Variable Frequency Drives

advertisement
Variable
Frequency Drives
Table of Contents
PRODUCT
PRODUCT CODE
RESOURCE DOCUMENTS PAGE #
Variable Frequency Drives
Introduction
C-3
BT300 HVAC Drives
C-5
BT300
NEW!
154-126
BT300
C-15
Legacy SED2 Variable Frequency Drives
SED2
154-042
C-19
Legacy SED2 Variable Frequency Drives with Bypass Options
SED2
154-044, 154-041
C-23
Legacy SED2 Variable Frequency Drives
NEMA Type 3R & Type 3R Harsh Environment Bypass
SED2
154-062
C-29
BT300 HVAC Drives with Bypass Options
NEW!
Accessories & Service Kits
C-35
C-1
Variable Frequency Drives
www.usa.siemens.com/hvac
Variable Frequency Drives
C-2
www.usa.siemens.com/hvac
Introduction
Variable Frequency Drives
C-3
While constantly expected to do more with less, managing energy consumption and optimizing occupant comfort
remains of utmost importance to facility managers. They also require products that will integrate seamlessly into existing
equipment and building management systems. The highly efficient BT300 delivers all this and more.
The BT300 comes standard with unique and industry-leading features:
• View/Monitor nine parameters at one time – user selectable, users determine the parameters for their applications
• Thin Film Capacitors – eliminate the need to condition or reform the capacitors before applying power
• Smallest Type 12 footprint on the market – lower shipping cost and easy installation
• Motor Switch Ride Through – during maintenance the motor maintenance switch can be opened and closed
without stopping or tripping the drive
www.usa.siemens.com/hvac
Variable Frequency Drives
Siemens, a global leader in drives technology, is raising the bar with new BT300 Variable frequency Drives that are
designed specifically for the demands of today’s HVAC systems. Increased focus on energy efficiency of variable flow
systems has increased the need for easy-to-use and highly reliable variable frequency drives that reduce the cost of
installation and maintenance while maximizing energy savings. Siemens Industry’s BT300 HVAC drives are designed
to meet the demands of today’s HVAC systems. An increased focus on energy efficiency of variable flow systems has
increased the need for easy-to-use and highly reliable variable frequency drives that reduce the cost of installation and
maintenance while maximizing energy savings.
Variable Frequency Drives
C-4
We’re happy to assist you
Our customer support teams are accessible and happy
to assist you with ordering, fulfillment, and shipping
questions. Call a representative at 1-800-516-9964
from 7 am to 5:30 pm (CST) Monday through Friday.
Contact Customer Support or your Account Executive
with any questions. We appreciate your business and
look forward to helping you!
www.usa.siemens.com/hvac
BT300
BT300 Variable
Frequency Drives
Important Note:
VFD products are only available
through authorized distribution
channels. To locate an authorized
distributor, please contact a
Siemens Building Technologies
representative at: 1.800.516.9964.
Energy &
Atmosphere
Description
Features
• Motor Switch Ride Through – during maintenance
the motor maintenance switch can be opened and
closed without stopping or tripping the drive
• Thin Film Capacitors – eliminate the need to condition
or reform the capacitors before applying power
• Intuitive graphical keypad with multilingual display
• Monitor nine user-defined values at one time
• Built-in wizards for faster start-up and easy setup of advanced functions
• Integrated harmonic filters on the DC link reduce noise
and interference and eliminate the need for additional
filters and reactors
C-5
• Built in fire mode controller
• Energy Savings with > 97.5% efficiency
• Optimized cooling fan runs only when needed
• Belt failure detection with or without an external sensor
• Accepts a wide variety of digital and analog I/O types,
including direct Ni 1000 RTD sensor level inputs
• One common interface throughout all power ranges
• Two form C relays
• RoHS Compliant
• Smallest Type 12 footprint on the market – lower
shipping cost and easy installation
Options
• LON Interface
• Flange Mounting Kits for Frame Sizes 4-7
• Built-in plain text help and maintenance manual shows possible causes and suggested remedies
• Varnished I/O Option Boards
• Real time clock allows up to five calendar-based
schedules and three timer inputs
• PC Cable for NET Tool, USB to RS-485,
cable length 9.8 ft. (3 m)
• Ready to communicate to a Building Management
System, embedded RS485 and Ethernet HVAC
protocols: BACnet IP, Modbus TCP, Modbus RTU,
BACnet MSTP, Metasys N2, APOGEE® FLN
• Real Time Clock Battery Package
• Door Mounting Kits
• SED2 to BT300 Migration Kits
• Two built-in PID controllers enable fast and accurate
process control
www.usa.siemens.com/hvac
Variable Frequency Drives
Siemens Industry’s BT300 HVAC drives are designed
to meet the demands of today’s HVAC systems. An
increased focus on energy efficient variable flow systems
has increased the need for easy-to-use and highly
reliable variable frequency drives that reduce the cost of
installation and maintenance while maximizing energy
savings. HVAC demands are unique to other drive
applications.
BT300 Variable Frequency Drives
without and with Integral Disconnect.
