view meter information. Each of these functions can be accomplished by pressing the Up, Down, and Enter buttons on the front panel. These button actions achieve different results according to the mode that the meter is in: ◆ Display mode (default): view parameter measurements ◆ Reset mode: reset demand measurements ◆ Configuration Select/Edit modes: configure a parameter ◆ Information mode: verify that the front panel display LEDs operate, and view meter information, e.g, meter options, firmware version etc. This section describes how to interpret Display mode values on a meter with the Megawatt option. Refer to the 9200 Installation and Basic Setup Instructions to learn about Reset, Configuration, and Information modes. The Megawatt option displays different values than the standard meter, but does not differ operationally for these modes. Display Mode Phase Measurements: This list displays per phase measurements (A, B, C). System Measurements: This list displays system measurements. Each line of the display shows a different system measurement. A 2 A lit LED below A, B, or C indicates that the measurement has a negative value. B 1 C Demand / Peak Demand (Max) Measurements: This list displays Demand and Peak Demand (Max) measurements. (Min/Max measurements will be in a future release). 4 8 5 Energy Readings: Parameters in this row display energy readings. 3 Numbers 1 – 5 represent the order that the measurement groups display when you scroll in Display mode. You can scroll from group to group with the Enter button, or from parameter to parameter within a group with the Up/ Down buttons. Display Mode In Display mode, you can view values from these measurement groups: System (total), Per Phase, Energy, Demand, and Peak Demand. (This assumes that you have ordered Enhanced Measurements Package 2. Refer to “Standard Measurements and Enhanced Packages 1 & 2” on page 20, or the 9200 Options Card Retrofit Instructions for information regarding Options Cards). Display Mode Parameter Measurements The following table lists the parameters in each measurement group: Measurement Group Parameters Measured System (Total) kVAVG, IAVG, MW, MVA, MVAR, PF, Frequency, I4 Phase A, B, and C kVLN, kVLL, I, PF, MW, MVA, MVAR, VTHD, ITHD Energy MWh, MVAh, MVARh Demand* MVA, MVAR, MW, IAVG Peak Demand (Max)* MVA, MVAR, MW, IAVG Min/Max Min/Max measurements provided in a future release * Displays system (total) values. x1000 Indicator When the “x1000” LED is lit, multiply the displayed value by 1000 for the actual value. Viewing Parameter Measurements The meter defaults to Display mode, and to the System measurements within this mode. The following graphics illustrate how to interpret Display mode measurements on a meter with the Megawatt option. 9 9200 Features Guide 1. System Measurements System measurements kVLN kVAVG MVA PF A kVLL I PF MW MVA x1000 IAVG MVAR FREQ B M VA R VTHD I THD x1000 C MW I4 DMD MAX MIN MWh MVAh MVARh x1000 kVAVG M VA PF OR x1000 Press the Up/Down buttons to display a previous parameter value or the next in this group of System measurements IAVG M VAR FREQ x1000 MW I4 x1000 Each line of the display shows a System measurement. In the above example, line 1 = System Average Kilovolts (kVAVG) with a value of 450.1 kV; line 2 = System Average Line Current (IAVG) with an actual* value of 2,315 A; line 3 = System Total Active Power (MW) with an actual* value of 1,042 MW. (*Actual value = displayed x 1000.) Press the Enter button to display Phase measurements. 