Integrated Magnetic Filter Transformer Design for Grid Connected

advertisement
Integrated Magnetic Filter Transformer
Design for Grid Connected Single Phase
PWM-VSI
A Project Report
Submitted in Partial Fulfilment of
Requirements for the Degree of
Master of Engineering
in
Electrical Engineering
By
D. Venkatramanan
Department of Electrical Engineering
Indian Institute of Science
Bangalore - 560 012
India
June 2010
Acknowledgements
I am grateful to my guide Dr. Vinod John, for giving me the opportunity to work with him
on a fascinating and challenging problem. I sincerely thank him for his timely suggestions,
brilliant ideas, remarkable patience and constant encouragement. The lively discussions that
I had had with him and the great deal of freedom that I had enjoyed during my work are
deeply acknowledged.
I consider myself fortunate for having been thought by Prof. V. Ramanarayanan. His hypnotic lectures made the subject exceedingly simple. I express my heartfelt gratitude to him
for all that I have learnt from him (including power electronics), his invaluable suggestions,
motivation and above all, for the excellent example he has set as a professor. He has throughout been a strong source of inspiration as a person.
I thank Prof. V. T. Ranganathan for his splendid course on Electric drives. He had given
me a broad perspective on closed loop control through his wonderful (patient) lectures.
I sincerely thank Prof. G. Narayanan and Prof. Udaya Kumar for their extraordinary lectures
on Pulse Width Modulation and Electromagnetics respectively.
It was a privilege for me to be associated with all of them.
I specially thank Anirban da for patiently helping at many critical junctures of my project
work. I also thank all other PhD students of the PEG group viz. Kamalesh Hatua, Amit
Jain, Shivaprasad, Deepankar De, AKP and Pavan Kumar Hari for maintaining an excellent
work culture in the lab and also for helping me in project.
I thank Anand, Manoj Modi, Shan (Reddy) of the Gang for all the technical and nontechnical engagements that we had had during our stay at IISc.
I also thank Vishnu, Tarak, Prakash, Raju, Hedyati Mohammad, Aneesa, Jim, Rajesh, Anil
das, Anil adapa, Srikanth Reddy for helping me in various ways and being very supportive
friends.
i
ii
Acknowledgements
Special thanks must go to Anand and Prakash for making the lab (Room 112) environment
amicable and conducive for learning.
I sincerely thank my father for extending his valuable support and encouragement throughout.
I thank Silvi madam for her kind help and support. I also extend my thanks to Mr D.
M. Channegowda and his team in the EE office for the smooth conduct of administrative
activities. I thank Mr.Ravi and his workshop team for their help during the project. I am
also grateful to IISc administration for providing a very good working environment overall.
Finally I would like to thank God Almighty for making everything go so smoothly.
Abstract
Background
Now a days, several governments and utilities worldwide promote renewable energy sources
such as Photovolaics (PV), Fuel cells, micro-turbines etc for distributed power generation
systems(DGPS), so as to deal with issues like rising prices of energy and environmental
concerns. DGPS are renewable energy sources linked up to the grid at the point of load.
This eliminates losses during transmission and distribution and also improves reliability of
the power supply. However, a DC/AC power converter and a filter are invariably required
for such an interconnection. The power quality of the grid interface is influenced by the
quality of the injected current and the filter here essentially brings down the distortion (in
the sinusoidal current and voltage waveforms) caused by the power converter.
The conventional way of interface is through a simple first order filter, which is bulky,
inefficient and cannot meet the regulatory requirements pertaining to interconnection of
harmonic loads to the grid. Higher order filters are becoming exceedingly popular as they
offer higher attenuation even at lower switching frequency for a similar filter size. Many a
times, a transformer would be necessary after the filter stage to enable grid interface. The
transformer provides galvanic isolation and an extra degree of freedom to adjust the output
voltage level to that of the grid.
Magnetic components often constitute a significant part of the overall size and cost of
the grid connected power system. Hence a compact and inexpensive design is desirable.
The present work is on design of an integrated filter-transformer structure where the
magnetic components of the higher order filter are integrated into the transformer. A three
winding transformer configuration is proposed for such an integration. The single compact
structure would now perform the functions of both the filter and the transformer. This work
iii
iv
Abstract
targets single phase applications and hence focus is laid on Proportional-Resonant (PR)
controllers for accurate AC reference tracking in closed loop control. The power converter is
being operated as a STATCOM and as an Active Front End Converter (AFEC) in the grid
interactive mode for performance evaluation.
Organisation of report
Introduction introduces the issues pertaining to grid interface, imparts relevant background knowledge and finally presents the goal of this work.
Transformer and Magnetic integration discusses about the proposed three winding
configuration for magnetic integration, principle of operation, winding structure, transfer
function analysis, transformer design, and leakage inductance evaluation.
Power circuit for grid interface, sensor and digital controller deals with the
hardware details of the power converter, non-isolated sensor cards and the FPGA based
digital controller; It also explains single phase grid interface scheme, starting procedure, and
digital control implementation.
Single phase closed loop control deals with all the essentials for closing the loop, single
phase resonant PLL design, PR controller design for current control, PI controller design for
DC bus voltage regulation and STATCOM/ AFEC operation of the power converter.
Results and conclusion reports various simulation and experimental results that are
used to verify the performances of integrated filter-transformer, PR/PI controllers, grid
connected power converter etc. and finally concludes the work based on the results.
Contents
Acknowledgements
i
Abstract
iii
List of Tables
viii
List of Figures
ix
1 Introduction
1
1.1
Current Scenario . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
1.1.1
Higher order filter design . . . . . . . . . . . . . . . . . . . . . . . . .
2
1.2
Prospects in existing interface scheme . . . . . . . . . . . . . . . . . . . . . .
4
1.3
Project Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
1.4
Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
2 Magnetic integration and Transformer design
8
2.1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
2.2
Proposed multi-winding transformer configuration . . . . . . . . . . . . . .
8
2.2.1
Winding attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
2.2.2
External capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
2.3
Equivalent circuit development . . . . . . . . . . . . . . . . . . . . . . . . .
12
2.4
Transfer function analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14
2.5
Core-type and Shell-type Transformers . . . . . . . . . . . . . . . . . . . . .
17
2.5.1
Core-type transformer . . . . . . . . . . . . . . . . . . . . . . . . . .
18
2.5.2
Shell type transformer . . . . . . . . . . . . . . . . . . . . . . . . . .
20
Three-winding filter-transformer design . . . . . . . . . . . . . . . . . . . . .
21
2.6
v
vi
Contents
2.6.1
2.7
First pass design procedure . . . . . . . . . . . . . . . . . . . . . . .
26
Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
27
3 Power circuit for grid interface, sensor and Digital controller
28
3.1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
28
3.2
Power Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
28
3.2.1
Power converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
28
3.2.2
PWM Technique . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
28
3.2.3
Power circuit and starting Procedure . . . . . . . . . . . . . . . . . .
32
Non-isolated Sensor circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33
3.3.1
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33
3.3.1.1
Voltage sensor . . . . . . . . . . . . . . . . . . . . . . . . .
33
3.3.1.2
Current sensor . . . . . . . . . . . . . . . . . . . . . . . . .
35
Digital controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36
3.4.1
FPGA board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36
3.4.2
ADC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
37
3.4.3
DAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
37
3.5
Experimental set-up with digital controller . . . . . . . . . . . . . . . . . . .
38
3.6
Digital implementation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
38
3.6.1
Base Values for Various Quantities . . . . . . . . . . . . . . . . . . .
39
3.6.2
Transfer function implementation . . . . . . . . . . . . . . . . . . . .
40
3.6.2.1
Low pass filter . . . . . . . . . . . . . . . . . . . . . . . . .
40
3.6.2.2
PI controller . . . . . . . . . . . . . . . . . . . . . . . . . .
40
3.6.2.3
PR controller . . . . . . . . . . . . . . . . . . . . . . . . . .
41
Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
3.3
3.4
3.7
4 Single phase closed loop control
42
4.1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
42
4.2
Grid interactive mode
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
42
4.3
Phase Locked Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
44
4.4
Resonant controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
51
4.4.1
Proof . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
52
4.4.2
Testing of resonant controller . . . . . . . . . . . . . . . . . . . . . .
53
vii
Contents
4.5
DC bus voltage determination . . . . . . . . . . . . . . . . . . . . . . . . . .
55
4.6
Overall control structure and strategy . . . . . . . . . . . . . . . . . . . . . .
56
4.6.1
Control strategy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
57
4.6.1.1
Feed-forward terms . . . . . . . . . . . . . . . . . . . . . . .
58
4.7
Current controller design . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
58
4.8
Voltage controller design . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
59
4.9
Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
60
5 Results and conclusion
61
5.1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
61
5.2
Frequency response characteristics . . . . . . . . . . . . . . . . . . . . . . . .
61
5.3
Standalone mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
65
5.4
Grid interactive mode
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
66
5.4.1
Operation as a two-winding transformer . . . . . . . . . . . . . . . .
66
5.4.2
Operation as a three-winding transformer
. . . . . . . . . . . . . . .
69
5.5
Harmonic analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
76
5.6
Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
81
References
83
List of Tables
2.1
Details of core-type test transformer
. . . . . . . . . . . . . . . . . . . . . .
18
2.2
Test results of core-type transformer . . . . . . . . . . . . . . . . . . . . . .
20
2.3
Design details of three winding shell-type test transformer . . . . . . . . . .
24
2.4
O.C test results of three winding shell-type transformer . . . . . . . . . . . .
25
2.5
S.C test results of three winding shell-type transformer . . . . . . . . . . . .
25
2.6
Three-winding transformer and its equivalent circuit parameters . . . . . . .
26
2.7
Three-winding transformer and its equivalent circuit parameters . . . . . . .
27
3.1
Details of the Power Converter . . . . . . . . . . . . . . . . . . . . . . . . . .
29
3.2
Design Data for voltage sensor . . . . . . . . . . . . . . . . . . . . . . . . . .
34
3.3
Design Data for current sensor . . . . . . . . . . . . . . . . . . . . . . . . . .
35
3.4
ALTERA FPGA device data . . . . . . . . . . . . . . . . . . . . . . . . . . .
37
3.5
PU values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
39
3.6
Base values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
39
4.1
Test system specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . .
53
4.2
Rated system specifications . . . . . . . . . . . . . . . . . . . . . . . . . . .
56
4.3
Control loop design data . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
60
5.1
TDD comparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
80
5.2
Comparison of theoretical and practical resonance/anti-resonance frequencies
80
viii
List of Figures
1.1
Typical Grid interface scheme of a Power converter . . . . . . . . . . . . . .
1
1.2
A LCL filter connecting inverter and grid . . . . . . . . . . . . . . . . . . . .
2
1.3
Bode plots for L-filter and LCL filter (with resonance at 1.03kHz) . . . . . .
3
1.4
Control transfer function bode plot (with anti-resonance at 726Hz and resonance at 1.03kHz) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
1.5
Grid interface through LCL filter and transformer . . . . . . . . . . . . . . .
5