BT300 Specifications
Variable Frequency Drives
C-6
Input Voltage and Power Ranges (3-phase)
208V - 240V, +/-10%.................................. .1 to 125 HP (0.75 to 90 kW)
380V - 480V, +/-10%................................ 1.5 to 250 HP (1.1 to 160 kW)
Input Frequency....................................................................... 45 to 66 Hz
Output Frequency.................................................................... 0 to 320 Hz
Frequency Resolution................................................................... 0.01 Hz
Power Factor............................................................ 0.98 at Nominal Load
Efficiency ...................................................................................... >97.5%
Overload Capacity.................. 1.1 x Nominal Rated Output Current 110%
for 1 Minute/10 Minutes
Peak Overload Capacity ............200% for 2 Seconds Every 20 Seconds
Switching Frequency........ 1.5 to 10kHz; Automatic Switching Frequency
Derating in Case of Overheating
Short Circuit Withstand Rating.............................................100,000 AIC
Frequency Reference Analog Input......0.01 Hz Resolution 0.1% (10-bit)
Field Weakening Point............................................................ 8 to 320 Hz
Acceleration/Deceleration Time.......................................0.1 to 3000 sec
Ambient Operating Temperature......................... -14º F (-10º C) no Frost
to 104º F (40º C) Without De-rating and 131º F (55º C) With De-rating
Storage Temperature ............................-40º F (-40º C) to 158º F (70º C)
Relative Humidity .............0 to 95% RH, Non-condensing, Non-corrosive
Air Quality......................................................................... IEC 60068-2-60
Chemical Vapors.................IEC 60721-3-3, Unit in Operation, Class 3C3
Mechanical Particles...........IEC 60721-3-3, Unit in Operation, Class 3S2
Altitude. .......100% Load Capacity (no De-rating) up to 3,280 ft (1,000 m)
1% De-rating for Each 328 ft (100 m) Above 328 ft (1,000 m)
Maximum Altitude 14,763 ft (4,500 m)
Accessories & Service Kits
www.usa.siemens.com/hvac
Vibration...............................................IEC 61800-5-1 and IEC 60068-2-6
Shock . .............................................IEC 61800-5-1 and IEC 60068-2-27
Enclosures............................................................. UL Type 1, UL Type 12
EMC Immunity...........Fulfills IEC 61800-3, First and Second Environment
EMC Emissions...................................................................EN61800-3C2
Average Noise level (Cooling Fan)
Sound Level in dB(A)......................FS4 - 65; FS5 - 61; FS6 and FS7: 68
FR8: 77; FR9: 78
Agency Approvals..................................................UL 508C; CE, UL, cUL
Analog Inputs...................... 2 Voltage or Current (0-10Vdc, 0/4 to 20 mA)
Analog Output...........................................1 Selectable Voltage or Current
Digital Inputs............................................... 6 Programmable and Isolated
Relay Outputs.................................................2 Form C; 1 Normally Open
Auxiliary Input Voltage.................................24 Vdc +/-10% 250 mA Max.
Auxiliary Input Voltage................................24 Vdc +/-10% 250 mA Max.,
Total of Both Outputs
Control Method.........................................................Linear, Parabolic and
Programmable V/f; Flux Current Control Low-Power Mode
PWM Frequency........... 2k Hz to 16k Hz (Adjustable in 2k Hz Increments)
Fixed Frequencies.........................................................15 Programmable
Skip Frequency Bands....................................................3 Programmable
Embedded Resident Protocols..........................RS485 and Ethernet P1,
BACnet MS/TP, BACnet IP, Modbus RTU,
Modbus TCP, Metasys N2, APOGEE FLN
Protection Features................Under-voltage and Over-voltage Trip Limit,
Ground Fault, Mains Supervision, Motor Phase Supervision,
Over-current, Unit Over-temperature, Motor Overload, Motor Stall,
Motor Underload, Short Circuit of +24V and +10V Reference Voltages
C-35
BT300 Product Ordering
Your Product Number
Example Product Number
BT 300 -0 0 1X2 - 01X
Example Product Number
BT 300 -0 0 154 - 12DL
Model
BT300VFD only
HP
1, 1.5, 2, 3, 5, 7.5, 10, 15
20, 25, 30, 40, 50, 60, 75
100, 125, 150, 200, 250
X
5
No Fract HP,
1/2 HP
Voltage
2
4
200 to 240
380 to 480
NEMA
01
12
UL Type 1
UL Type 12
Type
X
D
Drive Only
Disconnect Box – ONLY WITH TYPE 12
Options
L
LON Card Installed
C-7
www.usa.siemens.com/hvac
Variable Frequency Drives
Example Shown:
BT300-001X2-01X = 1 HP, 208V Drive in Type 1 enclosure.
BT300-00154-12DL = 1.5 HP, 480V Drive in Type 12 enclosure with an integral disconnect switch and LON card.
BT300 Output Ratings
Voltage (±10%)
208V
(3-Phase)
Variable Frequency Drives
C-8
230V
(3-Phase)
380V to 480V
(3-Phase)
Product Number
Output Rating
Rated
Continuous
Current
Frame
Size
UL Type 1
UL Type 12
BT300-001X2-01X
BT300-001X2-12X
UL Type 12 with
Drive Disconnect
BT300-001X2-12D
1.0
0.75
4.8
FS4
BT300-00152-01X
BT300-00152-12X
BT300-00152-12D
1.5
1.1
6.7
FS4
BT300-002X2-01X
BT300-002X2-12X
BT300-002X2-12D
2.0
1.5
8.0
FS4
BT300-003X2-01X
BT300-003X2-12X
BT300-003X2-12D
3.0
2.2
11.0
FS4
BT300-005X2-01X
BT300-005X2-12X
BT300-005X2-12D
5.0
4.0
18.0
FS5
BT300-00752-01X
BT300-00752-12X
BT300-00752-12D
7.5
5.5
24.0
FS5
BT300-010X2-01X
BT300-010X2-12X
BT300-010X2-12D
10.0
7.5
31.0
FS5
BT300-015X2-01X
BT300-015X2-12X
BT300-015X2-12D
15.0
11.0
48.0
FS6
BT300-020X2-01X
BT300-020X2-12X
BT300-020X2-12D
20.0
15.0
62.0
FS6
BT300-025X2-01X
BT300-025X2-12X
BT300-025X2-12D
25.0
18.5
75.0
FS7
BT300-030X2-01X
BT300-030X2-12X
