SEDAC TECH NOTE Variable Frequency Drives TN 11-01: Revised November 2011 A variable frequency drive (VFD) is a type of adjustable speed drive used to control the rotational speed of an alternating current electric motor by adjusting the frequency and voltage applied to the motor. Electric motors drive many types of equipment, including fans, pumps, and air compressors. Motor-driven equipment accounts for 64% of the electricity consumed by U.S. industry, according to the U.S. Department of Energy1. Although equipment can generally operate at velocities less than the maximum design speed, motors typically drive equipment at a constant rate. Flow and pressure are regulated through the use of a throttling device, such as a valve, damper, or bypass. A variable frequency drive provides a more efficient way to control varying flow rates and pressures. VFDs are also often called variable speed drives, variable frequency inverters, or frequency converters. VFDs are used for motor control in diverse applications. Before investing in VFDs, consider the type of load and potential benefits. Motor loads fall into three categories: constant torque loads, constant horsepower loads, and variable torque loads. Constant torque loads have torque that remains constant regardless of the speed at which the system is running. This category of load includes conveyors, extruders, positive displacement pumps, and compressors. The advantages of VFDs for this application are precise speed control, soft starts and stops, and energy savings from low speed operation. Constant horsepower loads are loads in which power does not vary, regardless of speed. The torque here varies inversely with the speed of the motor. Examples of constant horsepower loads include lathes, drilling, and milling. Since power remains constant for this application, a VFD would not achieve any energy savings, though qualitative benefits could still be realized. Here, qualitative benefits refer to non-quantifiable factors, such as better process control. Ideally, variable torque loads maintain torque that varies directly with the speed squared, and power that varies directly with the speed cubed. Since fan and pump efficiencies decrease at reduced speeds, the Commercial Energy Auditing Reference Handbook suggests it is more accurate to assume the power varies with the speed squared.4 As a result, a reduction in speed significantly decreases motor energy use and demand. For example, decreasing motor speed by 10% reduces required power by 19%. Due to the energy savings potential, VFDs are most commonly used for this load type. Typical applications are centrifugal fans, blowers, and pumps. Additional benefits are more precise process control and maintenance savings from reduced stress on the system. “ITP BestPractices: Motors, Pumps and Fans.” EERE: EERE Server Maintenance; 20 Dec 2010. <http://www1.eere.energy.gov/industry/bestpractices/motors.html> 2 www.oregon.gov/ENERGY/CONS/Industry/docs/AuditGuide.pdf?ga=t 3 “Variable Frequency Drives Introduction.” Office of Energy Efficiency. Web. 20 Dec. 2010. <http://oee.nrcan.gc.ca/industrial/equipment/vfd-ref/index.cfm?attr=24> 1 BENEFITS OF VFDS The use of variable frequency drive control offers several advantages. The most significant benefit is its potential to reduce electrical energy consumption and demand from motor-driven processes. Figure 1 below compares the relative power requirements of a fan at different flow rates, using three types of throttling control: outlet damper control, variable inlet vane control, and VFD control. Although VFDs save far more energy than throttling, the technology has not yet achieved widespread adoption. According to the Bonneville Power Administration, throttling continues as “one of the most common and inefficient methods to control a fan or pump.” 2 120% % of Design Power A P P L I C AT I O N S 100% 80% 60% 40% 20% 0% 50 Outlet Damper 75 % Flow Inlet Vanes 100 VFD Figure 1. Comparison of relationship between power and flow for different fan control types.3 Variable frequency drives also have the potential to reduce system maintenance and related costs. Control with a VFD affords the capability to “soft start” a motor, which means the motor can be brought up to its running speed slowly rather than abruptly starting and stopping. Soft starting a motor results in less mechanical stress on equipment and, over time, less maintenance is required. Similarly, running the motor at lower speeds extends the lifetime of other equipment components, including shafts and bearings. Note that variable frequency drives have the potential to fail, and a manual bypass should be included so that the motor can operate in case the VFD fails. 