SCHEDULE OF WORK Name of work: Supply of 1 x 1000 KVA, 6KV/415 V, 3-phase, 50 Hz Indoor Type, Cast Resin, Dry Transformer for augmentation of the existing Substation of IACS (Phase-III), Jadavpur, Kolkata. Sl. No. Item of Work Rate Qty (Rs. 1. Supply of 1000 KVA, 3-phase, 50 Hz, 6KV/ 415Volt self cooled (Air-Natural) Cast resin, dry type, step down, double wound copper, indoor distribution transformer having Delta primary and Star secondary, with Dyn11 vector group connection having neutral brought out on star side with matching percentage impedance, voltage ratio and vector group etc (details of existing machine data attached) i/c provision for terminating cables on LT & HV side, fitted with adequate size Cable End Boxes and provided with temperature protection devices and all other standard fittings etc. as 1 No per attached specifications complete. Note: 1. 2. 3. 4. 5. 6. 7. Unit P) Amount (Rs. P) each The rate should be inclusive of all taxes, transportation charges including transit insurance, loading & unloading at site etc as per enclosed ANNEXURE. Nothing extra will be paid in addition to the quoted rate. The firm should mention the model no, make and shall submit a printed literature of the product with the technical bid positively. The vendor should sign on all pages of the tender document along with their company seal towards acceptance of all NIT conditions. Rates should be written in the relevant space of the schedule of works (on the basis of price derived from ANNEXURE) in figure and word both. 90% of the bill value will be made against successful delivery of materials at site at IACS, Jadavpur, Kolkata on physical verification. However, balance 10% will be kept as Security deposit with adjustment of EMD which will be paid after twelve months on satisfactory performance of the equipments. The security deposit may be accepted by performance bank Guarantee also, if opted for by the vendor. Guarantee certificate, users manual etc are required to be handed over to the user after successful commissioning of the system. Conditional/incomplete tenders or tender without EMD or EMD not in proper form shall be summarily rejected. Signature of bidder with seal Specification for Cast Resin dry type transformer 1 2 3 A-General Data Reference Rated KVA Rated Voltage 4 5 6 7 Rated Frequency Class of Insulation No of phases on the system % impedance 8 9 10 11 Double wound or Single wound Vector Group Winding Materials Taps Required 12 13 14 Tap change type Type of Cooling Neutral Terminal 15 Parallel Operation 16 17 18 19 Diagram requirement Reference Ambient temperature Temperature rise of windings above the ambient temperature Basic insulation level 20 Termination 1 2 3 B-constructional data Type of Installation Enclosure Protection Standard Fittings 4 Testing IS: 2026/1977 & IS: 11171/1985 1000 KVA HV Side: 6 KV MV Side: 415 volts 50 HZ Class “F” Three Phases 4.75% (the existing transformer is having impedance of 4.75%) Double wound Dyn11 Electrolytic Copper +5% to -10% in steps of 2.5% each on HV side for variation with Off circuit tap links Off-circuit tap link type Air Natural Neutral shall be brought out separately at the secondary side. Shall be suitable for parallel operation with the existing transformers of similar type & capacity Connection diagram plate is required 50 Deg C 90 Deg C (Hot Spot Temp.105 Deg. C above Ambt.) HV-60 KV (peak) HV-Cable end box for 1x3C.185Sq.mm Al/XLPE/Ar.11Kv.Cable LV-Cable end box for 6x3.5C.400Sq.mm Al/PVC/Ar.1.1Kv.Cable Indoor IP-23 (Indoor) 1) Rating & Technical plate 2) Earthing Terminals with lugs 3) 4Nos Flat, bi-directional rollers 4) Lifting lugs 5) Off circuit tapping links 6) HV termination-Cable end box 7) LV termination cable end box. 8) Door limiting switch 9) Marshalling box fitted with temperature scanner suitable for 230V A.C. 10) Vision window (panel) on HT side with toughen glass All Routine Tests as per IS 2026/1977 & IS 11171/1985 shall be conducted on transformer and Test Report shall be submitted before the delivery of the transformer. Nothing extra shall be paid on this account. Detailed Specification for Dry Type (Cast Resin) Distribution Transformer 1. SCOPE: i) These specifications cover the design, manufacture and delivery of dry type (Cast resin) distribution transformers with enclosures. ii) The dry type distribution transformer shall be complete with all the components and necessary accessories for the efficient and trouble free performance. The details of various parts have been indicated in general in these specifications. However, the parts not specified but required otherwise should form part of the equipment. 2. GENERAL: The average ambient temperature shall be taken as 50 degree Celsius. The transformers shall be suitable for installation in hot, humid monsoon area with seasonal dry, duty conditions at Kolkata. 