NOTES 1. Read drawing in conjunction with drawing 3797/E-02. 2. Refer to current Periodic Inspection Report Schedule of Circuits details for final circuit cable types and destinations.. LIFT Panel 63A TPN Switchfuse LIFT Located in roof plantroom SIDE STAIRCASE (Serves 1st flr disabled toilet) DB DT2 1ST FLOOR Located in Library - 30. Appears redundant, all circuits cut off inside need to establish if any point of connection 1ST FLR GENERAL REF LIB DB No Ref ?? MEM 100A SPN 13W MCB DB In GRP enclosure CARNEGIE ROOM 1ST FLR GENERAL REF LIB LOCAL LIB BEHIND STAGE DB 10 DB 8 1ST FLR HELP DESK DB 9 MEM 100A TPN 8W MCB DB MG 100A TPN 8W MCB DB WYLEX 63A SPN 6W MCB CU Not labeled and poss not tested GENERATOR PLANTROOM DB No Ref MEM 100A TPN 4W HRC FB MEM 63A SPN 4W HRC FB HUB ROOM DB IT GENERATOR ROOM DB 7 Loadstar 63A SPN 8W MCB DB GRD FLOOR MEM 63A TPN 2W HRC FB HUB ROOM DB HUB FRONT OF LIBRARY DB 4 `MEM2 100A TPN 8W MCB DB MEMERA 63A SPN 12W MCB DB 63A TPN Switchfuse GENERATOR ROOM DB 4 BOTTOM REAR STAIRS DB 12 WYLEX 63A SPN 4W MCB CU BSMT GENERATOR C/O PANEL MK 63A SPN 12W MCB DB BOILER ROOM DB 5 BOILER ROOM DB 6 FED ELEC 100A TPN 4W MCB DB BILL 63A TPN 4W WIRE FUSEBOARD Power & control in combined cable CONTROL SWITCHFUSE DB Fans appears redundant (all fuses removed) - need to verify connection to FB MAIN SWITCHROOM BILL 63A TPN 6W WIRE FUSEBOARD COMP C/O PANEL FANS DB - (No Ref) MAIN SWITCHROOM DB 2 BILL 63A TPN 3W WIRE FUSEBOARD BILL 63A TPN 3W WIRE FUSEBOARD BILL 63A TPN 3W WIRE FUSEBOARD 32A TPN MEM Switchfuse 63A TP Switch 63A TP Switch 30A TP Switch 63A SP Switch MAIN SWITCHROOM DB COMP 2 MK 63A SPN MCB DB MK 63A SPN MCB DB NON -ESS 63A TPN MEM Switchfuse 09aug12 Minor amendments. 29may12 Minor amendments. 15mar12 General amendments following further survey. ESSENTIAL John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com 100A TPN DB DTI Switchfuse 63 32 63 63 63 63 - 32 1 2 3 4 5 6 7 8 - - - L1 L2 L3 9 63 10 8 Nr WYLEX RCD UNITS MCCB - MAIN MEM 200A TPN 10W FUSEBOARD Main 200A TPN switchfuse Incoming 100A TPN supply REC metering - RCD's serve socket circuits off DB's 1, 2 & 3. Contractor to verify and decommission when new DB1 installed. TENDER ISSUE 63A TPN BILL Switchfuse 63A TP Switch MAIN SWITCHROOM DB COMP 1 C B A SPARE ELEC SWITCHROOM POWER ISOLATOR MAIN SWITCHROOM DB 1 MAIN SWITCHROOM DB 3 100KVA/80KW GENERATOR NOTES LIFT Panel 63A TPN Switchfuse New Ref DB 7 LOCAL LIB BEHIND STAGE DB 8 MEM 100A SPN 13W MCB DB 1ST FLOOR New Ref DB 8 1ST FLR HELP DESK DB 9 NEW MEM 100A TPN 8W MCB DB MEM 100A TPN 8W MCB DB NEW EXTG New Ref DB 8/1 1ST FLR GENERAL REF LIB DB 10 Located in roof plantroom MG 100A TPN 8W MCB DB NEW MEM 63A SPN 7W MCB DB NEW EXTG 6mm PVC/PVC cable New Ref DB 3/1 HUB ROOM DB IT New Ref DB 5 GENERATOR ROOM DB 7 Loadstar 63A SPN 8W MCB DB New Ref DB 4 FRONT OF LIBRARY DB 4 MEM2 100A TPN 8W MCB DB GRD FLOOR New Ref DB 2/1 BOTTOM REAR STAIRS DB 12 EXTG NEW MEM 100A SPN 7W MCB DB Install new 10mm 2C SWA via 50A MCB New Ref DB 2 BOILER ROOM DB 5 Extend existing 16mm 4C SWA NEW 100A TPN 8W MCB DB NEW NEW ELEC SWITCHROOM Install new 16mm 4C SWA NEW MEM 100A TPN 12W MCB DB Extend existing 16mm 4C SWA cable via adaptable box/fixed terms Install new 16mm 4C SWA Install new 25mm 4C SWA New Ref DB 1 MAIN SWITCHROOM DB 1 Reconnect existing 16mm 4C SWA BSMT Reconnect existing 16mm 3C SWA NEW MEM 100A SPN 16W MCB DB NEW GENERATOR C/O PANEL NEW 63A TPN Switchfuse Reroute and reconnect existing 16mm 2C SWA HUB ROOM DB HUB NEW MEM 100A TPN 6W MCB DB Reconnect existing 16mm 4C SWA EXTGNew Ref DB 3 100KVA/80KW GENERATOR A 09aug12 General amendments and cable sizes added. John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com 63 1 63 63 - L1 L2 L3 2 63 63 63 63 63 - - - 3 4 5 6 7 8 9 10 MCCB - REC meter to be replaced Existing Incoming supply (fuses to be confirmed 100A TPN) - NEW MAIN MEM 250A TPN 10W MCCB PANELBOARD New MCCB current ratings are 63A SP/TP as appropriate TENDER ISSUE New Ref DB 6 SIDE STAIRCASE DB DT2 Located in Library - 30. Appears redundant, all circuits cut off inside. Establish point of connection, make safe and remove 1ST FLR GENERAL REF LIB DB No Ref ?? 