BT300-030X2-12D
30.0
22.0
88.0
FS7
BT300-040X2-01X
BT300-040X2-12X
BT300-040X2-12D
40.0
30.0
105.0
FS7
BT300-050X2-01X
BT300-050X2-12X
—
50.0
37.0
140.0
FS8
BT300-060X2-01X
BT300-060X2-12X
—
60.0
45.0
170.0
FS8
BT300-075X2-01X
BT300-075X2-12X
—
75.0
55.0
205.0
FS8
BT300-100X2-01X
BT300-100X2-12X
—
100.0
75.0
261.0
FS9
BT300-125X2-01X
BT300-125X2-12X
—
125.0
90.0
310.0
FS9
BT300-00154-01X
BT300-00154-12X
BT300-00152-12D
1.5
1.1
3.7
FS4
BT300-002X4-01X
BT300-002X4-12X
BT300-002X4-12D
2.0
1.5
5.3
FS4
BT300-003X4-01X
BT300-003X4-12X
BT300-003X4-12D
3.0
2.2
6.2
FS4
BT300-005X4-01X
BT300-005X4-12X
BT300-005X4-12D
5.0
4.0
10.6
FS4
BT300-00754-01X
BT300-00754-12X
BT300-00752-12D
7.5
5.5
13.2
FS4
BT300-010X4-01X
BT300-010X4-12X
BT300-010X4-12D
10.0
7.5
16.0
FS5
BT300-015X4-01X
BT300-015X4-12X
BT300-015X4-12D
15.0
11.0
23.0
FS5
BT300-020X4-01X
BT300-020X4-12X
BT300-020X4-12D
20.0
15.0
31.0
FS5
BT300-025X4-01X
BT300-025X4-12X
BT300-025X4-12D
25.0
18.5
38.0
FS6
BT300-030X4-01X
BT300-030X4-12X
BT300-030X4-12D
30.0
22.0
46.0
FS6
BT300-040X4-01X
BT300-040X4-12X
BT300-040X4-12D
40.0
30.0
61.0
FS6
BT300-050X4-01X
BT300-050X4-12X
BT300-050X4-12D
50.0
37.0
72.0
FS7
BT300-060X4-01X
BT300-060X4-12X
BT300-060X4-12D
60.0
45.0
87.0
FS7
BT300-075X4-01X
BT300-075X4-12X
BT300-075X4-12D
75.0
55.0
105.0
FS7
BT300-100X4-01X
BT300-100X4-12X
—
100.0
75.0
140.0
FS8
BT300-125X4-01X
BT300-125X4-12X
—
125.0
90.0
170.0
FS8
BT300-150X4-01X
BT300-150X4-12X
—
150.0
110.0
205.0
FS8
BT300-200X4-01X
BT300-200X4-12X
—
200.0
132.0
261.0
FS9
BT300-250X4-01X
BT300-250X4-12X
—
250.0
160.0
310.0
FS9
www.usa.siemens.com/hvac
HP
kW
208V
480V
KW 0.75
1.1
1.5
2.2
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
HP
1.5
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
200
250
Frame
Size
Voltage
BT300 Type 1 and 12 Frame Sizes and Power Range
1
4
N/A
5
6
4
5
7
8
6
7
9
NA
8
9
BT300 Dimensions and Weights
Frame Size
Height
in. (mm)
Width
in. (mm
Depth
in. (mm
Depth
in. (mm
FS4
12.9 (328)
5.0 (128)
FS5
16.5 (419)
FS6
21.9 (557)
FS7
FS8
FS9
Weight
lb. (kg)
(without Disconnect)
(with Disconnect)
7.5 (190)
10.6 (270)
13.0 (6)
5.7 (144)
8.4 (214)
11.6 (294)
22.0 (10)
7.7 (195)
9.0 (229)
11.9 (302)
44.0 (20)
26.0 (660)
9.3 (237)
10.2 (259)
13.1 (332)
83.0 (37.5)
38.0 (966)
11.4 (290)
13.5 (343)
N/A
145.5 (66)
45.3 (1150)
18.9 (480)
14.4 (365)
N/A
238.0 (108)
C-9
Variable Frequency Drives
www.usa.siemens.com/hvac
BT300 Dimensions
FS4, Wall-Mount
Ø7 (.27)
190 (7.48)
100 (3.93)
Ø25 (.98)
328 (12.91)
313 (12.32)
112 (4.40)
151 (5.94)
Ø13 (.51)
Type 1 / IP21
128 (5.03)
Type 12 / IP54
C-10
100 (3.93)
Variable Frequency Drives
mm (in.)
147 (5.78)
112 (4.40)
Ø25 (.98)
BT9080
FS5, Wall-Mount
www.usa.siemens.com/hvac
BT300 Dimensions
FS6, Wall-Mount
Ø40 (1.57)
Ø 15,5 (.61)
Ø40 (1.57)
541 (21.29)
557 (21.92)
148 (5.82)
Ø9 (.35)
Ø33 (1.29)
229 (9.01)
148 (5.82)
151 (5.94) 43,7 (1.72)
195 (7.67)
Type 1 / IP21
Ø25 (.98)
148 (5.82)
Type 12 / IP54
BT9082
FS7, Wall-Mount
237 (9.33)
190 (7.48)
259 (10.19)
Ø20 (.78)
Ø9 (.35)
Ø16 (.62)
Type 1 / IP21
645 (25.39)
211 (8.30)
Type 12 / IP54
Ø25 (.98)
Ø50 (1.96)
160 (6.29)
217 (8.54)
660 (25.98)
160 (6.29)
Ø51 (2)
9083bt
mm (in)
www.usa.siemens.com/hvac
C-11
Variable Frequency Drives
mm (in)
Ø9 (.35)
151 (5.94)
148 (5.82)
42 (1.65)
Ø25 (.98)
BT300 Dimensions
FS8, Wall-Mount
Variable Frequency Drives
C-12
www.usa.siemens.com/hvac
BT300 Dimensions
FS9, Wall-Mount
C-13
Variable Frequency Drives
www.usa.siemens.com/hvac
Variable Frequency Drives
C-14
Online 24/7 ordering convenience
Use this Master HVAC Catalog and Siemens online ordering to maximize
ordering efficiency. Go online to:
• Place orders
• Browse this catalog online
• Check product availability and pricing
• Specify FREE valve tagging
• Download invoices
• Track shipments
• Print out product information for submittals
• Link to technical documentation
• Download installation instructions
• Create a reusable template order form for frequently ordered parts
See how easy it is to save time and money. Register today at:
www.usa.siemens.com/buildingtechnologiesonlineordering
www.usa.siemens.com/hvac
BT300
BT300 with Bypass Options
Important Note:
VFD products are only available
through authorized distribution
channels. To locate an authorized
distributor, please contact a
Siemens Building Technologies
representative at: 1.800.516.9964.
Energy &
Atmosphere
BT300 Variable Frequency Drives
with Bypass Options.
Features
The BT300 was designed from the onset with reliability in
mind. The BT300 is the first VFD in today’s market which
has utilized ALT testing from product design to production
deployment.
• Contactors electronically interlocked
However in today’s market, some customers want
additional assurance their equipment will run regardless of
the situation. To accommodate these situations, Siemens
has developed a companion product for the BT300, the
BT300 with Bypass Options.
– M1 and M2 contactors
– Overload
– Customer supplied start/stop
– Status of Essential Services
As the word indicates, a “bypass” is defined in an
engineering spec as a means of taking the drive out of the
electrical power loop while keeping the HVAC system up
and running.
BT300 is available with two types of bypass options.
The BT300 with Conventional bypass is designed
with 2 contactors and a service switch or the traditional
3-contactor configuration to bypass the drive, and
incorporates selector switches and indicator lights to
accomplish its primary functions. The second option, an
Electronic bypass utilizes internal control boards that act
as the brains and eliminates the control wiring, relay logic,
terminal blocks and replaces them with advanced built-in
features accessible from an electronic keypad.