4 Doty, Steve. Commercial Energy Auditing Reference Handbook. Lilburn, GA: Fairmont, 2008. SMART ENERGY DESIGN ASSISTANCE CENTER PROVIDING EFFECTIVE ENERGY STRATEGIES FOR PUBLIC AND PRIVATE BUILDINGS IN ILLINOIS COSTS Costs for a variable frequency drive vary significantly, dependent upon the application and features required, such as horsepower (HP). According to the RS Means Mechanical Cost Data 2011, installation costs start at approximately $642 per HP for a 3 HP drive and level off at roughly $101 per HP for a 200 HP drive.5 In addition to the drive itself, installation cost may include cable and conduit, foundations, and labor expenses.6 Due to these costs, SEDAC recommends investigating the application of VFDs for motors that: (1) are greater than 1HP (2) run 2000 hours or more per year and (3) can have their speed reduced. E XA M P L E Consider a 20-horsepower motor that drives a centrifugal pump. The pump operates at full speed for 365 days annually, 24 hours each day. The operational cost is calculated with the following formula: ADDITIONAL RESOURCES Bonneville Power Administration Offers calculator to estimate savings from the installation of VFDs on pumps and fans. www.bpa.gov/Energy/N/industrial/xls/ ASDCalculators.xls U.S. Department of Energy Industrial Technologies Program: BestPractices Find tip sheets, case studies, software, and other resources for motors and drives. www1.eere.energy.gov/industry/bestpractices/ motors.html So, when constantly running at 100% speed (and assuming $0.10/kWh), the cost is: Natural Resources Canada Provides an introduction to VFDs as well as a guidebook and case studies. Since this particular pump accommodates a varying load, the pump does not need to be run at full speed throughout the day and therefore, a variable frequency drive can be employed to reduce the pump motor speed. The pump load schedule is: 20% of the time at 50% full speed; 50% of the time at 80% full speed; and 30% of the time at 100% full speed. Very often, the savings from the installation of a VFD to control a motor are estimated using the pump affinity laws, which estimate that the power required by a motor is proportional to the cube of the speed. To account for a decrease in fan and pump efficiencies when run at reduced speeds, the Commercial Energy Auditing Reference Handbook suggests using a modified affinity law to estimate savings, as follows: 4 http://oee.nrcan.gc.ca/industrial/equipment/ vfd/vfd.cfm?attr=24 At 50% speed for 20% of the time: At 80% speed for 50% of the time: FIND ENERGY INCENTIVES Public bodies: DCEO - ILLINOIS ENERGY NOW $92 per motor HP for chillers, pumps, fans. Customers of: COMED - SMART IDEAS® $25 per motor HP for chiller, $60 per motor HP for fans and pumps, or $100 per motor HP for air compressors. AMEREN IL - ActOnEnergy® $90 per motor HP for pumps and fans SEDAC Who We Are The Finally, at 100% speed for 30% of the time: @% 20 0.746 ⁄ 30% 8760 $0.10/ $3,921 Annual cost savings from installing a VFD on this motor are: Based on an estimated installation cost of $4,025 from RS Means, this application would have a simple payback of approximately 0.93 years. Mossman, Melville. RSMeans Mechanical Cost Data 2011. Kingston, MA: R.S. Means, 2010. www.oregon.gov/ENERGY/CONS/Industry/docs/AuditGuide.pdf?ga=t 5 6 www.SEDAC.org | 1-800-214-7954 | info@SEDAC.org Smart Energy Design Assistance Center 1 Saint Mary’s Road, Champaign, IL 61820 Smart Energy Design Assistance Center provides no-cost advice and analyses to Illinois private and public facilities to increase economic viability through the efficient use of energy resources. SEDAC is sponsored by the Illinois Department of Commerce and Economic Opportunity in partnership with ComEd and Ameren Illinois Utilities. SEDAC is an applied research unit of the School of Architecture at the University of Illinois at Urbana Champaign and is supported by the 360 Energy Group.