3. DESIGN DETAILS i) Type: The Transformer shall be of indoor, three phase, Delta/Star connected (Dyn11), Air cooled, cast resin Dry type totally enclosed step down double copper wound distribution transformer. The transformer shall be as per IS: 2026/1977 & 11171 / 1985 with up to date amendments. ii) Frequency / HT voltage variation: a) Frequency: 50 HZ ± 3% b) HT Voltage: 6 KV +10% iii) Impendence: The impedance of the transformer shall be of such values, so that the transformers could be put to operate in parallel with the existing Transformers of similar type. iv) Temperature Rise: The temperature rise of the transformer and the ceiling air temperature, when tested at the rated KVA shall not exceed the following limit as per ISS: 2026 pt. II/77 as amended up to date: a) Winding: Average temperature rise as measured by increased resistance of winding connected between terminals 90°C. b) Hot spot: Temperature rise as measured shall be 105°C. above ambient v) Insulation: Insulation class for winding and bushings of transformers shall be as under as per IS: 2026 / 1977 with up to date amendments. vi) Test Voltage Withstand Nominal voltage Impulse withstand voltage 6 KV Not less than 60KV BIL Double the Power frequency withstand voltage 20 KV (rms) in HT side & 3 KV (rms) in LT side vii) Parallel Operation: All the transformers as per detailed specifications shall be capable of operating in parallel satisfactorily among themselves with an anticipated 25% unbalanced load. The transformer should have 4.75% of impedance on principal tap at rated KVA at 75 degree centigrade. TRANSFORMER CONSTRUCTION DETAILS: The transformer shall be glass fibre reinforced Epoxy insulated cast resin type. The features and construction detail of the transformer shall be in accordance with the requirement detailed herein. ENCLOSURES FOR EPOXY CAST RESIN TRANSFORMERS a. The epoxy cast resin transformer shall be housed in metal protective housing having a degree of protection of IP-23 with perforated/ louvers enclosure. The enclosure fabricated in two parts shall also accommodate cable terminations of 6 KV side. The sheet steel thickness of enclosure shall be at least 2.0mm with necessary reenforcement. b. The housing shall be provided with a door, which shall be inter-locked such that it should be possible to open the door only when power supply to the transformer is switched off. A suitable danger plate shall be provided on the door/ cable end box cover etc. c. The enclosure shall be provided with suitable lifting lugs and necessary hardware for mounting on the floor. d. Enclosure of the transformer should be openable on all sides except at marshalling box cable end box for getting necessary access of maintenance personnel. MOUNTING ARRANGEMENTS: For transformers, suitable 4 Nos. bidirectional rollers shall be provided with the body for fixing the transformer on foundation. These rollers shall be such that the bottom of the body is at a sufficient height above foundation for cleaning purpose. TEMPERATURE INDICATOR: a) Winding temperature indicator (WTI) scanner suitable for 230V. A.C. A device (temp. scanner) for measuring the hot spot temperature of the winding shall be provided. The accuracy class of winding temperature indicator shall be ± 2 deg. C or better. It shall comprise of the following devices/features. i) Temperature sensing element. ii) Suitable local indicating instrument with maximum reading pointer mounted. It shall have two potential free contacts, one for winding temperature high alarm and one for trip when permitted temperature is exceeded. EARTHING TERMINALS: a) Two earthing ends suitable for connecting 25mm x 5mm copper strip shall be provided at positions close to the two diagonally opposite bottom corner of body. These grounding terminals shall be suitable for bolted connection. b) i) The neutral terminal of solid earthed winding shall be brought to the ground level by MS grounding bar which shall be supported from the tank by epoxy insulators. ii) The end of grounding bar shall have two bolted neutral grounding terminals and necessary accessories for connecting to ground network through two copper strips. CORE: b) The core shall be constructed from high grade non-ageing cold rolled grain oriented (CRGO) silicon steel laminations and protected against corrosion by resin coat. c) The design of the magnetic circuit shall be such so as to avoid static discharges, development of short circuit paths within itself or to the earthed clamping structure and the production of flux component at right angles to the planes of laminations, which may cause local heating. d) Adequate number of core bandages shall be provided to ensure uniform compression of core lamination. The insulation of core clamp plates shall be able to withstand a power frequency voltage of 2 KV (rms) for one minute. e) Core and windings shall be capable of withstanding shocks during transport, installation, service and adequate provision shall be made to prevent movement of core and winding during these conditions. f) All steel sections used for supporting the core shall be thoroughly sand blasted after cutting, drilling and welding shall be hot dip galvanised /electro-galvanise. g) Adequate provision shall be provided for lifting core and winding assembly. Windings: a) The conductor shall be of electrolytic grade copper, free from scales & burrs. b) The winding shall be insulated with material of Class-“F” or better. c) Both the windings shall be encapsulated with epoxy cast resin under vacuum. d) The windings should be moisture proof and non-inflammable. NEUTRAL TERMINATION ARRANGEMENT: The neutral terminal bar shall be brought out on a bushing similar to phase terminals to form a 4 wire system for the 415 V. In addition to that; a parallel neutral connection from star point shall be brought out to connect to the ground by a copper flat of size 100mm x 12 mm. One CT is to be provided on neutral bus for providing earth fault protection. OFF CIRCUIT TAPPINGS The tapping shall be bolted link type from +5% to -10% in steps of 2.5% each on