MOTOR CONTROL CENTER AFG ABOVE FINISHED GRADE MCM THOUSAND CIRCULAR MILS AHJ AUTHORITY HAVING JURISDICITION MDS MAIN DISTRIBUTION SYSTEM AHU AIR HANDLING UNIT MECH MECHANICAL ANN ANNUNCIATOR MFG MANUFACTURER ARCH ARCHITECT MLO MAIN LUGS ONLY AT AMPERE TRIP MTD, MTG MOUNTED, MOUNTING ATS AUTOMATIC TRANSFER SWITCH MTS MANUAL TRANSFER SWITCH AWG AMERICAN WIRE GAUGE MW MICROWAVE BAS BUILDING AUTOMATION SYSTEM N NEUTRAL BLDG BUILDING NC NORMALLY CLOSED C CONDUIT NEC NATIONAL ELECTRIC CODE - NFPA 70 CATV COMMUNITY ANTENNA TV NF NON-FUSED cd CANDELA RATING NIC NOT IN CONTRACT CB CIRCUIT BREAKER NL NIGHT LIGHT CCTV CLOSED CIRCUIT TELEVISION NO NORMALLY OPEN CL CENTER LINE NTS NOT TO SCALE CLG CEILING Ø , PH PHASE COMMUNICATIONS P POLE OR PHASE CT CURRENT TRANSFORMER PA PUBLIC ADDRESS CU COPPER PB PULLBOX dBA DECIBEL LEVEL PNL PANEL DISC DISCONNECT DN DOWN REF REFRIGERATOR DW DISHWASHER SPD SURGE PROTECTIVE DEVICE DWG DRAWING SPEC SPECIFICATION EF EXHAUST FAN SPKR SPEAKER ELEV ELEVATOR SWBD SWITCHBOARD EM EMERGENCY SWGR SWITCHGEAR ER MAIN EQUIPMENT ROOM TCC TEACHER CONTROL CENTER STATION EUH ELECTRIC UNIT HEATER TEL TELEPHONE EWC ELECTRIC WATER COOLER TR TELECOMMUNICATIONS ROOM TRANSFER SWITCH - MANUAL EX EXISTING TTB TELECOMMUNICATIONS TERMINAL BOARD CIRCUITRY FA FIRE ALARM TV TELEVISION FAA FIRE ALARM ANNUNCIATOR TYP TYPICAL FACP FIRE ALARM CONTROL PANEL UC UNDER COUNTER FCU FAN COIL UNIT UH UNIT HEATER FLA FULL LOAD AMPS UON UNLESS OTHERWISE NOTED FLR FLOOR UPS UNINTERRUPTIBLE POWER SUPPLY G, GND GROUND V VOLTS GFI, GFCI GROUND FAULT CIRCUIT INTERRUPTER VA VOLT-AMP HOA HAND-OFF-AUTOMATIC VAV VARIABLE AIR VOLUME BOX HP HORSEPOWER VFD VARIABLE FREQUENCY DRIVE HWCP HOT WATER CIRCULATION PUMP W WATTS, WIRES IG ISOLATED GROUND W/ WITH JB JUNCTION BOX W/O WITHOUT KAIC THOUSAND AMPERES INTERRUPTION CAPACITY WH WATER HEATER THOUSAND CIRCULAR MILS WAP WIRELESS ACCESS POINT KV KILOVOLT WP WEATHERPROOF KVA KILO VOLT-AMPERE CALL OUT NOTE TAG KW KILO WATT KITCHEN OR SHOP EQUIPMENT TAG LC LIGHTING CONTACTOR LUMINAIRES RECEPTACLE MODIFIERS SURFACE, RECESSED, OR WALL MOUNTED LUMINAIRE CONNECTED TO NORMAL BRANCH CIRCUIT SURFACE, RECESSED, OR WALL MOUNTED LUMINAIRE WITH BATTERY PACK CONNECTED TO NORMAL BRANCH CIRCUIT AHEAD OF SWITCHING OR CONNECTED TO LIFE SAFETY BRANCH CIRCUIT AC ABOVE COUNTER UC UNDER COUNTER ##A DESIGNATES AMPERE RATING REQUIRED RISER/ONELINE DIAGRAM CEILING MOUNTED, WALL WASHER M CEILING OR WALL MOUNTED EXIT SIGN, SHADED AREA INDICATES FACE, WALL ARROWS INDICATE EXIT DIRECTION CEILING METER / METER WITH ENCLOSURE M CIRCUIT BREAKER TRACK LIGHTING, LENGTH AS SHOWN ON DRAWINGS, QUANTITY OF HEADS AS SHOWN ON DRAWINGS SWITCH - SINGLE POLE, SINGLE THROW EMERGENCY BATTERY PACK UNIT COM, COMM SWITCH - SINGLE POLE, DOUBLE THROW FUSE LUMINAIRE MODIFIERS FUSED SWITCH F# DESIGNATED LUMINAIRE TYPE - SEE SCHEDULE RELAY - NORMALLY OPEN a LOWERCASE LETTERS DESIGNATES LUMINAIRE SWITCHING GROUP RELAY - NORMALLY CLOSED EM EMERGENCY FIXTURE PUSH BUTTON - NORMALLY OPEN NL NIGHT LIGHT FIXTURE - TO REMAIN ON ALWAYS PUSH BUTTON - NORMALLY CLOSED GENERATOR LIGHTING DEVICES ATS TRANSFER SWITCH - AUTOMATIC MTS SINGLE POLE SNAP SWITCH HOMERUN TO PANELBOARD, QUANTITY OF ARROWS INDICATES NUMBER OF CIRCUITS. CONDUIT CONCEALED OVERHEAD IN FURRED CEILING, IN CEILING SLAB OR IN WALLS CONDUIT EXPOSED SWITCH MODIFIERS CONDUIT BELOW GRADE OR CONCEALED IN SLAB 3 THREE WAY CONDUIT TURNED UP 4 FOUR WAY D DIMMER SWITCH CONDUIT TURNED DOWN CONDUIT STUB OUT K KEY OPERATED P PILOT LIGHT REFERENCE AND NOTE TAGS M MOTOR RATED T TIMER # REFERENCE NOTE TAG 1 LV KCM, KCMIL LOW VOLTAGE CONTROL SWITCH ### # AC ABOVE COUNTER UC UNDER COUNTER RECEPT, REC TRANSF, XFMR XFR RECEPTACLE License No. 37172 RECESSED SURFACE T NOTE: SOME ABBREVIATIONS MAY NOT BE USED. PANELBOARD SPECIAL CABINET TRANSFORMER CIRCUIT AND TYPE DESIGNATIONS GROUND CIRCUIT DESIGNATION SIMPLEX RECEPTACLE 20 AMP, 120V GROUNDING TYPE SIMPLEX RECEPTACLE 20 AMP, 120V GROUNDING TYPE. CEILING MOUNTED OR 1LB-5 5 1LB-5 SIMPLEX RECEPTACLE 20 AMP, 120V GROUNDING TYPE, FLOOR MOUNTED DUPLEX RECEPTACLE 20 AMP, 120V GROUNDING TYPE WITHOUT HOMERUNS AND CIRCUITS SHOWN DUPLEX RECEPTACLE 20 AMP, 120V GROUNDING TYPE, CEILING MOUNTED TYPICAL RECEPTACLE OR DEVICE CIRCUIT DESIGNATION DUPLEX RECEPTACLE 20 AMP, 120V GROUNDING TYPE, FLOOR MOUNTED QUADRAPLEX RECEPTACLE 20A, 120V GROUNDING TYPE QUADRAPLEX RECEPTACLE, 20A, 120V GROUNDING TYPE, CEILING MOUNTED QUADRAPLEX RECEPTACLE, 20A, 120V GROUNDING TYPE, FLOOR MOUNTED WITH HOMERUNS AND CIRCUITS SHOWN *FIXTURE TYPE APPLICABLE TO ROOM ALL F2 1HB-5 a F2 SS IO N A L E N G IN TRANSFER PROJECT NAME: SURFACE FE TRANSFORMER POWER RECESSED N JEFFERY LAMBERT REVISION REFERENCE # OF LOUISIA OR 1HB-5 5 TYPICAL LIGHT FIXTURE SWITCH DESIGNATION (IF MORE THAN ONE SWITCH IN ROOM/AREA) DATE 2016-08-19 FIXTURE TYPE PROJECT NO. CIRCUIT DESIGNATION 2016.026 SHEET NO. E0.1 OF SHEETS SYMBOLS & ABBREVIATIONS J WALL MOUNTED JUNCTION BOX WITH COVER, MOUNTED FLUSH IN FINISHED SPACES OR SURFACE IN UNFINISHED SPACES, UNLESS INDICATED OTHERWISE. SIZE PER NEC DESCRIPTION TE TA THIS SHEET: JUNCTION BOX WITH COVER, MOUNTED ABOVE CEILING OR FLUSH IN FINISHED CEILING UNLESS INDICATED OTHERWISE. SIZE PER NEC 900 CONVENTION CENTER BLVD. NEW ORLEANS, LOUISIANA 70130 SYMBOL J R MCC JL ABOVE FINISHED FLOOR CHECKED BY: AFF DISCONNECT SWITCH-SIZE/POLES/FUSE/NEMA TYPE JL, DL MAIN CIRCUIT BREAKER DRAWN BY: MCB EE AMPERE FUSE 909 Poydras Street, Suite 2150 New Orleans, Louisiana 70112-1034 Tel. 504-586-1725 Fax 855-327-4815 AF S LIGHTING 2016-08-19 100% CD LTC CONSULTING ENGINEERS ABOVE COUNTER A AC ENCLOSED CIRCUIT BREAKER CB NEW ORLEANS ERNEST N. MORIAL CONVENTION CENTER PHASE II MEETING ROOM LIGHTING PANEL RETROFIT THIS IS A TYPICAL SCHEDULE, SOME SYMBOLS MAY NOT BE USED. ALL ELECTRICAL DEVICES & EQUIPMENT ARE SHOWN APPROXIMATELY LOCATED. FOR ALL MEASUREMENTS USE ARCHITECTURAL PLANS. CONSULT WITH ENGINEER AND ARCHITECT IF CONFLICTS ARISE. REGARDLESS OF SYMBOL USED, REFER TO LIGHTING FIXTURE SCHEDULE FOR EXACT TYPE AND REQUIREMENTS. O LIGHTING CONTROL PANEL PR LCP SEAL 3. AMPERES DESCRIPTION BY 1. 2. STANDARD ABBREVIATIONS A SYMBOL NOTES: (CONTINUED) DESCRIPTION ELECTRICAL SYMBOLS DATE (CONTINUED) REV. ELECTRICAL SYMBOLS 10. PROVIDE COMPLETE INSTALLATION, INCLUDING ALL MINOR ITEMS. THIS INCLUDES ELECTRICAL AS WELL AS ANY OTHER SYSTEMS SHOWN IN THESE DRAWINGS. PROVIDE ALL MOUNTING HARDWARE FOR LIGHTING FIXTURES AND OTHER ELECTRICAL EQUIPMENT REQUIRED FOR A COMPLETE INSTALL. 11. A WARRANTY PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE OF FINAL COMPLETION OF THE PROJECT SHALL APPLY TO ALL ELECTRICAL EQUIPMENT FURNISHED AND TO ANY ELECTRICAL WORK FURNISHED UNDER THESE SPECIFICATIONS. CONTRACTOR SHALL REPAIR OR REPLACE ANY DEFECTS IN WORKMANSHIP, DESIGN OR MATERIALS AT HIS OWN EXPENSE. WARRANTY WORK SHALL BE PERFORMED WITHIN A REASONABLE TIMEFRAME AS SOON AS POSSIBLE AFTER THE DISCREPANCY IS NOTICED. 12. CONTRACTOR IS RESPONSIBLE FOR COORDINATION WITH GENERAL CONTRACTOR ON THE APPLICATION FOR PERMIT AND REMITTANCE OF ALL FEES. IN ADDITION, CONTRACTOR TO PROVIDE FINAL INSPECTION CERTIFICATE. 13. CONTRACTOR SHALL VISIT THE SITE OF THE PROPOSED WORK TO UNDERSTAND THE COMPLEXITY, RESTRICTIONS, AND ALL THE REQUIREMENTS TO PERFORM WORK OF THESE DOCUMENTS IN SAID FACILITY. NO ADDITIONAL COMPENSATION SHALL BE ALLOWED TO THE SUCCESSFUL BIDDER FOR FAILURE TO BE SO INFORMED. 14. CONTRACTOR SHALL CAREFULLY INVESTIGATE STRUCTURAL CONDITIONS, WALL AND CHASE LOCATIONS AND ROOM FINISHES AND MAKE ACTUAL MEASUREMENTS ON THE JOB SO THAT ALL ELECTRICAL EQUIPMENT SHALL HAVE ADEQUATE CLEARANCES AS REQUIRED BY NEC AND BY THE MANUFACTURER'S REQUIRED INSTALLATION PRACTICES. ALL EQUIPMENT SHALL BE CONNECTED IN A WAY THAT ALLOWS AMPLE MAINTENANCE SPACE AND PASSAGE SPACE. 15. CONTRACTOR SHALL CONTINUOUSLY MAINTAIN ADEQUATE PROTECTION OF STORED MATERIALS AND INSTALLED WORK. ALL FIXTURES AND EQUIPMENT SHALL BE TIGHTLY COVERED WITH SHEET POLYETHYLENE OR WATERPROOF TARPAULIN AND PROTECTED AGAINST DIRT, RUST, MOISTURE, CHEMICAL AND MECHANICAL INJURY REGARDLESS OF LOCATION. MATERIALS SHALL NOT BE STORED DIRECTLY ON EARTH ON IN AREAS WHERE THEY WILL BE SUBJECT TO PHYSICAL INJURY FROM VEHICLE TRAFFIC OR CONSTRUCTION EQUIPMENT. CONDUIT OPENINGS SHALL BE CAPPED OR PLUGGED DURING INSTALLATION. KEEP STOCK OF MATERIAL AND EQUIPMENT STORED ON THE PREMISES IN A NEAT AND ORDERLY MANNER. 16. AT THE END OF EACH WORK DAY, THE CONTRACTOR SHALL REMOVE ALL DEBRIS, SURPLUS MATERIALS OR FOREIGN MATTER CAUSED BY THE PERFORMANCE OF ELECTRICAL WORK ON THE PREMISES. UPON COMPLETION OF THE WORK THE CONTRACTOR SHALL BE RESPONSIBLE FOR LEAVING THE PREMISES IN A CLEAN CONDITION. 17. NO INSTALLATION WILL BE CONSIDERED COMPLETE UNTIL THE PROPER OPERATION OF ALL ELECTRICAL EQUIPMENT HAS BEEN DEMONSTRATED TO THE SATISFACTORY OF THE OWNER OR ITS AUTHORIZED REPRESENTATIVE. ALSO, ANY RECORD DRAWINGS, BOOKS NECESSARY TO MAINTAIN OR REPLACE ANY CONTRACTOR SUPPLIED MATERIAL SHALL BE COMPILED AND PRESENTED TO THE OWNER IN A FORM SUITABLE FOR REPRODUCTION. 18. CONTRACTOR SHALL PROVIDE ALL NECESSARY TESTING EQUIPMENT (INCLUDING 24VDC SYSTEM) AND PERSONNEL FOR MAKING TEST. ALL TEST SHALL BE MADE IN THE PRESENCE OF THE OWNER OR A REPRESENTATIVE THEREOF. WHEN TEST RESULTS ARE NOT SATISFACTORY, THE CONTRACTOR SHALL MAKE ALL NECESSARY ADJUSTMENTS AND/OR CHANGES AND SHALL NOTIFY OWNER THAT HE IS READY FOR ANOTHER TEST. CONTRACTOR SHALL REPEAT TEST OR TESTS WHICH DISCLOSED FAULTY OR DEFECTIVE WORK OR EQUIPMENT AND SHALL MAKE SUCH ADDITIONAL TESTS AS OWNER DEEMS NECESSARY. 8. ALL WORK SHALL BE PROPERLY SUPPORTED FROM THE BUILDING STRUCTURE IN AN APPROVED MANNER AND FASTENED TO BUILDING CONSTRUCTION WITH LISTED AND CODE COMPLIANT SUPPORTS. 9. USE ANTI-SHORT BUSHINGS WITH FLEXIBLE CONDUIT. 10. PROVIDE SEPARATE BOXES AND RACEWAYS FOR "EMERGENCY" SYSTEM WIRING AND FOR "NORMAL" SYSTEM WIRING. KEEP DIFFERENT VOLTAGE SYSTEMS SEPARATE IN DIFFERENT RACEWAYS AND BOXES. 11. WHERE NEW LIGHTS OR RECEPTACLES ARE DESIGNATED TO BE CONNECTED TO AN EXISTING CIRCUIT, CONTRACTOR SHALL TRACE EXISTING CIRCUIT TO DETERMINE CIRCUIT LOADING. THE LOAD ON A 20 AMP CIRCUIT SHALL NOT EXCEED 16 AMPS (80%) AT ANY POINT DURING A NORMAL WORKING DAY FOR THE FACILITY. WHERE THIS CANNOT BE ACHIEVED, CONTRACTOR SHALL CONTACT THE ENGINEER FOR ALTERNATIVE CIRCUITING INSTRUCTIONS. 12. MULTI-WIRE BRANCH CIRCUITS SHALL BE PROVIDED WITH A COMMON DISCONNECT AT THE SOURCE. THE DISCONNECT SHALL BE EITHER A MULTI-POLE CIRCUIT BREAKER OR INDIVIDUAL CIRCUIT BREAKERS WITH LISTED HANDLE TIES. ALL CIRCUIT CONDUCTORS OF EACH MULTI-WIRE BRANCH CIRCUIT SHALL BE GROUPED AND TIED TOGETHER IN AT LEAST ONE LOCATION IN THE PANEL. MULTI-WIRE BRANCH CIRCUITS SHALL ONLY SERVE SINGLE POLE LINE-TO-NEUTRAL LOADS. 