1. Read drawing in conjunction with drawing 3797/E-02.
2. Refer to current Periodic Inspection Report Schedule of
Circuits details for final circuit cable types and destinations..
LIFT
Panel
63A TPN
Switchfuse
LIFT
Located in roof
plantroom
SIDE STAIRCASE
(Serves 1st flr disabled toilet)
DB DT2
1ST FLOOR
Located in Library - 30.
Appears redundant, all circuits
cut off inside need to establish
if any point of connection
1ST FLR GENERAL REF LIB
DB No Ref ??
MEM 100A SPN 13W
MCB DB
In GRP
enclosure
CARNEGIE ROOM
1ST FLR GENERAL REF LIB LOCAL LIB BEHIND STAGE
DB 10
DB 8
1ST FLR HELP DESK
DB 9
MEM 100A TPN 8W
MCB DB
MG 100A TPN 8W
MCB DB
WYLEX 63A SPN 6W
MCB CU
Not labeled and
poss not tested
GENERATOR PLANTROOM
DB No Ref
MEM 100A TPN 4W
HRC FB
MEM 63A SPN 4W
HRC FB
HUB ROOM
DB IT
GENERATOR ROOM
DB 7
Loadstar 63A SPN 8W
MCB DB
GRD FLOOR
MEM 63A TPN 2W
HRC FB
HUB ROOM
DB HUB
FRONT OF LIBRARY
DB 4
`MEM2 100A TPN 8W
MCB DB
MEMERA 63A SPN
12W MCB DB
63A TPN
Switchfuse
GENERATOR ROOM
DB 4
BOTTOM REAR STAIRS
DB 12
WYLEX 63A SPN 4W
MCB CU
BSMT
GENERATOR
C/O PANEL
MK 63A SPN 12W
MCB DB
BOILER ROOM
DB 5
BOILER ROOM
DB 6
FED ELEC 100A TPN
4W MCB DB
BILL 63A TPN 4W
WIRE FUSEBOARD
Power & control in
combined cable
CONTROL
SWITCHFUSE
DB Fans appears
redundant (all fuses
removed) - need to
verify connection to FB
MAIN SWITCHROOM
BILL 63A TPN 6W
WIRE FUSEBOARD
COMP C/O
PANEL
FANS
DB - (No Ref)
MAIN SWITCHROOM
DB 2
BILL 63A TPN 3W
WIRE FUSEBOARD
BILL 63A TPN 3W WIRE
FUSEBOARD
BILL 63A TPN 3W WIRE
FUSEBOARD
32A TPN
MEM
Switchfuse
63A TP
Switch
63A TP
Switch
30A TP
Switch
63A SP
Switch
MAIN SWITCHROOM
DB COMP 2
MK 63A SPN
MCB DB
MK 63A SPN MCB
DB
NON -ESS
63A TPN
MEM
Switchfuse
09aug12 Minor amendments.
29may12 Minor amendments.
15mar12 General amendments following further survey.
ESSENTIAL
John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT
Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com
100A TPN
DB DTI
Switchfuse
63
32
63
63
63
63
-
32
1
2
3
4
5
6
7
8
-
-
-
L1
L2
L3
9
63
10
8 Nr WYLEX RCD UNITS
MCCB
-
MAIN MEM 200A TPN 10W FUSEBOARD
Main 200A TPN
switchfuse
Incoming 100A
TPN supply
REC
metering
-
RCD's serve socket circuits off DB's 1, 2 & 3. Contractor
to verify and decommission when new DB1 installed.
TENDER ISSUE
63A TPN
BILL
Switchfuse
63A TP
Switch
MAIN SWITCHROOM
DB COMP 1
C
B
A
SPARE
ELEC SWITCHROOM
POWER
ISOLATOR
MAIN SWITCHROOM
DB 1
MAIN SWITCHROOM
DB 3
100KVA/80KW
GENERATOR
NOTES
LIFT
Panel
63A TPN
Switchfuse
New Ref DB 7
LOCAL LIB BEHIND STAGE
DB 8
MEM 100A SPN 13W
MCB DB
1ST FLOOR
New Ref DB 8
1ST FLR HELP DESK
DB 9
NEW MEM 100A
TPN 8W MCB DB
MEM 100A TPN 8W
MCB DB
NEW
EXTG
New Ref DB 8/1
1ST FLR GENERAL REF LIB
DB 10
Located in roof
plantroom
MG 100A TPN 8W
MCB DB
NEW MEM 63A SPN
7W MCB DB
NEW
EXTG
6mm PVC/PVC cable
New Ref DB 3/1
HUB ROOM
DB IT
New Ref DB 5
GENERATOR ROOM
DB 7
Loadstar 63A SPN 8W
MCB DB
New Ref DB 4
FRONT OF LIBRARY
DB 4
MEM2 100A TPN 8W
MCB DB
GRD FLOOR
New Ref DB 2/1
BOTTOM REAR STAIRS
DB 12
EXTG
NEW MEM 100A SPN
7W MCB DB
Install new 10mm 2C
SWA via 50A MCB
New Ref DB 2
BOILER ROOM
DB 5
Extend existing 16mm 4C SWA
NEW 100A TPN
8W MCB DB
NEW
NEW
ELEC SWITCHROOM
Install new 16mm 4C SWA
NEW MEM 100A
TPN 12W MCB DB
Extend existing 16mm 4C
SWA cable via adaptable
box/fixed terms
Install new 16mm 4C SWA
Install new 25mm 4C SWA
New Ref DB 1
MAIN SWITCHROOM
DB 1
Reconnect existing 16mm 4C SWA
BSMT
Reconnect existing 16mm 3C SWA
NEW
MEM 100A SPN 16W
MCB DB
NEW
GENERATOR
C/O PANEL
NEW
63A TPN
Switchfuse
Reroute and reconnect existing 16mm 2C SWA
HUB ROOM
DB HUB
NEW MEM 100A
TPN 6W MCB DB
Reconnect existing 16mm 4C SWA
EXTGNew Ref DB 3
100KVA/80KW
GENERATOR
A
09aug12 General amendments and cable sizes added.