1.6
Integration of L2 into the transformer . . . . . . . . . . . . . . . . . . . . . .
5
1.7
Grid interface through Integrated Magnetic Filter-Transformer . . . . . . . .
6
2.1
Multi-winding transformer configuration . . . . . . . . . . . . . . . . . . . .
9
2.2
Filter-transformer present between inverter and grid . . . . . . . . . . . . . .
9
2.3
Low frequency illustrative equivalent circuit of Filter-transformer
. . . . . .
10
2.4
High frequency illustrative equivalent circuit of Filter-transformer . . . . . .
10
2.5
Primary side of non-ideal filter-transformer at high frequencies . . . . . . . .
11
2.6
Equivalent circuit of Two-winding transformer . . . . . . . . . . . . . . . . .
12
2.7
A Three-winding transformer . . . . . . . . . . . . . . . . . . . . . . . . . .
13
2.8
Equivalent circuit of Three-winding transformer . . . . . . . . . . . . . . . .
13
2.9
Proposed winding structure of Filter-transformer
. . . . . . . . . . . . . . .
14
2.10 Equivalent circuit of Filter-transformer . . . . . . . . . . . . . . . . . . . . .
15
2.11 Equivalent circuit with secondary shorted . . . . . . . . . . . . . . . . . . . .
15
2.12 MagNet simulation of core-type transformer . . . . . . . . . . . . . . . . . .
19
2.13 MagNet simulation of shell-type transformer . . . . . . . . . . . . . . . . . .
19
2.14 Core-type test prototype . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20
2.15 Shell-type test transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21
ix
x
List of Figures
2.16 (a)Leakage field with equivalent height; (b) MMF variation [Ref.[18]]
. . . .
22
2.17 3kVA three-winding filter-transformer test prototype . . . . . . . . . . . . .
23
2.18 Filter-transformer geometry . . . . . . . . . . . . . . . . . . . . . . . . . . .
24
3.1
Carrier and references in unipolar PWM technique
29
3.2
Actual output voltage with unipolar switching scheme along with its funda-
. . . . . . . . . . . . . .
mental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30
3.3
Actual output voltage with bipolar switching scheme along with its fundamental 30
3.4
DC bus Common-mode voltage with transformer’s primary neutral earthed .
31
3.5
DC bus Common-mode voltage with transformer’s primary neutral unearthed
31
3.6
Actual DC bus voltage and the sensed DC bus voltage . . . . . . . . . . . .
32
3.7
Power Circuit with filter-transformer . . . . . . . . . . . . . . . . . . . . . .
32
3.8
DC bus voltage profile during pre-charging . . . . . . . . . . . . . . . . . . .
33
3.9
Non-isolated voltage sensor circuit . . . . . . . . . . . . . . . . . . . . . . . .
34
3.10 Current sensor circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
35
3.11 Block diagram of FPGA board
. . . . . . . . . . . . . . . . . . . . . . . . .
36
3.12 Experimental set-up with digital controller . . . . . . . . . . . . . . . . . . .
38
3.13 Resonant controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
4.1
Scheme for power transfer between two active sources . . . . . . . . . . . . .
42
4.2
A three phase PLL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
44
4.3
Phasor diagram for grid voltage alignment . . . . . . . . . . . . . . . . . . .
45
4.4
A general single phase PLL structure . . . . . . . . . . . . . . . . . . . . . .
46
4.5
Resonant controller based orthogonal vector generation . . . . . . . . . . . .
46
4.6
4.7
Bode plot for
Bode plot for
Vph (s)
Vg (s)
0
Vqd (s)
Vg (s)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
47
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
47
0
4.8
Simulated response of Vqd and Vph for a DC offset in grid voltage . . . . . . .
4.9
Grid voltage [CH1(Yellow)] and unit vectors [CH4(Green) and CH3(Pink)]
when PLL is enebled [CH2(Blue)] . . . . . . . . . . . . . . . . . . . . . . . .
48
49
4.10 Unit vectors [CH4(Green) and CH3(Pink)] and grid voltage [CH1(Yellow)] at
steady state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
49
4.11 In-phase unit vector [CH4(Green)] when there is a sudden dip in grid voltage
[CH3(Pink)]; CH2(Blue): Enable signal . . . . . . . . . . . . . . . . . . . . .
50
xi
List of Figures
4.12 In-phase unit vector [CH4(Green)] with DC offset in grid voltage [CH3(Pink)]
50
4.13 A resonant controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
51
4.14 Bode plot of resonant controller (with resonance at 50Hz . . . . . . . . . . .
51
4.15 A simple control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
52
4.16 Error function comparison for a reference of 10A through simulation . . . . .
54
4.17 Output current[CH3(Pink)] with PR current controller for a reference of 10A;
CH4(Green): Reference; CH3(Blue): Feedback . . . . . . . . . . . . . . . . .
54
4.18 Bode plot for a PR controller set to track 50Hz reference . . . . . . . . . . .
55
4.19 Phasor diagram for DC bus voltage evaluation . . . . . . . . . . . . . . . . .
56
4.20 Overall control structure for single phase AFEC/STATCOM . . . . . . . . .
57
4.21 Current control loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
59
4.22 Voltage control loop
59
5.1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Simulated frequency response of O.C secondary voltage (Vs (s)) to primary
voltage (Vi (s)) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2
Measured frequency response for O.C secondary voltage (Vs (s)) to primary
voltage (Vi (s)) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3
Simulated frequency response of injected grig current to inverter voltage
Simulated frequency response of inverter current to inverter voltage
64
Measured frequency response of inverter current to inverter voltage ( VIii(s)
)
(s)
with Vg = 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.7
63
( VIii(s)
)
(s)
with Vg = 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6
63
Measured frequency response of injected grig current to inverter voltage ( VIgi (s)
)
(s)
with Vg = 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5
62
( VIgi (s)
)
(s)
with Vg = 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4
62
64
CH1(Yellow):Applied primary (inverter) voltage; CH2(Blue): Secondary (output) voltage; Without AW . . . . . . . . . . . . . . . . . . . . . . . . . . .
65
5.8
CH1(Yellow): Primary voltage; CH2(Blue): Secondary voltage; With AW .
65
5.9
CH1(Yellow,1A/div): Grid current; CH2(Blue,0.1A/div): Inverter current;
CH3(Pink): Sensed grid voltage; With control not enabled . . . . . . . .
66
5.10 CH1(Yellow,50V/div): DC bus voltage boost profile; CH2(Blue): Enable signal 67
5.11 CH1(Yellow,2A/div): Grid current; CH2(Blue,5A/div): Inverter current; CH4(Green):
Grid unit vector; with control enabled, 0A reference . . . . . . . . . . .
67
xii
List of Figures
5.12 CH2(Blue,5A/div): Inverter current; CH4(Green,2V/div): Grid unit vector;
In STATCOM mode at 90% load . . . . . . . . . . . . . . . . . . . . . .
68
5.13 CH1(Yellow,5A/div): Grid current; CH4(Green,2V/div): Grid unit vector;
In STATCOM mode at 90% load . . . . . . . . . . . . . . . . . . . . . .
68
5.14 CH1(Yellow,50V/div): DC bus voltage boost profile; CH2(Blue): Enable signal 69
5.15 CH1(Yellow,2A/div): Capacitor current; CH2(Blue,2A/div): Inverter current; CH3(Pink): Sensed grid voltage; with control enabled, 0A reference 70
5.16 CH1(Yellow,2A/div): Grid current; CH2(Blue,5A/div): Inverter current; CH4(Green):
Grid unit vector; with control enabled, 0A reference . . . . . . . . . . .
70
5.17 CH1(Yellow,50V/div): DC bus voltage ripple; CH2(Blue,5A/div): Grid current; CH3(Pink,5A/div): Inverter current; CH4(Green,2V/div): Grid unit
vector; with control enabled, 80 % load . . . . . . . . . . . . . . . . . .
71
5.18 CH1(Yellow,50V/div): DC bus voltage ripple profile; CH3(Pink): Enable signal for Current reference change from 25% to 90% . . . . . . . . . . .
71
5.19 CH2(Blue,5A/div): Inverter current; CH4(Green,2V/div): Grid unit vector;
with control enabled, 90% current reference at 0 p.f (leading) . . . .
72
5.20 CH1(Yellow,5A/div): Grid current; CH4(Green,2V/div): Grid unit vector;
with control enabled, 90% current reference at 0 p.f (leading) . . . .
72
5.21 CH2(Blue,10A/div): Inverter current; CH4(Green,2V/div): Grid unit vector;
with control enabled, 90% current reference at 0 p.f (lagging) . . . .
73
5.22 CH1(Yellow,10A/div): Grid current; CH4(Green,2V/div): Grid unit vector;
with control enabled, 90% current reference at 0 p.f (lagging) . . . .
73
5.23 CH2(Blue,5A/div): Inverter current; CH4(Green,2V/div): Grid unit vector;
with control enabled, AFEC UPF operation . . . . . . . . . . . . . . .
74
5.24 CH1(Yellow,5A/div): Grid current; CH4(Green,2V/div): Grid unit vector;
with control enabled, AFEC UPF operation . . . . . . . . . . . . . . .
74
5.25 CH2(Blue,10A/div): Inverter current; CH4(Green,5V/div): Grid unit vector;
with control enabled, AFEC operation with 10% reactive (leading)
current reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
75
5.26 CH1(Yellow,10A/div): Grid current; CH4(Green,5V/div): Grid unit vector;
with control enabled, AFEC operation with 10% reactive (leading) current reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
75
5.27 Inverter current under two-winding operation . . . . . . . . . . . . . . . . .
76
List of Figures
xiii
5.28 Inverter current harmonics under two-winding operation . . . . . . . . . . .
77
5.29 Grid current under two-winding operation . . . . . . . . . . . . . . . . . . .
77
5.30 Grid current harmonics under two-winding operation . . . . . . . . . . . . .
78
5.31 Inverter current under three-winding operation . . . . . . . . . . . . . . . . .
78
5.32 Inverter current harmonics under three-winding operation . . . . . . . . . . .
79
5.33 Grid current under three-winding operation . . . . . . . . . . . . . . . . . .
79
5.34 Grid current harmonics under three-winding operation . . . . . . . . . . . .
80
Chapter 1
Introduction
Now a days, several governments and utilities worldwide promote renewable energy sources
such as Photovolaics (PV), Fuel cells, micro-turbines etc for distributed power generation
systems(DGPS), so as to deal with issues like rising prices of energy and environmental
concerns. DGPS are renewable energy sources linked up to the grid at the point of load.
This eliminates losses during transmission and distribution and also improves reliability of
the power supply. However, a DC/AC power converter and a filter are invariably required
for such an interconnection. Fig.1.1 shows a typical interface scheme of a DGPS. The power
quality of the grid interface is influenced by the quality of the injected current and the filter
here essentially brings down the distortion in the sinusoidal current and voltage waveforms
caused by the power converter.
Figure 1.1: Typical Grid interface scheme of a Power converter
1
2
Chapter 1. Introduction
1.1
Current Scenario
The conventional way of interface is through a simple first order L-filter whose design is
merely based on 10% filter drop. But then, it is bulky, inefficient and cannot meet the regulatory requirements such as IEEE512-1992 and IEEE1547-2003 pertaining to interconnection
of harmonic loads to the grid. Making it satisfy the standards would render it vast.
Higher order filters (such as LC and LCL filters) are becoming exceedingly popular (especially at higher power levels) as they offer higher attenuation even at lower switching
frequency for a similar filter size [1]. For a grid application, LC-filter is no better than a
L-filter as the grid which is present across capacitor would make its presence futile [23].
So,third order LCL filter is the next available option.
1.1.1
Higher order filter design
Figure 1.2: A LCL filter connecting inverter and grid
LCL-filter design methodologies have been well reported in the literature. The method
adopted here is based on per-unit values [23]. The transfer function pertinent to our design
procedure is given by,
1
ig (s) =
L2
vi (s) vg =0 s(L1 + L2 )(s2 LL11+L
C + 1)
2
(1.1)
It can be seen that the filter has a resonant frequency ωres given by,
2
ωres
=
1
Lp C
(1.2)
1.1. Current Scenario
3
where,
Lp =
With L = L1 + L2 and aL =
L1
,
L2
L1 L2
L1 + L2
(1.3)
Equation1.1 becomes,
ig (s) 1
=
2
vi (s) vg =0 sL(s Lp C + 1)
(1.4)
Figure 1.3: Bode plots for L-filter and LCL filter (with resonance at 1.03kHz)
On per-unitization with suitable base quantities [23], the resonant frequency becomes,
2
ωres(pu)
=
1
L
Cpu Lpu (aLa+1)
2
(1.5)
Choice of ωres(pu) is based on the available system bandwidth. To find Lpu and Cpu , Equation.(1.4)
is evaluated (in per unit) at switching frequency fsw .
i (jω ) sw g
vi (jωsw ) =
3 L L C
|−jωsw
1 2
1
+ jωsw (L1 + L2 )|
(1.6)
ig (jωsw ) is the switching ripple current at the point of common coupling to the grid at
switching frequency. This is guided by the recommendations of IEEE 519-1992 or IEEE
1547.2-2008 standard.
4
Chapter 1. Introduction
Equation.(1.6) is solved by converting all parameters to per-unit and substituting Equation.(1.5)
in Eq (1.6).
Lpu =
1
i
g(pu) ωsw(pu) vi(pu) 1 −
1
2
ωsw(pu)
2
ωres(pu) (1.7)
Then, Cpu will be calculated from Equation.1.5.
Another transfer function of interest from control perspective is,
ii (s) 1 (s2 L2 C + 1)
=
vi (s) vg =0 sL (s2 Lp C + 1)
(1.8)
This would be the filter transfer function considered for closed loop controller design and
Figure 1.4: Control transfer function bode plot (with anti-resonance at 726Hz and resonance