1. Read drawing in conjunction with drawing 3797/E-01 & 03. 2. Refer to current Periodic Inspection Report Schedule of Circuits details for final circuit cable types and destinations. 3. Upgrade earthing in accordance with BS7671 - 17th Edition Regulation requirements. Reconnect existing 16mm 4C SWA Presently in GRP enclosure. Remove enclosure, new DB to be enclosed in timber cupboard (by others) LIFT Existing DB1 onto which all the final circuits from DB2 & 3 are to be temp transferred. Existing DB1 is to be removed once all circuits have been ransferred to new DB Existing meter New 250A TPN 10W MCCB panelboard Existing Sub main for DB9 (to be extended via adpatable box/fixed terminals Existing conduits Existing Header trunking (retain) Exist DB1 REC CT enc (redundant) Remove existing switchfuses (will be redundant) New DB1 125A TPN 16W Existing DB2 , 3 and fans all removed Existing sub main trunking (remove up to 2 comp for IT cables) REC cut-out ELECTRICAL SWITCHROOM ELEVATIONS 1/50 Rev DB New DB1 00abc00 Text Date Revision text HU B John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT DB 1 New Main MCCB panelboard ELECTRICAL SWITCHROOM PLAN 1/100 DB 4 TENDER ISSUE Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com SYMBOLS LEGEND - ELECTRICAL DISTRIBUTION Device Description Switchfuse (rating as detailed) H1E-P C5 C5 C5 C4 C4E DB 12 H1E-P PIR Exist C5 O M K O PIR C5 C4E K M PIR C1 DB Distribution board - 3 phase MCCB panelboard PB PIR K Exist EX K C1 Distribution board - 1 phase 5A supply (spur) PIR C5E Exist O DB C1E Rotate luminaires thro 90 degrees to achieve light distribution SYMBOLS LEGEND - LIGHTING Luminaire type Description Type A1-D 1 x 49W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire Type A2-D 2 x 35W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire Type A3-D 2 x 49W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire Type A4-D 2 x 35W T5 Surface HF Dimmable Fluorescent Louvre Luminiare Type B1-D 2 x 35W T5 Surface HF Dimmable Fluorescent Opal diff Luminiare PIR C5 C5 C5 K 3G O C1 C1E C5 C5 C1 C1 C3 C3 K K M C1 E2 DB 5 C4E K1 Type C1 K1 Type C1-C DB 6 PIR C5 Exist 2G PIR C5 O C1 C5E C5 C3 C3 C1 C4 K1 MW PIR C5 C5 C5 C3 C3 C1E C4 K EX M G1E-P K O Line of susp clg G1E-P Existing illuminated exit Existing conversion unit Existing conversion unit 1 x 35W T5 Surface HF Fluorescent Prismatic Luminaire 1 x 35W T5 Surface HF Corri-func Fluorescent Prismatic Luminaire Type C2 1 x 49W T5 Surface HF Fluorescent Prismatic Luminaire Type C3 2 x 35W T5 Surface HF Fluorescent Prismatic Luminaire Type C4 2 x 49W T5 Surface HF Fluorescent Prismatic Luminaire Type C5 1 x 35W T5 Surface HF Fluorescent batten Luminaire Type D4E-D 2 x 49W T5 Surface HF Dimmable Fluor Pris Luminaire c/w 3hr Emer Type E1-O 3 Hr SC NM LED Surface Emergency unit - open area optic Type E1-C 3 hr SC NM LED Surface Emergency unit - corridor optic Type E2 3 hr SC NM LED Surface IP65 Emergency bulkhead Type EX 3 Hr SC Maintained LED Surface Emergency exit sign Type G1E-P 24W LED Surface decorative bulkhead c/w 3hr Emer Type H1E-P 24W LED Surface bulkhead c/w 3hr Emer Type J1E 2 x 35W T5 Surface HF IP44 Fluorescent Pris Luminairec/w 3hr Emer Type K1 38W 2D Surface HF Fluor Bulkhead Type K2E-P 28W 2D Surface HF Fluor Bulkhead c/w 3hr Emer & Photocell Type L1E 26W PL Recessed CF downlight c/w IP44 Lens and 3hr Emer Type M1 IP44 Surface LED Luminaire above skylight Type N1 Suspended 320W MH Pris Bowl Luminaire - mod existing -dimmable Type P1 Existing susp LG luminaire to be modified for dimming operation SYMBOLS LEGEND- SWITCHING Existing lighting scheme to be retained (recently replaced.) Swiching type Description 1 way switch 2 way switch Intermediate switch Existing susp LG luminaires to be modified with dimmable ballast and controlled via seperate dimmer switch. P1 P1 P1 P1 M Existing illuminated exit Exist B IT Exist D4E PIR overide switch MW Microwave sensor with time/daylight