• Advanced diagnostic board built into the bypass for
determining status of
• Step-down transformer with fused primary and thermal
fused secondary circuit
• Fused disconnect or circuit breaker Option
• 100,000 AIC short circuit rating
• Customer Supplied Terminal strip
Conventional Bypass Control:
• Drive test switch
• Drive-Off-Bypass selector
• Bypass Light
• Fused disconnect or circuit breaker
• Optional 2-contactor with service switch or 3-contactor
design (input, output and bypass)
Electronic Bypass Control
• Auto Bypass
• Option to install 8 separate safety circuits
• Fieldbus in Bypass
• Essential Service Mode (Fire mode)
• Damper Interlock
• Remote start via network
www.usa.siemens.com/hvac
C-15
Variable Frequency Drives
Description
BT300 with Bypass Options Product Ordering
Your Product Number
Example Product Number
B
T
E
-
1
2
5
X
4
-
B
0
1
2
L
Model(s)
BTC Conventional
BTE Electronic
HP
1, 1.5, 2, 3, 5, 7.5,10,15
20, 25, 30, 40, 50, 60, 75
100, 125, 150, 200, 250
X=no fract HP
5= 1/2 hp
Voltage
2
200 to 240
4
380 to 480
Disconnect
C-16
F
Fused Disconnect
B
Circuit Breaker
Enclosure
01
Enclosure Type 1
3
3 contactors (input/output and bypass contactors) (Conventional option only)
2
2 contactors bypass with service switch
Options
L
Lon Card Installed
Example shown:
BTE -125X4 -B012L
BT300 Electronic Bypass, 480 volt, 125hp, Type 1, circuit breaker and 2 Contactor bypass with
a service switch and LonWorks card installed in drive
BT300 Bypass Options Frame Sizes and Power Ranges
208V
480V
KW 0.75
1.1
1.5
2.2
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
HP
1.5
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
200
250
Frame
Size
Voltage
Variable Frequency Drives
Contactor
1
4
5
N/A
6
4
5
7
8
6
7
9
NA
8
9
Type 1 Bypass Approximate Weights
Frame Size
4
5
6
7
8 and 9
Weight lbs. (kg)
50 (23)
69 (31)
112 (51)
187 (85)
1000 (454)
www.usa.siemens.com/hvac
BT300 Bypass Options Dimensions
35.48
34.625
Frame Size 4
.38 MOUNTING HOLES
TYPICAL (4) PLACES
.38
1.49
4.000
6.76
35.48
Frame Size 6
1/2" CONDUIT HOLE
WITH 3/4" KNOCKOUT RING
TYPICAL (5) PLACES
34.625
.44 MOUNTING HOLES
TYPICAL (4) PLACES
.38 MOUNTING HOLES
TYPICAL (4) PLACES
.38
1.49
4.000
6.76
C-17
54.75
1/2" CONDUIT HOLE
WITH 3/4" KNOCKOUT RING
TYPICAL (5) PLACES
53.750
43.250
Frame Size 5
.38 MOUNTING HOLES
TYPICAL (4) PLACES
.38
1.49
4.000
6.76
.50
1/2" CONDUIT HOLE
WITH 3/4" KNOCKOUT RING
TYPICAL (3) PLACES
44.10
43.250
3/4" CONDUIT HOLE
WITH 1" KNOCKOUT RING
TYPICAL (2) PLACES
1.49
6.000
8.76
1/2" CONDUIT HOLE
WITH 3/4" KNOCKOUT RING
TYPICAL (3) PLACES
1-1/4" CONDUIT HOLE
WITH 1-1/2" KNOCKOUT RING
TYPICAL (2) PLACES
.38
1.49
4.000
6.76
1/2" CONDUIT HOLE
WITH 3/4" KNOCKOUT RING
TYPICAL (3) PLACES
www.usa.siemens.com/hvac
3/4" CONDUIT HOLE
WITH 1" KNOCKOUT RING
TYPICAL (2) PLACES
Variable Frequency Drives
44.10
BT300 Bypass Options Dimensions
Frame Size 7
Frame Size 8 & 9
.50 MOUNTING HOLES
TYPICAL (4) PLACES
TOP ENTRY, BLANK
CONDUIT PLATES
58.50
1.18 TYPICAL
(4) PLACES
57.375
Variable Frequency Drives
C-18
90.71
.50
4.18
6.000
14.16
1/2" CONDUIT HOLE
WITH 3/4" KNOCKOUT RING
TYPICAL (3) PLACES
92.99
2" CONDUIT HOLE
WITH 2-1/2" KNOCKOUT RING
TYPICAL (2) PLACES
32.58
(TYPE 1 & 12)
1.28
29.409
29.409
.94 (4) PLACES
TYPICAL
www.usa.siemens.com/hvac
SED2
Legacy Variable
Frequency Drives
Important Note:
VFD products are only available
through authorized distribution
channels. To locate an authorized
distributor, please contact a
Siemens Building Technologies
representative at: 1.800.516.9964.
SED2 Variable Frequency Drives Family.
