January 2012 Remote Output Driver Modules, Models ATM-L and ATM-R Installation Manual FM APPROVED A UTC Fire & Security Company Remote-Output Driver Modules REMOTE-OUTPUT DRIVER MODULES, MODELS ATM-L AND ATM-R 1-1 DESCRIPTION The Model ATM-L Annunciator Driver Module, P/N 76-200004-032, provides Kidde intelligent systems with up to 32 programmable outputs for remote LEDs, along with six (6) system-level LEDs and five (5) systemlevel functional switches. The system-level LEDs correspond to the following general conditions: • Module Power/Lockout • Alarm • Pre-Alarm • Alarm Silence • Supervisory • Trouble The functional switches provide for the following operator intervention: • System Reset • Event Acknowledgment • Alarm Silence • Fire Drill • Lamp Test All ATM-Ls will not respond to local commands from functional switches for ten (10) seconds after a key is pressed on the keypad/display of the control unit. A flashing module-power LED will signify this lockout condition. The Model ATM-R Relay Driver Module, P/N 76-200005-032, provides the system with up to 32 programmable outputs for remote relays. The ATM-L and -R Modules communicate with the control unit via an external RS-485 communications circuit, with the most remote module capable of being located up to 4,000 feet from the control unit. Up to 31 ATM-Ls and ATM-Rs, in any combination but subject to a limitation of 16 for each type of driver module, can be connected in a daisy-chained loop to the RS-485 communications circuit. No “t-tapping” is allowed in the communications circuit. Both modules can be powered from the intelligent control unit's power supply, or from an external, regulated and power-limited power supply Listed for use with fire protective signaling systems, depending upon the total load of the remote outputs. A typical external power supply is Kidde Fire Systems P/N 297106. Note: Refer to the appropriate control unit design, installation and maintenance manual for auxiliary power output ratings. When using any other Listed power supply to power either the ATM-L or ATM-R, ensure that the power supply has a means to isolate the common-negative power line from earth ground to prevent system ground faults. Both the ATM-L and ATM-R have an initiating circuit labeled “PS FLT” to monitor a normally-closed power supply fault contact. Refer to Figures 2, 3 and 4. The ATM-L and ATM-R modules are supported by Kidde Intelligent control units, including the ARIESTM, ARIES NET LinkTM and PEGAsysTM control unit with firmware version 81.0 or higher. January 2012 1 06-236179-002 Remote-Output Drive Modules 2-1 INSTALLATION ! CAUTION When performing installations, route field wiring away from sharp projections, corners and internal components. The ATM-L and ATM-R Modules are intended for mounting inside a UL-864/ULC S527 Listed enclosure with no other electronics. Use the mounting hardware (hex spacers and screws) provided with the module. Any switches installed with the ATM-L that are used for silencing must be either a key lock type with the key removable only in the Normal position, or located inside a locked panel, or arranged to provide equivalent protection against unauthorized use. Wire routing and