adjustment - CP Range MW Wireless PIR sensor with dimming capability - CP Range EBD pc C3E RC Wireless RF Relay controller - AT-SL- DDR-SA RF Wireless PIR control (RF input) Unit - AT/BB 2G+K Exist Nr denotes gangs, K denotes keyswitch E2 D C B A Rev Replace TH spots lamps in existing spots lights with 3W GU10 LED spot lamps D4E 10sep12 28aug12 23jul12 23may12 Date Amendments to book store 26 fitting types. Wireless equipment added, minor amendments Minor amendments Type C5 ftgs to book racks, MW detection to office47 . Revision text John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com BASEMENT TENDER Type D4E fittings controlled via 2way switching between Basement and Ground O PIR sensor with time/daylight adjustment - CP Range EBD PIR UB D Momentary switch PIR O DB H M RF Input unit for ceiling mounted RF Relay Controllers to be behind switching located in staff corridor. SYMBOLS LEGEND - ELECTRICAL DISTRIBUTION Device Description Switchfuse (rating as detailed) H1E-P pc ELEC SUB STN A1-D A1-D A1-D A1-D 4G-M A1-D A1-D H1E-P A1-D pc REAR STAFF ENTRANCE H1-P O A1-D A1-D C2 K A1-D C1 E1-O M A1-D C2 C1 PIR C/O Generator supply switchfuse A1-D A1-D pc A1-D A1-D pc E1-O A1-D A1-D A1-D A1-D Disconnect make safe and remove existing wall lighting Exist G1E-P G1E-P A1-D EX G1E-P EX K A1-D A1-D RC MEZZ LEVEL A1-D RC O Exist E2 A1-D A1-D A1-D Proposed lighting to 09 - Comunity and Childrens Library to be controlled via daylight compensation detection. A1-D E1-O EMER ESCAPE ROUTE pc A1-D THE EXACT QUANTITY & LOCATIONS OF PHOTO-CELL UNITS ARE TO BE AGREED WITH THE MANUFACTURERS A1-D A1-D A1-D pc Type A2-D 2 x 35W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire Type A3-D 2 x 49W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire Type A4-D 2 x 35W T5 Surface HF Dimmable Fluorescent Louvre Luminiare Type B1-D 2 x 35W T5 Surface HF Dimmable Fluorescent Opal diff Luminiare Type C1-C C2 PIR Exist DB 7 DB 4 1 x 49W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire Type C1 DB (no ref) C1E Type A1-D PIR J1E A1-D MCCB panelboard Luminaire type Description C2 RC A1-D Distribution board - 3 phase 5A supply (spur) MK E1-O M Generator change-over panel DB SYMBOLS LEGEND - LIGHTING MW A1-D Distribution board - 1 phase H1-P C1-C C1-CE DB PB C1 Exist RC K2E-PC PIR E1-O A1-D H1E-P 2G PIR C1-C 2W for H/L wall lights Staff entrance door bulkhead to be replaced with Type K2E-PC with integral photo-cell H1E-P 3G EX EMER ROUTE A1-D H1E-P RF Exist 1 x 35W T5 Surface HF Fluorescent Prismatic Luminaire 1 x 35W T5 Surface HF Corri-func Fluorescent Prismatic Luminaire Type C2 1 x 49W T5 Surface HF Fluorescent Prismatic Luminaire Type C3 2 x 35W T5 Surface HF Fluorescent Prismatic Luminaire Type C4 2 x 49W T5 Surface HF Fluorescent Prismatic Luminaire Type C5 1 x 35W T5 Surface HF Fluorescent batten Luminaire Type D4E-D 2 x 49W T5 Surface HF Dimmable Fluor Pris Luminaire c/w 3hr Emer Type E1-O 3 Hr SC NM LED Surface Emergency unit - open area optic Type E1-C 3 hr SC NM LED Surface Emergency unit - corridor optic Type E2 3 hr SC NM LED Surface IP65 Emergency bulkhead Type EX 3 Hr SC Maintained LED Surface Emergency exit sign Type G1E-P 24W LED Surface decorative bulkhead c/w 3hr Emer Type H1E-P 24W LED Surface bulkhead c/w 3hr Emer Type J1E 2 x 35W T5 Surface HF IP44 Fluorescent Pris Luminairec/w 3hr Emer Type K1 38W 2D Surface HF Fluor Bulkhead Type K2E-P 28W 2D Surface HF Fluor Bulkhead c/w 3hr Emer & Photocell Type L1E 26W PL Recessed CF downlight c/w IP44 Lens and 3hr Emer Type M1 IP44 Surface LED Luminaire above skylight Type N1 Suspended 320W MH Pris Bowl Luminaire - mod existing -dimmable Type P1 Existing susp LG luminaire to be modified for dimming operation SYMBOLS LEGEND- SWITCHING A1-D A1-D pc A1-D A1-D A1-D pc A1-D A1-D Swiching type Description 4G A1-D E1-O A1-D A1-D A1-D RC RC 4K DB H UB C1 M Type D4E-D ftgs controlled via Photocell at 1st flr 3 A2-D D4E-D H1E-P H1E-P H1E-P K2E-PC Main electrical switchroom - refer to FKH drawing 3797/E-03 for existing and proposed layouts & scope