John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT
Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com
63
1
63
63
-
L1
L2
L3
2
63
63
63
63
63
-
-
-
3
4
5
6
7
8
9
10
MCCB
-
REC meter to
be replaced
Existing Incoming
supply (fuses to be
confirmed 100A TPN)
-
NEW MAIN MEM 250A TPN
10W MCCB PANELBOARD
New MCCB current ratings
are 63A SP/TP as
appropriate
TENDER ISSUE
New Ref DB 6
SIDE STAIRCASE
DB DT2
Located in Library - 30. Appears
redundant, all circuits cut off inside.
Establish point of connection, make
safe and remove
1ST FLR GENERAL REF LIB
DB No Ref ??
1. Read drawing in conjunction with drawing 3797/E-01 & 03.
2. Refer to current Periodic Inspection Report Schedule of
Circuits details for final circuit cable types and destinations.
3. Upgrade earthing in accordance with BS7671 - 17th Edition
Regulation requirements.
Reconnect existing 16mm 4C SWA
Presently in GRP enclosure. Remove
enclosure, new DB to be enclosed in
timber cupboard (by others)
LIFT
Existing DB1 onto which all the final circuits
from DB2 & 3 are to be temp transferred.
Existing DB1 is to be removed once all
circuits have been ransferred to new DB
Existing
meter
New 250A
TPN 10W
MCCB
panelboard
Existing Sub main for DB9 (to
be extended via adpatable
box/fixed terminals
Existing conduits
Existing Header trunking (retain)
Exist
DB1
REC
CT
enc
(redundant)
Remove existing
switchfuses (will be
redundant)
New
DB1
125A
TPN
16W
Existing DB2 , 3
and fans all
removed
Existing sub main trunking (remove up to 2 comp for IT cables)
REC
cut-out
ELECTRICAL SWITCHROOM
ELEVATIONS
1/50
Rev
DB
New DB1
00abc00 Text
Date Revision text
HU
B
John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT
DB 1
New Main MCCB
panelboard
ELECTRICAL
SWITCHROOM PLAN
1/100
DB 4
TENDER ISSUE
Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com
SYMBOLS LEGEND - ELECTRICAL DISTRIBUTION
Device
Description
Switchfuse (rating as detailed)
H1E-P
C5
C5
C5
C4
C4E
DB 12
H1E-P
PIR
Exist
C5
O
M
K
O
PIR
C5
C4E
K M
PIR
C1
DB
Distribution board - 3 phase
MCCB panelboard
PB
PIR
K
Exist
EX K
C1
Distribution board - 1 phase
5A supply (spur)
PIR
C5E
Exist
O
DB
C1E
Rotate luminaires thro
90 degrees to achieve
light distribution
SYMBOLS LEGEND - LIGHTING
Luminaire type Description
Type A1-D
1 x 49W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire
Type A2-D
2 x 35W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire
Type A3-D
2 x 49W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire
Type A4-D
2 x 35W T5 Surface HF Dimmable Fluorescent Louvre Luminiare
Type B1-D
2 x 35W T5 Surface HF Dimmable Fluorescent Opal diff Luminiare
PIR
C5
C5
C5
K 3G
O
C1
C1E
C5
C5
C1
C1
C3
C3
K
K
M
C1
E2
DB 5
C4E
K1
Type C1
K1
Type C1-C
DB 6
PIR
C5
Exist
2G
PIR
C5
O
C1
C5E
C5
C3
C3
C1
C4
K1
MW
PIR
C5
C5
C5
C3
C3
C1E
C4
K
EX M
G1E-P
K
O
Line of susp clg
G1E-P
Existing
illuminated
exit
Existing
conversion
unit
Existing
conversion
unit
1 x 35W T5 Surface HF Fluorescent Prismatic Luminaire
1 x 35W T5 Surface HF Corri-func Fluorescent Prismatic Luminaire
Type C2
1 x 49W T5 Surface HF Fluorescent Prismatic Luminaire
Type C3
2 x 35W T5 Surface HF Fluorescent Prismatic Luminaire
Type C4
2 x 49W T5 Surface HF Fluorescent Prismatic Luminaire
Type C5
1 x 35W T5 Surface HF Fluorescent batten Luminaire
Type D4E-D
2 x 49W T5 Surface HF Dimmable Fluor Pris Luminaire c/w 3hr Emer
Type E1-O
3 Hr SC NM LED Surface Emergency unit - open area optic
Type E1-C
3 hr SC NM LED Surface Emergency unit - corridor optic
Type E2
3 hr SC NM LED Surface IP65 Emergency bulkhead
Type EX
3 Hr SC Maintained LED Surface Emergency exit sign
Type G1E-P
24W LED Surface decorative bulkhead c/w 3hr Emer
Type H1E-P
24W LED Surface bulkhead c/w 3hr Emer
Type J1E
2 x 35W T5 Surface HF IP44 Fluorescent Pris Luminairec/w 3hr Emer
Type K1
38W 2D Surface HF Fluor Bulkhead
Type K2E-P
28W 2D Surface HF Fluor Bulkhead c/w 3hr Emer & Photocell
Type L1E
26W PL Recessed CF downlight c/w IP44 Lens and 3hr Emer
Type M1
IP44 Surface LED Luminaire above skylight
Type N1
Suspended 320W MH Pris Bowl Luminaire - mod existing -dimmable
Type P1
Existing susp LG luminaire to be modified for dimming operation
SYMBOLS LEGEND- SWITCHING
Existing lighting
scheme to be retained
(recently replaced.)