13. RACEWAYS AND OUTLETS PASSING THROUGH OR INSTALLED IN FIRE RATED CONSTRUCTION SHALL BE SEALED WITH U.L LISTED FIRE RATED SEALANT SYSTEM IN ACCORDANCE WITH SEALANT MANUFACTURERS' RECOMMENDATIONS. WHERE ELECTRICAL RACEWAYS ARE INSTALLED THROUGH RATED FLOORS OR WALLS, THE CONTRACTOR SHALL PROVIDE APPROPRIATE FIRE RATED DEVICES APPROVED BY ALL REQUIRED LOCAL AUTHORITIES FOR THE INTENDED APPLICATION. REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION. PROCESSORS FOR DIMMING PANEL AND RELAY PANEL WILL INCLUDE BATTERY BACKUP FOR BRIEF POWER OUTAGES. ARCHITECTURAL CONTROL PROCESSING AND NETWORK EQUIPMENT WILL BE ON UPS. 6. SYSTEM SHALL HAVE NETWORK CAPABLE CONTROL, PROGRAMMING, AND MONITORING; AND PROVIDE REAL TIME FEEDBACK FROM A NETWORKED COMPUTER. 7. THE SYSTEM SHALL HAVE THE ABILITY TO PROGRAM AND ACTIVATE GROUPWIDE PRESETS FROM NETWORKED COMPUTER OR HANDHELD DEVICE. GENERAL NOTES - SEQUENCING OF WORK THE FOLLOWING LISTS THE GROUPS OF MEETING ROOMS IN THE ORDER THAT THEY SHOULD BE COMPLETED WITH NUMBER 1 BEING HIGHEST PRIORITY AND SHOULD BE FINISHED FIRST: 1. 338 - 341 and 343 2. 348 - 355 BASE BID (GROUP #'s 1-6) 3. 356 - 357 4. 235 - 241 5. 333 - 337 6. 344 - 347 and 342 7. 242-245 .......................... ALTERNATE #1 (ADDITIVE) 8. 252 - 254 ........................ ALTERNATE #2 (ADDITIVE) 9. 255 - 257 ........................ ALTERNATE #3 (ADDITIVE) ALL WORK ASSOCIATED WITH EACH GROUP SHALL BE COMPLETED IN ITS ENTIRETY PRIOR TO MOVING ONTO THE NEXT, SO THAT THE GROUP OF ROOMS IS FULLY FUNCTIONAL. FOR THE PURPOSES OF MAINTAINING FACILITY'S SYSTEM STANDARDS FOR THIS PROJECT, PRODUCTS MANUFACTURED BY ELECTRONIC THEATRE CONTROLS (ETC) FOR THE LIGHTING DIMMING AND CONTROL SYSTEM SHALL BE UTILIZED. THE EXISTING DIMMING/LIGHTING CONTROL PANELS IN EACH ELECTRICAL ROOM SHALL BE REPLACED WITH THE FOLLOWING: 1. 2. 3. 15. PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT ENCLOSURE ASSEMBLY SHALL BE LIMITED TO THOSE LISTED PER NFPA 101: 7.1.3.2.1(10). 4. GENERAL NOTES - DEMOLITION/RENOVATION 1. DRAWINGS INTEND TO SHOW THE EXTENT OF ELECTRICAL DEMOLITON WORK, HOWEVER, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO BID TO ASCERTAIN LIMITS OF DEMOLITION & CONSTRUCTION; INCLUDE ALL ASSOCIATED COSTS IN THE BID. 2. ELECTRICAL CONTRACTOR SHALL REMOVE ALL EXISTING ELECTRICAL MATERIALS, EQUIPMENT, WIRING DEVICES, WIRING, CONDUITS, AND CONDUIT HANGERS/SUPPORTS ASSOCIATED WITH THE EXISTING DIMMING SYSTEMS THAT WILL NOT BE REUSED WHEN REINSTALLING THE NEW DIMMING SYSTEM. A COMPLETE REMOVAL AND REPLACEMENT OF THE EXISTING DIMMING/LIGHTING CONTROL SYSTEM WITH A NEW IP NETWORK BASED DIMMING/LIGHTING CONTROL SYSTEM IN THE PHASE II MEETING ROOMS ON THE 2ND AND 3RD FLOORS. THE GENERAL WORK THAT THE CONTRACTOR IS RESPONSIBLE FOR INCLUDES, BUT IS NOT LIMITED TO, THE FOLLOWING: 3. ALL WIRING AND CABLING CONNECTED TO DEVICES AND EQUIPMENT TO BE DEMOLISHED SHALL BE REMOVED BACK TO THEIR SOURCE. 1. 4. ALL EXISTING ABANDONED WIRING AND CABLING IN AREAS OF DEMOLITION SHALL BE REMOVED BACK TO THEIR SOURCE. THIS INCLUDES ALL TELECOMMUNICATIONS AND SPECIAL SYSTEMS CABLING (VOICE, DATA, FIRE ALARM, SECURITY, CCTV, TELEVISION SYSTEMS, HVAC CONTROL CABLES, ETC.) IN THE DESIGNATED AREAS COMPLETELY DISCONNECT, REMOVE, AND DISPOSE OF THE EXISTING DIMMING SYSTEM COMPONENTS (DIMMERS, SWITCHING, CONTROL PANELS, ETC.) AS WELL AS ANY ASSOCIATED WIRING AND RACEWAYS THAT ARE BEING NOT BEING REUSED FOR THE NEW SYSTEM. 2. MODIFY, REWORK, AND EXTEND EXISTING CIRCUITS (WIRE AND RACEWAY) THAT ARE BEING REUSED AS REQUIRED TO CONNECT TO NEW SYSTEM. 3. PROVIDE AND INSTALL A NEW DIMMING/LIGHTING CONTROL SYSTEM INCLUDING DIMMING, RELAY AND CONTROL EQUIPMENT AS SPECIFIED AND DESCRIBED HEREIN. CONTRACTOR SHALL PROVIDE ALL THE SYSTEM COMPONENTS, CIRCUITING, AND CONNECTIONS REQUIRED FOR A COMPLETE INSTALLATION. ALL EQUIPMENT, MATERIAL AND LABOR MUST BE FURNISHED WHETHER OR NOT SPECIFICALLY MENTIONED. 4. CONNECT NEW DIMMING SYSTEM TO FACILITY DATA NETWORK. PROVIDE PROGRAMMING AND COMPONENTS NECESSARY TO INTEGRATE NEW SYSTEM INTO THE EXISTING ETC PARADIGM NETWORK LIGHTING SOFTWARE SYSTEM. OWNER TO PROVIDE AND INSTALL ETHERNET SWITCHES AT EACH NEW DIMMING SYSTEM RACK THAT SHALL BE USED AS THE POINT TO CONNECT TO FACILITY'S NETWORK. ALL EXISTING UNUSED CONDUITS SHALL BE REMOVED BACK TO THEIR SOURCE EXCEPT WHERE THEY PASS IN NON-ACCESSIBLE LOCATIONS SUCH AS EXISTING FLOOR SLABS THAT ARE NOT TO BE DEMOLISHED. THESE UNUSED CONDUITS SHALL BE CUT OFF AND PLUGGED FLUSH WITH SLAB. 6. REUSE EXISTING CONDUITS CONCEALED IN WALLS AS APPLICABLE TO ROUTE NEW CIRCUITS. 7. PROVIDE BLANK COVERPLATES ON ALL ABANDONED DEVICE BOXES. 8. CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF ALL EXISTING CIRCUITS (CONDUCTORS AND CONDUIT) THAT FEED OTHER AREAS THAT ARE NOT AFFECTED BY DEMOLITION. THIS INCLUDES REROUTING AND/OR REWORKING OF EXISTING CIRCUITS. 9. CONTRACTOR IS RESPONSIBLE FOR PROTECTING AND RETAINING AND/OR RE-ESTABLISHING POWER TO ALL EXISTING EQUIPMENT AND DEVICES IN AREAS OF NEW CONSTRUCTION THAT ARE TO REMAIN. THIS INCLUDES REROUTING AND/OR REWORKING OF EXISTING CIRCUITS. GENERAL NOTES - SCOPE OF WORK ETC POWER CONTROL SYSTEM SENSOR DIMMING RACKS · SR3 SENSOR 3 RACK, MULTI-MODULE, MULTI-CIRCUIT DIMMING RACK ENCLOSURE RATED AT 208/120V, 3-PH, 4W · CEM3 CONTROL MODULE · SR3 RIDE THRU CARD · D20 DIMMER MODULES · AFM MODULES ECHO RELAY PANELS · ERPA 20A DMX CONTROLLED SINGLE POLE RELAYS. · EFPA 20A DMX CONTROLLED SINGLE POLE RELAYS. · ERP-RTO RIDE THRU CARD EMERGENCY ACCESSORIES · EBDK EMERGENCY BYPASS DETECTION KIT · SR3-TAP SENSOR3 PHASE BAR FUSE KIT NETWORK CONTROL EQUIPMENT · EQUIPMENT RACK · NETWORK SWITCH · PATCH PANEL · NETWORK TAP RECEPTACLES - SURFACE MOUNT DUAL NETWORK JACKS WITH FACEPLATE LOCAL JACKS IN EACH ROOM FOR PORTABLE TOUCHSCREEN OR NETWORK ACCESS. · LOT MISC. - PATCH CABLES AND CONNECTORS AS NEEDED · UPS RACK MOUNT - 1000VA ARCHITECTURAL CONTROL EQUIPMENT - UNISON PARADIGM CONTROL SYSTEM · ERN2 RACK MOUNT ENCLOSURE · PACP PARADIGM ARCHITECTURAL CONTROL PROCESSOR · PSPM PARADIGM STATION POWER MODULE · CUSTOM RECESSED BACK BOX FOR 7 GANG. · UH10005 - 1 GANG, FLUSH MOUNT, 5 BUTTON CONTROL STATION FOR ROOM 12. RACEWAY IN EXPOSED UNFINISHED AREAS SHALL BE SURFACE MOUNTED EMT PAINTED TO MATCH SURROUNDINGS. FASTEN TO WALL PER NEC WITH STAINLESS STEEL STRAPS FOR SUPPORT. 14. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITON AND RENOVATION WORK. S R EE IN THE EXISTING SLIDER STATION IN EACH MEETING ROOM SHALL BE REPLACED WITH THE FOLLOWING: 1. PTS7 7” TOUCHSCREEN CONTROL STATION WITH CUSTOM RECESSED BACKBOX AND CUSTOM GUI. (REFER TO DRAWINGS AND SPECIFICATIONS FOR EXACT QUANTITIES FOR EACH COMPONENT.) CONTROL WIRE 1. FURNISH, INSTALL AND TERMINATE ALL NECESSARY LENGTHS OF CONTROL WIRE RUNS BETWEEN THE LIGHTING FIXTURES, PLUGGING STATIONS, LOCAL CONTROL DEVICES, NETWORK INTERFACES, REMOTE FOCUS UNITS, AND DIMMERS. THE CONTROL WIRE SHALL BE OF THE TYPE AND AMOUNTS ACCEPTABLE TO THE MANUFACTURER. 2. ALL LOW-VOLTAGE CONTROL CABLE THAT IS RUN WITHIN 4 FEET OF DRY-TYPE POWER TRANSFORMERS SHALL BE SHIELDED. UTILIZE CRIMP STYLE GROUNDING CONNECTORS TO PROVIDE PERMANENT, SAFE SHIELD TERMINATION ON SHIELDED CABLE USING COPPER GROUNDING WIRE. CRIMP STYLE GROUNDING CONNECTORS FOR SHIELDED CABLE SHALL BE EITHER: · ONE-PIECE WRAP-AROUND CONNECTOR · TWO-PIECE (INNER AND OUTER SLEEVE) CONNECTOR (THIS SCOPE OF WORK IS SUMMARIZED FOR REFERENCE AND DOES NOT CONSTITUTE A DETAILED AND FULL EXPLANATION OF THE REQUIREMENTS OF THE CONTRACT DOCUMENTS) 10. WHERE CIRCUIT BREAKERS ARE SHOWN TO BE ADDED ON THE PLANS TO PANELBOARDS AND/OR SWITCHBOARDS, CONTRACTOR SHALL FURNISH ALL CIRCUIT BREAKER MOUNTING ACCESSORIES REQUIRED TO INSTALL. VERIFY CONDTIONS PRIOR TO BID. UPDATE EXISTING PANEL DIRECTORIES APPROPRIATELY. 11. ALL JUNCTION BOXES FOR RECEPTACLES, DATA OUTLET, LIGHT FIXTURES, ETC. SHALL BE INSTALLED RECESSED IN WALLS AND CEILINGS. CUT AND PATCH WALLS AS NECESSARY. COORDINATE CUT AND PATCH WORK WITH ARCHITECT. IO N AL ENG EQUIPMENT: 14. MAINTAIN FIRE RATING OF WALLS, FLOORS, AND CEILINGS WHEN PERFORMING WORK AND INSTALLING DEVICES, BOXES, ETC. USE FIRE CAULK, "PUTTY PADS," AND OTHER APPROVED AND APPROPRIATE METHODS TO MAINTAIN RATING. 5. SS JL PROVIDE EXPANSION AND DEFLECTION FITTINGS FOR CONDUITS CROSSING EXPANSION JOINTS. PROVIDE BONDING JUMPERS FOR ALL EXPANSION FITTINGS. 5. FE CHECKED BY: DRAWINGS ARE DIAGRAMMATICAL. ALL ELECTRICAL EQUIPMENT LOCATIONS ARE APPROXIMATE ONLY. FOR ALL MEASUREMENTS, USE ARCHITECTURAL, MECHANICAL OR OTHER RESPECTIVE DIVISION'S PLANS AND FIELD SURVEYS. COORDINATE WITH AIR CONDITIONING WORK, CABINET WORK, PARTITION WORK, ETC., WHEN NEEDED. LAYOUT OF EQUIPMENT, ACCESSORIES, SPECIALTIES, WIRING AND CONDUIT SYSTEMS ARE STRICTLY DIAGRAMMATIC UNLESS SPECIFICALLY DIMENSIONED, AND DO NOT INDICATE EVERY REQUIRED FITTING, ELBOW, TRANSITION, JUNCTION BOX OR SIMILAR ITEMS THAT ARE REQUIRED FOR A COMPLETE INSTALLATION. 7. ALL STATIONS WILL INCLUDE CUSTOM LABELING. License No. 37172 JL, DL 9. RACEWAYS AND CABLES SHALL BE INSTALLED CONCEALED UNLESS OTHERWISE NOTED. 4. JEFFERY LAMBERT DRAWN BY: COMPLETELY BOND AND GROUND ELECTRICAL SYSTEM IN ACCORDANCE WITH THE CURRENT NEC ARTICLE 250 IN IT'S ENTIRETY. 6. 7” TOUCHSCREEN IN EACH ROOM WILL REPLACE EXISTING STATIONS AND BE RECESSED IN CUSTOM BACK BOX. NETWORK PORTS WILL REPLACE PORTABLE PLUG-IN JACKS. DATE 2016-08-19 15. OWNER SHALL HAVE RIGHT OF FIRST REFUSAL FOR ALL EQUIPMENT AND MATERIAL REMOVED DURING DEMOLITION. CONTRACTOR IS RESPONSIBLE FOR DISPOSAL OF ALL OTHER MATERIALS NOT SALVAGED TO THE OWNER. PROJECT NO. 16. OWNER SHALL BE NOTIFIED 2-WEEKS PRIOR TO ANY POWER OUTAGES REQUIRED BY ELECTRICAL. SHEET NO. 2016.026 E0.2 OF SHEETS NOTES & ABBREVIATIONS 8. ALL ELECTRICAL DEVICES SHOWN BEING LOCATED IN EXISTING WALLS SHALL BE CONCEALED AND NOT SURFACE MOUNTED. WALLS MODIFIED TO ACCOMMODATE SAID DEVICES SHALL BE PATCHED AND REFINISHED AFTER INSTALLATION TO RESTORE TO EXISTING CONDITIONS. 3. THIS SHEET: IF A CONFLICT OCCURS BETWEEN DRAWINGS, SPECIFICATIONS, AND/OR NOTES BID THE GREATER QUANTITY AND/OR QUALITY. UNDER NO CIRCUMSTANCES SHALL THE CONTRACTOR SWITCH OFF ANY ELECTRICAL SERVICE AT ANY POINT IN THE ELECTRICAL DISTRIBUTION SYSTEM OR PERFORM ANY WORK THAT WOULD INTERRUPT OR AFFECT THE NORMAL OPERATIONS OF THE FACILITY, OR TENANT OFFICES, UNLESS OTHERWISE NOTED. ANY WORK INCLUSIVE OF THE ABOVE SHALL BE PERFORMED DURING "OTHER THAN NORMAL HOURS" AT A TIME AND DATE CONVENIENT WITH THE OWNER. THE CONTRACTOR, IN ADVANCE, SHALL PRESENT A METHOD OF PROCEDURE DETAILING THE SCOPE OF WORK AND LENGTH OF TIME TO COMPLETE THE WORK AND A PROPOSED TIME AND DATE. OWNER RETAINS THE RIGHT TO ADJUST THE TIME AND DATE OR CANCEL AN APPROVED SCHEDULE AT NO ADDITIONAL COST. N 909 Poydras Street, Suite 2150 New Orleans, Louisiana 70112-1034 Tel. 504-586-1725 Fax 855-327-4815 7. 3. OF LOUISIA 900 CONVENTION CENTER BLVD. NEW ORLEANS, LOUISIANA 70130 THE TERM "PROVIDE" MEANS TO FURNISH AND INSTALL. THE PROJECT SCHEDULE WILL BE AS DICTATED AND REQUIRED BY THE OWNER, BASED ON OPERATIONAL REQUIREMENTS OF THE BUILDING FOR OWNER AND VISITOR'S USES. TE TA 2016-08-19 100% CD 6. 5. 