installation methods are to be in accordance with the annunciator installation instructions. Note: Maintain a minimum 1/2" clearance around the ATM-L and ATM-R modules when installed in the UL-864/ ULC S527 Listed enclosure. Select an enclosure with dimensions of at least 6" H x 9" W x 2" D. Use consecutive LED outputs, starting from LED Output No. 1. There can be no gaps in the output-LED sequence. Cut the next-higher supervised-output termination jumper after the last LED output that is being used. Refer to Figure 2 for details. The LEDs and functional switches for the ATM-L must be installed in conduit within 20 feet of the UL-864/ULC S527 Listed enclosure. The relays for the ATM-R must be installed in conduit within 20 feet of the UL-864/ULC S527 Listed enclosure. Use consecutive relay outputs, starting from Relay Output No. 1. There can be no gaps in the output-relay sequence. Cut the next-higher supervised-output termination jumper after the last relay output that is being used. Refer to Figure 3 for details. See Figure 1 for module mounting dimensions. 2-1.1 Electrical Table 1. Electrical Specifications Operating Voltage: 16.0 to 28.8 Vdc (non-resettable) Standby Current: 0.045 A Max. Output Activation: Common Positive; Individual-output negative pull downs ATM-L Outputs: LED 0.015 A maximum (28.8 Vdc) Audible Appliance 0.015 A maximum (28.8 Vdc) ATM-R Outputs: 0.080 A maximum (28.8 Vdc) Total Alarm Current: Depends upon output load. Must be calculated for each application. Wire Sizes: RS-485 Communications #14 - #18 AWG, (twisted, shielded) 24 Vdc Power #14 - #18 AWG (as required) LEDs #18 AWG (or as required by annunciator) Functional Switches #18 AWG Audible Appliance #18 AWG (or as required by annunciator) Power-Supply Supv.Initiating Circuit #14 - #18 AWG Relays #14 - #18 AWG 06-236179-002 2 January 2012 Remote-Output Driver Modules Refer to the wiring diagrams for point-to-point connections. S2 S1 ATM-L/R Out B Out A In B In A W1 4.625 LK32 LK16 LK14 LK12 LK10 +24 V Com PS Flt Earth Gnd 5.000 LK17 LK8 LK6 A B 0.188 1.375 Trouble Sup. Sil. Out Pre Alm Alarm Pwr On Lamp Test Com Ack Reset Silence Drill LK4 LK2 LK15 16 15 LK13 14 13 12 LK11 11 10 9 LK9 8 7 LK7 6 5 4 LK5 3 2 LK3 1 LK31 LK30 LK29 LK28 LK27 LK26 LK25 LK24 LK23 LK22 LK21 LK20 LK19 LK18 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 LK1 5.175 8.000 Note: Maintain a minumum one-half (1/2) inch clearance around ATM-L and ATM-R Modules when installed in mounting enclosure. Figure 1. Module Mounting Dimensions 3-1 POWER SUPPLY CALCULATION 3-1.1 ATM-L Power Supply Calculation ATM-Ls will operate down to 16.0 Vdc. If the nominal power supply output is 24 Vdc, the minimum system voltage after 24 hours of battery operation is 20.4 Vdc. Therefore, the maximum voltage drop to any ATM-L is 4.4 Vdc. Calculate the total ATM-L current and maximum power-line resistance using the following procedure. 