of works. RC A4-D 6 Nr Type A4-D fittings to 06 Recordings to be mounted to existing positions on beams. pc A3-D E1-O pc A3-D E1-O A3-D A4-D A3-D Replace TH spot lamps in existing 5nr downlights with 3W GU10 LED lamps EX RC Existing entrance lighting to be controlled via RF Input units. Exist Proposed lighting to 04 - Ent cafe and part 06 - Recordings to be controlled via daylight compensation detection. EX A3-D K2E-PC pc RC RC A3-D A3-D E1-C Exist EX Install a Type K2E-PC Luminaire with integral 3hr Emer and photo-cell to the existing emergency lighting circuit / conduit containment L1E GRD FLOOR MAIN LIBRARY ENTRANCE Wireless PIR sensor with dimming capability - CP Range EBD RC Wireless RF Relay controller - AT-SL- DDR-SA RF Wireless PIR control (RF input) Unit - AT/BB Nr denotes gangs, K denotes keyswitch 14dec12 28aug12 23jul12 23may12 Date Lighting amended to Rent 04 and additional control photo-cells Wireless equipment added, minor amendments Minor amendments Type A4-D surface ftgs to Recording. Wireless detection amended. Revision text Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com A3-D pc Microwave sensor with time/daylight adjustment - CP Range MW John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT A4-D RC pc MW RF Input unit for ceiling mounted RF Relay Controllers to be behind switching located in staff corridor. RC Exist Install recessed downlight c/w emerg conversion to entrance lobby. pc A4-D A3-D PIR sensor with time/daylight adjustment - CP Range EBD Location of RF Input unit for ceiling mounted RF Relay Controller behind master switching and emergency lighting test keyswitches. A3-D PIR RF controller above suspended ceiling Emergency ltg test switches for ent/cafe and recordings to be located at distribution board DB 4 4G-M 4K RF A3-D A3-D O MEZZ LEVEL A4-D TENDER H1E-P pc O 2W switching for main staircase ltg to bsmt PIR overide switch PIR D C B A Rev RC A4-D K K Momentary switch O pc A2-D p2 J1E M 2G+K E1-O 1 Com FB A2-D D4E-D Comp C1E THE TYPE A LUMINAIRES TO THE MAIN PUBLIC LIBRARY AREAS ARE TO BE SUSPENDED FROM THE EXISTING LUMINAIRE POSITIONS. REFER TO PROJECT LUMINAIRE SCHEDULE FOR DETAILS OF THE PROPOSED FITTINGS. A2-D DB IT E1-O B 2 DB DB 1 D Intermediate switch EX A1-D Exist PIR 2 way switch A1-D Remove 2W for H/L wall lights Multigang keyswitches for emergency lighting test. 1 way switch Remove existing lighting to 09 - Comunity and Childrens Library controlled in four zones via 4 G switch and contactors at DB HUB SYMBOLS LEGEND - ELECTRICAL DISTRIBUTION Hatch to roof level RF Input unit for RF Relay Unit mounted in behind switching in office corridor Device Switchfuse (rating as detailed) H1E-P RF Distribution board - 1 phase DB Distribution board - 3 phase MCCB panelboard H1E-P N1 N1 5A supply (spur) N1 SYMBOLS LEGEND - LIGHTING EX 2G Existing 2W for 30 - Library ltg to be removed EX pc M Luminaire type Description C4 PIR C1-CE Provide primary and emergency lighting to the roof voids above Library areas 26 & 30. Include for the supply and installation of 2Nr Type J1E luminaires to each roof space. The circuits for these installations are to be devired from the nearest convenient distribution board. Access to these roof voids (and lift plantroom) is via the roof ladder at 1st floor rear staircase 35. Type A1-D 1 x 49W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire Type A2-D 2 x 35W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire Type A3-D 2 x 49W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire Type A4-D 2 x 35W T5 Surface HF Dimmable Fluorescent Louvre Luminiare Type B1-D 2 x 35W T5 Surface HF Dimmable Fluorescent Opal diff Luminiare PIR N1 pc N1 N1 E1-O E1-O C4 C1-C PIR Type C1 Type C1-C M M C4E N1 N1 LIFT A4-D A4-D K 3G RC DB 10 A4-D Redundant DB DB RF Input units for RF Relay Controllers installed in new cupboard to DB10. K 2G Existing 2G for 26B - Library ltg to be removed G1E-P C4 PIR N1 Existing 3G for 30 - Library ltg to be removed conduits to level roof space to be reused Line of lower clg bulkhead J1E B1-D