2. ALL BRANCH CIRCUITRY INSTALLATION AND LOADING SHALL COMPLY WITH THE NEC. SYSTEM WILL ALLOW DISCRETE CONTROL OF EACH CIRCUIT, RECALL PRESETS, AND COMBINE CONTROLS FOR ADJOINING MEETING ROOMS. CONSULTING ENGINEERS INCLUDE THE COSTS TO INCORPORATE ALL CODES AND ORDINANCES REQUIRED BY ANY AUTHORITY HAVING JURISDICTION ON THE PROJECT INTO THE BASE BID FOR THE PROJECT. NO ADDITIONAL FUNDS WILL BE ALLOCATED FOR WORK TO CONFORM TO REGULATIONS AND REQUIREMENTS AND/OR TO OBTAIN APPROVAL OF WORK. 4. 2. NEW ORLEANS ERNEST N. MORIAL CONVENTION CENTER PHASE II MEETING ROOM LIGHTING PANEL RETROFIT CIRCUITS WITH UNMARKED CONDUCTOR AMOUNTS AND SIZES SHALL DEFAULT TO 2#12, #12G, 1/2"C. SEAL 3. THE NATIONAL ELECTRICAL CODE - NFPA 70 2011 EDITION (NEC) NFPA - NATIONAL FIRE PROTECTION ASSOCIATION NFPA-101, LIFE SAFETY CODE NFPA - NATIONAL FIRE PROTECTION ASSOCIATION NFPA-72, FIRE ALARM CODE ASHRAE STANDARD 90.1 ANSI HANDICAPPED CODE-A117.1 APPLICABLE STATE AND LOCAL CODES/ORDINANCES IES - ILLUMINATING ENGINEERING SOCIETY APPLICABLE HEALTH CODES OSHA 1926 SAFETY AND HEALTH REGULATIONS FOR CONSTRUCTION INTERNATIONAL BUILDING CODE - 2012 EDITION (IBC) EQUIPMENT FOR POWER CONTROL SYSTEMS FOR DIMMING AND SWITCHING WILL CONSIST OF: DIMMERS, NORMAL POWER RELAYS, EMERGENCY POWER RELAYS. CONTROL SYSTEM WILL CONSIST OF AN ARCHITECTURAL CONTROL PROCESSING UNIT, NETWORK PATCH PANEL, NETWORK SWITCH, BUTTON STATIONS AND NETWORK PORTS. BY a. b. c. d. e. f. g. h. i. j. 1. DESCRIPTION ALL CABLE SHALL BE COPPER UNLESS OTHERWISE NOTED. THE FACILITY WILL BE OPEN AND OPERATIONAL DURING THE COURSE OF THE CONSTRUCTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ADHERE TO THE POLICIES AND REGULATIONS PROMULGATED BY OWNERSHIP. COORDINATE FULLY WITH MANAGEMENT TO MINIMIZE INCONVENIENCE TO FACILITY OCCUPANTS AND VISITORS. PROVIDE ALL NECESSARY AND REQUIRED RESCHEDULING OF WORK, PROVISION OF SAFETY AND TEMPORARY DUST/SECURITY PARTITIONS AS NEEDED TO ACCOMMODATE. DATE 2. 1. A ALL POWER TERMINATIONS SHALL BE LISTED FOR 75 DEGREES C UNLESS OTHERWISE NOTED. O 1. PR 5. WORK PERFORMED SHALL AT A MINIMUM BE IN ACCORDANCE WITH THE LATEST APPLICABLE EDITION ADOPTED BY THE AUTHORITY HAVING JURISDICTION OF THE STANDARDS LISTED BELOW. WHERE THESE SPECIFICATIONS, PLANS, AND NOTES ARE MORE STRINGENT THAN ADOPTED CODE, THEY SHALL TAKE PRECEDENCE. IN CASE OF CONFLICT, OBTAIN A DECISION FROM THE ARCHITECT AND ENGINEER. GENERAL NOTES - DIMMING SYSTEM PROJECT NAME: 1. GENERAL NOTES - WORKING CONDITIONS (CONT.) GENERAL NOTES - WIRING METHODS REV. GENERAL NOTES - ELECTRICAL SKY-WALK ESCALATORS "PW" GROUP 1,2 MISSISSIPPI RIVER PE 12 SPRINKLER VALVE 8 PIV 4 FLOODWALL Guard Shack PUBLIC SAFETY ELECT. SHOP ELECT. FORMAN OFFICES FE SPRAY PAINT BOOTH CARPENTER SHOP 7 6 SPRINKLER VALVES 5 PIV 3 PAINT STORAGE FLOODWALL LOADING DOCKS SERVICE CORRIDOR Clearance 12' Clearance 12' PHASE III PIV 22 PIV 2 SPRINKLER VALVES 1,3,4 LOADING DOCKS STAIR 19 KEEP CLEAR 47 FLOODWALL GATE 22 TRUCK DOCKS TRUSS 24 F-12 F-13 Box Baler R AIR WALLS AIR WALLS AIR WALLS AIR WALLS AIR WALLS Air wall AIR WALLS C-10 C-9 D-8 D-7 D-9 D-10 E-9 E-12 E-11 E-10 34 CONC. STOR. CONCESS ION STAIR 60 FE 29 MEN STAND "13" STAIR 61 WOMEN 51 50 49 SPRINKLER VALVES F-10 WATER CONC. STOR. WS 33 30 E-8 AIR WALLS AIR WALLS F-9 ESCALATORS "A" GROUP 1,2,3 PE 4 MEN TO HALL B C-1 C-3 C-4 D-1 D-3 D-2 D-4 AIR WALLS E-1 G-27 STAND "4" PT H-28 H-32 G-21 COVERED DRIV E TO HALL C TO HALL C W S TO HALL D STAIR 27 PE 15 SO D 109 WOMEN SO E111 TO HALL D GATE 9B UP STAIR 2-B TO HALL E FE 11 15 16 SPRINKLER VALVES MEN STAND "10" PE 17 REG. STOR. CONC. STOR. GATE 10C WS STORAGE TO HALL E FE 16 G-9 G-10 TO HALL F ELECT. G-1 G-2 STAIR 36 Phase II 25 House Pumps 4,5,6 ELECT. EQUIP. GATE 8A STAIR 20 SPRINKLER VALVE UP STAIR 1-B STARBUCKS PT STAIR 22 UP ATRIUM UP SERVICE VESTIBULE ONE WAY LOBBIES/PUBLIC AREAS PE 14 UP STAIR 28 STAIR 26 PT 3M CELL PHONE 4M BOOTH LOBBY STAIR 31 STAIR 30 STAIR 23 Gas Meter 2 GATE 8 17 ROADWAY VALVE 2A ESC. PW GROUP 1,2 SPRINKLER VALVE 8" FIRE MAIN FIRE PUMP ROOM CONVENTIO N CE NTER BLVD. SPRINKLER VALVE 18 SKYWALK LOBBY GATE 9 19 20 PE 13 FP 21 22 SPRINKLER VALVES STOR. SPRINKLER VALVES H-1 H-2 PHONE G-6 G-7 G-8 IRED H-3 ELE ESCALATORS "G" GROUP 1,2, 3 GRILL H-4 TO HALL H AL RIC TO HALL G R W H-19 H-20 N H-6 GATE 11B H-7 E H-8 ELECT. H-9 TO HALL H FACILITY SERVICES STORAGE CONCESSI ON III 23 H-22 H-23 H-24 I-14 I-15 I-16 I-17 I-18 I-19 H-12 H-13 STAIR 45 ADVANCE I-1 ED RIGGING ARRANGEM ENTS REQU IRED I-2 I-3 WS TO HALL H HALL I2 ROADWAY VALVE I-4 I-5 ELE. I-6 W R I-7 I-8 MEN SHOW OFFICE TO HALL I1 WOMEN ICS I-9 I-10 I119 WS R W I-13 29 SPRINKLER VALVE TO HALL I2 J-1 TO HALL J ESCALATORS "I" GROUP 1,2, 3 ROADWAY VALVE 6 J-3 COAT ROOM IV AC J-14 J-15 GATE 13 J-4 W R LOBBY I2 III J-13 CEILING HEIG HT 23'-3" VERY LIMIT ED RIGGING ADVANCE ARRANGEM ENTS REQU IRED W R I120 J-5 EG J-6 J-7 SHOW OFFICE GATE 12B TO HALL J GATE ROADWAY VALVE 7 1ST FLOOR OVERALL PLAN LOBBY J 35 SPRINKLER VALVE 9 STAIR 53 GATE 12 PE 25 8 N CENTER BLVD. ROADWAY VALVE W R R02 R03 R04 VIDEO ROOM R06 R07 R08 WS STAIR 54 PHASE III MAIN WATER VALVE 6" 10 FIRE WATER TANK 376,700 Gals. 38 SPRINKLER VALVE 1"= 128'-0" ROADWAY VALVE 11 R WS WS R R PT R FE 7 STR 7 ELEVATOR STORAGE PT SUBSTATION 3 PT STAIR 10 IN PLANT SUBSTATION 1 STAIR 15 WS ESCALATORS B-2 REAR GROUP 1,2 SUBSTATION 5 TRUSS 24 SERVICE CORRIDOR STAIR 8 STAIR 9 ELEC SUBSTATION 2 F&B WAREHO USE CELL SITE ABOVE Great Hall TRUSS 25 FE 30 STAIR 63 TEC. ABOVE HALL D ABOVE HALL E SHOP INV. STORAGE SUBSTATIO N 19 TRUSS PASSAGEWAY ABOVE HALL C TRUSS PASSAGEWAY ABOVE HALL B2 TRUSS PASSAGEWAY ABOVE HALL B1 South Public Truss North Public Truss FE 29 F & B SMALLWARES STORAGE SUBSTATIO N 20 ABOVE HALL F STAIR 62 CARPET STORAGE SHIPPING & RECIEVING FE 5&6 STR 16 STAIR 59 TRUSS 26 ANNEX O SO B202 SUBSTATIO N 22 Above Hall H e Fire Supression System STAIR 38 Above Hall I1 Cooler SERVICE CORRIDOR EXEC SOUS CHEF Cooler Above Hall I2 KITCHEN II WS WS SUB STATION 13 Cooler SERVICE CORRIDOR OPEN TO BELOW STR 3A ICE ROOM 260 F&B SHIPPING & RECEIVING OFFICE 229 228 WS STR 27 WS PE 17 PT STR 25 F&B BANQUET OFFICE 19 & 20 PE 15 R 230 STAIR 37 B FE 16 R Above Hall J Green Room Production Offices PLUMBING STORAGE H.V.A.C STORAGE Football Cooler STR 3B 205 GREEN ROOM NORTH TRUSS 33 Freezer N TRUSS 32 TIO TEC. OFFICE TRUSS 31 Cooler TRUSS 30 14 TA TRUSS 29 BS TRUSS 34 OPEN TO BELOW ESCALATORS "B" GROUP 1,2,3 Freezer SU FE WS STR 4B R TRUSS 35 Green Room STAIR 55 GREEN ROOM SOUTH 260 224 WS STR 22 225 R 244 Ballroom II La Nouvelle Orleans 245 R R R ESCALATORS "E" GROUP 1,2,3 GROUP 4,5,6 PE 14 PT 226 R STAIR 44 ICE ROOM ESC. PW GROUP 1,2 Atrium Bridge 232 STR 26 STR 28 WS STR 30 STR 31 SUBSTATIO N 24 277 270 271 272 FE 21 273 227 231 STAIR 54 264 PT 274 ESCALATOR GROUP 1,2 S "G" ,3 STR 32 275 276 277 STAIR 35 STR 23 WS PE 13 238 BALCONY 239 236 C F&B V.I.P PROP ROOM ESCALATOR GROUP 1,2 S "H" GROUP 4,5,3 ,6 PT 241 STAIR 34 237 FE 27 R PT 242 240 235 STAIR 55 R STAIR 49 265 266 R 268 269 STAIR 46 ESCALATOR S GROUP 1,2 "I" GROUP 4,5 ,3 ,6 GROUP 7,8 ,9 278 279 STAIR 47 280 281 PE 23 STAIR 48 282 286 STAIR 51 267 STAIR 45 F&B 299 PANTRY 277 R 291 287 SUBSTATIO N 29 292 293 294 PE 24 295 STAIR 50 1 1 E-1.1 E-2.1 296 STAIR 52 283 284 285 STAIR 53 PE 25 ICE ROOM 299 288 289 290 02 E1.0 (DEMO) SERVICE CORRIDOR PHASEIII BOILER ROOM STAIR 38 SERVICE CORRIDOR 357 356 355 354 PE 26 2ND FLOOR OVERALL PLAN 297 298 299 FIRE WATER TANK 376,700 Gals. 1"= 128'-0" FACILITY STORAGE 352 353 AUDITOR STAIR 51 IUM STAIR 37 STR 29 STR 27 F&B PROP ROOM STAIR 54 PE 15 STAIR 53 PE 17 FE 16 19 & 20 333 351 CEILING 334 345 344 350 BALLROOM ESCALATORS "E" GROUP 1,2,3 GROUP 4,5,6 PE 14 ESC. PW GROUP 1,2 STAIR 55 STAIR 36 FE 27 FE 21 F&B 399 PANTR 349 STR 22 STR 28 STR 26 Y STR 30 346 347 ESCALATO RS GROUP 1,2 "I" GROUP 4,5 ,3 GROUP 7,8 ,6 ,9 348 387 391 392 STAIR 48 335 336 337 338 339 340 341 393 386 342 394 395 STAIR 50 BALCONY SERVICE CORRIDOR STAIR 52 FACILITY STORAGE 396 LOBBY BELOW PROJECT NAME: 343 ESCALATORS "D" GROUP 1,2,3 GROUP 4,5,6 THIS SHEET: PT WS STR 1A 383 384 385 STAIR 53 PE 25 388 389 1 1 E-1.2 E-2.2 (DEMO) DATE 390 PE 26 STAIR 54 397 F&B 398 399 01 E1.0 3RD FLOOR OVERALL PLAN SHANGO CHINA ROO M 2016-08-19 PROJECT NO. 1"= 100'-0" 2016.026 SHEET NO. E1.0 OF SHEETS 1ST- 2ND - 3RD OVERALL PLANS - LIGHTING ESCALATORS "D" GROUP 1,2,3 GROUP 4,5,6 FE 1 STR 1A 900 CONVENTION CENTER BLVD. NEW ORLEANS, LOUISIANA 70130 243 STR 20 WS NEW ORLEANS ERNEST N. MORIAL CONVENTION CENTER PHASE II MEETING ROOM LIGHTING PANEL RETROFIT WS 219 263 TRUSS 44 STR 2B 218 214 262 TRUSS 43 STR 2A 217 213 261 STAIR 36 FE 212 WS TRUSS 42 R WS 211 TRUSS 41 PT R 23 SUBSTATION STR 4A 204 252 STR 29 PE 22 PE 2 PT WS WS 253 A SERVICE CORRIDOR WS WS 254 SUBSTATION 12 STR 42 202 255 TRUSS 18 SUBSTATION 4 WS 203 TRUSS 17 215 R TRUSS 16 223 TRUSS 15 222 TRUSS 14 210 221 TRUSS 13 220 R WS 256 216 TRUSS 12 209 TRUSS 11 208 TRUSS 10 207 TRUSS 28 257 R 206 TRUSS 9 R Office TRUSS 40 WS WS TRUSS 39 WS TRUSS 38 WS TRUSS 37 PANTRY 20 WS WS TRUSS 36 Frezzer WS ESCALATORS "A" GROUP 1,2,3 PE 4 WS STAIR 57 SUBSTATIO N 28 TRUSS 27 STEWARDING OFFICE ffic CARP. SHOP STAIR 58 TRUSS TRUSS 23 TRUSS 22 TRUSS 21 TRUSS 20 TRUSS 19 TRUSS 8 TRUSS 7 TRUSS 6 SO B201 56 FE 28 TRUSS 5 TRUSS 4 TRUSS 2 TRUSS 3 OFFICE STAIR SUBSTATIO N 21 Above Hall G Dishwasher SUBSTATION 7 201 ROADWAY VALVES 12 &13 GATE STR 19 R SO B211 WS PE 8 Below PHASE III FIRE PUMP ROOM FIRE TRUCK CONNECTION PE 26 R09 SO B212 WS Lobby Area PHASE III HOUSE PUMP 7,8,9 ea R SO B213 R05 ESCALATORS B-1 REAR GROUP 1,2 Below MAIN ELECTR ICAL SERVICE "J" Storage Ar SO B21D SO B214 Terrace E E 36 37 SPRINKLER VALVES CONVENTIO Gas Meter 3 "J" STORAGE FENCE STAIR 50 33 34 SPRINKLER VALVES Emergency Generators GATE J121 PE 24 STAIR 52 5 J-2 SPRINKLER VALVES ROADWAY VALVE 14 STAIR 55 FE 27 J-12 PHONE REGISTRATION STORAGE TICKET OFFICE iling Area J-10 40 39 TELECOM STORAGE Finished Ce 14'8" Ceiling Height 14'7" Ceiling Height PE 23 30 31 32 SPRINKLER VALVES 4 R W J-11 PHONE STAIR 51 J-9 WS GATE 12A MEN J-8 SO B216 WS RIVERSIDE PANTRY Mechanical Room Below SERVICE CORRIDOR I-12 WOMEN FACILITY SERVICE STORAGE LOBBY I1 P VEHICLE CONSULTING ENGINEERS STAIR 11 R01 Roof R W 14'7" Ceiling Height Ceiling Height at center of Breaks Column MAINT. SHO ARCHIVES WS HOSE ROOM I-11 PHONE TO HALL I2 ELE. ROOM R W T WS 14'8" Ceiling Height STAIR 49 STAIR 48 J-18 HALL J ROADWAY VALVE SUBSTATION 6 J-17 91,080 SQ. FEE W R WOOD STORAGE J-16 TELEPHONE 27 28 SPRINKLER VALVES 3 I-22 T I118 STAIR 47 GATE 14A WELDING SHOP HT 22'-3" CLEANING STORAGE STAIR 46 GATE 11 I-21 ROADWAY VALVE STAIR 12 GATE 15 41,959 SQ. FEE TO HALL I1 ROADWAY VALVE TEC. SHOP GATE 15B VERY LIMIT H-14 SHOW OFFICE H117 REGISTRATION STORAGE HCS 24 PIV 8 PHASE II MAIN WATER VALVE 8" I-20 CEILING HEIG CONVENTION CENTER BLVD. PE 9 PUBLIC SAFETY WATER GATE 14 LOBBY H ROADWAY VALVE EMPLOYEE LUNCH ROOM MEN J-21 CONF. ROOM ESCALATORS "H" GROUP 1,2, 3 26 SPRINKLER VALVE DRAPE ROOM CONF. ROOM I-26 iling Area TO HALL H MEDICAL/ FIRST AID III WOMEN STAIR 34 SPRINKLER VALVES P&D W R WOMEN Finished Ce H-11 cooler PIV 6&7 H-21 WS CONC. STOR. COAT ROOM G114 H-10 STAND "14" LOBBY G PHASE II MAIN WATER VALVE 12" PUBLIC SAFETY 42 43 STAIR 57 STAND "19" GATE 16 Parking Office 50,400 SQ. FEE T HT 23'-0" REGISTRATION STORAGE GATE 11A H-18 FEET MEN SEAFOOD FIRE TRUCK CONNECTION SPRINKLER VALVE ROADWAY VALVE 15 I-23 CEILING HEIG H-5 STAIR 35 SALADS BUSINESS CENTER OFFICE 01 E1.0 Box Baler WATER CONCESSIO HALL I1 H116 SHOW OFFIC TO HALL G CT Business Center R.R. GATE 10 G-17 NE FOOD COURT BUSINESS CENTER PT G-16 WS G-5 FE 21 LOBBY F UP G-15 g Area G115 PHO ELECTRICAL Medical/ First Aid II G-14 Finished Ce ilin TELE E STAIR 32 G-13 G-4 CEILING HEIG HT 23'-3" VERY LIMIT ED RIGGING ADVANCE ARRANGEM ENTS REQU STAIR 44 VESTIBULE LOBBY D G-12 G-3 MEN STAIR 1-A G-11 WOMEN TO HALL F PE 18 TO HALL E WOMEN ESCALATORS "E" GROUP 1,2,3 ESCALATORS "D" GROUP 1,2,3 SO D 108 ELEC. FE 1 ROADWAY VALVE 2 STAIR 29 GATE 10B HALL H STAIR 37 PT W M Medical First Aid 1 W S GATE 10A PT GATE 17 41 STAIR 56 FE 28 J-20 109,200 SQ. TRUSS 32 TRUSS 18 TRUSS 17 TRUSS 16 TO HALL D ELECT. OFFICE STAND "8" CONCESSION STAIR 25 STOR. STORAGE 01 02 J-19 TRUSS 33 GATE 9A MEN STOR. R UP OFFICE 03 SPRINKLER VALVES I-27 FDC WS WS CONCESSION 04 SHIPPING & RECIVING H-17 FDC PHONE LE NON-FUNCTIONAL COOLER EE FR STORAGE ELEC. ELECT. 