Energy &
Atmosphere
Features
•Built-in SBT P1 and JCI N2 (Metasys®) building
automation system protocols for easy network
integration
•Low harmonics design reduces noise and interference;
eliminates need for filters/reactors in most installations
•Built-in PID for fast and accurate pressure control
•Pump staging for open loop, constant pressure, and
constant flow-type applications
•Service mode for applications requiring continuous,
uninterruptible operation
•Accepts a wide variety of digital and analog
I/O types, including direct Siemens Ni 1000 RTD
sensor level inputs
• One common interface throughout all power ranges
•Optional Advanced Operator Panel for uploading/
downloading parameters
• Full form C relay contacts for digital outputs
• Multi-level program access
Options
•LON Interface
•Modbus RTU Interface
•Advanced Operator Panel (AOP) Module
•PC Kit
www.usa.siemens.com/hvac
C-19
Variable Frequency Drives
•LON, Modbus RTU Interfaces optional
• Belt failure detection with or without an external sensor
Variable Frequency Drives Specifications
Variable Frequency Drives
C-20
Input Voltage and Power Ranges (3 phase)
208V and 230V to 240V, 3 ac±10%....................................1 hp to 60 hp
380V to 480V, 3 ac ±10%..................................................1 hp to 125 hp
500V to 600V, 3 ac ±10%..................................................1 hp to 125 hp
Input Frequency..................................................................47 Hz to 63 Hz
Output Frequency...............................................................0 Hz to 150 Hz
Power Factor........................................................................................≥0.9
VFD degree of efficiency....................................................... 96% to 97%
Switch-on Current................................... Less than nominal input current
Auxiliary Supply 24V........................ Glavanically separated, unregulated
auxiliary supply (18V to 32V) 100 mA
Overload Capacity....................................................110% for 60 seconds
Control Method...........................Linear, parabolic and programmable V/f;
and flux current control low-power mode
PWM Frequency............2k Hz to 16k Hz (adjustable in 2k Hz increments)
Fixed Frequencies......................................................... 15 programmable
Skip Frequency Bands.................................................... 4 programmable
Setpoint Resolution.............................................................0.01 Hz digital
0.01 Hz serial
10 bit analog
Digital Inputs (Sink/Source).............................6: fully programmable and
scalable isolated digital inputs, switchable
Analog Inputs................................................2: 0 to 10 Vdc, 0/4 to 20 mA,
can also be configured as digital inputs
or Ni 1000 input
Relay Outputs..................................2: configurable 30 Vdc/5A (resistive),
250 Vac/2A (inductive)
Analog Outputs..................................2: programmable (0/4 mA to 20 mA,
or 0 Vdc to 10 Vdc)
Serial Interface..................................................RS-485 transmission rate:
Up to 38.4k Baud Protocols: USS, P1 and N2
Protection Level................................................................................. IP20
NEMA Type 1 with protective shield and gland plate installed
Temperature Ranges...............Operating: 14°F to 104°F (–10°C to 40°C)
Storage: –40°F to 158°F (–40°C to 70°C)
Humidity...............................................................95% rh, non-condensing
Operational Altitudes..............................................Up to 3280 ft (1000m)
above sea level without derating
Protection Features.....................Under-voltage, Over-voltage, Overload,
Ground fault, Short circuit, Stall prevention,
Locked motor, Motor overtemperature l2 t PTC,
Over-temperature, Parameter PIN protection.
Standards.................................................................... UL, cUL, CE, C-tick
CE Conformity.......Conformity with EC Low Voltage Directive 73/23/EEC
Options. ........................................ LON Interface, Modbus RTU Interface,
BACnet MS/TP Interface, Advanced Operator Panel
(AOP) Module, PC Kit
Variable Frequency Drives Product Ordering
Your Product Number
Example Product NumberSED2-0.75/22X
Model
SED2-
VFD only
kW rating
0.75, 1.1, 1.5, 2.2, 3, 4, 5.5, 7.5, 11,
15, 18.5, 22, 30, 37, 45, 55, 75, 90
[See Note 1 for these selections]
Voltage
2
3
4
(Uses 2 to 4 spaces plus a divider “/”)
200 to 240V
380 to 480V
500 to 600V
NEMA rating
2
(IP 20)
1
NEMA Type 1
Filter
X
Factory Required Designator
Notes:
Example Shown:
1. Available only with Voltage Codes 3 and 4.
SED2-0.75/22X =
SED2 VFD only, 0.75 kW (1 hp), 200 to 240V, open type IP20.
www.usa.siemens.com/hvac
Variable Frequency Drives Frame Sizes
VFD0163R1
SED2 IP20 and NEMA Type 1 Frame Sizes and Power Ranges
HP
1
1.5
2
3
4
5
kW
.75
1.1
1.5
2.2
3
4
240V
A
480V
B
7.5
10
15
20
25
30
5.5
7.5
11
15
18.5
22
C
A
D
B
575V
40
50
30
37
E
C
D
C
60
75
45
55
100
125
75
90
F
N/A
E
F
Variable Frequency Drives Dimensions and Weights
IP20 SED2 VFDs
Frame Size
Height
Width
Depth
Weight Lb. (kg)
A
6.8
(173)
2.9
(73)
5.9
(149)
2.9
(1.3)
B
8.0
(202)
5.9
(149)
6.8
(172)
7.5
(3.4)
C
9.6
(245)
7.3
(185)
7.7
(195)
12
(5.5)
D
20.5
(520)
10.8
(275)
9.6
(245)
35
(16)
E
25.6
(650)
10.8
(275)
9.6
(245)
44
(20)
F
33.5
(850)
13
(350)
12.6
(320)
116
(53)
Frame Size
Height
Width
Depth
Weight Lb. (kg)
A
9.1
(231)
2.9
(73)
5.9
(149)
3.2
(1.5)
B
11.8
(300)
5.9
(149)
6.8
(172)
8.3
(3.8)
C
13.8
(351)
7.3
(185)
7.7
(195)
13.6
(6.2)
D
24.6
(625)
10.8
(275)
9.6
(245)
37.5
(17)
E
29.7
(754)
10.8
(275)
9.6
(245)
46.4
(21)
F
54.5
(1384)
16.0
(406)
14.0
(356)
200
(91)
www.usa.siemens.com/hvac
Variable Frequency Drives
NEMA Type 1 SED2 VFDs Assembled with Protective Shield and Gland Plate
C-21
Variable Frequency Drives
C-22
Online order tracking
This handy online feature stores all your past and current orders online
for quick and easy reference. The Order Tracker function lets you access
information such as:
• Ordered By • Order No. • Shipping Date • Date Placed
• Acknowledgement of Order
• Shipment Tracking
To view your history and status, register online at
www.usa.siemens.com/buildingtechnologiesonlineordering
www.usa.siemens.com/hvac
SED2
Legacy Variable Frequency Drives
with Bypass Options
Important Note:
VFD products are only available
through authorized distribution
channels. To locate an authorized
distributor, please contact a
Siemens Building Technologies
representative at: 1.800.516.9964.
Energy &
Atmosphere
Bypass Power
SED2 Variable Frequency Drives
with Conventional Bypass Options Family.
3-Contactor: Input, Output, & Bypass
• Overload protection in bypass mode
• Step-down transformer with fused primary and secondary
• Contactors electrically and mechanically interlocked
• Drive test function
• Complete electrical isolation of drive
Conventional Bypass Control
Enable Input
•Generally used for safety tie-ins; the motor will not
operate the drive or bypass when open.
Input Device
• Fused disconnect
• Circuit breaker (optional)
• All doors are interlocked and padlockable
Input
Device
Reactor Options
• Input line reactor mounted in bypass option enclosure.
• Line reactor supplied separately.