1. Count the total number of output LEDs from all ATM-Ls that will be powered from the control unit power supply. Output LED current: # LEDs x 0.012 = ____A 2. Count the total number of ATM-Ls. ATM-L current: # ATM-Ls x 0.045 = ____A 3. Count the total number of ATM-Ls whose status lights will be powered from the control unit power supply. Status LED current: #ATM-Ls x 0.072 = ____A 4. Add 1 + 2 + 3 for total current from the control unit power supply ____A 5. Calculate maximum allowable resistance. Divide 4.4 Vdc by total current (Step 4) ____ohms January 2012 3 06-236179-002 Remote-Output Drive Modules Example: • ATM-L # 1 has 20 point- or group-specific output LEDs. • ATM-L #2 has 15 point- or group-specific output LEDs. • ATM-L #3 has 8 point- or group-specific output LEDs. • All ATM-Ls are utilizing the system status lights. • All outputs will be powered by a Kidde intelligent control unit power supply. • Total LEDs = 43 • Total output LED current = 43 x 0.012 = 0.516 A • Total ATM-Ls = 3 • Total ATM-L current = 3 x 0.045 = 0.135 A • Total ATM-Ls status lights • Total Status LED current = 3 x 0.072 = 0.216 A • Total Current = 0.867 A • Maximum Power-Line Resistance = 4.4 V/0.867 A = 5.1 ohms 3-1.2 ATM-R Power Supply Calculation ATM-Rs will also operate down to 16.0 Vdc. If the nominal power supply output is 24 Vdc, the minimum system voltage after 24 hours of battery operation is 20.4 Vdc. Use UL Listed/Recognized relays with a nominal 24 Vdc rating, and with an operating voltage range between 18.0 and 30.0 Vdc. Refer to the manufacturer supplied information for listed operating voltage range. Relay coil currents vary widely from about 15 mA to 80 mA. Refer to the manufacturer’s data sheet for the coil current of the specific relay being utilized in the application. Calculate the total ATM-R current and maximum power-line resistance using the following procedure. 1. Count total number of output relays from all ATM-Rs that will be powered from the control unit power supply. Output relay current: # relays x current/relay = ____A 2. Count the total number of ATM-Rs. ATM-R current: # ATM-Rs x 0.045 = ____A 3. Add 1 + 2 for total current from the control unit power supply ____A 4. Calculate maximum allowable resistance. Use the minimum relay operating voltage of 18 Vdc in this calculation. Divide 2.4 Vdc by total current (Step 3) _____ohms Example: • An ATM-R has 15 relay outputs. Each relay has a coil current of 25 mA. • All outputs will be powered by a Kidde intelligent control unit power supply. • Total Relays = 15 • Total output Relay current = 15 x 0.025 = 0.375 A • Total ATM-Rs = 1 • Total ATM-R current = 1 x 0.045 = 0.045 A • Total Current = 0.420 A • Maximum Power-Line Resistance 2.4 V/0.420A = 5.7 ohms 06-236179-002 4 January 2012 Remote-Output Driver Modules 4-1 REGISTRATION The ATM-L and ATM-R Modules are automatically registered into the intelligent system when they are uploaded into the system configuration software. They may also be registered manually, but without point or group-specific device mapping, by means of the keypad on the control unit. The manual registration procedure is documented in the appropriate control unit design, installation and maintenance manual. January 2012 5 06-236179-002 06-236179-002 L S 6 5 A B L L 6 Supervised Circuit Power-Limited Circuit L Figure 2. ATM-L Wiring Diagram 10 k, 0.5 W EOL Resistor Typ for each N.O. Input Switch N.O. Drill Switch (Press "Alm Sil" Switch to cancel Drill) N.O. Alm Sil Switch