at 1.03kHz)
the inverter current ii will be the one to be controlled by the regulator. The issue of resonance arising in higher order filters and their damping techniques are not discussed here.
Conventional resistive (passive) damping is employed in this work.
1.2
Prospects in existing interface scheme
Many a times, a transformer would be necessary after the filter stage to enable grid interface.
The transformer provides galvanic isolation and an extra degree of freedom to adjust the
1.2. Prospects in existing interface scheme
5
output voltage level to that of the grid. It must be noted that the copper used in filter as
well as the transformer must be gauged for the rated current. Again, magnetic materials are
to be used in both the filter and the transformer.
Figure 1.5: Grid interface through LCL filter and transformer
Magnetic components often constitute a significant part of the overall size, weight and cost
of the grid connected power system. Hence a compact and inexpensive design is desirable.
Since magnetic components are present in both filter and transformer, there is scope for their
potential integration.
It is quite straight forward to integrate the magnetics of a simple L-filter into the transformer. All that is required is to design a transformer with a value of leakage inductance
equal to that of the actual filter inductance. Such a design is relatively simple as the typical
values of leakage inductance and the filter inductance are quite close on a per-unit basis.
Figure 1.6: Integration of L2 into the transformer
While it is not conspicuous to achieve such a magnetic integration in case of higher
6
Chapter 1. Introduction
order LCL filters. One possible way is integrating only one of the two filter inductances
into the transformer as illustrated in Fig. 1.6. But this does not serve the purpose (of
magnetic integration) entirely. It is required to integrate all the magnetics of the filter
into the transformer.Typical ways entail complicated design procedures with sophisticated
winding and core structures which are hard to procure.
1.3
Project Work
The present work is on design of an integrated filter-transformer structure where the all
magnetic components of the higher order filter are integrated into the transformer. A three
winding transformer configuration is proposed which employs standard core structures for
achieving such an integration. The single compact structure would now perform the functions
of both the filter and the transformer. It will be seen that with a judicious design, the nonidealities viz. leakage inductances of the transformer can be exploited for our advantage for
the purpose of integration. Such a design economizes both copper and iron, while yielding a
compact design.
Figure 1.7: Grid interface through Integrated Magnetic Filter-Transformer
This work targets single phase applications and control in d-q domain is thus not possible.
This makes the closure of control loop rather tricky. References are no longer DC in nature.
Using a conventional PI controller would result in significant steady state errors depending on
the bandwidth of the system. Hence, focus is laid on Proportional-Resonant (PR) controllers
required for accurate AC reference tracking in closed loop control.
1.4. Conclusion
7
A PI controller’s transfer function is given by:
H(s) = Kp +
Ki
s
(1.9)
While a PR controller’s transfer function is given by:
H(s) = Kp + Ki
s2
s
+ ω02
(1.10)
As seen from (4.13), a resonant controller is a generalised integrator. PI controller is a special
case of PR controller when ω0 is set to zero. Thus, a PR controller can be suitably set to
track AC signal of any frequency, which is well suited for single phase applications.
The power converter is operated as a single phase STATCOM and as a Active Front End
Converter (AFEC) in the grid interactive mode for performance evaluation. Also, a heat run
test was performed to get a fair idea of the possible temperature rise of core and copper.
1.4
Conclusion
An outline of the project was given in this chapter. A brief description about the about the
intended magnetic integration of filter into the transformer and the complexity in controlling
single phase systems was given.
Chapter 2
Magnetic integration and Transformer
design
2.1
Introduction
In the foregoing chapter, it was seen that magnetic components are present in both filter
and the transformer of the grid interface scheme, and hence there is a possibility to integrate
them. The methods available in literature for integration of LCL filter and transformer
involve cumbersome design procedures with sophisticated core structures [2],[3]. Such unconventional core structures are hard to manufacture and procure.
In this work, a multi-winding transformer configuration is proposed that employs conventional C-core structures to achieve the desired integration.
2.2
Proposed multi-winding transformer configuration
The multi-winding structure that is intended to emulate a LCL-filter is depicted in Fig.2.1.
The structure consists of two primary windings and one secondary winding which are magnetically coupled by the core. The two primaries are of the same number of turns. One
primary acts as the main winding (MW) and the other is called the auxiliary winding (AW).
A capacitor (C) is externally connected to AW as shown. The primary side will be connected
to the inverter and the secondary winding (SW) will be connected to gird.
It must be noted that the two primaries are wound in opposite sense (opposite dots) over
the core. This is key feature that forms the basis of magnetic integration.
8
2.2.
Proposed multi-winding transformer configuration
Figure 2.1: Multi-winding transformer configuration
Figure 2.2: Filter-transformer present between inverter and grid
9
10
Chapter 2. Magnetic integration and Transformer design
Working principle
At low frequencies (including power frequency), the capacitor acts a open circuit due to its
very large impedance. In this situation, the AW is as good as being absent. Now, power
frequency component of the inverter voltage will see only the MW. Subsequently energy
transfer takes place to the secondary and hence to the grid.
Figure 2.3: Low frequency illustrative equivalent circuit of Filter-transformer
At higher frequencies (inclusive of switching frequencies), the capacitor acts as a short
as it going to offer very low impedance. Under this condition, the two primaries work in
conjunction with applied voltage (Vi ) being common to both. Due to their opposite sense
of winding, the flux produces by each winding are opposite in direction, hence cancel one
another. So for high frequency components, flux gets completely cancelled in the core. Thus
no energy transfer takes place to the secondary now due to the absence of any magnetic
field in the core. In other words, there is no magnetic coupling between MW and SW at
those frequencies. This would amount to filtering of all high frequency components (which are
responsible for distortion) other than the fundamental, present in the inverter output voltage.
Figure 2.4: High frequency illustrative equivalent circuit of Filter-transformer
2.2.
Proposed multi-winding transformer configuration
11
Figure 2.5: Primary side of non-ideal filter-transformer at high frequencies
This phenomenon is referred to as internal differential mode distortion cancellation [7].
But the pitfall here is that the inverter is ideally going to see a dead-short across the primary
side, since due to flux cancellation, no induced emf is produced across the magnetizing
inductance. Fortunately due to non-idealities, leakage inductances are present to limit the
current from the inverter.
2.2.1
Winding attributes
• Main winding (MW):
It works at high frequencies as well as low frequencies and thus carries both fundamental
and switching ripple current. Hence, an appropriate thick gauge is required depending
on the rated fundamental current and desired switching ripple current.
• Secondary winding (SW):
It again works at high frequencies as well as low frequencies but carries fundamental
and the filtered switching ripple current. An appropriate thick gauge is again required.
• Auxiliary winding (AW):
It functions only at high frequencies and thus carries only switching ripple current.
Hence a suitable thin gauge (depending on the desired switching ripple current) would
suffice.
12
Chapter 2. Magnetic integration and Transformer design
2.2.2
External capacitor
Metallised Polypropylene capacitors are AC capacitors that are especially designed for high
frequency current operation. These capacitors are constructed from polypropylene films on
which an extremely thin metal layer is vaccum deposited. Several such layers are wound
together in a tubular fashion to get higher capacitance.
Metallised film capacitors are characterized by small size, wide operating frequency range,
low losses, low to medium pulse handling capabilities, low parasitic impedances and selfhealing. In regular film-foil capacitors, if the electrode foils of opposite potential are exposed
to each other because of wearing away of the dielectric, the foils will short and the capacitor will be destroyed. But in case of metallised polypropylene capacitors, because of the
extremely thin metal layer, the contact points at the fault area are vaporised by the high
energy density, and the insulation between foils is maintained. Due to the above reasons,
these capacitors are perfectly suited for grid connected filter operation [23].
2.3
Equivalent circuit development
Leakage inductance is always defined for a pair of windings [16]. In case of a conventional twowinding transformer, the meaning of leakage inductance and the corresponding equivalent
circuit are straightforward [17].
Figure 2.6: Equivalent circuit of Two-winding transformer
where, L12 is the total leakage inductance between the two windings. This value can be
experimentally obtained by performing short circuit test. Whereas in case of a multi-winding
transformer, since there are multiple pairs of windings, leakage inductance must be defined
for every pair. Equivalent circuit now would not be as simple as that of a two-winding case.
2.3. Equivalent circuit development
13
Figure 2.7: A Three-winding transformer
Figure 2.8: Equivalent circuit of Three-winding transformer
Fig.2.8 shows the equivalent circuit of a three-winding transformer.
Here, we have a set of three (different) leakage inductances as there are three pairs
of windings. And LI ,LII and LIII shown in Fig.2.8 are composite inductances formed by
linear combinations of different leakage inductances [17]. It is first necessary to evaluate
the composite inductances before we go about analysing the transfer function. A rigorous
derivation for the composite inductances is available in literature [16], [17]. For brevity, end
is result is being used here, which is given by,
LI =
L12 + L13 − L23
2
L21 + L23 − L13
2
L31 + L32 − L21
=
2
(2.1)
LII =
(2.2)
LIII
(2.3)
14
Chapter 2. Magnetic integration and Transformer design
where,
L12 = L21 = leakage inductance of windings 1 and 2 with winding 3 open.
L23 = L32 = leakage inductance of windings 2 and 3 with winding 1 open.
L31 = L13 = leakage inductance of windings 1 and 3 with winding 2 open.
These leakage inductances can be measures by performing multiple short-circuit tests
with pertinent windings. It must be noted that winding resistances have been disregarded
here for simplicity.
2.4
Transfer function analysis
Figure 2.9: Proposed winding structure of Filter-transformer
The proposed structure is shown in Fig.2.9. The corresponding equivalent circuit is
shown in Fig.2.10 This equivalent circuit conveniently models the opposite winding sense
of the auxiliary winding by reversing its applied (inverter) voltage. The voltage across
the magnetizing inductance essentially represents the open circuit voltage produced in the
secondary due to the net flux present in the core. The first transfer function of interest is
that of the secondary voltage e(s) to primary voltage Vi (s) which can be obtained easily
using superposition theorem. Shunt branch consisting of magnetizing impedance of the
transformer (which is very large) can be opened up for simplicity in the analysis.
1
sLIII + sC
e(s) = vi (s)
sLI + sLIII +
=⇒
!
1
sC
sLI
+ (−vi (s))
sLI + sLIII +
1
(sLIII + sC
− sLI )
e(s)
=
1
vi (s)
(sLIII + sLI + sC
)
!
1
sC
(2.4)
(2.5)
which yields,
e(s)
=
vi (s)
1 + (LIII − LI )Cs2
1 + (LIII + LI )Cs2
!
(2.6)
2.4. Transfer function analysis
15
Figure 2.10: Equivalent circuit of Filter-transformer
The next transfer function of interest is that of the shorted circuited secondary current
Is (s) to inverter voltage vi (s). It should be noted that the grid voltage is a short for all
frequency components except the fundamental. So, Is (s) essentially represents the injected
grid current. Once again, superposition theorem can be employed to evaluate short-circuited
secondary current.
Figure 2.11: Equivalent circuit with secondary shorted
16
Chapter 2. Magnetic integration and Transformer design
Is = Is1 − Is2
(2.7)
From Fig.2.11(b),
1
sLIII + sC
vi (s)
×
Is1 (s) = sLII (sLIII + 1 )
sLIII + sLII +
sLI + sL +sL +sC1
II
III
!
(2.8)
1
sC
sC
On simplification,