• Load reactor (in NEMA 1/3R enclosure)
supplied separately.
VF0302R1
Drive
Motor
2 Contactor Bypass
Input
Device
Drive
Motor
3 Contactor Bypass
E-Bypass Control
Auto Bypass
•Relay logic allows user to send the motor to bypass
mode based on the drive’s programmable relay.
•The drive’s programmable relay, typically set to fault,
can be set up for applications that run full speed for an
extended period of time.
Essential Services Mode
•Typically used for smoke purge; the motor goes to
bypass regardless of the selected mode.
•No call to stop will have an effect, including open safety
or stop commands.
•Only turning the power off or opening this contact will
stop the motor.
Conventional Bypass –
Door Mounted Control Devices
• Drive-Off-Bypass selector
•Bypass pilot light
•Drive Test on/off selector
Enable Input
•Generally used for safety tie-ins; the motor will not
operate the drive or bypass when open.
Common Remote Start/Stop
•Common remote start/stop can be used in both drive
and bypass mode.
www.usa.siemens.com/hvac
C-23
Variable Frequency Drives
Essential Services Mode
•Also used for smoke purge; the motor goes to bypass
regardless of the selected mode.
•No call to stop will have an effect, including open safety
or stop commands.
•Only turning the power off or opening this contact will
stop the motor.
Variable Frequency Drives with Conventional Bypass Option Specifications
Electronic Bypass Specifications
Conventional Bypass Specifications
Input Voltage (3-phase)
208V, 3 AC±10%..........................1 hp to 60 hp (2.3 amps to 154 amps)
240V, 3 AC±10%..........................1 hp to 60 hp (2.3 amps to 154 amps)
480V, 3 AC ±10%.......................1 hp to 125 hp (1.2 amps to 178 amps)
575V, 3 AC ±10%.......................1 hp to 125 hp (2.3 amps to 125 amps)
Protection Level...................................................................NEMA Type 1
Digital Inputs
Six Digital Inputs as follows...........Remote start input, Remote safety 1,
Remote safety 2, Interlock start,
Essential services, Overload trigger.
Inputs require a contact closure capable of providing a
low impedance path at currents less than 20 mA.
Relay/Digital Outputs
Six Relay/Digital Outputs as follows.........................................VFD fault,
Programmable output, Drive select, Bypass select,
Running on bypass, Overload fault,
Each relay has a maximum rating of 2A at 120Vac.
Input Voltage (3-phase)
208V, 3 AC±10%..........................1 hp to 60 hp (2.3 amps to 154 amps)
240V, 3 AC±10%..........................1 hp to 60 hp (2.3 amps to 154 amps)
480V, 3 AC ±10%.......................1 hp to 125 hp (1.2 amps to 178 amps)
575V, 3 AC ±10%.......................1 hp to 125 hp (2.3 amps to 125 amps)
Protection Level...................................................................NEMA Type 1
Temperature
Operating......................................................... 32 to 104°F (0 to +40°C)
Storage.......................................................-40 to +158°F (-40 to +70°C)
Humidity......................................................0 to 95% RH, non-condensing
E-Bypass — Door Mounted Control Devices
C-24
VFD
Variable Frequency Drives
Input
On/Off
Bypass
Hand
Start
Input
Contactor
VFD
Bypass
Contactor
Remote
Start
Enable
Output
Contactor
Overload
Relay
Motor
VFD0097R2
STOP
RESET
Accessories & Service Kits
www.usa.siemens.com/hvac
Auto Bypass Enabled
Essential Services
INTERLOCK START LOGIC
VFD Fault
Safety Fault
Overload Fault
Enable Commanded Proofed
C-35
Legacy Variable Frequency Drives with Conventional Bypass Option Product Ordering
Your Product Number
Example Product Number
Model
VB
VBA340 .B133X
VFD with an Extended Box
Series
AConventional Bypass
E
Electronic Bypass
Voltage
1
2
3
4
208 V
230 to 240 V
380 to 480 V
500 to 600 V
HP rating
1.0, 1.5, 2.0, 3.0, 4.0, 5.0, 7.5, 10, 15, 20, 25, 30, 40, 50,
60, 75, 100, 125 [See Note 1 for these selections]
Fused Disconnect
Circuit Breaker
NEMA rating
1
NEMA Type 1
Contactor
3
0
3 Contactors (Input, output, and bypass contactors)
None (Extended box only. No bypass.)
Reactor
0
3
[See Note 3]
None
Line Reactor
Filter
X
Factory Required Designator
C-25
Notes:
1. Available only with Voltage Codes 3 and 4.
2. Input line reactors will be installed in bypass enclosures. Load reactors are supplied seperately in NEMA 1 or
NEMA 3R enclosures.
Example shown:
VBA340.B133X
VBA Conventional Bypass, 40 HP, 480V, Circuit Breaker, NEMA Type 1, 3-Contactor Bypass with Input Line Reactor.
VBE340.F130X
VBE Electronic Bypass, 40 hp, 480V, fused disconnect, NEMA Type 1, 3 contactors bypass, no reactor.
www.usa.siemens.com/hvac
Variable Frequency Drives
Disconnect
F
B
NEMA 1 Bypass Approximate Weights
Frame Size
Wt. Lb (kg)
A
45 (20)
B
55 (25)
C
75 (34)
D
150 (68)
E
180 (82)
F
470 (213)
Note: Exact weight will be affected by the actual horsepower/voltage and the selected power options.