N.O. Reset Switch Note: Use consecutive LED outputs, starting from LED Output No. 1. There can be no gaps in the output LED sequence. Cut the next-higher supervised output termination jumper after the last LED output used. LED 1 LED 2 LED 4 LED 5 LED 6 LED 7 LED 8 LED 9 LED 10 LED 11 LED 12 LED 13 LED 14 LED 15 LED 16 Power LED L L N.O. Acknowledge Switch N.O. Lamp-Test Switch S Maximum 15 ma per LED Note: LED 17 LED 18 LED 19 LED 20 LED 21 LED 22 LED 23 LED 24 LED 25 LED 26 LED 27 LED 28 LED 29 LED 30 LED 31 LED 32 LED 3 L LK18 L Alarm LED S LK1 LK19 S L LK2 LK4 LK21 LK23 LK25 LK27 LK29 LK31 32 LK30 31 30 LK28 29 28 27 LK26 26 25 LK24 24 23 22 LK22 21 20 LK20 19 18 17 LK32 Cut the jumper following the last supervised LED output (e.g., if last LED output is 15, cut Jumper LK16). Output Supervision Termination Jumper L Lamp Test Com Ack Reset Silence Drill 16 15 LK13 14 13 12 LK11 11 10 9 LK9 8 7 LK7 6 5 4 LK5 3 2 LK3 1 LK15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 F Pre-Alm LED Trouble Sup. Sil. Out Pre Alm Alarm Pwr On LK6 LK8 LK10 LK12 LK14 LK16 LK17 ATM-L Address B C D E Alm. Sil. LED Local Audible Appliance (mimics control unit sonalert, 15 ma maximum) L A B ATM-L S1 Install 20 K, 0.25 W Resistor from +24 V to AlarmSilence Output when Alarm-Silence Output not used. W1 +24 V Com PS Flt Earth Gnd Out B Out A In B In A S2 (See Table) Address Switch S1 Reset Switch S2 S1 Switch Setting 1 2 3 4 5 6 7 8 9 A ATM-L Address Table L Supervisory LED L S S Trouble LED L (Jumper "PS Flt" to "Com" when not used.). Note: Locate local audible applicance in conduit in the same room within 20 feet of the ATM-L. Normally-closed, trouble contact from Remote Power Supply P/N 297106 Non-resettable 24 VDC from Control Unit Power Supply Module (Aux. Pwr. Output) S RS-485 Communications from Control Unit RS-485 Communications to next ATM-L/R, RDCM, or RDM S Install if ATM-L is last assembly in RS-485 communications loop from CCM Display PCB. Remove if ATM-L is intermediate assembly in RS-485 loop. RS-485 Termination Jumper W1 Remote-Output Drive Modules January 2012 January 2012 L S 6 5 A B L L 7 L S Power-Limited Circuit Supervised Circuit +24 V Com PS Flt Out B Out A In B In A S1 ATM-R W1 S2 LK2 LK4 LK6 LK8 LK10 LK12 LK14 LK16 (See Table) LK1 16 15 LK13 14 13 12 LK11 11 10 9 LK9 8 7 LK7 6 5 4 LK5 3 2 LK3 1 LK15 LK17 Address Switch S1 LK19 LK21 LK23 LK25 LK27 LK29 LK31 LK18 32 LK30 31 30 LK28 29 28 27 LK26 26 25 LK24 24 23 22 LK22 21 20 LK20 19 18 17 LK32 ATM-R Address B C D E F 0 L Use consecutive relay outputs, starting from Relay Output No. 1. There can be no gaps in the output relay sequence. Cut the next-higher supervised output termination jumper after the last relay output used. Note: S Maximum 80 mA per relay. L Note: S Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Relay 7 Relay 8 Relay 9 Relay 10 Relay 11 Relay 12 Relay 13 Relay 14 Relay 15 Relay 16 Relay 17 Relay 18 Relay 19 Relay 20 Relay 21 Relay 22 Relay 23 Relay 24 Relay 25 Relay 26 Relay 27 Relay 28 Relay 29 Relay 30 Relay 31 Relay 32 Cut the jumper following the last supervised relay output (e.g., if last relay output is 15, cut Jumper LK16). Output Supervision Termination Jumper 