HV side for variation with Off circuit tap links with suitable arrangement for locked in position. PAINTING: All the surfaces to be painted shall be thoroughly cleaned from soiled/dirt coating by sand blusting. Exterior surfaces shall be given two coats of light coloured paint with good heat reflecting, corrosion and abrasion resisting characteristics as per relevant IS of approved shade. ACCESORRIES: The offer shall be inclusive of all the accessories as mentioned below. a) Winding temperature indicator with fan alarm and trip contacts. b) Rating plate c) Lifting lugs on the body d) Rollers & base with provision for skidding in any direction. e) One cable end box complete with cable lugs for XLPE cable of 185 sq. mm / 3 core on the HT side. f) LT side- 4 nos. required size of copper busbar size supported by ceiling mounted epoxy resin insulator with cable end box for accommodating 6 nos. 3-1/2 core 400 sq. mm Al. Conductor PVC armoured Cable g) Earthing terminals: 2 nos. TESTS on dry type Transformer: Routine tests of the transformer shall be completely carried out in factory in accordance with the IS: 11171 & 2026 and or any more tests, if considered necessary to ensure that all the equipments are in accordance with the specifications. IACS reserves the right to witness such tests. No extra payment will be made for such tests. Routine tests shall include, but shall not be limited to: a) Resistance measurement of all windings. b) Ratio tests for all sets of windings on each tap. c) Polarity and phase relation tests (Vector Group) d) No load (excitation) losses at rated voltage. e) Impedance and load losses at rated current. f) Exciting current at 100% and 110% of the rated voltage. g) Applied potential tests h) Induced potential tests. i) Insulation resistance test. j) Heat run test Copies of test certificates for the type tests & routine tests along with certified drawings as per ISS of transformer shall be furnished by the tenderer along with the transformer. Specification for Cast Resin Dry type Transformer (To be filled up by the bidder) 1 2 3 4 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Make Model No. Rated KVA Rated Voltage Rated Frequency Class of Insulation % impedance No of phases on the system Double wound or Single wound Vector Group Winding Materials Type of Tap setting: On load/Off load Tap setting on HT or LT side No. of Tap settings steps and % variations Type of Cooling Whether Neutral brought out separately at secondary side Whether suitable for Parallel Operation with the existing transformer of same type & capacity having % impedance of 4.75%. Diagram provided or not Reference Ambient temperature Temperature rise of windings ( above the ambient temperature) Regulation at rated output and 0.8 pf , 0.9 pf and unity pf mentioning % resistance and % reactance drop Impedance at rated KVA and at 75°C Exciting current with rated voltage & frequency No load losses at 75°C , rated voltage and frequency Total losses at 75°C, 0.8 pf and ½, ¾ and full rated KVA. Efficiency at 75°C, 0.8 pf and ½, ¾ and full rated KVA. Efficiency at 75°C, unity pf and ½, ¾ and full rated KVA. 26 27 28 29 30 31 32 33 34 35 36 37 38 Load at which maximum efficiency occurs in % of full load Maximum efficiency at % Type of installation (Indoor or Outdoor) Enclosure protection (IP) Enclosure sheet metal thickness Induced over voltage withstand test (twice rated voltage at 100 Hz for 1 min.) Separate source voltage withstand HV: test LV: Flux density HV: LV: Current density Core & coil Assy. Weight Total weight Whether the following standard fittings are provided : a. Rating and Technical plate b. Earthing terminals with lugs2 nos. c. 4 numbers flat , bi-directional rollers d. Lifting lugs e. Off circuit tapping links f. Winding temperature indicator (Scanner type with operating voltage of 240V) g. HV termination- Cable end box h. LV termination – Cable end box. i. Whether 2 nos. potential free contacts for high temperature alarm and trip provided j. Marshalling box fitted with WTI Scanner (230 V AC) k. Door limit switch Outline dimensions of the transformers a) Length (end to end ) b) Breadth (end to end) c) Height Note: Max overall dimension of the existing transformer is 2250 mm (W) including depth of cable end box at both sides x 1650 mm (L) x 1950 mm (H) wherein the size of the tank is 1200 (W) x 1650 (L) x 1950 mm (H). LT cable end box 700 mm (W) x 1000 mm (L) x 825 mm (H) from top of the tank. HT cable end box 300 mm (W) x 1000 mm (L) x 825 mm (H) from top of the tank. ANNEXURE-I Item No. 1 Description of item Basic Price (exclusive of all levies & charges) Central Excise duty in % only VAT/ CST in % only Packing, forwarding, transit insurance up to site i/c loading & unloading Other levies (if any) Unit price total (all inclusive) Supplying of 1000 KVA 3-phase 50 Hz self cooled (Air-Natural) Cast resin, dry type, step down, double wound copper, indoor distribution transformer having Delta primary and Star secondary designed for voltage ratio of 6 KV/415Volt, between phases at no-load, with Dyn11 vector group connection having neutral brought out on star side with matching percentage impedance, voltage ratio and vector group etc (details attached) i/c provision for connecting cable on HV & LT side, fitted with both side cable end boxes and provided with temperature protection devices and all other standard fittings etc. as per attached specifications complete. Signature of Bidder with seal