NEMA 1 Bypass Frame Sizes and Power Ranges
Variable Frequency Drives
C-26
HP
kW
208/240V
1
.75
A
1.5
1.1
2
1.5
3
2.2
5
4
7.5
5.5
10
7.5
15
11
20
15
25
18.5
30
22
40
30
50
37
60
45
75
55
100
75
125
90
HA1
—
480V
575V
A
B
B
C
C
C
D
E
F
N/A
D
D
E
E
F
F
N/A
www.usa.siemens.com/hvac
NEMA 1 Dimensions
Depth
With
20.8
2.9
Handle
(53)
(7.4) 4
10.4 (26)
(10)
1 Depth
20.8
2.9
(2.5) 2With
(5)
Handle
(53)
(7.4) 4
= Protective Shield
Depth
With
Handle
9.6 (24)
Depth
= Protective Shield
Depth
With
Handle
Depth
9.6
(24)
With
Handle
1.5
9.6 (24)
13.2
(34)
With
Handle
9.6 (24)
11.5
(29)
11.5
(29)
(3.8)
10.4 (26)
1
(2.5) 2
(5)
1.5
(3.8)
13.2
(34)
53.5
(136)
48
(122)
34
(86)
53.5
(136)
48
34
(86)
10.5 TYP
(122)
(27)
12.4
(31)
12.4
10.6
(27)
(3.8)
10.6
1.5
12.2 (31)
20.8
(53)
20.8
(53)
2
(5)
19.9
(51)
(5)
19.9
3.4
(51)
Frame (8.6)
2.9
3
3.4
(8.6)
Size D
Frame
Size D
Size C
(7.4)
2.9
(7.4) 3(7.6)
(7.6)
11.5 TYP
(29)
C-27
Depth
Depth17.4
17.4 (44)
45.5
(116)
45.5
(116)
(44)
57.5
57.5
(146)
(146)
58.5
58.5
(149)
(149)
10 TYP
VFD0127R2
VFD0127R2
10 TYP
(25)
(25)
19.9
19.9
(51)
(51)
5.5
5.5
(14)
(14)
FrameSize
SizeEE
Frame
Frame
Size
Frame
Size
F F
Dimensions shown in inches (mm).
www.usa.siemens.com/hvac
Variable Frequency Drives
Depth
With
Depth
Handle
With
12.2
(31)
Handle
11 TYP
(28)2
(27)
Frame
Size C
Frame
A and B
11.5 TYP
(29)
11 TYP
(28)
10.5 TYP
1.5
(27)
(31) Size
(3.8)
Frame
A
and
B
Frame Size
(10)
Variable Frequency Drives
C-28
We’re happy to assist you
Our customer support teams are accessible and happy
to assist you with ordering, fulfillment, and shipping
questions. Call a representative at 1-800-516-9964
from 7 am to 5:30 pm (CST) Monday through Friday.
Contact Customer Support or your Account Executive
with any questions. We appreciate your business and
look forward to helping you!
www.usa.siemens.com/hvac
SED2
Legacy VFD NEMA Type 3R &
Type 3R Harsh Environment (3RHE) Bypass
Energy &
Atmosphere
Important Note:
VFD products are only available
through authorized distribution
channels. To locate an authorized
distributor, please contact a
Siemens Building Technologies
representative at: 1.800.516.9964.
SED2 Variable Frequency Drives
NEMA Type 3R Bypass.
Features
Bypass – Door Mounted Control Devices
Bypass Power
•Drive-Off-Bypass selector
•Bypass pilot light
•Drive Test On-Off selector
Variable Frequency Drives
3-Contactor: Input, Output, and Bypass
• Overload protection in bypass mode.
•Step-down transformer with fused primary
and secondary.
• Contactors electrically and mechanically interlocked.
• Drive test function.
• Complete electrical isolation of drive.
C-29
Input Device
• Fused disconnect.
• All doors are interlocked and padlockable.
Reactor Options
• Line reactor mounted in bypass enclosure.
•Line reactor supplied separately
(in NEMA Type 3R enclosure).
•Load reactor supplied separately.
www.usa.siemens.com/hvac
NEMA Type 3R/3RHE Bypass Specifications
Input Voltage (3 phase)............................................... 208V, 3 AC ±10% *
240V, 3 AC ±10% *
480V, 3 AC ±10%
575V, 3 AC ±10%*
* Not available in the 3RHE models
Protection Level ...............................................................NEMA Type 3R
Temperature
Operating.............14°F to 104°F (–10°C to 40°C), HT1 to 122°F (50°C)
Storage..................................................–40°F to 158°F (–40°C to 70°C)
High-Temperature Model (HT1 and HT2)
Operating................................................14°F to 122°F (–10°C to 50°C)
Storage................................................. –40°F to 158°F (–40°C to 70°C)
Humidity........................................................0 to 95% rh, non-condensing
Variable Frequency Drives
C-30
www.usa.siemens.com/hvac
VFD NEMA Type 3R & Type 3R Harsh Environment (3RHE) Bypass Product Ordering
Your Product Number
Example Product Number
VBA340 . F330XHE2
Model
VB
VFD with an Extended Box
Series
A
Conventional Bypass
Voltage
1
2
3
4
208 V
230 to 240 V
380 to 480 V
500 to 600 V
HP rating
1.0, 1.5, 2.0, 3.0, 4.0, 5.0, 7.5, 10, 15, 20, 25, 30, 40,
50, 60, 75, 100, 125 [See Note 1 for these selections]
Disconnect
F
Fused Disconnect
C-31
NEMA Type 3R
Contactor
0
3
None
3 Contactors (Input, output, and bypass)
Reactor
0
3
[See Note 2]
None
Line Reactor
Filter
X
Factory Required Designator
Options
HT1
HE2
HT2
(If no option is required, leave field blank)
High Temperature [See note 3]
Harsh Enviroment Nema 3R [See note 4]
Harsh Enviroment Nema 3R — High Temperature Rating [See note 5]
Notes:
1. Available only with Voltage Codes 3 and 4.
2. Input line reactors will be installed in bypass enclosures. Load reactors are supplied seperately in NEMA 1 or
NEMA 3R enclosures.
3. HT1 (122°F, 50°C) is not available for all ratings. 208V and 230 to 240V to 3 hp are all HT1; 480V to 5 hp are all HT1.
4. HE2 available only with Voltage Codes 3 and 4. (480V to 40 hp)
5. HT2 (122°F, 50°C) is not available for all ratings. 480V to 5 hp are all HT2
Example Shown:
VBA340.F330XHE2
VBA Conventional Bypass, 480V, 40 hp, fused disconnect, NEMA Type 3R, 3 contactors, no reactor, harsh environment.
www.usa.siemens.com/hvac
Variable Frequency Drives
NEMA rating
3
NEMA Type 3R Enclosure Dimensions
Enclosure
Frame
ABC
ENCLOSURE
FRAME
ABC
Enclosure Frame
ENCLOSURE
FRAMEDE
DE
Enclosure
Frame
F F
ENCLOSURE
FRAME
46 (1169)
30
(762)
34 (864)
18
(457)
58 (1473)
42
(1067)
30
(762)
28-1/2
(724)
57
(1448)
75
(1905)
56-1/8
(1425)
74-1/8
(1882)
MOUNTING CLEARANCE
DepthDEPTH
= 12-1/2
Inches
= 12-1/2
(318)(318)
FOR PROPER AIRFLOW:
LEAVE 1 FOOT (305 mm) BETWEEN THE
NEMA TYPE 3R BYPASS AND ANY ADJACENT
SOLID STRUCTURE THAT IS NOT USED FOR
MOUNTING PURPOSES.