B1-D J1E K G1E-P K O E1-O A4-D EX A4-D A4-D pc B1-D B1-D RC Exact locations of RF Relay controller subject to existing conduit route 2G K Line of lower clg bulkhead pc ROOF LEVEL A3-D A3-D 1 x 35W T5 Surface HF Corri-func Fluorescent Prismatic Luminaire Type C2 1 x 49W T5 Surface HF Fluorescent Prismatic Luminaire Type C3 2 x 35W T5 Surface HF Fluorescent Prismatic Luminaire Type C4 2 x 49W T5 Surface HF Fluorescent Prismatic Luminaire Type C5 1 x 35W T5 Surface HF Fluorescent batten Luminaire Type D4E-D 2 x 49W T5 Surface HF Dimmable Fluor Pris Luminaire c/w 3hr Emer Type E1-O 3 Hr SC NM LED Surface Emergency unit - open area optic Type E1-C 3 hr SC NM LED Surface Emergency unit - corridor optic Type E2 3 hr SC NM LED Surface IP65 Emergency bulkhead Type EX 3 Hr SC Maintained LED Surface Emergency exit sign Type G1E-P 24W LED Surface decorative bulkhead c/w 3hr Emer Type H1E-P 24W LED Surface bulkhead c/w 3hr Emer Type J1E 2 x 35W T5 Surface HF IP44 Fluorescent Pris Luminairec/w 3hr Emer Type K1 38W 2D Surface HF Fluor Bulkhead Type K2E-P 28W 2D Surface HF Fluor Bulkhead c/w 3hr Emer & Photocell Type L1E 26W PL Recessed CF downlight c/w IP44 Lens and 3hr Emer Type M1 IP44 Surface LED Luminaire above skylight Type N1 Suspended 320W MH Pris Bowl Luminaire - mod existing -dimmable Type P1 Existing susp LG luminaire to be modified for dimming operation SYMBOLS LEGEND- SWITCHING B1-D THE TYPE A3-D LUMINAIRES TO LIB 26A ARE TO BE SUSPENDED FROM THE EXISTING LUMINAIRE POSITIONS. REFER TO PROJECT LUMINAIRE SCHEDULE FOR DETAILS OF THE PROPOSED FITTINGS. 1 x 35W T5 Surface HF Fluorescent Prismatic Luminaire A3-D B1-D Swiching type Description THE EXACT QUANTITY & LOCATIONS OF PHOTO-CELL UNITS ARE TO BE AGREED WITH THE MANUFACTURERS pc 1 way switch 2 way switch Intermediate switch E1-O A3-D pc A3-D A3-D B1-D pc B1-D 4 Nr RF Input units for RF Relay Controllers installed within cupboard for DB 9. E1-O RC RC RC RC A3-D Existing MH low bay fittings and emergency lighting above the 2nr skylights are to be replaced with Type M1 ftgs controlled via photo-cell A3-D pc A3-D M Momentary switch O PIR overide switch PIR PIR sensor with time/daylight adjustment - CP Range EBD MW Microwave sensor with time/daylight adjustment - CP Range MW Wireless PIR sensor with dimming capability - CP Range EBD pc Switching for Library staircase and skylight luminaires K 4G-M DB 9 RC Wireless RF Relay controller - AT-SL- DDR-SA RF Wireless PIR control (RF input) Unit - AT/BB 2G+K Nr denotes gangs, K denotes keyswitch Exist D4E-D Cct to ftgs at grd & bsmt Exist D4-D Exist M1 pc E1-O RF K D C B A Rev Retain existing FP emer ltg circuit Exist Exist Retain existing lighting to toilet and doorway (recently refurbished.) M1 EX 14dec12 28aug12 23jul12 23may12 Date Lighting control photo-cell units added Wireless equipment added, minor amendments Minor amendments Wireless detection amended. Revision text EX D4-D EX H1E-P 2 DB DT H1E-P E1-O DB 8 Lampholder - investigate source, disconnect, make safe and remove/blank off. EX E1-O Exact location of RF unit to skylight lighting to be within skylight shelters on roof John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com Connect to existing ltg cct. Utilise existing containment for wiring emergency circuit. Install emer ftg to underside of existing surface trunking at picture rail height, provide new cct back to DB Connect to existing ltg cct. Existing chandelier to be fitted with 5 Nr 6W LED candle lamps E1-O Existing lighting scheme to Carnegie Hall is to be retained (future project.) H1E-P Replace existing fitting with H1E-P luminaires H1E-P Replace existing fitting with H1E-P luminaires 1ST FLOOR 1ST FLOOR BALCONY TENDER Lift control panel DB PB 4G-M THE TYPE N1 SUSPENDED LUMINAIRES TO LIB 30 ARE TO BE RETAINED AND MODIFIED FOR DIMMABLE DAYLIGHT COMPENSATION FEATURE. Description SYMBOLS LEGEND- FIRE ALARM SYSTEM Works to Staircase 60 to be undertaken out of normal working hours. Access to be maintained to staff at all times. S Device S S DB 12 S S S S S FA cables installed