2. Phase Measurements Phase measurements kVLN kVAVG MVA PF A kVLL B I PF MW MVA x1000 IAVG MVAR FREQ B M VA R VTHD I THD DMD MAX MIN x1000 C MW I4 x1000 kWh kVAh kVARh OR Press the Up/Down buttons to display a previous parameter value or the next in this group of Phase measurements kVL-N kVL-L I PF kW MVA VTHD I THD A B C Each line of the display shows a Phase measurement. The example above shows current for Phase A, Phase B, and Phase C on lines 1, 2, and 3 respectively. Phase B shows a negative value for current, indicated by the lit bar-shaped LED below the “B.” Press the Enter button to display Energy readings. 10 Display Mode 3. Energy Readings kVLN kVAVG MVA PF A kVLL I PF MW MVA x1000 IAVG MVAR FREQ B x1000 EnergyV readings C THD MW I THD DMD MAX MIN MWh I4 MVAh MVARh OR Press the Up/Down buttons to display a previous parameter value or the next in this group of Energy readings x1000 MWh MVAh MVARh An Energy reading wraps around the three lines of the front panel display. A maximum of three digits appear on each line. The most significant digit is in the left hand corner of the first display line, and the least significant digit is in the bottom right hand corner of the third display line. This energy reading is 32,876,013 MWh. Press the Enter button to display Demand measurements. 4. Demand Measurements OR kVLN kVAVG MVA PF A kVLL x1000 I PF IAVG MVAR FREQ Demand measurements I THD DMD MAX MIN x1000 C MW Press the Up/Down buttons to toggle between Total Power and Total Current Demand I4 MWh MVAh MVARh x1000 DMD MAX MIN kVAVG M VA PF x1000 IAVG M VAR FREQ x1000 MW I4 x1000 Demand measurements include Total Power Demand and Total Current Demand. The example above shows Total Power Demand for: Apparent Power (MVA), Reactive Power (MVAR), and Real Power (MW). The values are: 214.9 MVA, 71.0 MVAR, and 202.9 MW. Press the Enter button to display Peak Demand measurements. 11 9200 Features Guide 5. Peak Demand Measurements OR kVLN kVAVG MVA PF A kVLL I x1000 IAVG MVAR FREQ Demand/Max measurements I THD DMD MAX MIN x1000 C MW Press the Up/Down buttons to toggle between Total Power/Total Current Peak Demand I4 kWh kVAh kVARh x1000 DMD MAX MIN kVAVG M VA PF x1000 IAVG M VAR FREQ x1000 MW I4 x1000 Peak (Max) Demand measurements include Total Power Peak Demand, and Total Current Peak Demand. The example above shows Total Power Peak Demand for: Apparent Power (MVA), Reactive Power (MVAR), and Real Power (MW). The values are: 251.9 MVA; 96.0 MVAR; and 232.9 MW. Press the Enter button to return to System measurements. Configuration Mode You must set the PTS (PT Scaling) register to “x1000” for the correct operation of a meter with the Megawatt option. Refer to the section “Before You Use the Megawatt Option” on page 6. To learn about Configuration mode, refer to the 9200 Installation and Basic Setup Instructions. Configurable Meter Settings Configurable meter settings are listed in “Meter Settings” on page 21. 12 Appendix A: Communications Appendix A: Communications This section describes the Modbus communications protocol employed by a meter with the Megawatt option in a Modbus network. It is assumed that the user is familiar with serial communications in general, and the Modbus protocol. Refer to the document 9200 Modbus Protocol for more information. Modbus Address Table In the following Modbus map, many numeric measurements are scaled. Scaling is either fixed or programmable. For an example of fixed scaling, suppose that the frequency register 40115 contains the value 5987. Since this register is scaled