Is1 (s) = vi (s) 

2
s(LI +
1 + LIII Cs
LI LII +LII LIII +LIII LI
LII )[(
)Cs2
LI +LII
+ 1]

(2.9)
Similarly, from Fig.2.11(c),

Is2 =
vi (s)  s LIII +

1
LI LII
LI +LII
+
1
sC

LI
LI + LII
(2.10)
On simplification,

Is2 = vi (s) 
LI
sC LI +L
II

LIII +LIII LI
[( LI LII +LLIII +L
)Cs2 + 1]
II

(2.11)
Substituting Equation.2.9 and Equation.2.11 in Equation.2.7, we get,

Is (s) = vi (s) 
1 + LIII Cs2

LIII +LIII LI
s(LI + LII )[( LI LII +LLIII +L
)Cs2 + 1]
II


−vi (s) 
LI
sC LI +L
II

LIII +LIII LI
[( LI LII +LLIII +L
)Cs2 + 1]
II

(2.12)
which yields,










Is (s)
1
1 + (LIII − LI )Cs2
=

LI LII + LII LIII + LIII LI
vi (s)
s(LI + LII ) 



)Cs2 + 1 
(

LI + LII
(2.13)
Equation.2.13 is the required transfer function that governs the injected grid current. The
term outside the braces represents the injected grid current transfer function for a conventional two-winding transformer. The term inside the braces represents the correction factor
introduced by the third winding (AW) to the otherwise two-winding transformer.
2.5. Core-type and Shell-type Transformers
17
It can be surmised that the proposed structure cannot emulate a LCL-filter entirely. It
behaves as a LCL-filter until the entry of the zeros, after which it becomes a first order
L-filter.
The final transfer function of interest is that of the inverter current Ii (s) to inverter voltage
vi (s). This is the control transfer function necessary for closed loop control. From Fig.2.11(a),
the actual inverter current is given by,
Ii (s) = Ix (s) + Iy (s)
(2.14)
Ix (s) and Iy (s) are readily evaluated using superposition theorem.