05 STAIR 58 H-16 A V F-3 STAIR 33 AT ELECT. PT ELECT. PT 06 WOMEN H-15 F-2 WATER WA O AT AT STOR. CO 07 MEN I-25 TO HALL G MOSAIC FOUNTAIN STAIR 2-A AT STAND "6" DISHWASHER R ZE FACILTY SERIVICE PE 22 LOBBY B2 PT 13 14 SPRINKLER VALVES Y E ON F-1 08 ELE. G-22 ADVANCE ARRANGEMENTS REQUIRED MEETING ROOM E-3 PHONES 12 TO HALL B2 WOMEN MEN DF PT 11 TRUSS 15 AT ESCALATORS "B" GROUP 1,2,3 VESTIBULE SPRINKLER VALVES MEETING ROOM E-2 WATER STAIR 42 AT STAIR 3-A&B Ticket Office 1 MEETING ROOM E-1 FE 19 & 20 TO HALL B1 PE 2 STAIR 3-A&B PT STAIR 4-A&B MEETING ROOM D-3 G-8 LOBBY B1 COOLER PT TRUSS 14 TRUSS 13 TRUSS 12 TRUSS 11 TRUSS 10 TRUSS 9 LOBBY A STAIR 4-A&B MEETING ROOM D-2 SO B105 Ramp Mosaic Lounge MEETING ROOM D-1 TRUSS 31 MEETING ROOM C-2 TRUSS 30 MEETING ROOM C-1 TRUSS 29 PE 10 WOMEN MEETING ROOM B2-2 09 I-24 G-20 Finished Ceiling Area TRUSS 28 MEETING ROOM B2-1 10 H-31 CEILING HEIGHT 25'-11" SO B104 FACILTY SERIVICE 11 H-30 VERY LIMITED RIGGING Entry Vestibule 12 Guard Shack PIV 9 F-6 G-19 CEILING HEIGHT 26'-2" 13 H-29 T Gas Pumps WS H-27 HALL G 91,451 SQ. FEE AIR WALLS ANNEX TRUSS TRUSS 23 F-5 AT CONCESSION STAIR 14 F-4 E-4 Finished Ceiling Area 14 H-25 G-18 E-3 E-2 15 WS G-26 TRUSS 22 TRUSS 21 TRUSS 20 AIR WALLS C-2 STAND "17" AIR WALLS To the Great Hall B-2 TRUSS 19 TRUSS 8 TRUSS 7 TRUSS 6 AIR WALLS AIR WALLS ON G-25 H-26 B-1 Show Office A101 16 SPRINKLER VALVE S 45 44 TELE. G-24 TRUSS 27 CONCESSI GATE 18 G-23 F-8 Pre-Function Area Rivergate Room GATE 19 Ramp 16 AIR WALLS E-7 E-6 CONC. STOR. AIR WALLS E-5 18 17 STAIR 59 WS TRUSS 35 D-6 19 WOMEN TRUSS 34 D-5 AIR WALLS AIR WALLS EXISTING PHASE I, MAIN DIMMING SYSTEM CONTROL PROCESSOR C-6 AIR WALLS C-5 AIR WALLS B-7 AIR WALLS B-6 20 LY B-5 21 P TO B-4 22 MEN W R Gas UST DOCKS ON B-3 23 Ramp 17 N OPE A-4 24 NG EIVI TRUSS 26 A-1 25 WATER 109,209 SQ. FEET 16 26 REC 104,862 SQ. FEET HALL F 127,634 SQ. FEET ROADWAY VALV E 27 C MC 66,257 SQ. FEET HALL E HALL D 103,365 SQ. FEET 28 LOADING NLY CO MC HALL C HALL B2 53,232 SQ. FEET 29 R CTO FE 5&6 FLOODWALL 17 P HALL B1 Kitchen 1 ROADWAY VALVE Ramp 18 31 SPRINKLER VALVES 48 47 46 GATE 20 STAIR 6 DOCKS Ramp 19 32 R W STAIR 62 W R Coole r LOADING 18 CONCESSI ON STAND "15" GATE 21 FDC ROADWAY VALV E MPA CO AIR WALLS FDC 19 N TO OPE Free z. HOUSE 35 P N TO OPE C-8 C-7 ROADWAY VALVE ELECTRICAL WARE 36 R CTO B-12 B-11 37 PHONES STR E 38 MPA CO B-10 39 P B-9 40 R B-8 A Air wall B Office A-6 41 STAIR 63 TRUSS 25 60,300 SQ. FEET 42 SNACK ROOM N TO OPE The Great Hall 43 TO PAC A-5 44 CE M CO Cooler COOLER 45 SPRINKLER VALVES WS WOMEN FACILITY SERVI Ramp 21 FE 30 53 52 MEN LY 46 AIR WALLS 20 ON TO AIR WALLS ROADWAY VALVE F&B Bulk Storage JL E-15 CHECKED BY: E-14 JL, DL E-13 DRAWN BY: WS 909 Poydras Street, Suite 2150 New Orleans, Louisiana 70112-1034 Tel. 504-586-1725 Fax 855-327-4815 PT RIVER DOCKS 2016-08-19 100% CD PT GATE 2 SEAL WOMEN BY MEN DESCRIPTION VESTIBULE DATE CONC. STOR. STAND "7" LOADING REV. CONCESSION WOMEN MISSISSIPPI GATE 1 STAIR 27 South Traffic Gate SPRINKLER VALVE 57 FOREMAN OFFICE 48 TRUSS 45 49 TRUSS 44 50 ELE. 51 ELE. STAND "5" 52 JAZZ CITY VESTIBULE 53 GATE 2A Storage STAIR 25 MEN 54 TRUSS 43 VESTIBULE WS STAND "3" PT 55 AIR WALLS GATE 3 56 Elec. CONCESSION CONCESSION 57 AIR WALLS PT 58 TRUSS 42 CONCESSION 59 TRUSS 41 STAIR 8 60 AIR WALLS FE 7 SPRINKLER VALVES IN PLANT 2A 2B WATER Storage FACILTY SERIVICE TOOL ROOM EXISTING HOUSEKEEPING C MPA Cooler Cooler Cooler Freezer ET Kit. Forman STAIR 15 PE 8 GATE 4 WS Elev. Room 60a CONSESSION GATE 5 61 ELECT. AIR WALLS WS STAIR 9 WOMEN 62 54 CONC. STOR. STAND "11" TRUSS 40 MEN 63 64 65 CONCESSION WOMEN TRUSS 39 AIR WALLS E UL STAIR 10 Freezer Gas 9 Meter 1 JUL IA TRUCK DOCKS 66 67 ESCALATORS B-2 REAR GROUP 1,2 MEN D C Cooler SPRINKLER VALVE 68 PIV 21 WS CO A-7 69 SPRINKLER VALVE GATE 23 TRUCK RAMP 2 F&B VE COMPACTOR 70 CONC. STOR. TRUSS 38 71 CONCESSION STAND "9" AIR WALLS 72 WOMEN WATER 73 74 MEN P TO 75 WS WS x Bo ler Ba RAMP ROADWAY VALVE 1 EN OP 76 TRUCK DOCKS ESCALATORS B-1 REAR GROUP 1,2 Box Baler 8A IB ST Clearance 12' CORRIDOR 77 SPRINKLER VALVE F& B DOCK MAIN ELECTRICAL SERVICE KITCHEN SHOP P TO GATE 6 TOOL ROOM SNACK ROOM RAMP 3 R 4 CTO MPA CO TRUCK RAMP 5 EN OP TRUCK RAMP OPEN TOP STORAGE 56 55 PIV 1 E E F SPRINKLER VALVES R CTO MPA CO STAIR 11 GATE 7 COMPACTOR STAIR 12 F ET Forman Office TRUSS 37 Facility Services PT TRUSS 36 Storage Box Baler Storage ELECT. FE ELECT. PE 9 SHEET REFERENCE NOTES EXISTING DIMMER PANEL TO BE REMOVED AND REPLACED WITH NEW. DISCONNECT LIGHTING BRANCH CIRCUITS THAT ORIGINATE FROM EXISTING DIMMER PANEL AND PREPARE THEM FOR REUSE. 2 SERVICE CORRIDOR 2HCDMW4:10,12 2EHCDMW4-2,4 D WS N License No. 37172 2HCDMW4-8 2EHCDMW4-6,8 2EHCDMW4-6,8 D D 2LCDMW4-10,12 2LCDMW4-10,12 2LCDMW4-1,3 257 256 255 2EHCDW5-9,11 WS 2ECHDMW5-9,11 WS D D 2LCDMW5-10,12 D 2LCDMW5-2,4 2LCDMW5-5,7 253 252 FE SS IO N AL ENG IN 2 JL 254 SUB STATION 13 O WS OF LOUISIA JEFFERY LAMBERT PR 2EHCDMW4-6,8 2HCDMW1-1,3,5 (TYP EXCEPT WHERE NOTED) 2HCDMW5-7,9,11 (TYP EXCEPT WHERE NOTED) TE TA A Fire Supression System R 2 EXIST DIMM PNLS: 2LCDMW4 2HCDMW4 2EHCDMW4 DM FOR MEETING ROOMS 255-257 EE CLEAN AND REPLACE ANY BURNED-OUT LAMPS IN MEETING ROOMS. EXISTING WALL DIMMER CONTROL STATION TO BE REMOVED AND REPLACED WITH NEW. S 2. 1 SEAL EXISTING LIGHTING FIXTURES AND CIRCUIT NUMBERS SHOWN FOR REFERENCE ONLY. ALL EXISTING CIRCUITS AND LIGHT FIXTURES SHALL BE REUSED. BY 1. DM SHEET GENERAL NOTES D D 2HECDMW4-8,10,12 D 2HECDMW4-1,3 2HECDMW4-9,11 2HCDMW4-7,9,11 (TYP EXCEPT WHERE NOTED) 2HCDMW4-1,3,5 (TYP EXCEPT WHERE NOTED) D D D 2HECDMW5-8,10,12 D D 2HECDMW5-2,4 R CHECKED BY: R 2LCDMW5-1,3 D 2HCDMW5-5,10,12 2HECDMW5-1,3 2HCDMW5-2,4,6 (TYP EXCEPT WHERE NOTED) DATE 2HCDMW4-2,4,6 (TYP EXCEPT WHERE NOTED) D 2LCDMW5-9,11 REV. SUBSTATION 12 PE 15 2EHCDMW2-10,12 WS STR 27 D PE 17 PT WS D D FE 16 2LCDMW2-9,11 2LCDMW2-26,28 2LCDMW2-21,22 2LCDMW2-5,7 2LCDMW2-22,24 2LCDMW2-17,19 243 R R 2LCDMW2-1,3 2LCDMW2-18,20 D 2LCDMW1-13,15 (TYP EXCEPT WHERE NOTED) 2 D 2LCDMW2-13,15,17 (TYP EXCEPT WHERE NOTED) 2EHCDMW2-13,15 D 2EHCDMW2-6,8 STR 28 STR 30 STR 32 STR 31 2EHCDMW2-2,4 DM D D D D 2LCDMW1-18,20 2LCDMW1-13,15 2LCDMW1-14,16 2LCDMW1-17,19 D 2EHCDMW2-9,11 2MCW2-11 2LCDMW2-14,16 2EHCDMW1-1,3 2EHCDMW1-9,11 D WS 2LCDMW2-10,12 D D 2LCDMW1-26,28 238 2LCDMW1-34,36 235 236 2LCDMW1-38,40 2LCDMW1-37,39 D 2EHCDMW1-17,19 2EHCDMW1-13,15 2EHCDMW1-10,12 2LCDMW1-2,4 D 2LCDMW1-1,3 2LCDMW2-6,8 2LCDMW1-33,35 2LCDMW1-21,23 2LCDMW1-22,24 D 2EHCDMW1-6,8 2 2LCDMW1-6,8 237 2LCDMW1-30,32 D 239 D 240 2LCDMW1-29,31 D 2LCDMW1-8,10,12 (TYP EXCEPT WHERE NOTED) 2LCDMW1-25,27 D 2LCDMW1-2,4,6 (TYP EXCEPT WHERE NOTED) 2LCDMW1-10,12 241 BALCONY 2LCDMW2-2,4 2LCDMW1-9,11 D 2LCDMW1-7,9,1 (TYP EXCEPT WHERE NOTED) 242 2LCDMW1-5,7 EXIST DIMM PNLS: 2LCDMW2 2HCDMW2 2EHCDMW2 FOR MEETING ROOMS 242-245 D 2LCDMW1-1,3,5 (TYP EXCEPT WHERE NOTED) D 2LCDMW2-8,10,12 (TYP EXCEPT WHERE NOTED) 1 PHASE II - 2ND FLOOR - ELECTRICAL DEMOLITION PUBLIC SAFETY PE 9 DRAPE ROOM P&D TEC. SHOP WOOD STORAGE EMPLOYEE LUNCH ROOM SUBSTATION 6 STAIR 12 PHASE I ARCHIVES WS HOSE ROOM STAIR 11 WS PHASE II KEY PLAN SO B216 WS SO B21D RIVERSIDE PANTRY R SO B214 SO B213 Mechanical Room Below VIDEO ROOM 1/16"= 1'-0" SO B212 WS WS SO B211 WS WS WS WS R R PT R FE 7 STR 7 ELEVATOR STORAGE PT SUBSTATION 3 PT STAIR 10 SUBSTATION 5 IN PLANT SUBSTATION 1 STAIR 15 ESCALATORS B-2 REAR GROUP 1,2 PE 8 R STR 19 R ESCALATORS B-1 REAR GROUP 1,2 SERVICE CORRIDOR STAIR 8 STAIR 9 Roof ELEC SUBSTATION 2 F&B WAREHOUSE D SHOP 2016-08-19 INV. STORAGE SUBSTATION 19 TRUSS PASSAGEWAY C TRUSS PASSAGEWAY B FE 5&6 TRUSS PASSAGEWAY South Public Truss A F & B SMALLWARES STORAGE STR 16 TEC. FE 29 E DATE PHASE III CELL SITE FE 30 STAIR 63 North Public Truss F SUBSTATION 20 STAIR 62 CARPET STORAGE SHIPPING & RECIEVING STAIR 59 STAIR 56 SUBSTATION 21 PROJECT NO. FE 28 CARP. SHOP ANNEX STAIR 58 G TRUSS OFFICE SO B201 Off SO B202 EXIST DIMM PNLS: 2LCDMW4 2HCDMW4 2EHCDMW4 Dishwasher 2 ROOMS 255-257 SERVICE CORRIDOR 2EHCDMW4-6,8 ESCALATORS "A" GROUP 1,2,3 PE 4 WS WS PANTRY 20 WS WS WS D WS OPEN TO BELOW R 2HCDMW4:10,12 2EHCDMW4-2,4 WS 2HCDMW4-8 2EHCDMW4-6,8 D 2LCDMW4-10,12 257 2EHCDW5-9,11 22 EXEC SOUS CHEF 28 D Office 252 R 2LCDMW5-1,3 R 2 EXIST DIMM PNLS: 2LCDMW5 2HCDMW5 2EHCDMW5 FOR MEETING ROOMS 252-254 Freezer SUB D SUBSTATION 4 WS STR 3A PE 2 ESCALATORS "B" GROUP 1,2,3 D 2HECDMW4-1,3 2HCDMW4-1,3,5 (TYP EXCEPT WHERE NOTED) D D 2HECDMW5-8,10,12 D D 2HECDMW5-2,4 2HCDMW5-2,4,6 (TYP EXCEPT WHERE NOTED) D D STA TIO Cooler OPEN TO BELOW 2EHCDMW2-17,19 2EHCDMW2-5,7 PE 15 ICE ROOM D D FE 16 2LCDMW2-26,28 F&B SHIPPING & RECEIVING STAIR 37 PE 17 PT WS D 2LCDMW2-9,11 GREEN ROOM NORTH 260 2EHCDMW2-10,12 WS STR 27 STR 25 R TEC. OFFICE Freezer 2016.026 J N 2HCDMW5-5,10,12 2HECDMW5-1,3 F&B BANQUET OFFICE OFFICE R 2LCDMW2-21,22 Offices Green Room SHEET NO. STAIR PLUMBING STORAGE 55 GREEN ROOM SOUTH H.V.A.C STORAGE Football Cooler STR 3B Green Room Production 23 SUBSTATION PT WS WS STR 4B D STR 29 PE 22 WS PT D 2HECDMW4-9,11 2HCDMW4-7,9,11 (TYP EXCEPT WHERE NOTED) SERVICE CORRIDOR STR 42 WS STR 4A D 2HCDMW4-2,4,6 (TYP EXCEPT WHERE NOTED) 19 & 20 WS WS D 2HECDMW4-8,10,12 SUBSTATION 12 FE R 14 R I2 Cooler SERVICE CORRIDOR 2LCDMW5-5,7 2LCDMW5-9,11 I1 H Cooler KITCHEN II Frezzer SUB STATION 13 STAIR 57 SUBSTATION 2ECHDMW5-9,11 253 2LCDMW5-6,8 STAIR 38 2HCDMW1-1,3,5 (TYP EXCEPT WHERE NOTED) 2LCDMW5-2,4 254 2LCDMW4-5,7 WS D 2LCDMW5-10,12 255 2LCDMW4-2,4 WS D 2LCDMW4-1,3 256 2LCDMW4-2,4 2HCDMW5-7,9,11 (TYP EXCEPT WHERE NOTED) 2EHCDMW4-6,8 D 2LCDMW4-10,12 R WS SUBSTATION Cooler STEWARDING OFFICE DM FOR MEETING ice DM SUBSTATION 7 260 WS STR 2A STR 2B R WS 2LCDMW2-5,7 2LCDMW2-22,24 243 WS ESCALATORS "D" GROUP 1,2,3 GROUP 4,5,6 FE 1 WS STR 1A STR 