by "x100" the actual measured value is 59.87 Hz. For an example of programmable scaling, suppose that the meter Vln a value is 480.1. If the PVS scaling is set to "x10" (default), then register 40100 will contain a value of 4801. If the PVS scaling is set to "0.1," then register 40100 will contain a value of 48. The meter supports programmable scaling for voltage (PVS), current (PCS), neutral current (PnS), and power (PPS). Modbus Addr Meter Measurement Format Scale Default Scale Description 40001 manufacturer's ID UINT32 x1 40003 firmware revision UINT16 x1 40004 oem ID UINT16 x1 See note 2. 40005 meter options UINT32 x1 See note 3. 40007 # meter power ups UINT16 x1 40008 # peak demand resets UINT16 x1 40009 meter on-time UINT32 x1 40011 # flash erase cycles UINT32 x1 UINT16 x1 UINT16 x1 40013 device type 40014 Reserved 40015 demand interval down counter See note 1. See note 4. See note 5. Reserved 40100 kVln a UINT16 PVS x10 40101 kVln b UINT16 PVS x10 See note 6. 13 9200 Features Guide Modbus Addr Meter Measurement 40102 kVln c UINT16 PVS x10 40103 kVln avg UINT16 PVS x10 40104 kVll ab UINT16 PVS x10 40105 kVll bc UINT16 PVS x10 40106 kVll ca UINT16 PVS x10 40107 kVll avg UINT16 PVS x10 40108 Ia UINT16 PCS x10 40109 Ib UINT16 PCS x10 40110 Ic UINT16 PCS x10 40111 I avg UINT16 PCS x10 40112 I demand UINT16 PCS x10 40113 I peak demand UINT16 PCS x10 40114 I4 UINT16 PnS x10 See note 8. 40115 Frequency INT16 x100 40116 PF sign total INT16 x100 40117 PF sign a INT16 x100 40118 PF sign b INT16 x100 40119 PF sign c INT16 x100 40120 MW total INT16 PPS x1 See note 9. 40121 MVAR total INT16 PPS x1 40122 MVA total INT16 PPS x1 40123 MW a INT16 PPS x1 40124 MW b INT16 PPS x1 40125 MW c INT16 PPS x1 40126 MVAR a INT16 PPS x1 40127 MVAR b INT16 PPS x1 40128 MVAR c INT16 PPS x1 40129 MVA a INT16 PPS x1 40130 MVA b INT16 PPS x1 40131 MVA c INT16 PPS x1 40132 MW demand INT16 PPS x1 40133 MW peak demand INT16 PPS x1 40134 MVAR demand INT16 PPS x1 40135 MVA demand INT16 PPS x1 40136 MVAR peak demand INT16 PPS x1 40137 MVA peak demand INT16 PPS x1 14 Format Scale Default Scale Description See note 7. Modbus Address Table Modbus Addr Meter Measurement Format Scale 40138 MWh del UINT32 x1 40140 MWh rec UINT32 x1 40142 MVARh del UINT32 x1 40144 MVARh rec UINT32 x1 40146 MVAh del+rec UINT32 x1 40148 V1 THD UINT16 x10 40149 V2 THD UINT16 x10 40150 V3 THD UINT16 x10 40151 I1 THD UINT16 x10 40152 I2 THD UINT16 x10 40153 I3 THD UINT16 x10 40154 I a demand UINT16 PCS 40155 I b demand UINT16 PCS x10 40156 I c demand UINT16 PCS x10 40157 I a peak demand UINT16 PCS x10 40158 I b peak demand UINT16 PCS x10 x10 40159 I c peak demand UINT16 PCS 40160 MWh a del UINT32 x1 40162 MWh b del UINT32 x1 40164 MWh c del UINT32 x1 40166 MWh a rec UINT32 x1 40168 MWh b rec UINT32 x1 40170 MWh c rec UINT32 x1 40172 MVARh a del UINT32 x1 40174 MVARh b del UINT32 x1 40176 MVARh c del UINT32 x1 40178 MVARh a rec UINT32 x1 40180 MVARh b rec UINT32 x1 40182 MVARh c rec UINT32 x1 40184 MVAh a UINT32 x1 40186 MVAh b UINT32 x1 MVAh c UINT32 x1 UINT16 x1 40188 Default Scale Description See note 10. x10 See note 10. Reserved 40500 Expansion, SnapOn 1, 25 regs 15 9200 Features Guide Modbus Addr Meter Measurement Format Scale 40700 Expansion, SnapOn 2, 25 regs UINT16 x1 41138 MWh del UINT32 x1 41140 MWh rec UINT32 x1 41142 MVARh del UINT32 x1 41144 MVARh rec UINT32 x1 41146 MVAh del+rec UINT32 x1 41160 MWh a del UINT32 x1 41162 MWh b del UINT32 x1 41164 MWh c del UINT32 x1 41166 MWh a rec UINT32 x1 41168 MWh b rec UINT32 x1 41170 