Swiching type Description
1 way switch
2 way switch
Intermediate switch
Existing susp LG luminaires
to be modified with dimmable
ballast and controlled via
seperate dimmer switch.
P1
P1
P1
P1
M
Existing
illuminated
exit
Exist
B IT
Exist
D4E
PIR overide switch
MW
Microwave sensor with time/daylight adjustment - CP Range MW
Wireless PIR sensor with dimming capability - CP Range EBD
pc
C3E
RC
Wireless RF Relay controller - AT-SL- DDR-SA
RF
Wireless PIR control (RF input) Unit - AT/BB
2G+K
Exist
Nr denotes gangs, K denotes keyswitch
E2
D
C
B
A
Rev
Replace TH spots lamps in
existing spots lights with
3W GU10 LED spot lamps
D4E
10sep12
28aug12
23jul12
23may12
Date
Amendments to book store 26 fitting types.
Wireless equipment added, minor amendments
Minor amendments
Type C5 ftgs to book racks, MW detection to office47 .
Revision text
John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT
Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com
BASEMENT
TENDER
Type D4E fittings
controlled via 2way
switching between
Basement and Ground
O
PIR sensor with time/daylight adjustment - CP Range EBD
PIR
UB D
Momentary switch
PIR
O
DB H
M
RF Input unit for ceiling mounted RF
Relay Controllers to be behind
switching located in staff corridor.
SYMBOLS LEGEND - ELECTRICAL DISTRIBUTION
Device
Description
Switchfuse (rating as detailed)
H1E-P
pc
ELEC
SUB
STN
A1-D
A1-D
A1-D
A1-D
4G-M
A1-D
A1-D
H1E-P
A1-D
pc
REAR STAFF
ENTRANCE
H1-P
O
A1-D
A1-D
C2
K
A1-D
C1
E1-O
M
A1-D
C2
C1
PIR
C/O
Generator supply
switchfuse
A1-D
A1-D
pc
A1-D
A1-D
pc
E1-O
A1-D
A1-D
A1-D
A1-D
Disconnect make safe and
remove existing wall lighting
Exist
G1E-P
G1E-P
A1-D
EX
G1E-P
EX
K
A1-D
A1-D
RC
MEZZ LEVEL
A1-D
RC
O
Exist
E2
A1-D
A1-D
A1-D
Proposed lighting to 09 - Comunity and
Childrens Library to be controlled via
daylight compensation detection.
A1-D
E1-O
EMER ESCAPE
ROUTE
pc
A1-D
THE EXACT QUANTITY & LOCATIONS OF
PHOTO-CELL UNITS ARE TO BE AGREED
WITH THE MANUFACTURERS
A1-D
A1-D
A1-D
pc
Type A2-D
2 x 35W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire
Type A3-D
2 x 49W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire
Type A4-D
2 x 35W T5 Surface HF Dimmable Fluorescent Louvre Luminiare
Type B1-D
2 x 35W T5 Surface HF Dimmable Fluorescent Opal diff Luminiare
Type C1-C
C2
PIR
Exist
DB 7
DB 4
1 x 49W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire
Type C1
DB (no ref)
C1E
Type A1-D
PIR
J1E
A1-D
MCCB panelboard
Luminaire type Description
C2
RC
A1-D
Distribution board - 3 phase
5A supply (spur)
MK
E1-O
M
Generator
change-over panel
DB
SYMBOLS LEGEND - LIGHTING
MW
A1-D
Distribution board - 1 phase
H1-P
C1-C
C1-CE
DB
PB
C1
Exist
RC
K2E-PC
PIR
E1-O
A1-D
H1E-P
2G
PIR
C1-C
2W for H/L wall lights
Staff entrance door bulkhead to
be replaced with Type K2E-PC
with integral photo-cell
H1E-P
3G
EX
EMER
ROUTE
A1-D
H1E-P
RF
Exist
1 x 35W T5 Surface HF Fluorescent Prismatic Luminaire
1 x 35W T5 Surface HF Corri-func Fluorescent Prismatic Luminaire
Type C2
1 x 49W T5 Surface HF Fluorescent Prismatic Luminaire
Type C3
2 x 35W T5 Surface HF Fluorescent Prismatic Luminaire
Type C4
2 x 49W T5 Surface HF Fluorescent Prismatic Luminaire
Type C5
1 x 35W T5 Surface HF Fluorescent batten Luminaire
Type D4E-D
2 x 49W T5 Surface HF Dimmable Fluor Pris Luminaire c/w 3hr Emer
Type E1-O
3 Hr SC NM LED Surface Emergency unit - open area optic
Type E1-C
3 hr SC NM LED Surface Emergency unit - corridor optic