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 S1 Switch Setting 1 2 3 4 5 6 7 8 9 A ATM-R Address Table Figure 3. ATM-R Wiring Diagram - Common Power Supply for Module and Outputs Normally-closed, trouble contact from Remote Power Supply P/N 297106 (Jumper "PS Flt" to "Com" when not used.) Non-Resettable 24 Vdc from Control Unit Power Supply (Aux. Pwr. Output) S RS-485 Communications from Control Unit RS-485 Communications to next ATM-L/R, RDCM, or RDM S Reset Switch S2 Install if ATM-R is last assembly in RS-485 communications loop from CCM Display PCB. Remove if ATM-R is intermediate assembly in RS-485 loop. RS-485 Termination Jumper W1 Remote-Output Driver Modules 06-236179-002 06-236179-002 8 Power-Limited Circuit L S L (+) (-) 28 VDC (-) (+) C BA W1 L (-) Trouble Batt2 Batt1 Load2 Load1 (+) (-) (+) (-) (+) (-) (+) LK1 16 15 LK13 14 13 12 LK11 11 10 9 LK9 8 7 LK7 6 5 4 LK5 3 2 LK3 1 LK15 LK17 COM N/O/C LK2 LK4 LK6 LK8 LK10 LK12 LK14 LK16 W3 (Set W3 to N.C. Position) (Refer to Installation Sheet 77.103) Power Supply, P/N 297106 DS3 DS1 DS2 C BA GND BATT BATT FLT OPR TBL W2 S ATM-R S1 S L LK19 LK21 LK23 LK25 LK27 LK29 LK31 LK18 32 LK30 31 30 LK28 29 28 27 LK26 26 25 LK24 24 23 22 LK22 21 20 LK20 19 18 17 LK32 ATM-R Address B C D E F 0 L Use consecutive relay outputs, starting from Relay Output No. 1. There can be no gaps in the output relay sequence. Cut the next-higher supervised output termination jumper after the last relay output used. Note: S Maximum 80 mA per relay. L Note: S Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Relay 7 Relay 8 Relay 9 Relay 10 Relay 11 Relay 12 Relay 13 Relay 14 Relay 15 Relay 16 Relay 17 Relay 18 Relay 19 Relay 20 Relay 21 Relay 22 Relay 23 Relay 24 Relay 25 Relay 26 Relay 27 Relay 28 Relay 29 Relay 30 Relay 31 Relay 32 Cut the jumper following the last supervised relay output (e.g., if last relay output is 15, cut Jumper LK16). Output Supervision Termination Jumper 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 S1 Switch Setting 1 2 3 4 5 6 7 8 9 A ATM-R Address Table Figure 4. ATM-R Wiring Diagram - Separate Power Supplies for Module and Outputs AC ON W1 +24 V Com PS Flt Earth Gnd Out B Out A In B In A S2 (See Table) Address Switch S1 Reset Switch S2 N.C. Supervised Circuit L 6 5 A B L N.O. S Non- Resettable 24 Vdc from Power Supply S RS-485 Communications from Control Unit RS-485 Communications to next ATM-L/R, RDCM, or RDM S Install if ATM-R is last assembly in RS-485 communications loop from CCM Display PCB. Remove if ATM-R is intermediate assembly in RS-485 loop. RS-485 Termination Jumper W1 Remote-Output Drive Modules January 2012 9 SW1 JP3 B A TB5 B JK2 PRINT PORT JK1 DISP PORT PC PORT JK3 TO DISPLAY JP4 TB4 A SOUNDER 1 SOUNDER 2 0V DISPLAY 24V 5V SKT1 TB6 TO DISPLAY 5V 0V PLG2 TB3 N N C O C JK4 NC C NO B A SYS GND W2 W3 W5 AC OUT 1 2 L N L L N G AC IN DS1 W4 W6 S2 S1 15A FUSE AUX1 AUX2 RET 24V RET 24V BAT W1 RET 24V S3 (HARD RESET) INSTALL W4 2 1 2 1 DC IN2 24V GREEN LED DC IN1 2 4V INSTALL W3 N SW2 PEGAsys Control Unit PLG1 JP2 JP1 TB2 N N N N O C C O C C TB1 JK5 SKT2 SW3 REMOVE W2 0V Twisted, Shielded Wire to ATM-Ls. (Total circuit length 4,000 FT. MAX.) NOTE: W2 I/O PORT RX/TX PORT RET DISPLAY PCB (on CCM) EARTH