surface to book admin/store areas, plantroom & rear staircase Works to Book store 46 and associated offices/admin rooms to be undertaken in normal working hours, with access for staff under escort as required. Description FA-P Fire Alarm Panel FA-R Fire Alarm Repeater Panel TU Wireless detection Translator Unit S H SW HW MW Smoke detector Heat detector Smoke detector - wireless Heat detector - wireless Multi detector - wireless (V denotes void mounted) Break glass unit Sounder incorporated onto ceiling point detector Strobe incorporated into ceiling point detector Electronic sounder - wall mounted DB 5 DB 6 Electronic sounder & strobe unit - wall mounted H Detector remote indicator RI S S S Strobe - wall or ceiling mounted INT Monitoring Communicator C Telephone line Interface to existing access control S INT 13A unswitched spur Door Controller Line of susp clg DC FA cables installed within false/suspended ceilings & surface lift lobby areas Remove existing BGU and asssociatd wiring. Provide new BGU on addressable system S Works to Main Staircase 55, Discovery 40 and Lift Lobby 44 to be undertaken out of normal working hours. FA cables installed surface to underside of Discovery Library area ceiling. DC Door access controller FS Firemans switch - 3 position for Auto/On/Off FA cables for basement areas installed within suspended ceiling void. Surface cabling Interface system with existing basement vent system. Remove existing Minerva system and associated wiring back to the BGU at the escape lobby. Interface unit (IP/OP) SV Smoke detector to ceiling void CP INT S FA cables installed surface to underside of Discovery Library area ceiling. S DB H UB D B IT S C B A Rev 28aug12 23jul12 28may12 Date Works zones added Minor amendments Minor amendments for wireless devices. Revision text FA cables run in false ceiling. Traps to be provided for access. John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com BASEMENT TENDER S SYMBOLS LEGEND- FIRE ALARM SYSTEM Device ELEC SUB STN Interface to existing access control EMER ROUTE S INT S SW FA-P Fire Alarm Panel FA-R Fire Alarm Repeater Panel TU Wireless detection Translator Unit S H SW HW MW Smoke detector REAR STAFF ENTRANCE S Works to Staircase 13 & 36 and all associated staff facilities at grd and mezz to be undertaken out of normal working hours. Access to be maintained to staff at all times. Heat detector Smoke detector - wireless Heat detector - wireless Multi detector - wireless (V denotes void mounted) Break glass unit H Sounder incorporated onto ceiling point detector Strobe incorporated into ceiling point detector DB ? FA cables installed surface to staff office, amenity, toilet & rear staircase areas. M Generator change-over panel Description DB 7 DB 4 Electronic sounder & strobe unit - wall mounted S SW C/O Electronic sounder - wall mounted Wireless detector translator unit Nr 2. provide elec supply from DB1 TU Generator supply switchfuse Detector remote indicator RI Strobe - wall or ceiling mounted INT Works to Lift lobby 11 and associated Generator room 53 to be undertaken out of normal working hours. Interface unit (IP/OP) Monitoring Communicator C Telephone line Wireless detection to underside of library area 09 ceilings. S 13A unswitched spur FA cables installed within false & suspended ceilings & surface lift lobby areas & G/p-rm MEZZ LEVEL Section works - barrier to be provided S Fire Alarm Repeater panel by rear escape doors. Electrical supply from DB1 DC Door access controller FS Firemans switch - 3 position for Auto/On/Off SW Section works - barrier to be provided Works to Comunity/Childrens Lib 09 to be undertaken in normal working hours on a section by section basis with areas open to public (as detailed) using barriers. Works within the barrier route to be undertaken out of normal working hours. EMER ESCAPE ROUTE SW FA sounder wired from comms room DB H UB D S S B IT DB 1 Works to Side Staircase 17 to be undertaken in normal working hours. (Electrical room 18 & Comms Room 63 works to be undertaken during agreed