1 + (2LII + LIII )Cs2

Ix (s) = vi (s) 
LIII +LIII LI
2 + 1]
s(LI + LII )[( LI LII +LLIII +L
)Cs
II
(2.15)
Similarly,


sC
LII


Iy (s) = vi (s)
LI LII +LII LIII +LIII LI
LI + LII
)Cs2 + 1
(
LI +LII
(2.16)
Therefore,

Ii (s) = vi (s) 
s(LI +

LII
s(LI + LII )
LI +LII

LIII +LIII LI
2 + 1]
LII )[( LI LII +LLIII +L
)Cs
II
1 + (2LII + LIII )Cs2 + sC +
(2.17)
which finally yields,










1 + (LI + 4LII + LIII )Cs2
Ii (s)
1
=

LI LII + LII LIII + LIII LI
vi (s)
s(LI + LII ) 



)Cs2 + 1 
(

LI + LII
(2.18)
Equation.2.18 would be the filter-transformer’s transfer function from control perspective.
Here again, the term inside the braces represents the correction factor introduced by the
third winding. It can be seen that without the third winding, the behaviour of the structure
is similar to that of a simple L-filter.
2.5
Core-type and Shell-type Transformers
As seen in the preceding section, leakage inductances of the filter-transformer governed the
nature of the relevant transfer functions. It may so happen that a large value of leakage
inductance is required to get the required attenuation of switching ripple current. So, a
judicious choice on the type of transformer to be used was essential.
18
Chapter 2. Magnetic integration and Transformer design
2.5.1
Core-type transformer
Core-type transformers are known to have relatively larger leakage inductances as compared
to their shell-type counterparts of similar rating [5]. To verify this, a core-type test transformer was built. The core-type test prototype and a shell-type transformer of identical
ITEM
VA
SPECIFICATION
600VA
Vp , Vs
120V, 120V
Ip , Is
5A, 5A
Np , Ns
Bm
580, 580
1.5T
2.5A/mm2
J
kw
f
0.6
50Hz
Inter-winding gap (Wg )
Core
1.1 cm
Amorphous AMCC367’s
Table 2.1: Details of core-type test transformer
rating were simulated in Infolytica MagNet 6.22.1, so as to have a fair idea of path of leakage
flux flow in either case and to obtain the corresponding leakage inductances.
As seen in
from Fig.2.12, leakage flux of a core type transformer exists both inside and outside the
transformer. In contrast, for a shell type, it exists only inside the transformer. For a core
type transformer, leakage inductance is three independent parts, one inside it and two outside [6]. For a shell type transformer, only the inside component of leakage inductance exists.
Analytical evaluation of leakage inductance of shell type transformer is well reported in literature [5], [18]. But for core-type ones, materials on its leakage inductance were not readily
available.
Open circuit and short circuit tests were performed on the prototype and Table.2.2 lists
the results. L12 value obtained from simulation differed significantly from the practical value
for the core-type transformer. Also,the prototype was found to have more than 1 p.u leakage
inductance, which is entirely undesirable. So, further analysis was ceased and focus was laid
2.5. Core-type and Shell-type Transformers
Figure 2.12: MagNet simulation of core-type transformer
Figure 2.13: MagNet simulation of shell-type transformer
19
20
Chapter 2. Magnetic integration and Transformer design
Figure 2.14: Core-type test prototype
Quantity
Value
Magnetizing inductance (LM )
Leakage inductance L12 (measured)
Leakage inductance L12 (from MagNet)
1.6H
90mH
5mH
Leakage impedance Xl
28Ω
Base impedance Zb
24Ω
p.u Leakage impedance Xl(pu)
Short circuit current Is.c at rated voltage
1.17p.u
4.3A
Table 2.2: Test results of core-type transformer
on shell type transformers.
2.5.2
Shell type transformer
Shell type transformers are extensively discussed in literature. Analytical expression for its
leakage inductance is also readily available with rigorous proof via different approaches [17],
[18]. It is given by Rogowski’s formula (Equation.2.19). Fig.2.15 and Fig.2.16 show the
basic construct of a shell type transformer and the corresponding leakage flux existing in it
respectively.
N2
1
π (T1 Dw1 + T2 Dw2 ) + Tg Dwg
Heq 3
Ll12 = µo
(2.19)
2.6. Three-winding filter-transformer design
21
Figure 2.15: Shell-type test transformer
with,
Heq =
kR = 1 −
Hw
kR
1−
(2.20)
−πHw
λ
πHw
λ
λ = T1 + T2 + Tg
(2.21)
(2.22)
where,
T1 and T2 = Winding widths of LV and HV windings respectively,
Tg = Inter-winding distance,
Dw1 , Dw2 and Dwg = Mean diameter of LV, HV and inter-winding gap respectively,
N = Number of turns.
Hw = Height of the winding,
kR = Rogowski factor
The above calculation is for a two-winding case. Even in three-winding case, same approach
is applicable for leakage inductance evaluation for every pair of windings.
2.6
Three-winding filter-transformer design
In order to verify the transfer functions obtained for the proposed structure, a three winding
test transformer was built as a first pass iteration. Conventional area-product approach was
22
Chapter 2. Magnetic integration and Transformer design
Figure 2.16: (a)Leakage field with equivalent height; (b) MMF variation [Ref.[18]]
employed for the design [22]. The structure’s geometry is illustrated in Fig.2.18
Open circuit and short circuit tests were performed on the structure and the pertinent
parameters were evaluated from the measurement data in Table.(2.5) and (2.4). Using the
parameters from these measurements, relevant transfer functions can be obtained.
2.6. Three-winding filter-transformer design
Figure 2.17: 3kVA three-winding filter-transformer test prototype
23
24
Chapter 2. Magnetic integration and Transformer design
ITEM
VA
SPECIFICATION
3kVA
VM W , VSW
240V, 240V
IM W , ISW
12.5A, 12.5A(SW G12)
IAW
NM W , NSW , NAW
Bm
1.6A(SW G20)
225, 225, 225
1.28T
2.5A/mm2
J
kw
0.656
f
50Hz
Core type
Amorphous AMCC367’s
Table 2.3: Design details of three winding shell-type test transformer
Figure 2.18: Filter-transformer geometry
2.6. Three-winding filter-transformer design
25
Quantity
Value
Vin(rms)
240V
I0 (rms)
1.77A
P
11W
Q
423.8V AR
LM
0.427H
R0
5.13kΩ
Table 2.4: O.C test results of three winding shell-type transformer
Quantity/Condition
MW excited;
SW excited;
AW excited;
SW shorted;
AW shorted;
MW shorted;
AW opened;
MW opened;
SW opened;
Vin(rms)
16.81V
6.13V
7.76V
Is.c (rms)
12.538A
1.551A
1.643A
Zs.c
1.34Ω
3.9522Ω
4.723Ω
P
99W
9W
10W
Q
186VAR
3VAR
8VAR
Table 2.5: S.C test results of three winding shell-type transformer
In general, the transfer function of the structure (from Equation.2.13) governing the
injected grid current can be written as,
s2
 2 + 1
ω

Ig (s)
1 
 zg

=
 s2

vi (s)
sLT 

+
1
2
ωp


(2.23)
Similarly the control transfer function (from Equation.2.18) can be written as,
s2
 2 + 1