Type E2
3 hr SC NM LED Surface IP65 Emergency bulkhead
Type EX
3 Hr SC Maintained LED Surface Emergency exit sign
Type G1E-P
24W LED Surface decorative bulkhead c/w 3hr Emer
Type H1E-P
24W LED Surface bulkhead c/w 3hr Emer
Type J1E
2 x 35W T5 Surface HF IP44 Fluorescent Pris Luminairec/w 3hr Emer
Type K1
38W 2D Surface HF Fluor Bulkhead
Type K2E-P
28W 2D Surface HF Fluor Bulkhead c/w 3hr Emer & Photocell
Type L1E
26W PL Recessed CF downlight c/w IP44 Lens and 3hr Emer
Type M1
IP44 Surface LED Luminaire above skylight
Type N1
Suspended 320W MH Pris Bowl Luminaire - mod existing -dimmable
Type P1
Existing susp LG luminaire to be modified for dimming operation
SYMBOLS LEGEND- SWITCHING
A1-D
A1-D
pc
A1-D
A1-D
A1-D
pc
A1-D
A1-D
Swiching type Description
4G
A1-D
E1-O
A1-D
A1-D
A1-D
RC
RC
4K
DB H
UB
C1
M
Type D4E-D ftgs controlled
via Photocell at 1st flr
3
A2-D
D4E-D
H1E-P
H1E-P
H1E-P
K2E-PC
Main electrical switchroom - refer to FKH
drawing 3797/E-03 for existing and
proposed layouts & scope of works.
RC
A4-D
6 Nr Type A4-D fittings to 06 Recordings to be mounted to
existing positions on beams.
pc
A3-D
E1-O
pc
A3-D
E1-O
A3-D
A4-D
A3-D
Replace TH spot lamps in
existing 5nr downlights
with 3W GU10 LED lamps
EX
RC
Existing entrance
lighting to be controlled
via RF Input units.
Exist
Proposed lighting to 04 - Ent cafe and
part 06 - Recordings to be controlled via
daylight compensation detection.
EX
A3-D
K2E-PC
pc
RC
RC
A3-D
A3-D
E1-C
Exist
EX
Install a Type K2E-PC Luminaire with
integral 3hr Emer and photo-cell to the
existing emergency lighting circuit /
conduit containment
L1E
GRD FLOOR
MAIN LIBRARY
ENTRANCE
Wireless PIR sensor with dimming capability - CP Range EBD
RC
Wireless RF Relay controller - AT-SL- DDR-SA
RF
Wireless PIR control (RF input) Unit - AT/BB
Nr denotes gangs, K denotes keyswitch
14dec12
28aug12
23jul12
23may12
Date
Lighting amended to Rent 04 and additional control photo-cells
Wireless equipment added, minor amendments
Minor amendments
Type A4-D surface ftgs to Recording. Wireless detection amended.
Revision text
Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com
A3-D
pc
Microwave sensor with time/daylight adjustment - CP Range MW
John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT
A4-D
RC
pc
MW
RF Input unit for ceiling mounted RF
Relay Controllers to be behind
switching located in staff corridor.
RC
Exist
Install recessed downlight
c/w emerg conversion to
entrance lobby.
pc
A4-D
A3-D
PIR sensor with time/daylight adjustment - CP Range EBD
Location of RF Input unit for ceiling mounted RF
Relay Controller behind master switching and
emergency lighting test keyswitches.
A3-D
PIR
RF controller above
suspended ceiling
Emergency ltg test switches for ent/cafe and
recordings to be located at distribution board
DB 4 4G-M 4K
RF
A3-D
A3-D
O
MEZZ LEVEL
A4-D
TENDER
H1E-P
pc
O
2W switching for main
staircase ltg to bsmt
PIR overide switch
PIR
D
C
B
A
Rev
RC
A4-D
K
K
Momentary switch
O
pc
A2-D
p2
J1E
M
2G+K
E1-O
1 Com
FB
A2-D
D4E-D
Comp
C1E
THE TYPE A LUMINAIRES TO THE MAIN
PUBLIC LIBRARY AREAS ARE TO BE
SUSPENDED FROM THE EXISTING
LUMINAIRE POSITIONS. REFER TO
PROJECT LUMINAIRE SCHEDULE FOR
DETAILS OF THE PROPOSED FITTINGS.
A2-D
DB IT
E1-O
B 2 DB
DB 1 D
Intermediate switch
EX
A1-D
Exist
PIR
2 way switch
A1-D
Remove 2W for
H/L wall lights
Multigang keyswitches for
emergency lighting test.