FAULT SUPPLY FAULT SPV RET TB1 24 V RET RET TBL RL Y RS485 SHARE 24 V 1 2 3 4 5 6 7 8 CCM MOTHER BOARD SPV V 24 January 2012 SYSTEM PO WER USE VR1 TO ADJUST CONTRAST. USE VR2 TO ADJUST BRIGHTNESS. W1 VR1 JK1 JK2 W1: A B +24 V Com PS Flt Lamp Test Com Ack Reset Silence Drill LK2 LK4 LK1 16 15 LK13 14 13 12 LK11 11 10 9 LK9 8 7 LK7 6 5 4 LK5 3 2 LK3 1 LK17 LK15 RS-485 Communications to ATM-L. Remove from CCM'S Display and intermediate ATM-Ls. Install on last ATM-L only. Trouble Sup. Sil. Out Pre Alm Alarm Pwr On LK6 LK8 LK10 LK12 LK14 LK16 See Table 1 S1 LK19 LK21 LK23 LK25 LK27 LK29 LK31 LK18 32 31 30 LK28 29 28 27 LK26 26 25 LK24 24 23 22 LK22 21 20 LK20 19 18 17 LK30 LK32 W1 Trouble Sup. Sil. Out Pre Alm Alarm Pwr On 16 16 Maximum Quantity (on RS-485 Circuit) A B +24 V Com PS Flt S2 S1 Use consecutive LED outputs, starting from LED Output No. 1, for each ATM-L/R. There can be no gaps in the output sequences. Cut the next-higher supervised output termination jumper after the last output used. Lamp Test Com Ack Reset Silence Drill LK18 LK20 LK22 LK24 LK26 LK28 LK30 LK32 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 1 2 3 4 5 6 7 8 9 A B C D E F 0 Table 1 LK19 LK21 LK23 LK25 LK27 LK29 LK31 ATM-L/R Address LK1 LK13 16 15 14 13 12 LK11 11 10 9 LK9 8 7 LK7 6 5 4 LK5 3 2 LK3 1 LK17 LK15 S1 Switch Setting LK2 LK4 LK6 LK8 LK10 LK12 LK14 LK16 See Table 1 ATM-L INSTALL W1 Out B Out A In B In A Any combination of ATM-Ls and ATM-Rs that does not exceed 16 can be used on the RS-485 circuit. There can be a maximum of 31 RS-485 assemblies in the system, including RDMs and RDCMs. Notes: ATM-L ATM-R Driver Type Figure 5. Typical PEGAsys Control Unit/ATM-L/R Wiring Diagram Note: 1.5A Maximum for Each Auxiliary Power Output. W1 S2 ATM-L REMOVE W1 Out B Out A In B In A Jumper Note: 24 Vdc from Power Supply (Install W3 for Non-Resettable Power) VR2 Remote-Output Driver Modules 1 2 34 06-236179-002 10 NO NC C NO NC C J10 Relay 2 Relay 3 Trouble Style 4 - - TB13 Batt Out TB3 S2 + + SLC J3 J3 PSU J12 Release 1 TB11 1 2 3 4 Release 2 6 1 1 2 3 4 J5 TB7 1 2 3 4 Combo 1 8 3 9 4 TB6 0 5 1 2 3 4 Combo 2 SCROLL SILENCE J8 RS-232 A TB14 Install Jumper when Remote Power Supply not used. TB5 W1 Trouble Sup. Sil. Out Pre Alm Alarm Pwr On Lamp Test Com Ack Reset Silence Drill LK2 LK4 LK6 LK8 LK10 LK12 LK14 LK16 LK1 16 15 LK13 14 13 12 LK11 11 10 9 LK9 8 7 LK7 6 5 4 LK5 3 2 LK3 1 LK17 LK15 W1 A B +24 V Com PS Flt S1 Trouble Sup. Sil. Out Pre Alm Alarm Pwr On Lamp Test Com Ack Reset Silence Drill ATM-L Install W1 Out B Out A In B In A S2 LK2 LK4 LK6 LK8 LK10 LK12 LK14 LK16 LK1 16 15 LK13 14 13 12 LK11 11 10 9 LK9 8 7 LK7 6 5 4 LK5 3 2 LK3 1 LK15 LK17 Leave shield wire floating at last annunciator driver. Do not connect wire for shield to the earth-ground screw in remote enclosure. Trim shield wire as much as possible. Connect wires for shields together at each intermediate annunciator driver. Do not connect wires for shields to the earth-ground screw in remote enclosures. A B +24 V Com PS Flt S1 ATM-L Remove W1 Out B Out A In B In A S2 Figure 6. Typical ARIES Control Unit/ATM-L/R Wiring Diagram 7 2 SYSTEM RESET SYSTEM ACKNOWLEDGE Aux 24 VDC TB2 Configure Auxiliary Power for Continuous