ω
Ii (s)
1 
 zc

=
 s2

vi (s)
sLT 

+
1
2
ωp


(2.24)
26
Chapter 2. Magnetic integration and Transformer design
Quantity
Value
RM W
0.3Ω
RSW
0.3Ω
RAW
3.6Ω
L12
3.77mH
L23
4mH
L31
9.32mH
LI
4.545mH
LII
-0.775mH
LIII
4.775mH
Table 2.6: Three-winding transformer and its equivalent circuit parameters
It can be seen that the control transfer function of the proposed structure is strikingly similar
to that of a discrete LCL-filter (obtained in chapter 1), even though the integrated structure
does not emulate a LCL-filter completely from grid current perspective. So, control strategy
is same as that of a discrete filter. The above transfer functions for the three winding test
transformer can be obtained by plugging in the parameter values furnished in Table.2.6.
2.6.1
First pass design procedure
It was desired to verify if the conceived idea would work. So the test prototype was not
designed based on a concrete design procedure. The primary (MW) and the secondary
windings (SW) were designed based on area-product approach with the available amorphous
core structures. Since these two windings are responsible for 50Hz power transformer, they
were wound concentrically as close as possible so as to have minimum leakage inductance.
Now, the desired transfer function must be achieved by placing the third winding (AW)
adequately away from the two windings. To begin with, it was placed at a distance of 2mm
away from the SW.
Now, leakage inductances of various winding pairs were measured and subsequently composite inductances were obtained. From these values and the desired location of zeros (which
causes a valley) in
Is (s)
vi (s)
(Equation.2.13, 2.23), the capacitance value was chosen.
2.7. Conclusion
27
Quantity
Value
ω zg
125663.7 rad/s
f zg
20kHz
Lzg
0.23mH
C
0.25µF
Table 2.7: Three-winding transformer and its equivalent circuit parameters
2.7
Conclusion
A three winding transformer configuration along with a capacitor was proposed for the
purpose of magnetically integrating a higher order filter into a transformer. Its equivalent
circuit was developed and relevant transfer functions were obtained. Core-type transformers
were found to be unsuitable for this application. A first pass design of the structure was
done. Experimental results verifying the transfer functions and performance of the structure
as a filter-transformer would be furnished in final chapter.
Chapter 3
Power circuit for grid interface, sensor
and Digital controller
3.1
Introduction
This chapter furnishes all the hardware details associated with the power converter employed
for this work. The converter was designed and built in the past. The grid interfacing
scheme with the filter-transformer is illustrated and the corresponding starting procedure
is described. Non-isolated sensor circuit design is discussed. Details pertaining to FPGA
based digital controller and implementation techniques are also furnished.
3.2
Power Circuit
3.2.1
Power converter
A 10 kVA three phase, two-level power converter is being operated as a 3 kVA single phase
converter in H bridge configuration. The Protection-Delay card, Gate-Drive card and the
annunciation card form the control cards of the inverter whose design existed beforehand.
The cards were tested sequentially for their working. Specifications of the converter are
furnished in Table. 3.1.
3.2.2
PWM Technique
Unipolar PWM technique is employed where each of the leg is switched at switching frequency
fs using sine-triangle comparison method and the output voltage of the converter is the
difference between the pole voltage of either legs. Fig. 3.1 depicts the reference sine for each
28
3.2. Power Circuit
29
ITEM
IGBT
SPECIFICATION
SKM100GB123D
CDC
2350µF
CAC
1µF
VDC(rated)
750V
IAC(rated)
100A
Bleeder Resistor
20kΩ
Power
10 kVA
Table 3.1: Details of the Power Converter
of the leg in this scheme. In this scheme, for a given polarity of the output funfamental,
Figure 3.1: Carrier and references in unipolar PWM technique
the actual output voltage switches between zero and a voltage (here ±VDC ) of identical
polarity as the fundamental. The clear-cut advantage with unipolar switching scheme is
that only even switching frequency harmonics (2fs , 4fs ...) and their associated side-bands
exist in the output waveform. This means the output voltage waveform is of better quality
when compared to that obtained with bipolar switching scheme [19]. In bipolar scheme, the
polarity of the output fundamental and the switching output voltage may be opposite as well
and the output waveform has both even and odd switching frequency harmonics along with
their side-bands (1fs , 2fs , 3fs ...). Thus, with unipolar scheme, burden on the output filter
30
Chapter 3. Power circuit for grid interface, sensor and Digital controller
is reduced. Another benefit with H-bridge topology is that burden on the DC bus voltage
is only 50% of that with single leg topology for a given output voltage fundamental. This
is because the peak output fundamental with H-bridge is Vdc and not
Vdc
2
as with single leg
topology [19] .
Figure 3.2: Actual output voltage with unipolar switching scheme along with its fundamental
Figure 3.3: Actual output voltage with bipolar switching scheme along with its fundamental
Fig. 3.2 and Fig. 3.3 show the actual output voltage along with its fundamental for
unipolar and bipolar technique respectively.
One drawback of these methods in grid interactive mode is that the common mode voltage
of the positive and negative rails is going to contain switching frequency components (fs ),
3.2. Power Circuit
31
which get reflected in the voltage sensor output as noise riding on the actual DC bus voltage.
This may be attributed to the inability of sensor to filter the common-mode noise entirely.
This is the case when the neutral of the filter-transformer is earthed. In the unearthed
case, since the neutral itself is going to see a common-mode voltage at 50 Hz, the DC bus
common-mode voltage (Vcm ) has both switching frequency and 50 Hz component.
Figure 3.4: DC bus Common-mode voltage with transformer’s primary neutral earthed
Figure 3.5: DC bus Common-mode voltage with transformer’s primary neutral unearthed
As a result, further filtering of sensed DC bus voltage is necessary. This may add to
the delay in the feedback. One possible way to deal with this sort of common-mode voltage
is to switch only one leg at fs and the other (connected to the neutral) at 50 Hz. Now,
32
Chapter 3. Power circuit for grid interface, sensor and Digital controller
Figure 3.6: Actual DC bus voltage and the sensed DC bus voltage
common-mode noise consists only a mild 50 Hz component. It is still a unipolar technique
but the references to each leg are different now.
3.2.3
Power circuit and starting Procedure
Pre-charging is done through the diode devices of the IGBT module through a 1kΩ precharging resistor as shown in Fig. 3.7. When the DC bus voltage reaches a preset value
0
(Vdc ), the pre-charging resistor is shorted by a contactor. Subsequently, DC bus voltage is
boosted to the rated value when the control is enabled. The transformer does not possess
a mechanically robust construct as it is self made. This makes its acoustic behaviour (due
to magnetostriction) considerably poor. To keep the humming noise low, the grid voltage is
stepped down by 10% of its rated value through an autotransformer and then used.
Figure 3.7: Power Circuit with filter-transformer
3.3. Non-isolated Sensor circuit
33
Figure 3.8: DC bus voltage profile during pre-charging
As seen in Fig. 3.8, the DC bus starts charging once the grid voltage is applied and when
the preset value is reached, it abruptly jumps to the grid voltage peak due to the closure of
the contactor.
3.3
Non-isolated Sensor circuit
The existing sensing cards incorporated isolation between the input and output through an
opto-isolater. The design employs a forward converter on board that acts as the isolated
power supply meant for the opto-isolater. Output of the opto-isolator was amplified using a
differential amplifier. 555-Timer was used to generate 50% duty ratio pulses for the forward
converter. Passive R-C based flux reset circuit was employed. These together make the
design more or less complicated and hence less reliable. Moreover, isolation is not mandatory
for sensing. Thus, a non-isolated sensing card was designed that employs just a potential
divider and a differential amplifier to serve the purpose. Noise filter is incorporated in the
differential amplifier itself. The circuit is both simple and more reliable.
3.3.1
Design
3.3.1.1
Voltage sensor
Here, a simple potential divider employed as a first stage to step-down the input voltage.
Mid-point of the divider and the op-amp ground are earthed.In the second stage, a differential
34
Chapter 3. Power circuit for grid interface, sensor and Digital controller
amplifier is used to amplify and to filter the differential signal obtained from the divider.
The final output voltage is fraction of difference of the input voltages which is given by:
Vo (s) =
fc1 =
R2
(Va (s)
R1
− Vb (s))
(1 + R2 Cf s)(1 + Ro Co s)
1
,
2πR2 Cf
fc2 =
(3.1)
1
2πRo Co
(3.2)
Figure 3.9: Non-isolated voltage sensor circuit
ITEM
SPECIFICATION
RX
12kΩ
RY
1M Ω
R1
560kΩ
R2
1.2M Ω
Ro
250Ω
Cf
28µF
Co
60nF
fc1 , fc2
Voltage gain
Input voltage range
4.737kHz, 10.61kHz
0.02V/V
±750V
Table 3.2: Design Data for voltage sensor
3.3. Non-isolated Sensor circuit
3.3.1.2
35
Current sensor
Here, a burden resistor is used to convert the current output produced by a Hall-effect based
current sensor into a voltage signal. Subsequently, a differential amplifier is employed to
amplify and filter the voltage signal.
Figure 3.10: Current sensor circuit
Vo (s) =
R2
I (s)Rb
R1 o
(1 + R2 Cf s)(1 + Ro Co s)
ITEM
SPECIFICATION
Rb
47Ω
R1
120kΩ
R2
1.2M Ω
Ro
250Ω
Cf
28µF
Co
60nF
fc1 , fc2
Current Sensor
CT ratio
Current gain
4.737kHz, 10.61kHz
HE055T01
1000:1
0.466V/A
Table 3.3: Design Data for current sensor
(3.3)
36
Chapter 3. Power circuit for grid interface, sensor and Digital controller
The output filter serves two purposes. Firstly, it attenuates the common-mode noise
present at the op-amp output. Common-mode noise may be present because of mismatch of
component values due to tolerances. Secondly, also acts as a current limiter if the output is
accidentally shorted.
3.4
Digital controller
FPGA based digital platform employed is employed for closed loop control.The choice of an
FPGA device for a given application is based on the size (i.e. no. of logic elements) required,
clock speed and number of I/O pins. ALTERA EP1C12Q240C8 was found to be suitable
for this application. The board was programmed using Quartus II (Version 9.0) software.
3.4.1
FPGA board
Figure 3.11: Block diagram of FPGA board
ALTERA EP1C12Q240C8 devics with CYCLONE FPGA chip has been chosen for this
work.The devices interfaced with the FPGA chip include configuration device (EEPROM),
ADC and DAC. Also dedicated I/O pins are also provided. The FPGA has logic elements
arranged in rows and columns. Each logic elements has certain hardware resources, which
will be utilized to realize the user logic. The vertical and horizontal interconnects of varying
3.4. Digital controller
37
speeds provide signal interconnects to implement the custom logic. The device data are
furnished in Table.3.4.
Part No
EP1C12Q240C8
Manufacturer
Altera
No of pins
240
No of I/O pins
60
Package
PQFP
No of logic elements
12,080
No of PLL
Maximum clock frequency using PLL
2
275 MHz
Power supply required for core
1.5 V (VCCINT)
Power supply required for I/O
3.3 V (VCCIO)
Power supply required for PLL circuit 1.5 V (VCCPLL)
Table 3.4: ALTERA FPGA device data
3.4.2
ADC
ADC on the board, the AD7864AS-1 of analog devices, is used to convert the analog input
signals from the system into digital signals which are used for further processing. This MQFP
packaged, 12 bit, 44-pins simultaneous sampling ADC has 4 channels with a conversion time
of 1.6µs per channel. There are four such ADCs on the board and hence can take up to
16-analog input.
3.4.3
DAC
DAC on the board,the AD5447, is used to output the digital variables in the controller in
analog form. The DAC is CMOS based working with +5V and -5V power supply. This is a
12-bit, 24 pin, dual channel, current output DAC of AD has a conversion time of 10µs.
38
3.5
Chapter 3. Power circuit for grid interface, sensor and Digital controller
Experimental set-up with digital controller
All the necessary controller transfer functions are digitally implemented in the digital controller. The relevant signals are fed into the FPGA through ADCs for processing. Once
processing is done, the digital controller subsequently produces the pertinent gate pulses for
each of the legs of converter such that system response tracks the set reference.
Figure 3.12: Experimental set-up with digital controller
3.6
Digital implementation
Implementation of all the algorithms and controllers has been done in 16-bit, 1’s complement
representation on the FPGA platform. But ADC and DAC are of 12-bits, so 4 LSB bits
are added as zeros and then properly scaled after sensing the signals to make them of 16bits. For outputting the signals through DAC, 4 LSB bits have been disregarded. 3FFF has
been chosen as 1 pu base. 16-bit by 16-bit, 32-bit output multipliers have been used. After
multiplication the 32-bit format have been retained for the state variables in integrations for
increasing the accuracy. After integration the signals have been scaled down to the 16-bit
format by shifting them 3-bits to left and and taking the 16 MSB bits.
The table 3.5 shows the digital equivalent (in Hex and Decimal formats) of the corresponding
pu value.
3.6. Digital implementation
39
pu value Equivalent Hex Value
Equivalent Decimal Value
2 pu
7F F FH
32767d
1 pu
3F F FH
16383d
0 pu
0000H
0d
-1 pu
C000H
49152d
-2 pu
8000H
32768d
Table 3.5: PU values
3.6.1
Base Values for Various Quantities
As the implementation is realized digitally, there arises the need for following a p.u system
for simple understanding. For perunitization of different quantities, their base values are
required, which can be chosen as per convenience. For example, the Table. 3.6 shows the
base values for voltage (chosen as the desired DC bus voltage), current (chosen as the peak
of the rated line current of the VSI) and frequency (chosen as grid frequency. The other base
quantities are calculated from the above mentioned base quantities.
Prated = 3kW
(3.4)
Vgrid = 240V
(3.5)
Irated = 12.5A
(3.6)
Voltage (Vb )
12.5 ∗
Current (Ib )
Frequency (fb )
√
400V
2 = 19A
50Hz
Frequency in rad/sec (ωb ) 2π ∗ fb = 314.16rad/sec
Impedance(Zb )
Vb
Ib
= 21.05Ω
Table 3.6: Base values
Every sensed quantity (i.e. VDCbus and Io ) must be perunitized inside the controller by
suitably scaling them for inerrant closed loop control. This measure is necessary when the
sensor gains are such that the sensor outputs are unperunitized in the firat place.
40
3.6.2
Chapter 3. Power circuit for grid interface, sensor and Digital controller
Transfer function implementation
Every frequency domain polynomial function that needs to be digitally implemented is first
discretized using suitable transformation procedure. A variety of discretization methods such
as Euler’s forward rule, Euler’s backward rule, Bilinear transformation, Impulse-invariant
transformation etc. are available in literature [21]. Suitable transformation technique may
be chosen for implementation. Depending on the sampling time (Ts ) used, every method
has a fixed error associated with it, when implemented . This error approaches zero as Ts
approaches zero. Of all the techniques, forward rule has the possibility of making the system
unstable, when used. Impulse-invariant gives minimal error among all.
3.6.2.1
Low pass filter
In frequency domain, a low-pass filter is represented as:
y(s)
1
=
x(s)
1 + ωsc
(3.7)
where,
1
(3.8)
τ
Here, ωc is the desired cut-off frequency. Equation.3.7 can be rewritten in time domain as:
ωc =
y(t) + τ
dy(t)
= x(t)
dt
(3.9)
Discretizing the above using Backward rule, we get,
y(k − 1) + τ
y(k) − y(k − 1)
= x(t)
Ts
(3.10)
which finally yields the equation to be implemented,
y(k) = y(k − 1) +
3.6.2.2
Ts
[x(k) − y(k − 1)]
τ
(3.11)
PI controller
In frequency domain, a PI controller is represented as:
y(s)
ki
= ks +
e(s)
s
(3.12)
3.7. Conclusion
41
Equation.3.12 can be rewritten in time domain as:
y(t) = kp e(t) + ki
Z
e(t)
(3.13)
Discretizing the above using Bilinear transformation, we get the required equation to be
implemented,
y(k) = kp e(k) +
3.6.2.3
ki
[e(k) + e(k − 1)]
2Ts
(3.14)
PR controller
Figure 3.13: Resonant controller
In frequency domain, a PR controller (whose details will be furnished in subsequent
chapter) is represented as:
y(s)
s
= kp + ki 2
e(s)
s + ωo2
(3.15)
To begin with, let us disregard the proportional term. The resonant structure would appear
as shown in the Fig.3.13. Now, Forward rule can be applied to discretize p(t) and q(t),
p(k) = p(k − 1) + ωo Ts q(n − 1) + ki e(k − 1)
(3.16)
q(k) = q(k − 1) + ωo Ts p(k)
(3.17)
So, with the proportional term included, the total output of the PR controller is given by,
y(k) = kp e(k) + p(k)
3.7
(3.18)
Conclusion
In this chapter, details pertaining to power circuit components were furnished. Non-isolated
sensor circuit design was discussed briefly. FPGA based digital controller and its attributes
were described along with per-unitization and digital implementation techniques.
Chapter 4
Single phase closed loop control
4.1
Introduction
In this chapter, all the essentials for closed loop control are dealt with in detail. Design of Single phase PLL structure based on resonant controller is discussed along with
AFEC/STATCOM operation of the power converter. Fundamentals of resonant controller
are explained. Design of current controller and voltage controller are done.
4.2
Grid interactive mode
Figure 4.1: Scheme for power transfer between two active sources
Whenever power needs to be needs to be transferred from one active source to another, it
is required that the two are of identical frequency, as shown in Fig.4.1. Grid interactive mode
of operation of a converter is basically one such situation where power is transferred from
grid to inverter or vice-versa. In AFEC mode, active power is transferred from grid to the
42
4.2. Grid interactive mode
43
converter at unity power factor . The converter here acts as an active rectifier (as opposed to
a conventional diode/thyrister based rectifier) catering DC load. Such a rectification process
is quite advantageous as the grid current harmonics are reduced to a large extent. It is also
very flexible as it allows bi-directional power flow at any desired power factor.
In STATCOM mode, the converter supplies lagging reactive power to grid thus improving
the effective power factor seen by the grid. This in turn reduces undesirable losses occurring
at generation, transmission, and distribution levels.
So, grid interface as such entails accurate tracking of grid frequency. Hence, a Phase
locked loop (PLL) is mandatory. Once tracking is done, DC bus voltage of the converter is
raised to the required value. This value, in AFEC case, depends on the application. In case
of STATCOM, this boost value depends on the maximum amount of reactive power that
needs to be supplied to the grid by the converter. Ideally, once DC bus voltage boosts, it
remains at that value even when the STATCOM is supplying rated reactive(lagging) current
to the grid. But practically, the DC bus voltage would fall due to the losses occurring in the
converter. These losses mainly include conduction and switching losses of the converter. It
case of AFEC, DC bus voltage promptly falls when the DC link is loaded, and the quantum
of fall depends on the quantum of loading. Hence, there arises a requirement to maintain
the DC bus voltage at the required (raised) value. So a control loop is required for this DC
bus voltage maintenance. It is also desirable to operate the converter as a current controlled
VSI rather than a voltage controlled VSI so as to avoid the possibility of instability [20]. So
a current control loop is required.
It is relatively easy to do such a control for a three phase power converter. Typically,
d-q control/vector control technique is employed where the three phase AC quantities are
transformed to DC through Synchronous Reference Frame (SRF) transformation. Consequently, all references become DC and hence conventional PI controllers would suffice to
yield zero steady state errors for both the aforementioned control loops. PI control design
is straightforward and well discussed in literature [15].
But, such a control is not so trivial in case of single phase systems. Here, d-q control
is not feasible since only one grid voltage is available. References are thus AC in nature.
And usage of PI controllers would result in significant gain and phase errors depending on
the bandwidth of the system. This is because, a PI controller has infinite gain only at DC
and thus loop gain will be infinite only at DC. Since infinite loop gain is essential for zero
steady-state error, a PI controller based control is satisfactory for DC quantities only. For AC
44
Chapter 4. Single phase closed loop control
references, PI controller’s performance is acceptable only for very large bandwidth systems.
At higher power levels, switching frequency is limited in order to bring down the losses in
the system. Hence system bandwidth is also limited. Again, for grid synchronisation, the
PLL structure in single phase case is not straight as it is in the three phase case.
In this work, single phase resonant PLL structure is employed for grid synchronisation
and PR controller is used for accurate AC reference current tracking. For DC bus voltage
control, conventional PI controller is sufficient.
4.3
Phase Locked Loop
Figure 4.2: A three phase PLL
In Fig.4.2, a conventional three phase PLL is shown. Vα and Vβ are stationary frame
orthogonal vectors obtained from the three phase grid voltages (through conventional 3φ to
2φ transformation).
3
(Va )
2√
3
Vβ (t) =
(Vb − Vc )
2
Vα (t) =
(4.1)
(4.2)
They are then transformed to synchronous reference frame where they get converted to DC
4.3. Phase Locked Loop
45
Figure 4.3: Phasor diagram for grid voltage alignment
quantities (viz. Vd and Vq ).