MWh c rec UINT32 x1 41172 MVARh a del UINT32 x1 41174 MVARh b del UINT32 x1 41176 MVARh c del UINT32 x1 41178 MVARh a rec UINT32 x1 41180 MVARh b rec UINT32 x1 41182 MVARh c rec UINT32 x1 41184 MVAh a UINT32 x1 41186 MVAh b UINT32 x1 41188 MVAh c UINT32 x1 Default Scale Description See note 11. Read-Write Configuration Map Modbus Addr Meter Configuration Format Scale Default Description 44000 Configuration via display password UINT16 x1 0 0 – 9999 5= Delta direct 0 = 4W (4-Wire WYE) 1 = dELt (Delta) 2 = 2W (Single Phase) 3 = dEM (Demonstration) 4 = 3W (3-Wire WYE) 5 = dELd (Delta Direct) 44001 16 Volts Mode Enumerated Read-Write Configuration Map Modbus Addr Meter Configuration Format Scale Default 44002 PT Primary UINT16 x1 480 44003 PT Secondary UINT16 x1 480 44004 CT Primary UINT16 x1 400 44005 CT Secondary UINT16 x1 5 44006 V1 Polarity 44007 V2 Polarity 44008 V3 Polarity 44009 I1 Polarity 44010 I2 Polarity 0= Normal Enumerated Description 1 – 65535 0 = nor (Normal) 1 = inv (Inverted) 44011 I3 Polarity 44012 Programmable Voltage Scale (PVS) 44013 Programmable Current Scale (PIS) 44014 Programmable Neutral Current Scale (PnS) 44015 Programmable Power Scale (PPS) 44016 Demand Sub Interval UINT16 x1 15 1 – 60 minutes 44017 Demand #Sub Intervals UINT16 x1 1 1–5 44018 Kt, Digital Output #1 UINT16 x10 44019 Kt, Digital Output #2 UINT16 x10 1.0 0.1 - 999.9 44020 Kt, Irda UINT16 x10 44021 Output Mode, Digital Output #1 44022 Output Mode, Digital Output #2 44023 44024 4 = 10 Enumerated = 0.001 = 0.01 = 0.1 =1 = 10 = 100 = 1000 3=1 0 = MWh Enumerated Output Mode, Irda Baud Rate 0 1 2 3 4 5 6 2= MVARh 3 = Ext1 Enumerated 3= 9600bps 0 = MWh Del. 1 = MVAh 2 = MVARh Del. 3 = Ext1 4 = Ext2 5 = MWh Rec. 6 = MVARh Rec. See note 12. 0 1 2 3 4 = 1200bps = 2400bps = 4800bps = 9600bps = 19200bps 17 9200 Features Guide Modbus Addr Meter Configuration Format 44025 Protocol Scale Default Description Enumerated 1= MODBUS 0 = PML 1 = MODBUS See note 13. 1 – 247 44026 Unit ID UINT16 x1 100 plus the last 2 digits of the Man. ID # 44027 RTS Delay UINT16 x1 20 0 – 1000 milliseconds See note 14. 44028 Display Scroll Time UINT16 x1 0 0 – 30 seconds See note 15. 44029 Display Refresh Period UINT16 x1 2 1 – 6 seconds See note 16. 44030 PT Scale Enumerated 0 = x1 0 = x1 1 = x1000 Read-Write Control Map Modbus Addr17 Meter Control Format Scale Description 42001 Energy Reset UINT16 x1 Reset MWh, MVAh, and MVARh to 0. 42002 Peak Power Demand Reset UINT16 x1 Reset MW, MVA, and MVAR peak demand to 0. 42003 Peak Current Demand Reset UINT16 x1 Reset I peak demand. 42004 Digital Output #1 UINT16 x1 42005 Digital Output #2 UINT16 x1 Refer to “Digital Output Control” in the 9200 Installation and Basic Setup Instructions. Notes 1. Manufacturer’s identification is the serial number of the meter. It has the format of the YYMM##### where YY and MM represent the manufacture date. 2. Identifies the Original Equipment Manufacturer (OEM). 3. Options codes identify meter options. To see a table that cross-references Options Cards and options codes, refer to the 9200 Options Card Retrofit Instructions. 4. Number of seconds that the meter has been powered up. 5. Device identification. 6. PVS = Programmable Voltage Scale. Ensure that scaling is compatible with the expected register value; this provides maximum resolution and prevents register overflow. 18 Modbus Data Formats 7. PCS = Programmable Current Scale. Ensure that scaling is compatible with the expected register value; this provides maximum resolution and prevents register overflow. 