1A PT WS STR 22 Atrium Bridge R 245 R R R 2LCDMW2-1,3 2LCDMW2-18,20 D D PT ESC. PW GROUP 1,2 STR 23 2LCDMW1-20,22,24 (TYP EXCEPT WHERE NOTED) EXIST DIMM PNLS: 2LCDMW2-1,3,5 2LCDMW1 (TYP EXCEPT 2HCDMW1 WHERE NOTED) 2EHCDMW1 FOR MEETING 2EHCDMW1-9,11 ROOMS 235-241 2EHCDMW1-2,4 STR 26 WS 2LCDMW1-13,15 (TYP EXCEPT WHERE NOTED) 2LCDMW1-14,16,18 (TYP EXCEPT WHERE NOTED) ESCALATORS "E" GROUP 1,2,3 GROUP 4,5,6 R 2LCDMW2-13,15 2HCDW-6 PE 14 2 D 2LCDMW2-14,16,18 (TYP EXCEPT WHERE NOTED) 2EHCDMW2-1,3 D D 2LCDMW2-13,15,17 (TYP EXCEPT WHERE NOTED) 2EHCDMW2-13,15 262 STAIR 54 STAIR 44 ICE ROOM 277 PT D 24 STR 30 STR 31 ESCALATOR S "G" GROUP 1,2,3 STR 32 2EHCDMW2-2,4 D D 2LCDMW1-13,15 D D STAIR 55 STAIR 35 2EHCDMW2-9,11 2MCW2-11 2LCDMW2-14,16 2EHCDMW1-1,3 2EHCDMW1-9,11 SUBSTATION FE 21 2EHCDMW2-6,8 STR 28 DM D 2LCDMW1-18,20 D 261 STAIR 36 2LCDMW2-17,19 244 STR 20 WS R STAIR 49 WS FE 27 R 2LCDMW2-10,12 D D D D 2LCDMW1-26,28 PE 13 2LCDMW1-43,45 2LCDMW1-14,16 238 2LCDMW1-34,36 235 236 2LCDMW1-38,40 2LCDMW1-37,39 2LCDMW1-33,35 D 2EHCDMW1-13,15 2EHCDMW1-10,12 1 2LCDMW1-17,19 239 D D 2LCDMW1-2,4 D D 2LCDMW1-1,3 2LCDMW1-25,27 D 2LCDMW1-2,4,6 (TYP EXCEPT WHERE NOTED) 2 2LCDMW1-10,12 D 2LCDMW1-7,9,1 (TYP EXCEPT WHERE NOTED) 242 2LCDMW1-5,7 241 240 2LCDMW1-29,31 2LCDMW1-8,10,12 (TYP EXCEPT WHERE NOTED) D 2LCDMW2-6,8 2LCDMW1-6,8 237 2EHCDMW1-6,8 D 2LCDMW1-21,23 2LCDMW1-22,24 2LCDMW1-30,32 D 2EHCDMW1-17,19 2LCDMW2-2,4 2LCDMW1-9,11 D 2LCDMW1-1,3,5 (TYP EXCEPT WHERE NOTED) DM 01 E1.1 SERVICE CORRIDOR PE 13 2LCDMW1-43,45 D D PROJECT NAME: D DM D THIS SHEET: 2LCDMW1-20,22,24 (TYP EXCEPT WHERE NOTED) WS 2LCDMW2-14,16,18 (TYP EXCEPT WHERE NOTED) 2EHCDMW2-1,3 D EXIST DIMM PNLS: 2LCDMW2 2HCDMW2 2EHCDMW2 FOR MEETING ROOMS 242-245 F&B V.I.P PROP ROOM 277 PT BALCONY ESCALATOR S "H" GROUP 1,2,3 GROUP 4,5,6 PT STAIR 34 STAIR 45 R STAIR 51 ESCALATO RS GROUP 1,2,3 "I" GROUP 4,5,6 GROUP 7,8,9 STAIR 46 STAIR 47 F&B 299 PANTRY R D 2LCDMW2-8,10,12 (TYP EXCEPT WHERE NOTED) PE 23 29 PE 24 STAIR 50 SUBSTATION STAIR 48 STAIR 52 STAIR 53 ICE ROOM 299 PE 25 F&B PROP E1.1 ROOM 1"=400'-0" PE 26 STAIR 54 FIRE WATER TANK 376,700 Gals. OF SHEETS 2ND FLOOR PLAN - ELECTRICAL DEMOLITION STR 23 2LCDMW2-1,3,5 EXIST DIMM PNLS: (TYP EXCEPT 2LCDMW1 WHERE NOTED) 2HCDMW1 2EHCDMW1 FOR MEETING 2EHCDMW1-9,11 ROOMS 235-241 2EHCDMW1-2,4 D D PT 2LCDMW1-14,16,18 (TYP EXCEPT WHERE NOTED) ESCALATORS "E" GROUP 1,2,3 GROUP 4,5,6 2HCDW-6 PE 14 STR 26 R 2LCDMW2-13,15 900 CONVENTION CENTER BLVD. NEW ORLEANS, LOUISIANA 70130 STR 22 R 245 NEW ORLEANS ERNEST N. MORIAL CONVENTION CENTER PHASE II MEETING ROOM LIGHTING PANEL RETROFIT ESCALATORS "D" GROUP 1,2,3 GROUP 4,5,6 244 909 Poydras Street, Suite 2150 New Orleans, Louisiana 70112-1034 Tel. 504-586-1725 Fax 855-327-4815 2EHCDMW2-17,19 2EHCDMW2-5,7 CONSULTING ENGINEERS STR 29 SERVICE CORRIDOR PT JL, DL D 2LCDMW5-6,8 DRAWN BY: D 2LCDMW4-5,7 2016-08-19 100% CD 2LCDMW4-2,4 DESCRIPTION 2LCDMW4-2,4 EXIST DIMM PNLS: 2LCDMW5 2HCDMW5 2EHCDMW5 FOR MEETING ROOMS 252-254 2. EXISTING LIGHTING FIXTURES AND CIRCUIT NUMBERS SHOWN FOR REFERENCE ONLY. ALL EXISTING CIRCUITS AND LIGHT FIXTURES SHALL BE REUSED. 1 EXISTING WALL DIMMER CONTROL STATION TO BE REMOVED AND REPLACED WITH NEW. 2 EXISTING DIMMER PANEL TO BE REMOVED AND REPLACED WITH NEW. DISCONNECT LIGHTING BRANCH CIRCUITS THAT ORIGINATE FROM EXISTING DIMMER PANEL AND PREPARE THEM FOR REUSE. CLEAN AND REPLACE ANY BURNED-OUT LAMPS IN MEETING ROOMS. EXIST DIMM PNLS: 3LCDMW5 3HCDMW5 3EHCDMW5 FOR MEETING ROOMS 355-357 3EHCDMW5-2,4 SERVICE CORRIDOR 3HCDMW6-2,4,6 (TYP EXCEPT WHERE NOTED) 3HCDMW6-14 3EHCDMW5-9,11 3EHCDMW5-5,7 2 3HCDMW6-1,3,5 (TYP EXCEPT WHERE NOTED) 3EHCDMW6-10,12 3HCDMW6-8,10,12 3EHCDMW6-1,3 3EHCDMW6-5,7 S D D 3LCDMW6-21,23 3LCDMW5-43,45 EXIST DIMM PNLS: 3LCDMW6 3HCDMW6 3EHCDMW6 FOR MEETING ROOMS 348-354 3LCDMW6-22,24 3LCDMW5-13,15 3LCDMW6-1,3 License No. 37172 2 FE O 3LCDMW5-47,44 SS 3LCDMW6-18,20 3LCDMW6-25,27 N JEFFERY LAMBERT PR 3LCDMW5-14,16 D D SEAL D DM D OF LOUISIA A DM TE TA R 1. SHEET REFERENCE NOTES EE SHEET GENERAL NOTES IO N AL E N G IN BY 3LCDMW6-5,7 3LCDMW5-9,11 357 3LCDMW5-51,53 356 3LCDMW6-29,31 3LCDMW6-14,16 354 353 3LCDMW6-33,35 3LCDMW6-10,12 3LCDMW6-37,39 3LCDMW6-6,8 3LCDMW6-26,28 3LCDMW6-2,4 355 3LCDMW6-55,67 3LCDMW6-9,11 3LCDMW5-5,7 CHECKED BY: 3LCDMW5-6,8 352 JL 3LCDMW5-10,12 3LCDMW6-13,15 3LCDMW6-44,41 3LCDMW6-17,19 D D D D D D D D D D 3EHCDMW5-5,7 3EHCDMW6-5,7 3EHCDMW6-2,4 3HCDMW6-7,9,11 (TYP EXCEPT WHERE NOTED) DATE 3HCDMW2-13,15,17 (TYP EXCEPT WHERE NOTED) 3EHCDMW6-14,16 3EHCDMW2-10,12 3EHCDMW6-17,19 D 3EHCDMW4-13,15 3EHCDMW2-10,12 D 351 D 3LCDMW4-30,32 3LCDMW4-18,20 3LCDMW2-35,37 3LCDMW4-30,32 3LCDMW4-21,23 D 3LCDMW2-31,33 3EHCDMW4-2,4 3EHCDMW4-9,11 D D D 3LCDMW1-9,11 338 3LCDMW1-5,7 3LCDMW2-14,16 3LCDMW1-2,4 3LCDMW2-13,15 D D D D 3EHCDMW1-10,12 PHASE II - 3ND FLOOR - ELECTRICAL DEMOLITION 1/16"= 1'-0" KEY PLAN PHASE II PHASE III E D EXIST DIMM PNLS: 3LCDMW5 3HCDMW5 3EHCDMW5 FOR MEETING ROOMS 355-357 3EHCDMW5-2,4 DATE 3HCDMW6-2,4,6 (TYP EXCEPT WHERE NOTED) 3HCDMW6-14 3EHCDMW5-9,11 3EHCDMW5-5,7 2 2016-08-19 3HCDMW6-1,3,5 (TYP EXCEPT WHERE NOTED) 3EHCDMW6-10,12 3HCDMW6-8,10,12 3EHCDMW6-1,3 3EHCDMW6-5,7 DM C 3LCDMW6-21,23 3LCDMW6-22,24 3LCDMW5-13,15 3LCDMW6-1,3 3LCDMW5-47,44 3LCDMW6-25,27 EXIST DIMM PNLS: 3LCDMW6 3HCDMW6 3EHCDMW6 FOR MEETING ROOMS 348-354 2 DM 3LCDMW5-43,45 3LCDMW5-14,16 3LCDMW6-18,20 3LCDMW6-5,7 3LCDMW5-10,12 3LCDMW5-9,11 357 3LCDMW5-51,53 356 355 3LCDMW6-55,67 3LCDMW5-6,8 3LCDMW6-29,31 352 3LCDMW6-14,16 354 353 3LCDMW6-33,35 3LCDMW6-10,12 3LCDMW6-9,11 3LCDMW5-5,7 3LCDMW6-13,15 3LCDMW6-44,41 3LCDMW5-2,4 3LCDMW6-37,39 3LCDMW6-6,8 3LCDMW6-17,19 3LCDMW5-1,3 3LCDMW6-48,50 3LCDMW6-26,28 3LCDMW6-2,4 3EHCDMW5-1,3 3EHCDMW5-8 3EHCDMW5-5,7 3HCDMW5-2,4,6 (TYP EXCEPT WHERE NOTED) 3EHCDMW1-9,11 3HCDMW2-13,15,17 (TYP EXCEPT WHERE NOTED) 333 3HCDMW5-7,9,11 (TYP EXCEPT WHERE NOTED) 3EHCDMW6-13,15 3HCDMW2-13,15,17 (TYP EXCEPT WHERE NOTED) 3EHCDMW6-14,16 3EHCDMW6-5,7 3EHCDMW6-2,4 3HCDMW6-7,9,11 (TYP EXCEPT WHERE NOTED) 3EHCDMW2-10,12 3EHCDMW6-17,19 3EHCDMW4-13,15 3EHCDMW2-10,12 PE 17 3HCDMW6-19,21,23 (TYPICAL FOR 6) 351 FE 16 3LCDMW2-31,33 3LCDMW4-18,20 FE 3HCDMW1-13,15,17 (TYPICAL FOR 6) 3LCDMW4-30,32 19 & 20 PE 15 3LCDMW6-52,54 3HCDMW1-14,16,18 (TYPICAL FOR 6) 3LCDMW6-56,58 01 E1.2 PROJECT NAME: 3HCDMW4-4,6,8 (TYP EXCEPT WHERE NOTED) 3LCDMW6-79,81 3HCDMW2-2,4,6 (TYP EXCEPT WHERE NOTED) 3HCDMW2-1,3,5 (TYP EXCEPT WHERE NOTED) 3LCDMW6-59,61 3HCDMW1-1,3,5 (TYP EXCEPT WHERE NOTED) 3HCDMW2-7,9,11 (TYP EXCEPT WHERE NOTED) 3LCDMW6-63,65 3HCDMW2-8,10,12 (TYP EXCEPTWHERE NOTED) 334 3LCDMW2-35,37 3EHCDMW1-6,8 3LCDMW4-30,32 343 2 DM PE 14 EXIST DIMM PNLS: 3LCDMW1 3HCDMW1 3EHCDMW1 FOR MEETING ROOMS 333-337 3LCDMW2-39,41 2 3LCDMW4-21,23 3LCDMW4-26,28 3EHCDMW2-6,8 EXIST DIMM PNLS: 3LCDMW2 3HCDMW2 3EHCDMW2 FOR MEETING ROOMS 338-341 3EHCDMW2-2,4 345 344 ESCALATORS "D" GROUP 1,2,3 GROUP 4,5,6 ESC. PW GROUP 1,2 3LCDMW4-17,19 3EHCDMW4-10,12 3LCDMW2-26,28 3HCDMW4-14,16,18 (TYP EXCEPT WHERE NOTED) 3LCDMW1-14,16 3LCDMW1-6,8 336 3LCDMW2-22,24 3LCDMW2-21,23 337 3LCDMW2-18,26 3LCDMW2-17,19 3LCDMW1-5,7 338 339 346 3LCDMW4-1,3 3EHCDMW6-25,27 3LCDMW2-13,15 3LCDMW4-5,7 347 3LCDMW4-14,16 3LCDMW4-10,12 3LCDMW4-6,8 3LCDMW2-5,7 3LCDMW1-1,3 3EHCDMW1-1,3 3HCDMW1-7,9,11 (TYP EXCEPT WHERE NOTED) 3EHCDMW6-21,23 3EHCDMW4-9,11 3LCDMW4-14,16 3EHCDMW2-1,3 3LCDMW2-9,11 3LCDMW2-14,16 3LCDMW1-2,4 3EHCDMW1-5,7 3EHCDMW1-2,4 349 3EHCDMW4-17,19 3LCDMW1-9,11 335 350 3HCDMW6-20,22,24 (TYPICAL FOR 6) 3EHCDMW4-5,7 3EHCDMW4-2,4 3LCDMW2-10,12 3LCDMW2-25,27 3LCDMW2-6,8 3LCDMW1-10,12 3HCDMW6-25,27,29 (TYPICAL FOR 6) ESCALATORS "E" GROUP 1,2,3 GROUP 4,5,6 3EHCDMW4-6,8 3HCDMW4-20,22,24, (TYP EXCEPT WHERE NOTED) FE 27 340 341 3LCDMW2-2,4 342 2 EXIST DIMM PNLS: 3LCDMW1 3HCDMW1 3EHCDMW1 FOR MEETING ROOMS 342-347 348 2016.026 ESCALATOR S GROUP 1,2,3 "I" GROUP 4,5,6 GROUP 7,8,9 3EHCDMW4-29,31 3HCDMW4-7,9,11 (TYP EXCEPT WHERE NOTED) 3HCDMW4-1,3,5 (TYP EXCEPT WHERE NOTED) PROJECT NO. FE 21 3EHCDMW2-9,11 DM 3LCDMW4-5,7 3HCDMW1-8,10,12 (TYP EXCEPT WHERE NOTED) 3LCDMW6-67,69 3HCDMW1-7,9,11 (TYP EXCEPT WHERE NOTED) D 3LCDMW2-1,5 3LCDMW6-71,73 3EHCDMW1-1,3 D 3LCDMW4-2,4 3LCDMW6-75,77 3EHCDMW1-2,4 3LCDMW2-2,4 D 2 341 3HCDMW4-26,28,30 (TYPICAL FOR 6) 3HCDMW4-1,3,5 (TYP EXCEPT WHERE NOTED) 3LCDMW6-79,81 3EHCDMW1-5,7 340 3HCDMW4-7,9,11 (TYP EXCEPT WHERE NOTED) 3EHCDMW4-29,31 D 3LCDMW6-64,66 D 342 3LCDMW2-5,7 339 3LCDMW1-1,3 D 3LCDMW4-6,8 3LCDMW2-17,19 D 3LCDMW6-72,74 3LCDMW1-14,16 3LCDMW2-18,26 337 EXIST DIMM PNLS: 3LCDMW1 3HCDMW1 3EHCDMW1 FOR MEETING ROOMS 342-347 3LCDMW6-68,70 336 3LCDMW2-9,11 DM 335 3LCDMW1-6,8 D 3LCDMW1-22,24 3LCDMW1-10,12 D 3HCDMW4-26,28,30 (TYPICAL FOR 6) 3LCDMW4-2,4 3LCDMW2-1,5 3EHCDMW1-10,12 3HCDMW2-8,10,12 (TYP EXCEPTWHERE NOTED) 3HCDMW1-1,3,5 (TYP EXCEPT WHERE NOTED) 3HCDMW2-7,9,11 (TYP EXCEPT WHERE NOTED) 3HCDMW2-2,4,6 (TYP EXCEPT WHERE NOTED) 3HCDMW2-1,3,5 (TYP EXCEPT WHERE NOTED) 3HCDMW4-4,6,8 (TYP EXCEPT WHERE NOTED) PE 25 PE 26 SHEET NO. E1.2 1"=400'-0" OF SHEETS 3RD FLOOR PLAN - ELECTRICAL DEMOLITION D THIS SHEET: D 3LCDMW1-18,20 D 3LCDMW4-14,16 3LCDMW1-14,16 D 348 3LCDMW4-10,12 DM D 3LCDMW4-1,3 3LCDMW2-21,23 D D 347 3EHCDMW2-1,3 3LCDMW2-6,8 3LCDMW2-22,24 346 3LCDMW4-14,16 900 CONVENTION CENTER BLVD. NEW ORLEANS, LOUISIANA 70130 3LCDMW2-10,12 3LCDMW2-25,27 3LCDMW4-5,7 D 3LCDMW2-26,28 D NEW ORLEANS ERNEST N. MORIAL CONVENTION CENTER PHASE II MEETING ROOM LIGHTING PANEL RETROFIT 3LCDMW4-5,7 3HCDMW1-8,10,12 (TYP EXCEPT WHERE NOTED) D D D D D STR 30 D STR 28 3LCDMW6-71,73 3EHCDMW2-9,11 D 3EHCDMW4-17,19 3LCDMW6-64,66 3EHCDMW4-5,7 DM D 349 3HCDMW6-20,22,24 (TYPICAL FOR 6) 3HCDMW4-14,16,18 (TYP EXCEPT WHERE NOTED) 3LCDMW6-75,77 D 3LCDMW6-68,70 D 3EHCDMW4-6,8 D 3EHCDMW6-25,27 3LCDMW6-79,81 D D 3EHCDMW6-21,23 D 2 3EHCDMW4-10,12 D 3HCDMW4-20,22,24, (TYP EXCEPT WHERE NOTED) EXIST DIMM PNLS: 3LCDMW2 3HCDMW2 3EHCDMW2 FOR MEETING ROOMS 338-341 3EHCDMW2-2,4 D ESCALATORS "E" GROUP 1,2,3 GROUP 4,5,6 3LCDMW6-72,74 3EHCDMW2-6,8 D STR 22 3LCDMW4-17,19 3LCDMW1-13,15 PE 14 3LCDMW2-39,41 3LCDMW1-17,19 EXIST DIMM PNLS: 3LCDMW1 3HCDMW1 3EHCDMW1 FOR MEETING ROOMS 333-337 3LCDMW4-26,28 350 D ESCALATORS "D" GROUP 1,2,3 GROUP 4,5,6 DM 3LCDMW1-21,23 2 344 3HCDMW6-25,27,29 (TYPICAL FOR 6) D 343 345 3LCDMW6-59,61 3EHCDMW1-6,8 3LCDMW6-67,69 D 334 3LCDMW6-63,65 D 3LCDMW1-13,15 3LCDMW1-17,19 3LCDMW1-21,23 D D FE 16 3LCDMW6-52,54 D D 3LCDMW6-56,58 3HCDMW6-19,21,23 (TYPICAL FOR 6) 3LCDMW6-79,81 PE 17 CONSULTING ENGINEERS PE 15 D D 3HCDMW2-13,15,17 (TYP EXCEPT WHERE NOTED) 333 3LCDMW1-22,24 3LCDMW1-18,20 3LCDMW1-14,16 D 3EHCDMW1-9,11 3EHCDMW6-13,15 REV. 3HCDMW5-7,9,11 (TYP EXCEPT WHERE NOTED) 3HCDMW5-2,4,6 (TYP EXCEPT WHERE NOTED) JL, DL D DESCRIPTION 3EHCDMW5-1,3 3EHCDMW5-8 DRAWN BY: 3LCDMW6-48,50 909 Poydras Street, Suite 2150 New Orleans, Louisiana 70112-1034 Tel. 504-586-1725 Fax 855-327-4815 3LCDMW5-1,3 2016-08-19 100% CD 3LCDMW5-2,4 SHEET REFERENCE NOTES 2 REUSE ALL EXISTING MEETING ROOM LIGHTING CIRCUITS AS APPLICABLE. MODIFY, REWORK AND/OR REPLACE CIRCUIT CONDUIT AND WIRING AS REQUIRED PER NEC TO MAKE NEW CONNECTIONS. NEW DIMMER RACKS AND RELAY PANELS AT LOCATION OF EXISTING DIMMER PANELS. RECONNECT EXISTING LIGHTING CIRCUITS TO NEW DIMMER RACK. REWORK AND/OR EXTEND CIRCUIT (CONDUIT AND WIRING) AS REQUIRED PER NEC TO RECONNECT CIRCUITS TO NEW DIMMER RACKS. SEE DETAILS ON SHEETS E4.1-E4.3. E-3.1 E-3.1 TE TA OF LOUISIA N SERVICE CORRIDOR JEFFERY LAMBERT License No. 37172 WS WS NEW WALL TOUCHSCREEN LIGHTING CONTROL STATION INSTALLED AT THE LOCATION OF EXISTING SLIDER STATION. INSTALL NEW WIRING TO NEW DIMMING SYSTEM EQUIPMENT RACK. REUSE EXISTING CONDUIT AS APPLICABLE. SEE WIRING DIAGRAMS AND INSTALLATION DETAILS. SUB STATION 13 ALTERNATE #2: ALL WORK ASSOCIATED WITH MEETING ROOMS 252-254 256 253 254 255 SS IO N AL ENG IN 252 JL 257 FE O WS WS PR 3 Fire Supression System A 3. 