1 way switch
Remove existing lighting to 09 - Comunity and
Childrens Library controlled in four zones via
4 G switch and contactors at DB HUB
SYMBOLS LEGEND - ELECTRICAL DISTRIBUTION
Hatch to roof
level
RF Input unit for RF Relay
Unit mounted in behind
switching in office corridor
Device
Switchfuse (rating as detailed)
H1E-P
RF
Distribution board - 1 phase
DB
Distribution board - 3 phase
MCCB panelboard
H1E-P
N1
N1
5A supply (spur)
N1
SYMBOLS LEGEND - LIGHTING
EX
2G
Existing 2W for
30 - Library ltg
to be removed EX
pc
M
Luminaire type Description
C4
PIR
C1-CE
Provide primary and emergency lighting to the roof
voids above Library areas 26 & 30. Include for the
supply and installation of 2Nr Type J1E luminaires to
each roof space. The circuits for these installations are
to be devired from the nearest convenient distribution
board. Access to these roof voids (and lift plantroom) is
via the roof ladder at 1st floor rear staircase 35.
Type A1-D
1 x 49W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire
Type A2-D
2 x 35W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire
Type A3-D
2 x 49W T5 Suspended HF Dimmable Fluorescent Louvre Luminaire
Type A4-D
2 x 35W T5 Surface HF Dimmable Fluorescent Louvre Luminiare
Type B1-D
2 x 35W T5 Surface HF Dimmable Fluorescent Opal diff Luminiare
PIR
N1
pc
N1
N1
E1-O
E1-O
C4
C1-C
PIR
Type C1
Type C1-C
M
M
C4E
N1
N1
LIFT
A4-D
A4-D
K
3G
RC
DB 10
A4-D
Redundant DB
DB
RF Input units for RF Relay
Controllers installed in new
cupboard to DB10.
K 2G
Existing 2G for
26B - Library ltg
to be removed
G1E-P
C4
PIR
N1
Existing 3G for 30 - Library
ltg to be removed conduits to
level roof space to be reused
Line of lower clg bulkhead
J1E
B1-D
B1-D
J1E
K
G1E-P
K
O
E1-O
A4-D
EX
A4-D
A4-D
pc
B1-D
B1-D
RC
Exact locations of RF Relay controller
subject to existing conduit route
2G
K
Line of lower clg bulkhead
pc
ROOF LEVEL
A3-D
A3-D
1 x 35W T5 Surface HF Corri-func Fluorescent Prismatic Luminaire
Type C2
1 x 49W T5 Surface HF Fluorescent Prismatic Luminaire
Type C3
2 x 35W T5 Surface HF Fluorescent Prismatic Luminaire
Type C4
2 x 49W T5 Surface HF Fluorescent Prismatic Luminaire
Type C5
1 x 35W T5 Surface HF Fluorescent batten Luminaire
Type D4E-D
2 x 49W T5 Surface HF Dimmable Fluor Pris Luminaire c/w 3hr Emer
Type E1-O
3 Hr SC NM LED Surface Emergency unit - open area optic
Type E1-C
3 hr SC NM LED Surface Emergency unit - corridor optic
Type E2
3 hr SC NM LED Surface IP65 Emergency bulkhead
Type EX
3 Hr SC Maintained LED Surface Emergency exit sign
Type G1E-P
24W LED Surface decorative bulkhead c/w 3hr Emer
Type H1E-P
24W LED Surface bulkhead c/w 3hr Emer
Type J1E
2 x 35W T5 Surface HF IP44 Fluorescent Pris Luminairec/w 3hr Emer
Type K1
38W 2D Surface HF Fluor Bulkhead
Type K2E-P
28W 2D Surface HF Fluor Bulkhead c/w 3hr Emer & Photocell
Type L1E
26W PL Recessed CF downlight c/w IP44 Lens and 3hr Emer
Type M1
IP44 Surface LED Luminaire above skylight
Type N1
Suspended 320W MH Pris Bowl Luminaire - mod existing -dimmable
Type P1
Existing susp LG luminaire to be modified for dimming operation
SYMBOLS LEGEND- SWITCHING
B1-D
THE TYPE A3-D LUMINAIRES TO LIB 26A
ARE TO BE SUSPENDED FROM THE
EXISTING LUMINAIRE POSITIONS. REFER
TO PROJECT LUMINAIRE SCHEDULE FOR
DETAILS OF THE PROPOSED FITTINGS.
1 x 35W T5 Surface HF Fluorescent Prismatic Luminaire
A3-D
B1-D
Swiching type Description
THE EXACT QUANTITY & LOCATIONS OF
PHOTO-CELL UNITS ARE TO BE AGREED
WITH THE MANUFACTURERS
pc
1 way switch
2 way switch
Intermediate switch
E1-O
A3-D
pc
A3-D
A3-D
B1-D pc
B1-D
4 Nr RF Input units for RF
Relay Controllers installed
within cupboard for DB 9.