Vd



Vq

=
3
V
2
3
V
2
cos (ωt − φ)

sin (ωt − φ)

(4.3)
Now, to align the grid space phasor along q-axis, it is required to set Vd to zero. Information
about the grid voltage peak is not required. Once this alignment is done, q-axis would
correspond to real power axis and d-axis would stand for reactive power.
The open loop transfer function of the PLL and the corresponding PI controller design
has been well discussed in literature [11]. The plant transfer function and loop gain of the
system is given by,
Gplant (s) =
GHol = kpll
1
V
1 + sTs s
1 + sTpll
sTpll
!
1
1 + sTs
(4.4)
V
s
(4.5)
where, Ts is sampling time. Method of symmetrical optimum is used to calculate the controller gains [11].
ωc =
1
αTs
Tpll = α2 Ts
(4.6)
(4.7)
1 1
(4.8)
α V Ts
Fig.4.4 shows a general structure of a single phase PLL. It is quite similar to a three
kpll =
phase SRF PLL structure, except for the orthogonal vector generation block. In three
phase case, stationary frame orthogonal vectors are directly obtained from grid voltages. In
46
Chapter 4. Single phase closed loop control
Figure 4.4: A general single phase PLL structure
single phase case, an orthogonal vector corresponding to the single available grid voltage
Vg needs to be generated. Various ways of single phase PLL implementation are available
viz. transport delay method, pure integrator method, all-pass function method, inverse
Park transformation method etc. Each differs from the rest in the way of generation of the
aforementioned orthogonal vector [12].
In this work, the required orthogonal vector is generated using a resonant controller, as
shown in Fig.4.5. It can be seen that the block consists of two integrators connected back to
Figure 4.5: Resonant controller based orthogonal vector generation
4.3. Phase Locked Loop
47
back [13]. Here, ωo is fixed corresponding to 50Hz. To understand its working, it necessary
to comprehend certain transfer functions.
Vph (s)
ωo s
= 2
Vg (s)
s + ωo s + ωo2
(4.9)
0
Vqd (s)
ωo2
= 2
Vg (s)
s + ωo s + ωo2
(4.10)
Figure 4.6: Bode plot for
Vph (s)
Vg (s)
Figure 4.7: Bode plot for
Vqd (s)
Vg (s)
0
48
Chapter 4. Single phase closed loop control
The resonant controller has infinite gain at ωo which in this case corresponds to 50
Hz. Thus, error rapidly converges to zero making Vph to follow Vg . This is easily seen in
0
Equation. 4.9 whose gain is unity only at 50 Hz. Also, Vqd forms the quadrature component.
SRF transformation can now be applied.
But the setback here is that if the grid voltage happens to have a DC offset, it is directly
0
reflected in Vqd . This is evident from Fig.4.7, where the transfer function has unity gain for
DC. But this is not the case with Vph . This severely affects the performance of the PLL. Vd
0
and Vq are no longer DC quantities due do the DC offset present in Vqd and this seriously
affects the PI controller output. To deal with this, the error (which again contains the same
0
Figure 4.8: Simulated response of Vqd and Vph for a DC offset in grid voltage
0
DC offset) is filtered and subtracted from Vqd to get Vqd , which is the required orthogonal
vector. Now Vph and Vqd are our stationary frame orthogonal vectors for the single grid
voltage Vg . Now, SRF transformation may be applied to yield corresponding Vd and Vq .
Once Vd is made zero by the PI controller, grid voltage would align along q-axis and Vq
would then represent the peak of grid voltage. With θ available from the PLL, the unit
vectors can be conveniently obtained from a look-up table.
Fixing ωo to 50 Hz limits the frequency range in which the PLL would operate properly
as intended. In the present case, the PLL was found to track input frequency accurately
between 47Hz to 53Hz. Outside this range, performance was poor. Performance can be
significantly improved if the gain ωo was made adaptive depending on the PLL output ωref .
But then, for all practical purposes, this range was adequate as it accounts for the maximum
allowable grid frequency variation.
4.3. Phase Locked Loop
49
Figure 4.9: Grid voltage [CH1(Yellow)] and unit vectors [CH4(Green) and CH3(Pink)] when
PLL is enebled [CH2(Blue)]
Figure 4.10: Unit vectors [CH4(Green) and CH3(Pink)] and grid voltage [CH1(Yellow)] at
steady state
50
Chapter 4. Single phase closed loop control
Figure 4.11: In-phase unit vector [CH4(Green)] when there is a sudden dip in grid voltage
[CH3(Pink)]; CH2(Blue): Enable signal
Figure 4.12: In-phase unit vector [CH4(Green)] with DC offset in grid voltage [CH3(Pink)]
4.4. Resonant controller
4.4
51
Resonant controller
As explained in Section.4.2, a PI controller is not suitable when references are AC in nature.
Fig.4.13 shows the construct of a resonant controller [10]. Its transfer function is given by,
p(s)
s
= ki 2
e(s)
s + ωo2
(4.11)
Figure 4.13: A resonant controller
Figure 4.14: Bode plot of resonant controller (with resonance at 50Hz
It could be considered as a generalised integrator with a resonance at ωo . When ωo is set
to zero, it reduces to an ordinary integrator. The gain of the function tends to infinity a ωo .
Hence by suitable selecting ωo , it is possible to achieve very large loop gain for 50Hz and
negligible loop gain for other frequencies. Thus, it tracks the required 50Hz AC reference.
52
4.4.1
Chapter 4. Single phase closed loop control
Proof
To prove this more rigorously, internal model principle [9] may be used. The principle states
that the output of a control object follows its reference without a steady state error if the
open-loop transfer function of the system includes a mathematical model which can generate
the required reference. In a PI controller, the integrator ( 1s ) is the mathematical (frequency
domain) model for a DC quantity. Thus it achieves zero steady state error for DC references.
So, we need a sinusoidal model (such as the one in Equation.4.11) in the controller to achieve
zero steady state error for sinusoidal reference. Consider a simple system shown in Fig.4.15.
Figure 4.15: A simple control system
Gol (s) = G(s)H(s) =
N (s)
D(s)
(4.12)
For sinusoidal reference,
U (t) = Acos(ωt)
As
U (s) = 2
s + ωo2
(4.14)
U (s)
D(s)U (s)
=
1 + Gol (s)
D(s) + N (s)
(4.15)
D(s)
As
(s − p1 )(s − p2 )..(s − pn ) s2 + ωo2
(4.16)
E(s) =
=
(4.13)
where pi 0 s are the poles of a general nth order system with all Re(pi ) < 0. Using partial
fraction expansion, error can also be represented as,
E(s) =
a1
an
b1
b2
+ ..
+
+
(s − p1 )
(s − pn ) (s + jωo ) (s − jωo )
(4.17)
where,
b1 = (s + jωo )E(s)|s=−jωo
(4.18)
4.4. Resonant controller
53
b1 = (s − jωo )E(s)|s=+jωo
(4.19)
This yields,
b1 , b2 =
A
D(±jωo )
2 D(±jωo ) + N (±jωo )
(4.20)
If the open loop transfer function has +jωo and −jωo as poles, then,
0
D(s) = (s2 + ωo2 )D s
(4.21)
D(±jωo ) = 0
(4.22)
b 1 = b2 = 0
(4.23)
and this means,
This makes ,
Thus, from Equation.4.17, the error function converges to zero asymptotically.
4.4.2
Testing of resonant controller
A first order test plant with sinusoidal reference as shown in Fig.4.15 was used to verify
the above result. The converter was ran in standalone mode with just a current controller.
System specifications are listed in Table.4.2
Parameter Specification
Vdcbus
400V
R
10Ω
L
45mH
fp
35.3Hz
fBW
353Hz
kp
100
ki
44444.44
ωp
222.22
ωo
100π
Table 4.1: Test system specifications
54
Chapter 4. Single phase closed loop control
Plant transfer function is given by,
G(s) =
0.1
1 + ωsp
(4.24)
Transfer function of the PR controller used is given by,
H(s) = kp + ki
s2
s
+ ωo2
(4.25)
Figure 4.16: Error function comparison for a reference of 10A through simulation
Figure 4.17: Output current[CH3(Pink)] with PR current controller for a reference of 10A;
CH4(Green): Reference; CH3(Blue): Feedback
4.5. DC bus voltage determination
55
Figure 4.18: Bode plot for a PR controller set to track 50Hz reference
The current controller was found to track the reference accurately. For controller gains
calculation, firstly a PI controller (i.e. a DC compensation network) is designed. Subsequently, it is transformed into an equivalent AC compensation network (with generalised
integrator) as suggested in [8]. This yields,
4.5
kp |P R = kp |P I
(4.26)
ki |P R = 2ki |P I
(4.27)
DC bus voltage determination
Before closing the loop, it is essential to know the boost level of DC bus voltage so as to
set reference for the control loop. As mentioned before, this value depends on application in
case of AFEC. In case of STATCOM, it needs to be predetermined. Fig.4.19 illustrates the
relevant calculation.
To begin with, a 10% drop across the filter inductance may be assumed. It may be
note from the phasors that the burden on the DC bus is more in case of STATCOM when
compared to AFEC. This is because the filter drop adds algebraically to the grid voltage,
whereas with AFEC, it is a phasor addition. For a 3 kW operation, considering the worst
(STATCOM) case,
Vi(peak) = Vdcbus = Vg(peak) + ωLIg(peak)
(4.28)
56
Chapter 4. Single phase closed loop control
Figure 4.19: Phasor diagram for DC bus voltage evaluation
Prated
3kW
Vrated
240V
Irated
12.5A
fsw
9.76Hz
Ts
25.6µs
Table 4.2: Rated system specifications
4.6
√
√
= 240 2 + 0.1 × 240 2 ⇒ 373.35V
(4.29)
Assume Vdcbus = 400V
(4.30)
Overall control structure and strategy
The overall control structure for AFEC/STATCOM mode of operation is shown in Fig.4.20
4.6. Overall control structure and strategy
57
Figure 4.20: Overall control structure for single phase AFEC/STATCOM
4.6.1
Control strategy
In a conventional three phase case where d-q control is employed, Iq and Id represent real current and reactive current reference respectively (in synchronous reference frame), provided
the grid spacer is aligned along q-axis [24]. For brevity, same notation is being followed
here. However, in this case they represent the actual peak values of real and reactive current
references respectively in stationary reference frame. In the three phase case, SRF transformation enables decoupling of active and reactive currents and hence makes independent
power control possible. In the present case, such an isolation is achieved with the help of
PLL which produces unit vectors in phase and quadrature with the grid voltage.
The control structure has an outer voltage loop for maintaining the DC bus voltage at the
desired (calculated) value. A PI controller is employed in the loop as the reference here is DC.
Since the active power requirement in the system is directly reflected as fall in the DC bus
voltage, the output of the outer voltage loop is taken as the peak of active current reference
( denoted as Iq∗ ). The corresponding active AC current reference is obtained by merely
multiplying the in-phase unit vector with Iq∗ . In AFEC case, this reference is determined
by the quantum of loading on the DC side. In STSTCOM case, this reference is very small
catering the losses in the converter.
Reactive current reference depends on the desired operating power factor in case of AFEC
and on the amount of reactive power compensation desired, in case of STATCOM. The
58
Chapter 4. Single phase closed loop control
reactive current reference again is obtained by merely multiplying the quadrature unit vector
with Id∗ as illustrated in Fig.4.20. Desired Id∗ may be set externally in the controller. But
this is not the case with Iq∗ , as it is set by the voltage controller.
Since the current references are AC quantities, a PR controller is employed for the inner
current loop which is set to have a resonance at 50Hz . For inerrant operation of the system,
the inner current loop needs to be quire faster than the outer voltage loop [15], [24]. Typical
relationship used is,
fBW (inner)
10
fSW
fBW (inner) ≤
10
fBW (outer) ≤
4.6.1.1
(4.31)
(4.32)
Feed-forward terms
Feed-forward essentially helps in improving the dynamic performance of the system and
completes the decoupling of active and reactive currents. Typically DC load current feedforward (for voltage loop), inductive drop feed-forward and grid voltage feed-forward (VgF F )
(for current loop) are employed [14]. Here, only current loop feed-forward terms are being
used as illustrated in Fig.4.20. The inductive drop feed-forward terms to be added can be
readily obtained from the phasor diagram (Fig.4.19). To begin with, when control is not
enabled, due to VgF F which is same as the grid voltage, no power transfer takes place between
the two active sources. Once control is enabled, depending on the system conditions and
references, the controller produces adequate output above/below VgF F so as to make the
system response follow the references.
4.7
Current controller design
The design procedure here is similar to that of a three phase case [24]. The relevant plant
transfer function is given by,
G(s) =
ii (s)
1
=
Vi (s)
Rf + sLf
(4.33)
As mentioned in the foregoing section, to design a PR-controller, it is essential to design a
conventional PI controller first. The PI controller transfer function is given by,
0
H(s) = kp
1 + sTc
sTc
(4.34)
4.8. Voltage controller design
59
Figure 4.21: Current control loop
0
0
where ki =
kp
Tc
0
kp
1
G(s)H(s) =
=
sTbw
sTc Rf
Tc =
(4.35)
Lf
Rf
(4.36)
Lf
Tbw
(4.37)
The desired constants are,
0
kp =
0
ki = kp ωbw
(4.38)
Therefore, the constants for PR-controller are,
kp =
Lf
Tbw
ki = 2kp ωbw
4.8
(4.39)
(4.40)
Voltage controller design
For voltage controller design, the gain of inner current loop can be assumed to be unity
(from Eq.4.31 and Eq.4.32). To begin with, the same design methodology as that of a three
Figure 4.22: Voltage control loop
60
Chapter 4. Single phase closed loop control
phase case is adopted.
Vl−l(rms)
Idc
= √
Iac
2Vdc
1
kkv
=
sC
sTv
√
2CVdc
kv =
Vl−l(rms) Tv
k=
(4.41)
(4.42)
(4.43)
The voltage controller gains were slightly varied from design values to achieve satisfactory
system response. The design values are listed in Table.4.3
fsw
10kHz
fbw(inner)
600Hz
kp
4.68
ki
5616
fbw(outer)
8Hz
kv
2.5
Tv
120ms
Table 4.3: Control loop design data
4.9
Conclusion
In this chapter, closed loop control strategy is explained in detail. Design of single phase
resonant PLL, PR controller and PI controller for grid interactive mode of operation of the
converter is discussed. The converter was run in both AFEC and STATCOM mode and
the injected grid current was examined for harmonics. Experimental results are furnished in
forthcoming chapter.
Chapter 5
Results and conclusion
5.1
Introduction
In this chapter, some of the experimental results which were used to verify the transfer
function model developed for the proposed filter-transformer and its performance as a higher
order filter are discussed. The frequency response characteristics of the filter-transformer
configuration are obtained from a network analyzer. Experimental results pertaining to grid
interactive mode of operation of the power converter (with the proposed filter-transformer)
are furnished. Additionally, Fourier analysis results for the relevant output currents are
presented. Finally, conclusions are drawn.
5.2
Frequency response characteristics
Here, based on the developed transfer function model of the filter-transformer, simulated
frequency response of various transfer functions is presented. Also, the frequency response
was measured using an analog network analyzer manufactured by AP Instruments. The
network analyzer has a frequency range from 0.01 Hz to 15 MHz, with a maximum output
of 1.77V. Current measurements were made with Textronix TCP300 AC/DC current probe.