8. PnS = Programmable Neutral Current Scale. Ensure that scaling is compatible with the expected register value; this provides maximum resolution and prevents register overflow. 9. PPS = Programmable Power Scale. Ensure that scaling is compatible with the expected register value; this provides maximum resolution and prevents register overflow. 10. When it is read from that address the Low Order Word is fetched first. 11. These registers are duplicates of other UINT32 read-only registers differing only in that the High Order Word is fetched first. 12. Digital output modes are: MW pulsing, MVAR pulsing, MVA pulsing, and digital control. For digital output control information, refer to “Digital Output Control” in the 9200 Installation and Basic Setup Instructions. 13. The PML protocol is an ION compatible protocol used when other ION devices are sharing a RS-485 network. 14. The RTS Delay parameter defines the delay between the 9200 becoming ready to transmit data on the serial port, and the 9200 transmitting the data. 15. Number of seconds that a display is shown before scrolling to the next, 0 = no scrolling (disabled). 16. Number of seconds that a measurement value is held on the display before being refreshed; limited to 1-6 seconds. 17. To use the Read-Write Control Map, it is recommended that your meter has firmware version 202 or later. For detailed information, contact Technical Services. Modbus Data Formats To learn about Modbus data formats, refer to the 9200 Installation and Basic Setup Instructions. Exception Responses To learn about Modbus exception responses, refer to the 9200 Installation and Basic Setup Instructions. 19 9200 Features Guide Appendix B: Configuration Reference Tables Standard Measurements and Enhanced Packages 1 & 2 Standard Parameter Enhanced Pkg. 1 Enhanced Pkg. 2 Display Comm Pulse Display Comm Pulse Display Comm Pulse Volts L-N Avg ● ● ● ● ● ● Volts L-N Per Phase ● ● ● ● ● ● Volts L-L Avg ● ● ● ● ● ● Volts L-L Per Phase ● ● ● ● ● ● Current Avg ● ● ● ● ● ● Current Per Phase ● ● ● ● ● ● Current Neutral (I4) ● ● ● ● Power Total (MW) ● ● ● ● Power Per Phase (MW) ● ● Reactive Power Total (MVAR) ● ● Reactive Power Per Phase (MVAR) ● ● Apparent Power Total (MVA) ● ● Apparent Power Per Phase (MVA) ● ● ● ● Energy Del. (Imp.) (MWh) ● ● ● ● Energy Rec. (Exp.) (MWh) ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● Apparent Energy Per Phase (MVAh) Frequency ● ● ● ● Power Factor Total ● ● ● ● ● ● Power Factor Per Phase Current Avg. Demand ● ● ● ● Current Demand Per Phase ● ● ● ● Current Avg. Peak Demand ● ● ● ● Current Peak Demand Per Phase ● ● ● ● ● ● ● ● Reactive Power Demand (MVAR) ● ● Reactive Power Peak Demand (MVAR) ● ● Apparent Power Demand (MVA) ● ● Apparent Power Peak Demand (MVA) ● ● THD Voltage Per Phase ● ● THD Current Per Phase ● ● Power Demand (MW) Power Peak Demand (MW) 20 ● ● ● Reactive Energy Rec. (Exp.) Per Phase (MVARh) Apparent Energy (MVAh) ● ● Reactive Energy Del. (Imp.) Per Phase (MVARh) Reactive Energy Rec. (Exp.) (MVARh) ● ● Energy Rec. Per Phase (Exp.) (MWh) Reactive Energy Del. (Imp.) (MVARh) ● ● Energy Del. Per Phase (Imp.) (MWh) ● ● ● Meter Settings Meter Settings These settings can be configured with the meter front panel or software. COMMUNICATIONS DEMAND POLARITY CTS PTS MODE String Description Range (Values) Default tYPE Volts Mode 4W (4-Wire WYE) dELt (Delta) 2W (Single Phase) dEM (Demonstration) 3W (3-Wire WYE) dELd (Delta Direct) Delta Direct Pt1 PtS Pt2 Ct1 Ct2 PT1 (Primary) 1 to (65.53 x 1000 LED) 