E1-O
RC
RC
RC
RC
A3-D
Existing MH low bay fittings
and emergency lighting above
the 2nr skylights are to be
replaced with Type M1 ftgs
controlled via photo-cell
A3-D
pc
A3-D
M
Momentary switch
O
PIR overide switch
PIR
PIR sensor with time/daylight adjustment - CP Range EBD
MW
Microwave sensor with time/daylight adjustment - CP Range MW
Wireless PIR sensor with dimming capability - CP Range EBD
pc
Switching for Library staircase
and skylight luminaires
K
4G-M
DB 9
RC
Wireless RF Relay controller - AT-SL- DDR-SA
RF
Wireless PIR control (RF input) Unit - AT/BB
2G+K
Nr denotes gangs, K denotes keyswitch
Exist
D4E-D
Cct to ftgs at
grd & bsmt
Exist
D4-D
Exist
M1
pc
E1-O
RF
K
D
C
B
A
Rev
Retain existing FP
emer ltg circuit
Exist
Exist
Retain existing lighting to
toilet and doorway
(recently refurbished.)
M1
EX
14dec12
28aug12
23jul12
23may12
Date
Lighting control photo-cell units added
Wireless equipment added, minor amendments
Minor amendments
Wireless detection amended.
Revision text
EX
D4-D
EX
H1E-P
2
DB DT
H1E-P
E1-O
DB 8
Lampholder - investigate
source, disconnect, make
safe and remove/blank off.
EX
E1-O
Exact location of RF unit to
skylight lighting to be within
skylight shelters on roof
John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT
Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com
Connect to
existing ltg cct.
Utilise existing containment for
wiring emergency circuit. Install
emer ftg to underside of existing
surface trunking at picture rail height,
provide new cct back to DB
Connect to
existing ltg cct.
Existing chandelier to
be fitted with 5 Nr 6W
LED candle lamps
E1-O
Existing lighting scheme
to Carnegie Hall is to be
retained (future project.)
H1E-P
Replace existing fitting
with H1E-P luminaires
H1E-P
Replace existing fitting
with H1E-P luminaires
1ST FLOOR
1ST FLOOR BALCONY
TENDER
Lift control panel
DB
PB
4G-M
THE TYPE N1 SUSPENDED LUMINAIRES TO
LIB 30 ARE TO BE RETAINED AND
MODIFIED FOR DIMMABLE DAYLIGHT
COMPENSATION FEATURE.
Description
SYMBOLS LEGEND- FIRE ALARM SYSTEM
Works to Staircase 60 to be undertaken
out of normal working hours. Access to
be maintained to staff at all times.
S
Device
S
S
DB 12
S
S
S
S
S
FA cables installed surface to
book admin/store areas,
plantroom & rear staircase
Works to Book store 46 and associated
offices/admin rooms to be undertaken in
normal working hours, with access for
staff under escort as required.
Description
FA-P
Fire Alarm Panel
FA-R
Fire Alarm Repeater Panel
TU
Wireless detection Translator Unit
S
H
SW
HW
MW
Smoke detector
Heat detector
Smoke detector - wireless
Heat detector - wireless
Multi detector - wireless (V denotes void mounted)
Break glass unit
Sounder incorporated onto ceiling point detector
Strobe incorporated into ceiling point detector
Electronic sounder - wall mounted
DB 5
DB 6
Electronic sounder & strobe unit - wall mounted
H
Detector remote indicator
RI
S
S
S
Strobe - wall or ceiling mounted
INT
Monitoring Communicator
C
Telephone line
Interface to existing
access control
S
INT
13A unswitched spur
Door
Controller
Line of susp clg
DC
FA cables installed within
false/suspended ceilings &
surface lift lobby areas
Remove existing BGU and
asssociatd wiring. Provide new
BGU on addressable system
S
Works to Main Staircase 55, Discovery
40 and Lift Lobby 44 to be undertaken
out of normal working hours.
FA cables installed surface to
underside of Discovery Library
area ceiling.
DC
Door access controller
FS
Firemans switch - 3 position for Auto/On/Off
FA cables for basement areas
installed within suspended
ceiling void.
Surface
cabling
Interface system with existing basement
vent system. Remove existing Minerva
system and associated wiring back to the
BGU at the escape lobby.
Interface unit (IP/OP)
SV
Smoke detector
to ceiling void
CP
INT
S
FA cables installed surface to
underside of Discovery Library
area ceiling.
S
DB H
UB D
B IT
S
C
B
A
Rev
28aug12
23jul12
28may12
Date
Works zones added
Minor amendments
Minor amendments for wireless devices.
Revision text
FA cables run in false ceiling.
Traps to be provided for access.
John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT
Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com
BASEMENT
TENDER
S
SYMBOLS LEGEND- FIRE ALARM SYSTEM
Device
ELEC
SUB
STN
Interface to existing
access control
EMER
ROUTE
S
INT
S
SW
FA-P
Fire Alarm Panel
FA-R
Fire Alarm Repeater Panel
TU
Wireless detection Translator Unit
S
H
SW
HW
MW
Smoke detector
REAR STAFF
ENTRANCE
S
Works to Staircase 13 & 36 and
all associated staff facilities at grd
and mezz to be undertaken out of
normal working hours. Access to
be maintained to staff at all times.
Heat detector
Smoke detector - wireless
Heat detector - wireless
Multi detector - wireless (V denotes void mounted)
Break glass unit
H
Sounder incorporated onto ceiling point detector
Strobe incorporated into ceiling point detector
DB ?