All the transfer functions of the filter-transformer as detailed in chapter 2 were measured
in the frequency range of 10 Hz to 1 MHz with atleast 1000 data points, each point averaged
40 times. The actual output of the network analyzer are compared with simulated frequency
response
61
62
Chapter 5. Results and conclusion
Figure 5.1: Simulated frequency response of O.C secondary voltage (Vs (s)) to primary voltage
(Vi (s))
Figure 5.2: Measured frequency response for O.C secondary voltage (Vs (s)) to primary
voltage (Vi (s))
5.2. Frequency response characteristics
63
Figure 5.3: Simulated frequency response of injected grig current to inverter voltage ( VIgi (s)
)
(s)
with Vg = 0
Figure 5.4: Measured frequency response of injected grig current to inverter voltage ( VIgi (s)
)
(s)
with Vg = 0
64
Chapter 5. Results and conclusion
Figure 5.5: Simulated frequency response of inverter current to inverter voltage ( VIii(s)
) with
(s)
Vg = 0
Figure 5.6: Measured frequency response of inverter current to inverter voltage ( VIii(s)
) with
(s)
Vg = 0
5.3. Standalone mode
5.3
65
Standalone mode
Here, the filter-transformer’s performance with and without the third winding (AW) are
shown under open secondary (SW) condition. Without AW, the structure is similar to a
simple first order L-filter. With the third winding, the structure exhibits a higher order filter
behaviour as seen in the foregoing chapter.
Figure 5.7: CH1(Yellow):Applied primary (inverter) voltage; CH2(Blue): Secondary (output) voltage; Without AW
Figure 5.8: CH1(Yellow): Primary voltage; CH2(Blue): Secondary voltage; With AW
66
5.4
Chapter 5. Results and conclusion
Grid interactive mode
The power converter was interfaced with grid through the proposed integrated filter-transformer.
Experimental results pertaining to its performance with and without the third winding (AW)
under STATCOM and AFEC modes of operation are presented. Tektronix TPS 2024 DSO
was employed to capture the results.
5.4.1
Operation as a two-winding transformer
Here, the structure is operated without the third winding (AW). Thus, the structure behaves as a first order L-filter. The corresponding inverter and grid currents under different
operating conditions are captured and presented.
Figure 5.9: CH1(Yellow,1A/div): Grid current; CH2(Blue,0.1A/div): Inverter current;
CH3(Pink): Sensed grid voltage; With control not enabled
5.4. Grid interactive mode
67
Figure 5.10: CH1(Yellow,50V/div): DC bus voltage boost profile; CH2(Blue): Enable signal
Figure 5.11: CH1(Yellow,2A/div): Grid current; CH2(Blue,5A/div): Inverter current;
CH4(Green): Grid unit vector; with control enabled, 0A reference
68
Chapter 5. Results and conclusion
Figure 5.12: CH2(Blue,5A/div): Inverter current; CH4(Green,2V/div): Grid unit vector; In
STATCOM mode at 90% load
Figure 5.13: CH1(Yellow,5A/div): Grid current; CH4(Green,2V/div): Grid unit vector; In
STATCOM mode at 90% load
5.4. Grid interactive mode
5.4.2
69
Operation as a three-winding transformer
Here, the proposed structure is operated with the third winding (AW). Now, the structure
behaves as a higher order filter.The corresponding inverter and grid currents under different
operating conditions are captured and presented.
Figure 5.14: CH1(Yellow,50V/div): DC bus voltage boost profile; CH2(Blue): Enable signal
70
Chapter 5. Results and conclusion
Figure 5.15: CH1(Yellow,2A/div): Capacitor current; CH2(Blue,2A/div): Inverter current;
CH3(Pink): Sensed grid voltage; with control enabled, 0A reference
Figure 5.16: CH1(Yellow,2A/div): Grid current; CH2(Blue,5A/div): Inverter current;
CH4(Green): Grid unit vector; with control enabled, 0A reference
5.4. Grid interactive mode
71
Figure 5.17: CH1(Yellow,50V/div): DC bus voltage ripple; CH2(Blue,5A/div): Grid current;
CH3(Pink,5A/div): Inverter current; CH4(Green,2V/div): Grid unit vector; with control
enabled, 80 % load
Figure 5.18: CH1(Yellow,50V/div): DC bus voltage ripple profile; CH3(Pink): Enable signal
for Current reference change from 25% to 90%
72
Chapter 5. Results and conclusion
Figure 5.19: CH2(Blue,5A/div): Inverter current; CH4(Green,2V/div): Grid unit vector;
with control enabled, 90% current reference at 0 p.f (leading)
Figure 5.20: CH1(Yellow,5A/div): Grid current; CH4(Green,2V/div): Grid unit vector;
with control enabled, 90% current reference at 0 p.f (leading)
5.4. Grid interactive mode
73
Figure 5.21: CH2(Blue,10A/div): Inverter current; CH4(Green,2V/div): Grid unit vector;
with control enabled, 90% current reference at 0 p.f (lagging)
Figure 5.22: CH1(Yellow,10A/div): Grid current; CH4(Green,2V/div): Grid unit vector;
with control enabled, 90% current reference at 0 p.f (lagging)
74
Chapter 5. Results and conclusion
Figure 5.23: CH2(Blue,5A/div): Inverter current; CH4(Green,2V/div): Grid unit vector;
with control enabled, AFEC UPF operation
Figure 5.24: CH1(Yellow,5A/div): Grid current; CH4(Green,2V/div): Grid unit vector;
with control enabled, AFEC UPF operation
5.4. Grid interactive mode
75
Figure 5.25: CH2(Blue,10A/div): Inverter current; CH4(Green,5V/div): Grid unit vector;
with control enabled, AFEC operation with 10% reactive (leading) current reference
Figure 5.26: CH1(Yellow,10A/div): Grid current; CH4(Green,5V/div): Grid unit vector;
with control enabled, AFEC operation with 10% reactive (leading) current reference
76
Chapter 5. Results and conclusion
5.5
Harmonic analysis
Most utilities insist that current harmonic limits (as dictated by IEEE 519-1992 system
standard) should be met at the point of common coupling of non-linear equipments. In
the present case, it is a power converter. Hence, to measure the efficacy of the integrated
filter-transformer, harmonic analysis is necessary. Total demand distortion (TDD) of the
injected grid current is quantity of interest here, which is given by,
q
IT DD =
I22 + I32 + I42 ...
× 100%
Irated
(5.1)
TDD is a better way to measure current distortion as it is independent of fundamental
current and hence the operating point of the system. Data points of relevant currents
were captured and further processing (in MATLAB 7.0) was done to obtain their respective
harmonic spectrums.
Here, results pertaining to harmonic analysis and TDD value for inverter and grid currents
under two-winding and three-winding operation of the filter-transformer in STSTCOM mode
is presented.
Figure 5.27: Inverter current under two-winding operation
5.5. Harmonic analysis
Figure 5.28: Inverter current harmonics under two-winding operation
Figure 5.29: Grid current under two-winding operation
77
78
Chapter 5. Results and conclusion
Figure 5.30: Grid current harmonics under two-winding operation
Figure 5.31: Inverter current under three-winding operation
5.5. Harmonic analysis
Figure 5.32: Inverter current harmonics under three-winding operation
Figure 5.33: Grid current under three-winding operation
79
80
Chapter 5. Results and conclusion
Figure 5.34: Grid current harmonics under three-winding operation
Current(T DD)
Two-winding operation Three-winding operation
Ii(T DD)
7.9%
9%
Ig(T DD)
7.8%
5.2%
Table 5.1: TDD comparison
Resonant peak,valley/Transfer function
ig (s)
vi (s)
ii (s)
vi (s)
vs (s)
vi (s)
fpeak (calculated)
5.14kHz 5.14kHz
3.3kHz
fpeak (measured)
5.4kHz
5.9kHz
3.37kHz
fvalley (calculated)
20kHz
4.04kHz
20kHz
fvalley (measured)
18kHz
4.25kHz
16kHz
Table 5.2: Comparison of theoretical and practical resonance/anti-resonance frequencies
5.6. Conclusion
5.6
81
Conclusion
It was intended to emulate a discrete higher order LCL-filter with an integrated magnetic
structure. A multi-winding transformer configuration was proposed to serve the purpose. An
appropriate equivalent circuit was developed for obtaining the pertinent transfer functions.
From the so obtained transfer functions, it was found that the proposed structure did not
emulate a LCL-filter entirely from output current perspective due to the presence of zeros.
Nevertheless, from the input current perspective, it was similar to a LCL-filter. Hence control
strategy for the filter-transformer remained the same as that of a LCL-filter.
Initially, core-type transformers were investigated for the purpose of magnetic integration.
Later, it was found unsuitable for the application in hand. Hence, a single phase shell-type
3kVA three winding transformer was built and tested. The measured transfer functions of
the transformer (through network analyzer) closely matched the theoretically predicted ones
(from the equivalent circuit). Since the equivalent circuit model of the structure disregarded
winding resistances, the developed transfer functions had no damping terms in them. As
a result, frequency responses in simulation had much greater resonant/anti-resonant peaks
than those obtained from the network analyzer, since winding resistances are practically
finite.
To verify the effectiveness of the filter-transformer, a grid connected operation of a single
phase power converter was necessary. A three phase power converter was operated in single
phase H-bridge configuration as a STATCOM. A resonant controller based single phase PLL
was implemented to track grid frequency. It was found to function well in a rather small input
frequency range of 47Hz to 53Hz. This performance was adequate to track grid frequency.
Proportional-resonant current controller was employed to ensure zero steady state errors for
AC references. Its performance was very effective. Conventional PI controller was employed
for regulation of DC bus voltage at 400V.
A closed loop control of the power converter interfaced with the grid through the integrated filter-transformer was done using FPGA based digital controller. The transformer
was operated in two-winding configuration (without AW) emulating a first order L-filter and
in three-winding configuration (with AW) emulating a higher order filter. The corresponding inverter and grid currents were examined. With two-winding configuration, there was
no noticeable difference between the inverter current and grid current as far as the switching
harmonics were concerned. In contrast, with the third winding in place, notable reduction
82
Chapter 5. Results and conclusion
in grid current switching harmonics was observed. The structure’s performance was found
to be much better than a first-order L-filter. In all the cases, the two currents were found to
contain (mild) lower order harmonics that caused distortions in and around zero-crossings.
In terms of the total RMS value and third harmonic magnitude, the inverter side and grid
side currents differed slightly due to the peaky magnetizing current of the transformer (which
was not negligible in magnitude). The grid current was found to have slightly higher third
harmonic content and slightly lower total RMS value. The proposed structure and the controllers were found to perform satisfactorily. DC bus voltage was found to contain 100Hz
ripple (over 400V DC value) which increased with increase in operating AC line current
magnitude. However, the oscillation was within acceptable limits of 5%. This behaviour is
an outcome of single phase operation of the power converter.
References
[1] Parikshith.B.C, Dr. Vinod John,“ Higher order filter design for grid connected power
converters ”, Fifteenth National Power Systems Conference ,IIT Bombay, 2008
[2] Pleite. J, Valdivia. V, Zumel. P, Gonzalez. C,“ Transformer and series inductance integration for harmonic filtering in PWM inverters based on a simple design procedure ”,
IEEE International Symposium on Industrial Electronics, 2007.
[3] Valdivia. V, Pleite. J, Gonzalez. C, Salas. R,“ New approach to integrate an LCL filter
and a transformer for grid connected converters following a simple design procedure ”,
33rd Annual Conference of the IEEE Industrial Electronics Society (IECON), 2007.
[4] M. Van der Veen,“ Power Transformer with Internal Differential Mode Distortion cancellation ”, United States Patent 6,087,822, July 2000.
[5] Doebbelin. R, Benecke. M, Lindemann. A,“ Calculation of Leakage inductance of CoreType Transformers for Power Electronic Circuits ”, 13th International Power Electronics
and Motion Control Conference (EPE-PEMC), 2008.
[6] V.K. Lebedev,“ Calculation of the short-circuit resistance of welding transformers with
yoke leakage (russ.) ”, Automatic welding (Avtomaticeskaja Svarka) Kiev, vol. 11 (4),
1958.
[7] M. Van der Veen,“ Power Transformer with Internal Differential Mode Distortion cancellation ”, United States Patent 6,087,822, July 2000.
[8] Daniel Nahum Zmood, Donald Grahame Holmes,“ Stationary Frame Current Regulation of PWM Inverters with Zero Steady-State Error ”, IEEE Transactions on Power
Electronics, vol. 18 (3), 2003.
83
84
References
[9] Fukuda S, Yoda T,“ A novel current-tracking method for active filters based on a sinusoidal internal model ”, IEEE Transactions in Industrial Applications, vol.37(3), 2001.
[10] R. Teodorescu, F. Blaabjerg, M. Liserre and P.C. Loh,“ Proportional-resonant controllers and filters for grid-connected voltage-source converters ”, IEE Proc.-Electr. Power
Appl., Vol. 153, No. 5, September 2006.
[11] V.Kaura, and V.Blasko,“ Operation of a phase locked loop system under distorted utility
conditions ”, IEEE trans. On Industry Applications, vol.33 n0.1, pp.58-63, 1997.
[12] M. Ciobotaru, R. Teodorescu and F. Blaabjerg,“ Improved PLL structures for singlephase grid inverters ”, Proc. of PELINCEC05, 6 pages, paper ID 106.
[13] M. Ciobotaru, R. Teodorescu and F. Blaabjerg,“ A new single-phase PLL structure
based on second order generalized integrator ”, IEEE PESC 2006, Jeju, Korea, p. 15111516.B
[14] K. Thiyagarajah, V.T Ranganathan, B.S.R Iyengar,“ A high switching frequency IGBT
PWM rectifier/inverter system for AC motor drives operating from single phase supply ”,
IEEE Transactions on Power Electronics, vol. 6, No. 4, 1991.
[15] V.T. Ranganathan ,“Vector control of AFEC systems”, Lecture notes of Electric Drives,
IISc Bangalore.
[16] Udaya kumar ,“Power Transformers”, Lecture notes of High Voltage Power Apparatus,
IISc Bangalore.
[17] Blume L.F., Boyajian A, Camilli G, Lennox T.C., Minneci S, and Montsinger V.M,
Transformer Engineering, John Wiley and Sons, New York, and Chapman and Hall,
London, 1951.
[18] S.V Kulkarni, S.A Khaparde, Transformer Engineering- Design and Practice, Marcel
Dekker,Inc, 2004.
[19] Ned Mohan, T.M Undeland, W.P Robbins, Power Electronics- Converters, Applications
and Design, Wiley India (P)Ltd., Third edition, 2006.
[20] Muhammad.H Rashid, Power Electronics Handbook, Academic press , 2001.
References
85
[21] G.F Franklin, J.D Powell, M.L Workman, Digital Control of Dynamic Systems, AddisonWesley Publishing company , Second edition, 1990.
[22] G.S. Ramana Murthy, “Design of Transformers and Inductors at Power Frequency- A
modified Area-Product method”, M.Sc (Engineering) thesis, EE Dept, IISc, Bangalore,
March 1999.
[23] Parikshith B.C, “Integrated approach to filter design for grid connected power converters”, M.Sc (Engineering) thesis, EE Dept, IISc, Bangalore, March 2009.
[24] Vijay Venkatesh Kannan, “STATCOM and Active filter”, M.E. thesis, EE Dept, IISc,
Bangalore, March 2009.
[25] Parag A.R, Jayalakshmi, Ravi Krishna, “FPGA Board document, Ver.1.3”, EE Dept,
IISc, Bangalore, February 2007.
[26] “Three-phase 10kVA Inverter”, Hardware design manual, EE Dept, IISc, Bangalore,
February 2007.
Download