Output TB12 1 2 3 4 120 240 ARIES Control Unit SILENCE PRE-ALARM RS-232 B USB A SUPERVISORY USB B SYSTEM TROUBLE J6 ALARM RS 485 SLC TB15 AC POWER 4 3 2 1 4 3 2 1 NAC 2 TB1 Connect wire for shield to earth-ground screw in upper-edge of PCB. 1 2 3 4 06-236179-002 Relay 1 NAC 1 NO NC C NO NC C 1 2 3 4 Maximum Length: 4,000 Ft. (Twisted, Shielded, Low-Capacitance Wire) LK19 LK21 LK23 LK25 LK27 LK29 LK31 LK19 LK21 LK23 LK25 LK27 LK29 LK31 LK18 LK20 LK22 LK24 LK26 LK28 LK30 LK32 LK18 LK20 LK22 LK24 LK26 LK28 LK30 LK32 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 Remote-Output Drive Modules AC IN N L January 2012 Remote-Output Driver Modules S2 . Installation Notes: Out B Out A In B In A Non-Resettable 24 VDC from Control Unit Power Supply (Aux. Pwr. Output) 1. RS-485 circuits must be terminated at the first and last device in the circuit. Set termination resistor SW2 (located on the back of the Keypad/Display and RDCM boards) to the ON (terminated) position by moving the tiny white lever. S Out B Out A In B In A W1 +24 V Com PS Flt Earth Gnd L +24 V Com PS Flt ATM-R Communications Circuit (J8 ) 24 VDC Per RS-485 Standard Twisted, shielded, low-capacitance, fire-alarm wire 4,000 Ft. per twisted pair Max. Wire Length: S2 Out B Out A In B In A Out B Out A In B In A W1 Non-Resettable 24 VDC from Control Unit Power Supply (Aux. Pwr. Output) S +24 V Com PS Flt Earth Gnd L +24 V Com PS Flt A B Trouble Sup. Sil. Out Pre Alm Alarm Pwr On ATM-L IN-B OUT-A OUT-B J8 INOUT+ OUT- J4 RDCM NORM ISOL IN- OUT- IN+ OUT+ NORM ISOL IN- SLC 1 OUT- IN+ OUT+ SLC 2 J20 J19 J8 For Dual Channel Installation IN+ J4 24 VDC PWR On the R-LAM, the location of these 2 connectors is reversed; i.e., its J6 (PWR IN) 24 Vdc connector is at the top, and its J8 (RS485) bus connector is at the bottom. RS485 IN-A USB HOST USB DEVICE Figure 7. Wiring Diagram for ARIES NETLink/ATM-L/R Voltage: Current: Recommended Wire: IN-B OUT-A RS485 TB1 NC RELAY 1 NO C IN-A TB2 TB3 NC RELAY 3 NO C J8 S P TBL RELAY NC C NO RS232 B TB3 Installation Notes: 2. If ATM-R or ATM-L is last device, insert W1 jumper to terminate. If not last device, remove jumper. J9 BACKPLANE COMMS OUT NC RELAY 2 NO C OUT-B RS232 A J8 J10 24 VDC IN J2 PMU COMMS OUT Main-Controller Board (MCB) ARIES NET Link J17 J18 R-NAC 1 OUT+ IN+ IN- January 2012 OUT- ISOL NORM J16 J15 NAC 1 R-NAC 2 OUT+ IN+ IN- OUT- ISOL NORM OUT+ IN+ IN- NAC 2 OUT- ISOL NORM OUT+ IN+ IN- OUT- ISOL NORM 11 06-236179-002 Remote-Output Drive Modules THIS PAGE INTENTIONALLY LEFT BLANK. 06-236179-002 12 January 2012 Kidde is a registered trademark of Kidde-Fenwal, Inc. PEGAsys, ARIES and ARIES NETLink are trademarks of Kidde-Fenwal, Inc. A UTC Fire & Security Company 400 Main Street Ashland, MA 01721 Ph: 508.881.2000 Fax: 508.881.8920 www.kiddefiresystems.com These instructions do not purport to cover all the details or variations in the equipment described, nor do they provide for every possible contingency to be met in connection with installation, operation and maintenance. All specifications subject to change without notice. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to KIDDE-FENWAL INC., Ashland, Masssachusetts 06-236179-002 Rev. BC ©2012 Kidde-Fenwal, Inc.