FA cables installed surface to
staff office, amenity, toilet & rear
staircase areas.
M
Generator
change-over panel
Description
DB 7
DB 4
Electronic sounder & strobe unit - wall mounted
S
SW
C/O
Electronic sounder - wall mounted
Wireless detector translator unit
Nr 2. provide elec supply from DB1
TU
Generator supply
switchfuse
Detector remote indicator
RI
Strobe - wall or ceiling mounted
INT
Works to Lift lobby 11 and associated
Generator room 53 to be undertaken
out of normal working hours.
Interface unit (IP/OP)
Monitoring Communicator
C
Telephone line
Wireless detection to underside
of library area 09 ceilings.
S
13A unswitched spur
FA cables installed within false &
suspended ceilings & surface lift
lobby areas & G/p-rm
MEZZ LEVEL
Section works - barrier to be provided
S
Fire Alarm Repeater panel
by rear escape doors.
Electrical supply from DB1
DC
Door access controller
FS
Firemans switch - 3 position for Auto/On/Off
SW
Section works - barrier to be provided
Works to Comunity/Childrens Lib 09 to be
undertaken in normal working hours on a
section by section basis with areas open to
public (as detailed) using barriers. Works
within the barrier route to be undertaken out
of normal working hours.
EMER ESCAPE
ROUTE
SW
FA sounder wired
from comms room
DB H
UB D
S
S
B IT
DB 1
Works to Side Staircase 17 to be undertaken
in normal working hours. (Electrical room 18 &
Comms Room 63 works to be undertaken
during agreed shutdown.)
SW
FA BGU & sounder wired
from side staircase
S
S
W
Works to Main Ent, Issues, Rets, Recordings &
Shop) 02, 04, 06 & 08 and Main Staircase 16 to
be undertaken out of normal working hours.
S
S
C
B
A
Rev
DB 4
28aug12
23jul12
28may12
Date
Works zones added
Minor amendments
Minor amendments for wireless devices.
Revision text
SW
FA cables installed surface to
side staircase & elec room.
FA cables at high level to main
staircase. Install boxing to
conceal FA & elec cables
TU
SW
SW
John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT
FA cables installed surface to
structural beams, underside of
06 ceiling & walls.
Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com
Interface to existing
auto door, use false
panel to head of door
SW
Storeroom partition is
not full height to ceiling
FA cables installed within
suspended ceilings & surface to
walls in main entrance areas.
FA wiring to
follow line of
existing
trunking
S
SV
Smoke detector
to ceiling void
Main Fire Alarm panel by
main entrance doors.
Electrical supply from DB1
M
Interface to existing
auto door
G
Supply and install a
gas solenoid valve
and interface to fire
alarm system.
Wireless detection to underside
of library area 09 ceilings.
GRD FLOOR
MAIN LIBRARY
ENTRANCE
TENDER
MEZZ LEVEL
(grd & 1st)
Wireless detector
translator unit Nr 1
provide elec supply
from DB1
Hatch to roof
level
SYMBOLS LEGEND- FIRE ALARM SYSTEM
Device
Smoke detector
in book lift shaft
Works to Staircase 35 to be undertaken
out of normal working hours. Access to
be maintained to staff at all times.
S
S
RI
S
Interface to existing
access control
Wireless detection to underside
of library area 30 ceiling and
within roof void.
S W
Multi functional
detector in roof void
WM V
INT
S
TU
Wireless detection Translator Unit
S
H
SW
HW
MW
Smoke detector
Heat detector
Smoke detector - wireless
Heat detector - wireless
Multi detector - wireless (V denotes void mounted)
Break glass unit
Sounder incorporated onto ceiling point detector
Electronic sounder - wall mounted
Electronic sounder & strobe unit - wall mounted
Detector remote indicator
RI
Wireless detector
translator unit Nr 3.
provide elec supply
from DB1
S
DB ??
Strobe - wall or ceiling mounted
INT
Redundant DB
S
Fire Alarm Repeater Panel
Works to Offices 32, 33,& 34 & associated
corridor 31 to be undertaken in normal
working hours, with access for staff.
TU
Smoke detector
in lift shaft
FA-R
Strobe incorporated into ceiling point detector
Smoke detectors
mtd each side of
vent grills
Works to Lift lobby 11 and Roof Lift
plantroom are to be undertaken out of
normal working hours.
Fire Alarm Panel
S
FA sounder wired
from corridor 31
FA cables installed
surface to lift planroom
FA-P
FA cables installed surface to
staff office, circulation & rear
staircase areas.
SW
Description
Monitoring Communicator
C
Line of lower clg bulkhead
Interface unit (IP/OP)
Telephone line
Interface system with
lift controller for grd
homing feature
INT
DB 10
Section works - barrier to be provided
LIFT
RI
M
WS
S
FA cables installed within
false/suspended ceilings &
surface lift lobby areas
13A unswitched spur
S
DC
Door access controller
FS
Firemans switch - 3 position for Auto/On/Off
WS
Wireless detection to underside
of library area 26C ceilings.
Line of lower clg bulkhead
ROOF LEVEL
SW
Wireless detection to underside
of library area 26A & 26B
ceilings and within roof void
Works to Main Staircase 57, Foyer
22 & Library 26B to be undertaken
out of normal working hours.