4 3 R REPLACE ANY BURNED-OUT LAMPS IN MEETING ROOMS THAT NEW DIMMING SYSTEM IS BEING INSTALLED. DIMMING SYSTEM NETWORK PORT AT THE LOCATION OF EXISTING DIMMING SYSTEM PORTABLE PLUG-IN OUTLET. RUN CAT5 CABLE FROM NETWORK PORT TO ETHERNET SWITCH AT DIMMING SYSTEM EQUIPMENT RACK IN ELECTRICAL ROOM. REUSE EXISTING CONDUIT AS APPLICABLE. SEE WIRING DIAGRAMS AND INSTALLATION DETAILS. EE 2. 1 S THE PHRASE "MEETING ROOMS" USED IN THE DRAWINGS REFERS TO THE MEETING ROOMS IN WHICH NEW DIMMING SYSTEMS ARE BEING INSTALLED IN THIS CONTRACT. SEAL 1. 2 BY SHEET GENERAL NOTES NEW DIMMING SYSTEM POWER CONTROL EQUIPMENT FOR MEETING ROOMS 255-257 TS TS CHECKED BY: TS NEW DIMMING SYSTEM POWER CONTROL EQUIPMENT FOR MEETING ROOMS 252-254 2 DATE ALTERNATE #3: ALL WORK ASSOCIATED WITH MEETING ROOMS 255-257 REV. SUBSTATION 12 WS STR 27 PE 17 PT WS FE 16 243 ESCALATORS "D" GROUP 1,2,3 GROUP 4,5,6 STR 22 R 244 R TS TS 1 NEW DIMMING SYSTEM POWER CONTROL EQUIPMENT FOR MEETING ROOMS 235-241 E-3.1 STR 26 245 R PE 14 909 Poydras Street, Suite 2150 New Orleans, Louisiana 70112-1034 Tel. 504-586-1725 Fax 855-327-4815 PE 15 CONSULTING ENGINEERS STR 29 SERVICE CORRIDOR PT JL, DL TS DRAWN BY: TS 2016-08-19 100% CD TS R DESCRIPTION R R ESCALATORS "E" GROUP 1,2,3 GROUP 4,5,6 TS PT 2 ALTERNATE #1: ALL WORK ASSOCIATED WITH MEETING ROOMS 242-245 STR 28 WS STR 30 STR 32 STR 31 2 E-3.1 WS TS TS 238 235 BALCONY 239 240 236 241 NEW DIMMING SYSTEM POWER CONTROL EQUIPMENT FOR MEETING ROOMS 242-245 242 237 2 1 (TYPICAL) PHASE II - 2ND FLOOR - LIGHTING PUBLIC SAFETY PE 9 DRAPE ROOM P&D TEC. SHOP WOOD STORAGE EMPLOYEE LUNCH ROOM SUBSTATION 6 STAIR 12 PHASE I ARCHIVES WS HOSE ROOM STAIR 11 WS PHASE II KEY PLAN SO B216 WS SO B21D RIVERSIDE PANTRY R SO B214 SO B213 Mechanical Room Below VIDEO ROOM 1/16"= 1'-0" SO B212 WS WS SO B211 WS WS WS WS R R PT R FE 7 STR 7 ELEVATOR STORAGE PT SUBSTATION 3 PT STAIR 10 SUBSTATION 5 IN PLANT SUBSTATION 1 STAIR 15 ESCALATORS B-2 REAR GROUP 1,2 PE 8 R STR 19 R ESCALATORS B-1 REAR GROUP 1,2 SERVICE CORRIDOR STAIR 8 STAIR 9 Roof ELEC SUBSTATION 2 F&B WAREHOUSE D SHOP 2016-08-19 INV. STORAGE SUBSTATION 19 TRUSS PASSAGEWAY C TRUSS PASSAGEWAY B FE 5&6 TRUSS PASSAGEWAY South Public Truss A F & B SMALLWARES STORAGE STR 16 TEC. FE 29 E DATE PHASE III CELL SITE FE 30 STAIR 63 North Public Truss F SUBSTATION 20 STAIR 62 CARPET STORAGE SHIPPING & RECIEVING STAIR 59 STAIR 56 SUBSTATION 21 PROJECT NO. FE 28 CARP. SHOP ANNEX STAIR 58 G TRUSS Dishwasher SUBSTATION 7 OFFICE SO B201 Off SO B202 STAIR 38 SERVICE CORRIDOR SUBSTATION 22 EXEC SOUS CHEF PE 4 WS WS PANTRY 20 WS WS WS WS WS WS SUB STATION 13 28 WS Office R R R Freezer SUB 14 STA TIO Cooler TEC. OFFICE Freezer ICE ROOM GREEN ROOM NORTH 260 SUBSTATION 4 SUBSTATION 12 PE 22 WS STR 4A PT WS WS PT WS STR 4B STR 3A PE 2 ESCALATORS "B" GROUP 1,2,3 OPEN TO BELOW PE 15 WS STR 27 WS PE 17 PT STR 25 R F&B BANQUET OFFICE FE 16 OFFICE R Offices Green Room SHEET NO. STAIR PLUMBING STORAGE 55 GREEN ROOM SOUTH H.V.A.C STORAGE Football Cooler STR 3B Green Room Production 23 SUBSTATION WS STAIR 37 STR 29 SERVICE CORRIDOR STR 42 WS F&B SHIPPING & RECEIVING 19 & 20 WS J N R R 2016.026 I2 Cooler SERVICE CORRIDOR OPEN TO BELOW R I1 H Cooler KITCHEN II Frezzer WS ESCALATORS "A" GROUP 1,2,3 STAIR 57 SUBSTATION Cooler STEWARDING OFFICE ice FE 01 E2.1 SERVICE CORRIDOR PE 13 TS TS PROJECT NAME: TS 260 WS STR 2A STR 2B R WS R STR 20 WS ESCALATORS "D" GROUP 1,2,3 GROUP 4,5,6 FE 1 WS STR 1A STR 1A 261 STAIR 36 WS PT WS STR 22 Atrium Bridge R PE 14 R R ESCALATORS "E" GROUP 1,2,3 GROUP 4,5,6 R ESC. PW GROUP 1,2 STR 26 WS 262 STAIR 54 STAIR 44 ICE ROOM 277 PT SUBSTATION 24 FE 21 PT STR 28 STR 30 STR 31 ESCALATOR S "G" GROUP 1,2,3 STR 32 STAIR 55 STAIR 35 STR 23 R STAIR 49 WS PE 13 FE 27 R F&B V.I.P PROP ROOM 277 PT BALCONY ESCALATOR S "H" GROUP 1,2,3 GROUP 4,5,6 PT STAIR 34 STAIR 45 STAIR 47 F&B 299 PANTRY R R STAIR 51 ESCALATO RS GROUP 1,2,3 "I" GROUP 4,5,6 GROUP 7,8,9 STAIR 46 PE 23 29 PE 24 STAIR 50 SUBSTATION STAIR 48 STAIR 52 STAIR 53 ICE ROOM 299 PE 25 F&B PROP E2.1 ROOM 1"=400'-0" PE 26 STAIR 54 FIRE WATER TANK 376,700 Gals. OF SHEETS 2ND FLOOR PLAN - LIGHTING TS STR 23 THIS SHEET: TS 900 CONVENTION CENTER BLVD. NEW ORLEANS, LOUISIANA 70130 TS NEW ORLEANS ERNEST N. MORIAL CONVENTION CENTER PHASE II MEETING ROOM LIGHTING PANEL RETROFIT 3 (TYPICAL) 4 E-3.2 2 OF LOUISIA N JEFFERY LAMBERT NEW DIMMING SYSTEM POWER CONTROL EQUIPMENT FOR MEETING ROOMS 348-354 License No. 37172 FE O NEW WALL TOUCHSCREEN LIGHTING CONTROL STATION INSTALLED AT THE LOCATION OF EXISTING SLIDER STATION. INSTALL NEW WIRING TO NEW DIMMING SYSTEM EQUIPMENT RACK. REUSE EXISTING CONDUIT AS APPLICABLE. SEE WIRING DIAGRAMS AND INSTALLATION DETAILS. TE TA A NEW DIMMER RACKS AND RELAY PANELS AT LOCATION OF EXISTING DIMMER PANELS. RECONNECT EXISTING LIGHTING CIRCUITS TO NEW DIMMER RACK. REWORK AND/OR EXTEND CIRCUIT (CONDUIT AND WIRING) AS REQUIRED PER NEC TO RECONNECT CIRCUITS TO NEW DIMMER RACKS. SEE DETAILS ON SHEETS E4.1-E4.3. PR 3 SERVICE CORRIDOR E-3.2 R 2 REUSE ALL EXISTING MEETING ROOM LIGHTING CIRCUITS AS APPLICABLE. MODIFY, REWORK AND/OR REPLACE CIRCUIT CONDUIT AND WIRING AS REQUIRED PER NEC TO MAKE NEW CONNECTIONS. 5 EE 3. REPLACE ANY BURNED-OUT LAMPS IN MEETING ROOMS THAT NEW DIMMING SYSTEM IS BEING INSTALLED. DIMMING SYSTEM NETWORK PORT AT THE LOCATION OF EXISTING DIMMING SYSTEM PORTABLE PLUG-IN OUTLET. RUN CAT5 CABLE FROM NETWORK PORT TO ETHERNET SWITCH AT DIMMING SYSTEM EQUIPMENT RACK IN ELECTRICAL ROOM. REUSE EXISTING CONDUIT AS APPLICABLE. SEE WIRING DIAGRAMS AND INSTALLATION DETAILS. S 2. 1 THE PHRASE "MEETING ROOMS" USED IN THE DRAWINGS REFERS TO THE MEETING ROOMS IN WHICH NEW DIMMING SYSTEMS ARE BEING INSTALLED IN THIS CONTRACT. 2 SS IO N AL ENG IN BY 1. NEW DIMMING SYSTEM POWER CONTROL EQUIPMENT FOR MEETING ROOMS 355-357 SHEET REFERENCE NOTES SEAL SHEET GENERAL NOTES 357 352 356 354 353 TS TS TS REV. TS PE 15 351 FE 16 TS 334 343 350 345 344 909 Poydras Street, Suite 2150 New Orleans, Louisiana 70112-1034 Tel. 504-586-1725 Fax 855-327-4815 PE 17 CONSULTING ENGINEERS 333 JL, DL TS DRAWN BY: TS 2016-08-19 100% CD TS DATE TS DESCRIPTION CHECKED BY: JL 355 1 TS TS TS TS 2 2 STR 28 STR 30 TS 3 (TYPICAL) TS TS TS TS 346 3 347 348 E-3.2 TS TS TS TS TS TS 337 335 336 338 NEW DIMMING SYSTEM POWER CONTROL EQUIPMENT FOR MEETING ROOMS 342,344-347 342 339 340 341 2 1 (TYPICAL) PHASE II - 3RD FLOOR - LIGHTING 1/16"= 1'-0" KEY PLAN PHASE II PHASE III E D DATE 2016-08-19 C PE 15 PE 17 19 & 20 FE 16 FE 01 E2.2 THIS SHEET: STR 22 349 ESCALATORS "D" GROUP 1,2,3 GROUP 4,5,6 PE 14 ESCALATORS "E" GROUP 1,2,3 GROUP 4,5,6 FE 27 PROJECT NO. FE 21 2016.026 ESC. PW GROUP 1,2 ESCALATOR S GROUP 1,2,3 "I" GROUP 4,5,6 GROUP 7,8,9 PE 25 PE 26 SHEET NO. E2.2 1"=400'-0" OF SHEETS 3RD FLOOR PLAN - LIGHTING E-3.2 NEW DIMMING SYSTEM POWER CONTROL EQUIPMENT FOR MEETING ROOMS 338-341,343 900 CONVENTION CENTER BLVD. NEW ORLEANS, LOUISIANA 70130 2 PROJECT NAME: PE 14 ESCALATORS "E" GROUP 1,2,3 GROUP 4,5,6 NEW ORLEANS ERNEST N. MORIAL CONVENTION CENTER PHASE II MEETING ROOM LIGHTING PANEL RETROFIT NEW DIMMING SYSTEM POWER CONTROL EQUIPMENT FOR MEETING ROOMS 333-337 ESCALATORS "D" GROUP 1,2,3 GROUP 4,5,6 TS E-3.2 SHEET REFERENCE NOTES NEW DIMMER RACKS AND RELAY PANELS AT LOCATION OF EXISTING DIMMER PANELS. RECONNECT EXISTING LIGHTING CIRCUITS TO NEW DIMMER RACK. REWORK AND/OR EXTEND CIRCUIT (CONDUIT AND WIRING) AS REQUIRED PER NEC TO RECONNECT CIRCUITS TO NEW DIMMER RACKS. SEE DETAILS ON SHEETS E4.1-E4.3. INSTALL NEW RECEPTACLE AT EACH NEW RACK LOCATION. CIRCUIT (2)#12, (1)#12G IN 3/4" C HOMERUN TO EXISTING PANEL IN THE SAME ELECTRICAL ROOM. INSTALL 120V, 20A/1P CIRCUIT BREAKER IN PANEL OR UTILIZE EXISTING SPARE TO PROTECT CIRCUIT. LABEL BREAKER APPROPRIATELY. R SEAL SS IO N AL ENG IN JL 5 FE CHECKED BY: LIGHTING RELAY PANELS. LOCATE AT EXISTING 277V DIMMING PANEL. SEE SHEETS E4.1-E4.3. License No. 37172 BY 4 N O T T DIMMING SYSTEM DIMMER MODULE RACK. LOCATE AT LOCATION OF EXISTING 120V DIMMING PANEL SEE SHEETS E4.1-E4.3. OF LOUISIA JEFFERY LAMBERT PR 3 DIMMING SYSTEM AUXILIARY EQUIPMENT RACK, WALL-MOUNTED. ADJUST LOCATION AND MOUNTING AS REQUIRED TO MAINTAIN REQUIRED CLEARANCES ABOUT EXISTING ELECTRICAL EQUIPMENT. SEE SHEETS E4.1-E4.3. TE TA A 2 S T EE 1 DM HLC 3 4 2 HLC T 3 DR 5 REV. HLC HLC DM JL, DL 5 DR DATE 2 1 DRAWN BY: 4 (ABOVE XFMR) 2016-08-19 100% CD DESCRIPTION T 1 ENLARGED ELECTRICAL 2ND FLOOR PLAN - MEETING ROOMS 235 - 241 1/4"= 1'-0" 02 E3.1 ENLARGED ELECTRICAL 2ND FLOOR PLAN - MEETING ROOMS 252 - 254 1/4"= 1'-0" 909 Poydras Street, Suite 2150 New Orleans, Louisiana 70112-1034 Tel. 504-586-1725 Fax 855-327-4815 01 E3.1 CONSULTING ENGINEERS T DM 3 T 2 3 DR 2 T (ABOVE XFMR) 4 5 PROJECT NAME: T T THIS SHEET: 5 T DM DATE 03 E3.1 ENLARGED ELECTRICAL 2ND FLOOR PLAN - MEETING ROOMS 255 - 257 1/4"= 1'-0" 04 E3.1 ENLARGED ELECTRICAL 2ND FLOOR PLAN - MEETING ROOMS 242 - 245 1/4"= 1'-0" 2016-08-19 PROJECT NO. 2016.026 SHEET NO. E3.1 OF SHEETS 2ND FLOOR - ENLARGED ELECTRICAL PLANS DR HLC HLC HLC HLC 900 CONVENTION CENTER BLVD. NEW ORLEANS, LOUISIANA 70130 4 T NEW ORLEANS ERNEST N. MORIAL CONVENTION CENTER PHASE II MEETING ROOM LIGHTING PANEL RETROFIT 1 SHEET REFERENCE NOTES 5 S DM 3 5 INSTALL NEW RECEPTACLE AT EACH NEW RACK LOCATION. CIRCUIT (2)#12, (1)#12G IN 3/4" C HOMERUN TO EXISTING PANEL IN THE SAME ELECTRICAL ROOM. INSTALL 120V, 20A/1P CIRCUIT BREAKER IN PANEL OR UTILIZE EXISTING SPARE TO PROTECT CIRCUIT. LABEL BREAKER APPROPRIATELY. IO N AL ENG IN 02 E3.2 1/4"= 1'-0" 909 Poydras Street, Suite 2150 New Orleans, Louisiana 70112-1034 Tel. 504-586-1725 Fax 855-327-4815 CONSULTING ENGINEERS REV. DATE 1/4"= 1'-0" ENLARGED ELECTRICAL 3RD FLOOR PLAN - MEETING ROOMS 338 - 341 DESCRIPTION ENLARGED ELECTRICAL 3RD FLOORPLAN - MEETING ROOMS 333 - 337 CHECKED BY: 1 JL, DL 1 HLC JL 2 HLC 01 E3.2 LIGHTING RELAY PANELS. LOCATE AT EXISTING 277V DIMMING PANEL. SEE SHEETS E4.1-E4.3. SS DRAWN BY: DR DM 4 FE 2016-08-19 100% CD 4 DIMMING SYSTEM DIMMER MODULE RACK. LOCATE AT LOCATION OF EXISTING 120V DIMMING PANEL SEE SHEETS E4.1-E4.3. 