shutdown.) SW FA BGU & sounder wired from side staircase S S W Works to Main Ent, Issues, Rets, Recordings & Shop) 02, 04, 06 & 08 and Main Staircase 16 to be undertaken out of normal working hours. S S C B A Rev DB 4 28aug12 23jul12 28may12 Date Works zones added Minor amendments Minor amendments for wireless devices. Revision text SW FA cables installed surface to side staircase & elec room. FA cables at high level to main staircase. Install boxing to conceal FA & elec cables TU SW SW John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT FA cables installed surface to structural beams, underside of 06 ceiling & walls. Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com Interface to existing auto door, use false panel to head of door SW Storeroom partition is not full height to ceiling FA cables installed within suspended ceilings & surface to walls in main entrance areas. FA wiring to follow line of existing trunking S SV Smoke detector to ceiling void Main Fire Alarm panel by main entrance doors. Electrical supply from DB1 M Interface to existing auto door G Supply and install a gas solenoid valve and interface to fire alarm system. Wireless detection to underside of library area 09 ceilings. GRD FLOOR MAIN LIBRARY ENTRANCE TENDER MEZZ LEVEL (grd & 1st) Wireless detector translator unit Nr 1 provide elec supply from DB1 Hatch to roof level SYMBOLS LEGEND- FIRE ALARM SYSTEM Device Smoke detector in book lift shaft Works to Staircase 35 to be undertaken out of normal working hours. Access to be maintained to staff at all times. S S RI S Interface to existing access control Wireless detection to underside of library area 30 ceiling and within roof void. S W Multi functional detector in roof void WM V INT S TU Wireless detection Translator Unit S H SW HW MW Smoke detector Heat detector Smoke detector - wireless Heat detector - wireless Multi detector - wireless (V denotes void mounted) Break glass unit Sounder incorporated onto ceiling point detector Electronic sounder - wall mounted Electronic sounder & strobe unit - wall mounted Detector remote indicator RI Wireless detector translator unit Nr 3. provide elec supply from DB1 S DB ?? Strobe - wall or ceiling mounted INT Redundant DB S Fire Alarm Repeater Panel Works to Offices 32, 33,& 34 & associated corridor 31 to be undertaken in normal working hours, with access for staff. TU Smoke detector in lift shaft FA-R Strobe incorporated into ceiling point detector Smoke detectors mtd each side of vent grills Works to Lift lobby 11 and Roof Lift plantroom are to be undertaken out of normal working hours. Fire Alarm Panel S FA sounder wired from corridor 31 FA cables installed surface to lift planroom FA-P FA cables installed surface to staff office, circulation & rear staircase areas. SW Description Monitoring Communicator C Line of lower clg bulkhead Interface unit (IP/OP) Telephone line Interface system with lift controller for grd homing feature INT DB 10 Section works - barrier to be provided LIFT RI M WS S FA cables installed within false/suspended ceilings & surface lift lobby areas 13A unswitched spur S DC Door access controller FS Firemans switch - 3 position for Auto/On/Off WS Wireless detection to underside of library area 26C ceilings. Line of lower clg bulkhead ROOF LEVEL SW Wireless detection to underside of library area 26A & 26B ceilings and within roof void Works to Main Staircase 57, Foyer 22 & Library 26B to be undertaken out of normal working hours. Multi functional detector in roof void Works to 1st Floor Library areas 26A and 30 to be undertaken in normal working hours. To be sectioned from others areas open to public (as detailed) using barriers. WM V Vaulted clg WS Interface system with 1st floor extract systems via contactor and provide firemans switch for "Auto/On/Off" control FS C Works to Side Staircase 59 to be undertaken in normal working hours. Staircase to be in use when Carnegie Room is let. Disabled toilet 21 (recent new install) to be maintained operational during Library opening times. INT FA sounder