480 PTS (Scaling)* 1 (x 1); 1000 (x 1000) x1 PT2 (Secondary) 1 to (65.53 x 1000 LED) 480 CT1 (Primary) 1 to (65.53 x 1000 LED) 400 CT2 (Secondary) 1 to (65.53 x 1000 LED) 5 UPL1 V1 Polarity (Phase 1 voltage polarity) nor (Normal); inv (Inverted) Normal UPL2 V2 Polarity (Phase 2 voltage polarity) nor (Normal); inv (Inverted) Normal UPL3 V3 Polarity (Phase 3 voltage polarity) nor (Normal); inv (Inverted) Normal CPL1 I1 Polarity (Phase 1 current polarity) nor (Normal); inv (Inverted) Normal CPL2 I2 Polarity (Phase 2 current polarity) nor (Normal; inv (Inverted) Normal CPL3 I3 Polarity (Phase 3 current polarity) nor (Normal); inv (Inverted) Normal dPr Demand Sub Interval 1 – 60 min 15 ndPr Number of Demand Periods 1–5 1 Prot bAud Protocol PML**; Mod (Modbus RTU) Modbus Baud Rate 1200, 2400, 4800, 9600, 19200 9600 un d Unit ID 1 – 247 100 plus the last 2 digits of the Manufactu rer ID # rtS RTS Delay 0 – 1000 milliseconds 20 21 SECURITY DISPLAY DIGITAL OUTPUTS MODBUS SCALING 9200 Features Guide String Description Range (Values) Default PUS PCS PPS PnS Voltage Scale 0.001, 0.01, 0.1, 1, 10, 100, 1000 10 Current Scale 0.001, 0.01, 0.1, 1, 10, 100, 1000 10 Power Scale 0.001, 0.01, 0.1, 1, 10, 100, 1000 1 Neutral Scale 0.001, 0.01, 0.1, 1, 10, 100, 1000 10 out1 Output Mode Digital #1 (M)Wh Del., (M)VAh, (M)VARh Del., (M)Wh Rec., (M)VARh Rec. See note.† Ext 1††, Ext 2†† (M)Wh† tc1 Time Constant 1 (kT)††† 0.1 – 999.9 (only 1 digit after the decimal pt. permitted) 1.0 out2 Output Mode Digital #2 (M)Wh Del., (M)VAh, (M)VARh Del., (M)Wh Rec., (M)VARh Rec. See note.† Ext 1††, Ext 2†† (M)VARh† tc2 Time Constant 2 (kT)††† 0.1 – 999.9 (only 1 digit after the decimal pt. permitted) 1.0 otIr Output Mode, Irda (M)Wh Del., (M)VAh, (M)VARh Del., (M)Wh Rec., (M)VARh Rec. See note.† Ext 1††, Ext 2†† Ext 1†† tcIr Time Constant Irda (kT)††† 0.1 – 999.9 (only 1 digit after the decimal pt. allowed) 1.0 dScr Display Scroll Time 0 – 30 seconds (0 = disable) 0 dUPd Display Refresh Period 1 – 6 seconds 2 PSEt Password 0 – 9999 0 Programmable Meter Language (PML) Protocol * For the correct operation of a meter with the Megawatt option, PTS must be set to “x1000.” ** ION compatible protocol for use with an WinPM.Net system and other Access meters. Digital Outputs † The units displayed on the front panel are Wh, VAh, and VARh with the actual values of MWh, MVAh, and MVARh respectively. MWh Rec. and MVARh Rec. are represented by a lit “minus” (negative value) LED. †† In Ext 1 or Ext 2 mode, the digital outputs are reserved for Feature Packs or digital control. For digital output control information, refer to the 9200 Installation and Basic Setup Instructions. 22 Meter Settings ††† Time Constant, sometimes called kT, is the number of units (MWh, MVAh, MVARh) per output transition. The digital output uses KY pulsing. This means that the relay changes from open to closed or from closed to open whenever kT units have been measured (20 transitions/second maximum). 23 Siemens Energy & Automation, Inc. Power Management Technologies 3333 Old Milton Parkway Alpharetta, GA 30005 For Nearest Sales Office 1.800.964.4114 www.sea.siemens.com sales/salesoffices.html For More Information Visit © Siemens Energy & Automation, Inc. Windows is a trademark and Microsoft is a registered trademark of Microsoft Corporation. All others are of Siemens AG. Order No. PMIM-9206A-0103 PDF 0800 Printed in the U.S.A. Siemens is a registered trademark of Siemens AG. Specifications are subject to change without notice. www.sea.siemens.com/access