3 4 T 3 License No. 37172 O 5 JEFFERY LAMBERT PR T HLC N R DR DIMMING SYSTEM AUXILIARY EQUIPMENT RACK, WALL-MOUNTED. ADJUST LOCATION AND MOUNTING AS REQUIRED TO MAINTAIN REQUIRED CLEARANCES ABOUT EXISTING ELECTRICAL EQUIPMENT. SEE SHEETS E4.1-E4.3. SEAL 2 HLC OF LOUISIA BY 2 TE TA A T NEW DIMMER RACKS AND RELAY PANELS AT LOCATION OF EXISTING DIMMER PANELS. RECONNECT EXISTING LIGHTING CIRCUITS TO NEW DIMMER RACK. REWORK AND/OR EXTEND CIRCUIT (CONDUIT AND WIRING) AS REQUIRED PER NEC TO RECONNECT CIRCUITS TO NEW DIMMER RACKS. SEE DETAILS ON SHEETS E4.1-E4.3. EE 1 T T HLC HLC 5 DR 2 T (ABOVE XFMR) 2 DM HLC HLC T 4 1 T DM HLC 3 DR HLC 2 5 3 4 T DM 03 E3.2 ENLARGED ELECTRICAL 3RD FLOOR PLAN - MEETING ROOMS 342 - 347 1/4"= 1'-0" 04 E3.2 ENLARGED ELECTRICAL 3RD FLOOR PLAN - MEETING ROOMS 348 -354 1/4"= 1'-0" 05 E3.2 PROJECT NAME: 1 ENLARGED ELECTRICAL 3RD FLOOR PLAN - MEETING ROOMS 355 -357 1/4"= 1'-0" THIS SHEET: 5 4 DATE 2016-08-19 PROJECT NO. 2016.026 SHEET NO. E3.2 OF SHEETS 3RD FLOOR - ENLARGED ELECTRICAL PLANS DR 1 900 CONVENTION CENTER BLVD. NEW ORLEANS, LOUISIANA 70130 (ABOVE XFMR) NEW ORLEANS ERNEST N. MORIAL CONVENTION CENTER PHASE II MEETING ROOM LIGHTING PANEL RETROFIT 3 EXISTING 120V, 20A TRACK LIGHTING CIRCUITS UNISON PARADIGM P-TS7 TOUCHSCREEN CONTROL STATION (TYPICAL) 'HLC' UHLCD HLC STATION TS 'HLC' UHLCD HLC STATION TS 'HLC' UHLCD (5) FIRE ALARM UV BELDEN 8471, (1) #14 AWG. STRANDED WIRE (2) #16 AWG. STRANDED WIRES U BELDEN 8471, (1) #14 AWG. STRANDED WIRE UNISON (WITH +24V POWER) UNISON ETC SENSOR DIMMING RACK 225A 208Y/120V 3-PH 19" EIA, 12U WALL-MOUNT SWING FRAME NETWORK RACK. STEEL CONSTRUCTION WITH PAINTED BLACK FINISH. TO UPS ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 24 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS FACILITY NETWORK ETHERNET SWITCH PROVIDED AND INSTALLED BY OWNER. 5-BUTTON UH10005 STATION LOCATE ADJACENT RACK (TYPICAL) 02 E4.1 EXISTING 120V, 20A TRACK LIGHTING CIRCUITS 5-BUTTON UH10005 STATION LOCATE ADJACENT RACK (TYPICAL) TS TO UPS NEW DUPLEX RECEPTACLE, SURFACE MOUNTED ETC SENSOR DIMMING RACK 100A MLO 208Y/120V 3-PH WITH 120V, 20A ( 8 ) MODULES ( 16 ) CIRCUITS TS ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 12 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS SR3-12 RECONNECT EXISTING 480Y/277V 3-PH FEEDER 19" EIA, 12U WALL-MOUNT SWING FRAME NETWORK RACK. STEEL CONSTRUCTION WITH PAINTED BLACK FINISH. PATCH PANEL ERn-NET ETHERNET SWITCH ETHERNET SWITCH ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 16 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS FACILITY NETWORK ETHERNET SWITCH PROVIDED AND INSTALLED BY OWNER. TO UPS NEW DUPLEX RECEPTACLE, SURFACE MOUNTED ETC EBDK EMERGENCY BYPASS DETECTION KIT 1000 VA UPS APC SMT-1000-RMUS RECONNECT EXISTING 480Y/277V 3-PH EMERGENCY FEEDER ETC SENSOR DIMMING RACK 100A MLO 208Y/120V 3-PH WITH 120V, 20A ( 8 ) MODULES ( 16 ) CIRCUITS RECONNECT EXISTING 480Y/277V 3-PH FEEDER EXISTING 277V, 20A WALL MOUNTED INDIRECT LIGHTING CIRCUITS (EMERG.) UNISON ERN ETHERNET SWITCH WITH PoE 19" EIA, 12U WALL-MOUNT SWING FRAME NETWORK RACK. STEEL CONSTRUCTION WITH PAINTED BLACK FINISH. ERPA-24 ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 16 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS EQUIP RACK GROUND WIRE: #6 COPPER TO BUILDING GROUND RECONNECT EXISTING 208Y/120V 3-PH FEEDER FIRE ALARM CABLE IN 3/4" EMT. TIE INTO THE NEAREST SLC. ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 12 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS SR3-12 ETC ERN2 ENCLOSURE WITH PACP PARADIGM ARCHITECTURAL CONTROL PROCESSOR ERPA-24 EQUIP RACK GROUND WIRE: #6 COPPER TO BUILDING GROUND ERPA-12 DIMMING SYSTEM AUXILIARY EQUIPMENT RACK EXISTING 277V, 20A WALL MOUNTED INDIRECT LIGHTING CIRCUITS (EMERG.) UNISON ERN ETHERNET SWITCH WITH PoE RECONNECT EXISTING 208Y/120V 3-PH FEEDER R HLC STATION ERPA-12 1000 VA UPS APC SMT-1000-RMUS EE 'HLC' UHLCD TS FACILITY NETWORK ETHERNET SWITCH PROVIDED AND INSTALLED BY OWNER. EXISTING 277V, 20A LIGHTING CIRCUITS TS 'HLC' UHLCD ETHERNET SWITCH SEAL 'HLC' UHLCD HLC STATION ERn-NET ETHERNET SWITCH EXISTING 120V, 20A TRACK LIGHTING CIRCUITS HLC STATION EXISTING 277V, 20A LIGHTING CIRCUITS TS PATCH PANEL FIRE ALARM CABLE IN 3/4" EMT. TIE INTO THE NEAREST SLC. N.T.S. 'HLC' UHLCD ETC ERN2 ENCLOSURE WITH PACP PARADIGM ARCHITECTURAL CONTROL PROCESSOR RECONNECT EXISTING 480Y/277V 3-PH EMERGENCY FEEDER ETC EBDK EMERGENCY BYPASS DETECTION KIT DIMMING AND LIGHTING CONTROL SYSTEM SCHEMATIC - MEETING ROOMS 242-245 - ALTERNATE #1 UNISON PARADIGM P-TS7 TOUCHSCREEN CONTROL STATION (TYPICAL) HLC STATION DIMMING SYSTEM AUXILIARY EQUIPMENT RACK 5) ANY LOW-VOLTAGE WIRING THAT IS RUN WITHIN 4 FEET OF DRY-TYPE POWER TRANSFORMERS SHALL BE SHIELDED FOR THE ENTIRE RUN. ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 24 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS EQUIP RACK GROUND WIRE: #6 COPPER TO BUILDING GROUND FIRE ALARM CABLE IN 3/4" EMT. TIE INTO THE NEAREST SLC. N.T.S. TS EXISTING 277V, 20A WALL MOUNTED INDIRECT LIGHTING CIRCUITS (EMERG.) ERPA-24 RECONNECT EXISTING 208Y/120V 3-PH FEEDER DIMMING AND LIGHTING CONTROL SYSTEM SCHEMATIC - MEETING ROOMS 235-241 UNISON PARADIGM P-TS7 TOUCHSCREEN CONTROL STATION (TYPICAL) 1000 VA UPS APC SMT-1000-RMUS NEW DUPLEX RECEPTACLE, SURFACE MOUNTED RECONNECT EXISTING 480Y/277V 3-PH EMERGENCY FEEDER ETC EBDK EMERGENCY BYPASS DETECTION KIT 19" EIA, 12U WALL-MOUNT SWING FRAME NETWORK RACK. STEEL CONSTRUCTION WITH PAINTED BLACK FINISH. ETHERNET SWITCH TO UPS RECONNECT EXISTING 208Y/120V 3-PH FEEDER 01 E4.1 3.) ALL ETCNet RUNS SHALL BE CONTINUOUS. UNSPLICED RUNS LESS THAN 300 FEET (90 METERS). ALL NETWORK CONNECTIONS TO BE IEEE T568B. 4.) ALL CONDUCTORS SHALL BE COPPER. ERPA-24 EQUIP RACK GROUND WIRE: #6 COPPER TO BUILDING GROUND NEW DUPLEX RECEPTACLE, SURFACE MOUNTED RECONNECT EXISTING 480Y/277V 3-PH FEEDER ETC EBDK EMERGENCY BYPASS DETECTION KIT RECONNECT EXISTING 480Y/277V 3-PH EMERGENCY FEEDER FIRE ALARM CABLE IN 3/4" EMT. TIE INTO THE NEAREST SLC. DATE 2016-08-19 03 E4.1 DIMMING AND LIGHTING CONTROL SYSTEM SCHEMATIC - MEETING ROOMS 252-254 - ALTERNATE #2 N.T.S. 04 E4.1 DIMMING AND LIGHTING CONTROL SYSTEM SCHEMATIC - MEETING ROOMS 255-257 - ALTERNATE #3 N.T.S. PROJECT NO. 2016.026 SHEET NO. E4.1 OF SHEETS ELECTRICAL DETAILS 1000 VA UPS APC SMT-1000-RMUS 2.) TOTAL COMBINED LENGTH OF UNISON WIRING RUNS CANNOT EXCEED 1640 FEET (500 METERS). THIS SHEET: FACILITY NETWORK ETHERNET SWITCH PROVIDED AND INSTALLED BY OWNER. NOTES: CONSULTING ENGINEERS ETHERNET SWITCH DMX 1.) ALL CONTROL WIRING PROVIDED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. UNISON ERN ETHERNET SWITCH WITH PoE ERn-NET ETHERNET SWITCH IN CHECKED BY: PATCH PANEL IO N AL ENG JL, DL UNISON ERN ETHERNET SWITCH WITH PoE BELDEN 9729 SS DRAWN BY: EXISTING 277V, 20A WALL MOUNTED INDIRECT LIGHTING CIRCUITS (EMERG.) WITH 120V, 20A ( 16 ) MODULES ( 32 ) CIRCUITS D FE JL SR3-24 DIMMING SYSTEM AUXILIARY EQUIPMENT RACK ETC ERN2 ENCLOSURE WITH PACP PARADIGM ARCHITECTURAL CONTROL PROCESSOR RECONNECT EXISTING 480Y/277V 3-PH FEEDER ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 16 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS DATE ERn-NET ETHERNET SWITCH ERPA-24 909 Poydras Street, Suite 2150 New Orleans, Louisiana 70112-1034 Tel. 504-586-1725 Fax 855-327-4815 WITH 120V, 20A ( 24 ) MODULES ( 48 ) CIRCUITS ETCNet REV. ETC ERN2 ENCLOSURE WITH PACP PARADIGM ARCHITECTURAL CONTROL PROCESSOR TS BELDEN 1583A OR BELDEN 1212F BY ETC SENSOR DIMMING RACK 400A 208Y/120V 3-PH TS N (5) O ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 24 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS SR3-24 DIMMING SYSTEM AUXILIARY EQUIPMENT RACK 'HLC' UHLCD HLC STATION DESCRIPTION ERPA-24 PATCH PANEL N License No. 37172 TS PR TS OF LOUISIA JEFFERY LAMBERT HLC STATION TS TE TA A TS EXISTING 277V, 20A LIGHTING CIRCUITS BELDEN 1583A OR BELDEN 1212F (3) #16 AWG. STRANDED WIRES 900 CONVENTION CENTER BLVD. NEW ORLEANS, LOUISIANA 70130 TS F 2016-08-19 100% CD TS EXISTING 277V, 20A LIGHTING CIRCUITS EXISTING 120V, 20A TRACK LIGHTING CIRCUITS PROJECT NAME: TS 5-BUTTON UH10005 STATION LOCATE ADJACENT RACK (TYPICAL) S 5-BUTTON UH10005 STATION LOCATE ADJACENT RACK (TYPICAL) NEW ORLEANS ERNEST N. MORIAL CONVENTION CENTER PHASE II MEETING ROOM LIGHTING PANEL RETROFIT UNISON PARADIGM P-TS7 TOUCHSCREEN CONTROL STATION (TYPICAL) ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 16 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS 1000 VA UPS APC SMT-1000-RMUS TO UPS RECONNECT EXISTING 480Y/277V 3-PH EMERGENCY FEEDER ETC EBDK EMERGENCY BYPASS DETECTION KIT R JL CHECKED BY: DIMMING AND LIGHTING CONTROL SYSTEM SCHEMATIC - MEETING ROOMS 336-341 N.T.S. EXISTING 120V, 20A TRACK LIGHTING CIRCUITS TS 5-BUTTON UH10005 STATION LOCATE ADJACENT RACK (TYPICAL) EXISTING 277V, 20A LIGHTING CIRCUITS TS TS TS ETC SENSOR DIMMING RACK 225A 208Y/120V 3-PH PATCH PANEL ERn-NET ETHERNET SWITCH ETHERNET SWITCH 1000 VA UPS APC SMT-1000-RMUS TO UPS NEW DUPLEX RECEPTACLE, SURFACE MOUNTED WITH 120V, 20A ( 20 ) MODULES ( 40 ) CIRCUITS RECONNECT EXISTING 480Y/277V 3-PH FEEDER EXISTING 277V, 20A LIGHTING CIRCUITS TS TS 19" EIA, 12U WALL-MOUNT SWING FRAME NETWORK RACK. STEEL CONSTRUCTION WITH PAINTED BLACK FINISH. TS PATCH PANEL ERn-NET ETHERNET SWITCH ETHERNET SWITCH FACILITY NETWORK ETHERNET SWITCH PROVIDED AND INSTALLED BY OWNER. ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 24 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS TO UPS NEW DUPLEX RECEPTACLE, SURFACE MOUNTED ETC EBDK EMERGENCY BYPASS DETECTION KIT 1000 VA UPS APC SMT-1000-RMUS RECONNECT EXISTING 480Y/277V 3-PH EMERGENCY FEEDER ETC SENSOR DIMMING RACK 400A 208Y/120V 3-PH WITH 120V, 20A ( 32 ) MODULES ( 64 ) CIRCUITS RECONNECT EXISTING 480Y/277V 3-PH FEEDER 19" EIA, 12U WALL-MOUNT SWING FRAME NETWORK RACK. STEEL CONSTRUCTION WITH PAINTED BLACK FINISH. PATCH PANEL ERn-NET ETHERNET SWITCH ETHERNET SWITCH FACILITY NETWORK ETHERNET SWITCH PROVIDED AND INSTALLED BY OWNER. ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 24 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS TO UPS NEW DUPLEX RECEPTACLE, SURFACE MOUNTED ETC EBDK EMERGENCY BYPASS DETECTION KIT 1000 VA UPS APC SMT-1000-RMUS RECONNECT EXISTING 480Y/277V 3-PH EMERGENCY FEEDER ETC SENSOR DIMMING RACK 225A 208Y/120V 3-PH WITH 120V, 20A ( 16 ) MODULES ( 32 ) CIRCUITS RECONNECT EXISTING 480Y/277V 3-PH FEEDER EXISTING 277V, 20A WALL MOUNTED INDIRECT LIGHTING CIRCUITS (EMERG.) UNISON ERN ETHERNET SWITCH WITH PoE 19" EIA, 12U WALL-MOUNT SWING FRAME NETWORK RACK. STEEL CONSTRUCTION WITH PAINTED BLACK FINISH. ERPA-24 ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 16 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS EQUIP RACK GROUND WIRE: #6 COPPER TO BUILDING GROUND RECONNECT EXISTING 208Y/120V 3-PH FEEDER FIRE ALARM CABLE IN 3/4" EMT. TIE INTO THE NEAREST SLC. ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 12 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS SR3-24 ETC ERN2 ENCLOSURE WITH PACP PARADIGM ARCHITECTURAL CONTROL PROCESSOR ERPA-24 EQUIP RACK GROUND WIRE: #6 COPPER TO BUILDING GROUND ERPA-12 DIMMING SYSTEM AUXILIARY EQUIPMENT RACK EXISTING 277V, 20A WALL MOUNTED INDIRECT LIGHTING CIRCUITS (EMERG.) UNISON ERN ETHERNET SWITCH WITH PoE RECONNECT EXISTING 208Y/120V 3-PH FEEDER FIRE ALARM CABLE IN 3/4" EMT. TIE INTO THE NEAREST SLC. ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 24 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS SR3-48 HLC STATION TS ERPA-24 ETC ERN2 ENCLOSURE WITH PACP PARADIGM ARCHITECTURAL CONTROL PROCESSOR ERPA-24 EQUIP RACK GROUND WIRE: #6 COPPER TO BUILDING GROUND TS EXISTING 277V, 20A LIGHTING CIRCUITS 'HLC' UHLCD HLC STATION DIMMING SYSTEM AUXILIARY EQUIPMENT RACK EXISTING 277V, 20A WALL MOUNTED INDIRECT LIGHTING CIRCUITS (EMERG.) UNISON ERN ETHERNET SWITCH WITH PoE RECONNECT EXISTING 208Y/120V 3-PH FEEDER TS ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 24 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS SR3-24 ETC ERN2 ENCLOSURE WITH PACP PARADIGM ARCHITECTURAL CONTROL PROCESSOR FACILITY NETWORK ETHERNET SWITCH PROVIDED AND INSTALLED BY OWNER. TS EXISTING 120V, 20A TRACK LIGHTING CIRCUITS HLC STATION 'HLC' UHLCD ERPA-24 DIMMING SYSTEM AUXILIARY EQUIPMENT RACK 5-BUTTON UH10005 STATION LOCATE ADJACENT RACK (TYPICAL) 'HLC' UHLCD HLC STATION 'HLC' UHLCD HLC STATION TS EXISTING 120V, 20A TRACK LIGHTING CIRCUITS 'HLC' UHLCD TS TS UNISON PARADIGM P-TS7 TOUCHSCREEN CONTROL STATION (TYPICAL) ETC EBDK EMERGENCY BYPASS DETECTION KIT RECONNECT EXISTING 480Y/277V 3-PH EMERGENCY FEEDER FIRE ALARM CABLE IN 3/4" EMT. TIE INTO THE NEAREST SLC. NEW ORLEANS ERNEST N. MORIAL CONVENTION CENTER PHASE II MEETING ROOM LIGHTING PANEL RETROFIT UNISON PARADIGM P-TS7 TOUCHSCREEN CONTROL STATION (TYPICAL) 'HLC' UHLCD TS FIRE ALARM CABLE IN 3/4" EMT. TIE INTO THE NEAREST SLC. PROJECT NAME: 5-BUTTON UH10005 STATION LOCATE ADJACENT RACK (TYPICAL) HLC STATION TS RECONNECT EXISTING 480Y/277V 3-PH EMERGENCY FEEDER ETC EBDK EMERGENCY BYPASS DETECTION KIT DIMMING AND LIGHTING CONTROL SYSTEM SCHEMATIC - MEETING ROOMS 333-337 UNISON PARADIGM P-TS7 TOUCHSCREEN CONTROL STATION (TYPICAL) IN 3.) ALL ETCNet RUNS SHALL BE CONTINUOUS. UNSPLICED RUNS LESS THAN 300 FEET (90 METERS). ALL NETWORK CONNECTIONS TO BE IEEE T568B. 4.) ALL CONDUCTORS SHALL BE COPPER. ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 12 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS FIRE ALARM CABLE IN 3/4" EMT. TIE INTO THE NEAREST SLC. 02 E42 IO N AL ENG 2.) TOTAL COMBINED LENGTH OF UNISON WIRING RUNS CANNOT EXCEED 1640 FEET (500 METERS). EXISTING 277V, 20A WALL MOUNTED INDIRECT LIGHTING CIRCUITS (EMERG.) ERPA-12 RECONNECT EXISTING 208Y/120V 3-PH FEEDER N.T.S. SS DMX BELDEN 9729 5) ANY LOW-VOLTAGE WIRING THAT IS RUN WITHIN 4 FEET OF DRY-TYPE POWER TRANSFORMERS SHALL BE SHIELDED FOR THE ENTIRE RUN. EQUIP RACK GROUND WIRE: #6 COPPER TO BUILDING GROUND NEW DUPLEX RECEPTACLE, SURFACE MOUNTED RECONNECT EXISTING 208Y/120V 3-PH FEEDER 01 E4.2 FACILITY NETWORK ETHERNET SWITCH PROVIDED AND INSTALLED BY OWNER. FE 1.) ALL CONTROL WIRING PROVIDED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. RECONNECT EXISTING 480Y/277V 3-PH FEEDER 19" EIA, 12U WALL-MOUNT SWING FRAME NETWORK RACK. STEEL CONSTRUCTION WITH PAINTED BLACK FINISH. ETHERNET SWITCH ETCNet NOTES: UNISON ERN ETHERNET SWITCH WITH PoE ERn-NET ETHERNET SWITCH ERPA-24 EQUIP RACK GROUND WIRE: #6 COPPER TO BUILDING GROUND NEW DUPLEX RECEPTACLE, SURFACE MOUNTED PATCH PANEL License No. 37172 (5) JL, DL 1000 VA UPS APC SMT-1000-RMUS WITH 120V, 20A ( 18 ) MODULES ( 36 ) CIRCUITS D JEFFERY LAMBERT DRAWN BY: 19" EIA, 12U WALL-MOUNT SWING FRAME NETWORK RACK. STEEL CONSTRUCTION WITH PAINTED BLACK FINISH. ETHERNET SWITCH ETC SENSOR DIMMING RACK 225A 208Y/120V 3-PH BELDEN 1583A OR BELDEN 1212F N DATE 03 E4.2 DIMMING AND LIGHTING CONTROL SYSTEM SCHEMATIC - MEETING ROOMS 342-347 N.T.S. 04 E4.2 DIMMING AND LIGHTING CONTROL SYSTEM SCHEMATIC - MEETING ROOMS 348-354 N.T.S. 05 E4.2 DIMMING AND LIGHTING CONTROL SYSTEM SCHEMATIC - MEETING ROOMS 355-357 N.T.S. 2016-08-19 PROJECT NO. 2016.026 SHEET NO. E4.2 OF SHEETS ELECTRICAL DETAILS UNISON ERN ETHERNET SWITCH WITH PoE ERn-NET ETHERNET SWITCH TO UPS EXISTING 277V, 20A WALL MOUNTED INDIRECT LIGHTING CIRCUITS (EMERG.) ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 16 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS SR3-24 ETC ERN2 ENCLOSURE WITH PACP PARADIGM ARCHITECTURAL CONTROL PROCESSOR N UNISON OF LOUISIA THIS SHEET: PATCH PANEL ERPA-24 DIMMING SYSTEM AUXILIARY EQUIPMENT RACK RECONNECT EXISTING 480Y/277V 3-PH FEEDER BELDEN 8471, (1) #14 AWG. STRANDED WIRE TE TA O WITH 120V, 20A ( 16 ) MODULES ( 32 ) CIRCUITS U UNISON (WITH +24V POWER) PR ETC SENSOR DIMMING RACK 225A 208Y/120V 3-PH ETC ERN2 ENCLOSURE WITH PACP PARADIGM ARCHITECTURAL CONTROL PROCESSOR TS ETC ECHO RELAY PANEL 100A MLO 480Y/277V 3-PH WITH ( 20 ) 120-277V, 20A/1P DMX CONTROLLED RELAYS SR3-24 DIMMING SYSTEM AUXILIARY EQUIPMENT RACK FACILITY NETWORK ETHERNET SWITCH PROVIDED AND INSTALLED BY OWNER. TS ERPA-24 BELDEN 8471, (1) #14 AWG. STRANDED WIRE (2) #16 AWG. STRANDED WIRES 909 Poydras Street, Suite 2150 New Orleans, Louisiana 70112-1034 Tel. 504-586-1725 Fax 855-327-4815 TS 'HLC' UHLCD HLC STATION UV 900 CONVENTION CENTER BLVD. NEW ORLEANS, LOUISIANA 70130 'HLC' UHLCD HLC STATION TS CONSULTING ENGINEERS TS TS FIRE ALARM BY TS EXISTING 277V, 20A LIGHTING CIRCUITS (5) A TS EXISTING 277V, 20A LIGHTING CIRCUITS BELDEN 1583A OR BELDEN 1212F (3) #16 AWG. STRANDED WIRES F DATE TS HLC STATION EE 'HLC' UHLCD HLC STATION S 'HLC' UHLCD EXISTING 120V, 20A TRACK LIGHTING CIRCUITS 2016-08-19 100% CD EXISTING 120V, 20A TRACK LIGHTING CIRCUITS 5-BUTTON UH10005 STATION LOCATE ADJACENT RACK (TYPICAL) SEAL UNISON PARADIGM P-TS7 TOUCHSCREEN CONTROL STATION (TYPICAL) DESCRIPTION 5-BUTTON UH10005 STATION LOCATE ADJACENT RACK (TYPICAL) REV. UNISON PARADIGM P-TS7 TOUCHSCREEN CONTROL STATION (TYPICAL) SHEET GENERAL NOTES THREE TABS (SCREENS) DATE/TIME TURN ON/OFF 50% OF ALL THE CEILING FLUORESCENT LIGHT FIXTURE LAMPS OFF UP-LAMPS OFF c) DOWN-LAMPS ON d) DOWN-LAMPS OFF DEFAULT/HOME SCREEN 2. CEILING FLUORESCENTS: 2 BUTTONS ON - OFF b) CONTROLS (TURNS ON/OFF) 50% OF ALL THE CEILING FLUORESCENT LIGHT FIXTURES. SCREEN #2 (CLIENT SCREEN) a) b) CONTROL OF ALL ZONES IN IMMEDIATE MEETING ROOM CEILING FLUORESCENTS: 3 BUTTONS · BUTTON '50%' · BUTTON '100%' · BUTTON 'OFF' e) Home Fri Dec 30, 2016 Admin User 50% OF CEILING FLUOR FIXTURE LAMPS 100% OF CEILING FLUOR FIXTURE LAMPS CEILING FLUOR FIXTURES OFF WALL FLUORESCENTS: 2 BUTTONS (MAINTAINED STATE) PER WALL ROW PRESS ONCE UP-ON R PRESS AGAIN UP-OFF 09:00 am · BUTTON 'DOWN' PRESS ONCE DOWN-ON PRESS AGAIN DOWN-OFF Track Lights-1 TWO SLIDERS PER ROW OF TRACK (ONE FOR EACH CIRCUIT) #1 #2 #3 Track Lights-2 #4 #1A #2A #3A f) Overhead Lights #4A 50% TURN ON 50% CEILING FLUOR LAMPS 100% TURN ON 100% CEILING FLUOR LAMPS OFF TURN OFF CEILING FLUOR LAMPS FOR EACH LINEAR ROW *NOTE: MODIFY/EXTEND EXISTING CIRCUIT CONDUITS AND WIRING AS REQUIRED PER NEC TO MAKE CONNECTIONS TO NEW DIMMING RACK AND RELAY PANELS. 01 E4.1 CHECKED BY: a) Wall-1 POWER RISER DIAGRAM - TYPICAL EXISTING DIMMER RACK Wall-2 UP N.T.S. UP DOWN DOWN JL, DL SCREEN #1 - SCREEN #1 (DEFAULT/HOME SCREEN) · BUTTON 'UP' EXISTING XFMR IN DRAWN BY: 1. RECONNECT EXISTING 480Y/277V EMERGENCY FEEDER TO NEW RELAY PANEL* NEW DIMMER RACK AND RELAY PANELS IN PLACE OF EXISTING DIMMER PANELS. VERIFY CIRCUIT BREAKER AND DIMMER MODULE RATINGS & QUANTITIES AND PROVIDE NEW IN NEW EQUIPMENT MATCHING EXISTING (TYP). IO N AL E NG PRESS ONCE -TURN ON UP LAMPS PRESS AGAIN-TURN OFF UP LAMPS TRACK LIGHTS: 2 SLIDERS PER ROW · · · · 3. SLIDER #1 0-100% (TRACK-1 CKT. #1) SLIDER #1A 0-100% (TRACK-1 CKT. #2) SLIDER #2 0-100% (TRACK-2 CKT. #1) SLIDER #2A 0-100% (TRACK-2 CKT. #2) SCREEN #3 (ADMIN SCREEN) a) PASSWORD PROTECTED b) EVERYTHING ON SCREEN 2 AS WELL AS COMBINE/UNCOMBINE FEATURE TO ALLOW USER TO CONTROL ALL MEETING ROOMS SERVED BY THE DIMMING PANEL TOGETHER AS ONE. · BUTTON 'COMBINE' 909 Poydras Street, Suite 2150 New Orleans, Louisiana 70112-1034 Tel. 504-586-1725 Fax 855-327-4815 NEW 277V EMERG. LIGHTING RELAY PANEL b) SS 2016-08-19 100% CD NEW 120V DIMMING RACK NEW 277V LIGHTING RELAY PANEL UP-LAMPS ON FE CONSULTING ENGINEERS ETC ECHO a) DESCRIPTION ETC ECHO EACH LINEAR ROW OF WALL-MOUNT FLUORESCENTS HAVE UP-LAMPS AND DOWN-LAMPS SWITCHED SEPARATE CREATING FOUR SWITCHED STATES PER LINEAR ROW: LIGHTING CONTROL STATION TOUCHSCREENS TO EXISTING FEEDER SOURCES ETC SR3 License No. 37172 DATE RECONNECT EXISTING 208Y/120V FEEDER* OFF REV. WIREWAY c) JEFFERY LAMBERT JL RECONNECT EXISTING 480Y/277V FEEDER TO RELAY PANEL* 50% ON 100% ON OF LOUISIA N EE 3. a) b) TE TA A ON CEILING FLUORESCENT LIGHT FIXTURES HAVE LAMPS SWITCHED IN TWO GROUPS FOR (BI-LEVEL SWITCHING) WHICH CREATES THREE SWITCHED STATES PER MEETING ROOM: SEAL 09:00 am O EXISTING OUTGOING 120V LIGHTING BRANCH CIRCUITS WIREWAY EXISTING SAFETY SWITCH Fri Dec 30, 2016 Admin PR RECONNECT EXISTING LIGHTING BRANCH CIRCUITS TO NEW DIMMING RACK AND RELAY PANELS* EXISTING OUTGOING 120V LIGHTING BRANCH CIRCUITS User EACH SECTION OF TRACK HAS TWO ZONES WHICH ARE DIMMABLE. 2. BY Home 1. S MEETING ROOM LIGHTING ZONES PRESS ONCE TO COMBINE CONTROL OF MEETING ROOMS · BUTTON 'UNCOMBINE' PRESS ONCE -TURN ON DOWN LAMPS PRESS ONCE TO UNCOMBINE CONTROL OF MEETING ROOMS PRESS AGAIN-TURN OFF DOWN LAMPS BRIGHTNESS LEVEL 0% 75% 50% 100% 0% SCREEN #2 - EXISTING 480Y/277V FEEDER TO BE DISCONNECTED TO ALLOW FOR DEMOLITION. #1 #2 #3 Track Lights-2 #4 #1A #2A #3A Combine #4A Overhead Lights PRESS ONCE - COMBINE CONTROL OF ALL MEETING ROOMS ON THE ASSOCIATED DIMMING RACK AND RELAY PANELS SO THAT THE IMMEDIATE TOUCHSCREEN CONTROLS THEM TOGETHER AS ONE PRESS AGAIN- UNCOMBINE CONTROL 50% EXISTING 120V DIMMER RACK 100% OFF EXISTING 277V EMERGENCY DIMMER RACK EXISTING DIMMER PANELS TO BE REMOVED (TYP.) 0% EXISTING XFMR 75% 50% 100% SCREEN #3 0% - 75% 50% 100% Wall-1 Wall-2 UP UP DOWN DOWN ADMIN SCREEN (PASSWORD PROTECTED) NOTE: SCREEN DETAIL IS GENERIC IN NATURE AND SHOWN FOR REFERENCE IN ORDER TO SHOW BASIC LIGHTING CONTROL CONCEPTS. COORDINATE WITH OWNER FOR EXACT CONTROL REQUIREMENTS AND GRAPHICS. *NOTE: REMOVE EXISTING CIRCUIT CONDUIT AND WIRING AS REQUIRED TO ALLOW FOR CONNECTIONS TO NEW EQUIPMENT. 01 E4.1 DEMOLITION POWER RISER DIAGRAM - TYPICAL EXISTING DIMMER RACK N.T.S. 1 E4.3 MEETING ROOM TOUCHSCREEN LIGHTING CONTROLLER DETAIL DATE N.T.S. 2016-08-19 PROJECT NO. 2016.026 SHEET NO. E4.3 OF SHEETS ELECTRICAL DETAILS Track Lights-1 09:00 am THIS SHEET: EXISTING 480Y/277V EMERGENCY FEEDER TO BE DISCONNECTED TO ALLOW FOR DEMOLITION* Fri Dec 30, 2016 Admin User 900 CONVENTION CENTER BLVD. NEW ORLEANS, LOUISIANA 70130 EXISTING 277V DIMMER RACK Home NEW ORLEANS ERNEST N. MORIAL CONVENTION CENTER PHASE II MEETING ROOM LIGHTING PANEL RETROFIT TO EXISTING FEEDER SOURCES EXISTING 208Y/120V FEEDER TO BE DISCONNECTED TO ALLOW FOR DEMOLITION* EXISTING SAFETY SWITCH CLIENT SCREEN EXISTING OUTGOING 277V LIGHTING BRANCH CIRCUITS PROJECT NAME: DISCONNECT EXISTING LIGHTING BRANCH CIRCUITS TO ALLOW FOR DEMOLITION* EXISTING OUTGOING 120V LIGHTING BRANCH CIRCUITS 75% 50% 100%