wired from toilet 21 clg void SW Works to Carnegie Room 23 and associated areas to be undertaken in normal working hours, subject to bookings. SW 2 Works zones added & interface for extract systems Minor amendments Minor amendments for wireless devices. Revision text S S DB 8 Wireless detection to underside of Carnegie room 23 ceiling. FA cables installed surface to underside of balcony 62 ceiling & staircase 25 walls. FA cables installed in existing trunking below picture rail S John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com SW S SW Smoke detectors to underside of ceiling 28aug12 23jul12 28may12 Date FA cables installed withing the existing trunking dropper to low level DB DT FA cables installed surface to side staircase, stage area ceiling & elec room. C B A Rev To high level ceiling Store partitioning is not full height to store ceiling S S S Wireless detection to underside of Carnegie room 23 ceiling. 1ST FLOOR 1ST FLOOR BALCONY TENDER Lift control panel SYMBOLS LEGEND- FIRE ALARM SYSTEM LN&E supply and 1-10V dimming circuit from RC unit to all luminaires Device Description FA-P Fire Alarm Panel FA-R Fire Alarm Repeater Panel pc Max of 10 Nr ballasts per RC unit Lighting cct from DB Type A ftgs RC RC unit ceiling mounted in small white GRP/ABS adaptable box adjacent the ftg at the start of the circuit. Type A ftgs Type A ftgs Max range of RF unit to RC controller - 30m for conjested area, 100m for clear area Max of 10 Nr ballasts per RC unit M Refer to CP Electronics data sheet for connection details and cable reqirements Wireless detection Translator Unit S H SW HW MW Smoke detector Heat detector Smoke detector - wireless Heat detector - wireless Multi detector - wireless (V denotes void mtd) Break glass unit 13A spur for 240/12 DC power supply for RF unit RF TYPICAL WIRELESS CONTROL LIGHTING CIRCUIT SCHEMATIC TU Sounder incorporated onto ceiling point detector Strobe incorporated into ceiling point detector Electronic sounder - wall mounted Momentary switch for remote control of lighting via RF/RC units. Gangs as per layout drgs Electronic sounder & strobe unit - wall mounted RI Detector remote indicator Strobe - wall or ceiling mounted INT C Interface unit (IP/OP) Monitoring Communicator Telephone line 13A unswitched spur SW HW Wireless detection Wireless detection Translator unit H 13A unswitched spur from local DB TU H S Loop driven detection/sounders SW HW Wireless detection INT SW FS Firemans switch - 3 position for Auto/On/Off pc An-10 PIR - CP Range EBD RC An-10 Relay Controller - AT-SL-DDR-SA RF An-10 RF Unit - AT/BB HW Wireless detection 13A unswitched spur from local DB TU TU Wireless detection Translator unit Wireless detection Translator unit A Rev 10sep12 Detector symbols corrected Date Revision text John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT Single addressable fire alarm loop - 2 core 1.5mm PH60 cable Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com Repeater panel located at Ground floor lift looby Single loop Addressable fire alarm panel located at main entrance 13A unswitched spur from DB 1 Monitoring Communicator c/w integral PSU & battery FA-P C Enhanced cable - 2 core 1.5mm Red PH120 cable FA-R Telephone line by Client FIRE ALARM SCHEMATIC Diagramatical only, locations of equipment dependant on wired position on loop) 13A unswitched spur from DB 1 TENDER ISSUE 13A unswitched spur from local DB INT S Interface units for connection to gas valve, access control, bsmt vent, 1st flr extract and lift Door access controller NOTES 1. Single loop BS 5839 Cat L4 addressable fire alarm system for basement area. System to provide warning to Central Monitoring Station, operate smoke extract and fail safe open pedestrian escape gates/door access control system. 2. Refer to drawings 3797/E-07 to 09 for fire alarm installation. 3. Refer to drawings 3797/E-04 to 06 for primary and emergency lighting installation Loop driven detection/sounders Interface units for connection to gas valve, access control, bsmt vent, 1st flr extract and lift DC