Multi functional
detector in roof void
Works to 1st Floor Library areas
26A and 30 to be undertaken in
normal working hours. To be
sectioned from others areas open to
public (as detailed) using barriers.
WM V
Vaulted clg
WS
Interface system with 1st
floor extract systems via
contactor and provide
firemans switch for
"Auto/On/Off" control
FS
C
Works to Side Staircase 59 to be
undertaken in normal working hours.
Staircase to be in use when Carnegie
Room is let. Disabled toilet 21 (recent
new install) to be maintained operational
during Library opening times.
INT
FA sounder wired
from toilet 21 clg void
SW
Works to Carnegie Room 23
and associated areas to be
undertaken in normal working
hours, subject to bookings.
SW
2
Works zones added & interface for extract systems
Minor amendments
Minor amendments for wireless devices.
Revision text
S
S
DB 8
Wireless detection to underside
of Carnegie room 23 ceiling.
FA cables installed surface to
underside of balcony 62 ceiling
& staircase 25 walls.
FA cables installed in existing
trunking below picture rail
S
John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT
Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com
SW
S
SW
Smoke detectors to
underside of ceiling
28aug12
23jul12
28may12
Date
FA cables installed withing
the existing trunking dropper
to low level
DB DT
FA cables installed surface
to side staircase, stage
area ceiling & elec room.
C
B
A
Rev
To high
level ceiling
Store partitioning is not full
height to store ceiling
S
S
S
Wireless detection to underside
of Carnegie room 23 ceiling.
1ST FLOOR
1ST FLOOR BALCONY
TENDER
Lift control panel
SYMBOLS LEGEND- FIRE ALARM SYSTEM
LN&E supply and 1-10V dimming
circuit from RC unit to all luminaires
Device
Description
FA-P
Fire Alarm Panel
FA-R
Fire Alarm Repeater Panel
pc Max of 10 Nr ballasts per RC unit
Lighting cct from DB
Type A ftgs
RC
RC unit ceiling mounted in small white
GRP/ABS adaptable box adjacent the
ftg at the start of the circuit.
Type A ftgs
Type A ftgs
Max range of RF unit to RC
controller - 30m for conjested area,
100m for clear area
Max of 10 Nr
ballasts per RC unit
M
Refer to CP Electronics data sheet for connection details and cable reqirements
Wireless detection Translator Unit
S
H
SW
HW
MW
Smoke detector
Heat detector
Smoke detector - wireless
Heat detector - wireless
Multi detector - wireless (V denotes void mtd)
Break glass unit
13A spur for 240/12 DC
power supply for RF unit
RF
TYPICAL WIRELESS CONTROL LIGHTING CIRCUIT SCHEMATIC
TU
Sounder incorporated onto ceiling point detector
Strobe incorporated into ceiling point detector
Electronic sounder - wall mounted
Momentary switch for
remote control of lighting
via RF/RC units. Gangs
as per layout drgs
Electronic sounder & strobe unit - wall mounted
RI
Detector remote indicator
Strobe - wall or ceiling mounted
INT
C
Interface unit (IP/OP)
Monitoring Communicator
Telephone line
13A unswitched spur
SW
HW
Wireless detection
Wireless detection
Translator unit
H
13A unswitched
spur from local DB
TU
H
S
Loop driven detection/sounders
SW
HW
Wireless detection
INT
SW
FS
Firemans switch - 3 position for Auto/On/Off
pc
An-10 PIR - CP Range EBD
RC
An-10 Relay Controller - AT-SL-DDR-SA
RF
An-10 RF Unit - AT/BB
HW
Wireless detection
13A unswitched
spur from local DB
TU
TU
Wireless detection
Translator unit
Wireless detection
Translator unit
A
Rev
10sep12 Detector symbols corrected
Date Revision text
John Clare House, 69 The Avenue, Cliftonville, Northampton, NN1 5BT
Single addressable fire alarm loop - 2 core 1.5mm PH60 cable
Tel: 01604 622721 Fax: 01604 232084 Email: mail@fkhoward.com
Repeater panel
located at Ground
floor lift looby
Single loop Addressable
fire alarm panel located
at main entrance
13A unswitched
spur from DB 1
Monitoring Communicator
c/w integral PSU & battery
FA-P
C
Enhanced cable - 2 core
1.5mm Red PH120 cable
FA-R
Telephone line by Client
FIRE ALARM SCHEMATIC
Diagramatical only, locations of equipment dependant on wired position on loop)
13A unswitched
spur from DB 1
TENDER ISSUE
13A unswitched
spur from local DB
INT
S
Interface units for
connection to gas valve,
access control, bsmt vent,
1st flr extract and lift
Door access controller
NOTES
1. Single loop BS 5839 Cat L4 addressable fire alarm system for basement
area. System to provide warning to Central Monitoring Station, operate
smoke extract and fail safe open pedestrian escape gates/door access
control system.
2. Refer to drawings 3797/E-07 to 09 for fire alarm installation.
3. Refer to drawings 3797/E-04 to 06 for primary and emergency lighting
installation
Loop driven detection/sounders
Interface units for
connection to gas valve,
access control, bsmt vent,
1st flr extract and lift
DC