16-1/2 (419)
Depth =DEPTH
16-1/2= Inches
(419)
LEAVE 3 FEET (914 mm) BETWEEN THE NEMA TYPE 3R BYPASS
AND ANY OTHER NEMA TYPE 3R BYPASS OR VFD.
NEMA Type 3RHE Enclosure Dimensions
Enclosure Frame B
Enclosure Frame C
Enclosure Frame D
44
(1099)
42
(1051)
28
(711)
26
(660)
34
(848)
18
(457)
51
(1288)
57
(1440)
50
(1272)
30
(756)
56
(1424)
29
(724)
Depth = 10 Inches
VFD0228R1
VFD0225R1
VFD0222R1
Variable Frequency Drives
C-32
VFD0178R2
11-1/2 (292)
Depth = DEPTH
11-1/2=Inches
(292)
Depth = 11 Inches
Dimensions shown in inches (mm).
www.usa.siemens.com/hvac
Depth = 14 Inches
NEMA Type 3R and 3RHE Approximate Weights
3R Frame Size
Wt. Lb (kg)
3RHE Frame Size
ABC
130 (59)
B
Wt. Lb (kg)
150 (68)
DE
300 (136)
C
220 (100)
F
550 (249)
D
330 (150)
Note: Exact weight will be affected by actual horsepower/voltage and selected power options
NEMA Type 3R Bypass Non-HT1 Enclosure Frame Sizes and Power Ranges
HP
1
1.5
2
3
4
5
7.5
10
15
20
25
30
40
50
60
75
100
125
kW
.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
VFD0179R2
208/240V
(Rated as HT1,
High Temperature package)
ABC
DE
(Rated as HT1,
High Temperature package)
480V
575V
F
ABC
ABC
N/A
DE
F
DE
F
C-33
VFD0180R2
HP
1
1.5
2
3
4
5
7.5
10
15
20
25
30
40
50
60
75
100
125
kW
.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
208/240V
ABC
DE
480V
F
ABC
575V
N/A
DE
ABC
F
DE
N/A
F
N/A
VFD0180R2
NEMA 3RHE Bypasses HE2 Frame Sizes and Power Ranges
HP
1
1.5
2
3
4
5
7.5
10
15
kW
.75
1.1
1.5
2.2
3
4
5.5
7.5
11
208/240V
20
25
30
40
50
60
75
100
125
15
18.5
22
30
37
45
55
75
90
N/A
480V
N/A
C
D
575V
N/A
N/A
VFD0180R2
NEMA 3RHE Bypasses HT2 Frame Sizes and Power Ranges
HP
1
1.5
2
3
4
5
7.5
10
15
20
25
30
40
50
60
75
100
125
kW
.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
208/240V
480V
575V
N/A
N/A
B
C
D
N/A
N/A
www.usa.siemens.com/hvac
Variable Frequency Drives
NEMA Type 3R Bypass HT1 Enclosure Frame Sizes and Power Ranges
Variable Frequency Drives
C-34
Online 24/7 ordering convenience
Use this Master HVAC Catalog and Siemens online ordering to maximize
ordering efficiency. Go online to:
• Place orders
• Browse this catalog online
• Check product availability and pricing
• Specify FREE valve tagging
• Download invoices
• Track shipments
• Print out product information for submittals
• Link to technical documentation
• Download installation instructions
• Create a reusable template order form for frequently ordered parts
See how easy it is to save time and money. Register today at:
www.usa.siemens.com/buildingtechnologiesonlineordering
www.usa.siemens.com/hvac
Accessories &
Service Kits
Table of Contents
PRODUCT
BT300
PAGE #
NEW!
PC Cable for Software Tools
C-36
Real Time Clock Battery Package
C-36
Door Panel Kit
C-36
Hand Held Panel Kit
C-36
Flange Mounting Kits
C-36
Varnished Option Boards
C-37
SED2 to BT300 Migration Kits
C-38
SED2
C-39
Mounting Hardware
C-39
Filter Kits
C-39
Operator Panel
C-39
LON Interface Option
C-40
Modbus Interface
C-40
www.usa.siemens.com/hvac
C-35
Variable Frequency Drives
PC Kit
Accessories and Service Kits
Description
Part No.
BT300
PC Cable for Software Tools, USB to RS-485, 3m
BT300-CABLE
Battery package, 5 pcs
BT300-BATTERY
Door Panel Kit, Drive Side IP54 Protected, 3m
BT300-PANEL-N12
Hand Held Panel Kit
BT300-HHPANEL
Flange Mounting Kit, for FS4
BT300-FLG-FS4
Flange Mounting Kit, for FS5
BT300-FLG-FS5
Flange Mounting Kit, for FS6
BT300-FLG-FS6
Flange Mounting Kit, for FS7
BT300-FLG-FS7
Variable Frequency Drives
C-36
www.usa.siemens.com/hvac
Description
Part No.
BT300
6 X DI/DO, Programmable
BT300-OPT-B1-V
2 X RO + Thermistor
BT300-OPT-B2-V
1 X AI, 2 X AO (Isolated)
BT300-OPT-B4-V
C-37
BT300-OPT-B5-V
1 X RO, 5 X DI (42-240VAC)
BT300-OPT-B9-V
LonWorks
BT300-OPT-C4-V
1xAO, 1xDO, 1xRO
BT300-OPT-BF-V
NI1000 Sensor Card
BT300-OPT-BH-V
www.usa.siemens.com/hvac
Variable Frequency Drives
3 X RO
Accessories and Service Kits
Description
Part No.
BT300
Variable Frequency Drives
C-38
www.usa.siemens.com/hvac
SED2 208V to 3HP 480V to 5HP
SED2-BT300-AB-4
SED2 208V to 4HP 480V to 7.5HP
SED2-BT300-C-4
SED2 208V to 10HP 480V to 20HP
SED2-BT300-C-5
SED2 208V 15 to 20hp 480V 25 to 40hp
SED2-BT300-D-6
SED2 208V 25hp
SED2-BT300-D-7
SED2 208V 30hp 480V 50 to 60hp
SED2-BT300-E-7
SED2 FSC to BT300 Remote Mount
SED2-BT300-C-R
SED2 FSD and FSE to BT300 Remote Mount
SED2-BT300-DE-R
SED2 208V 40hp 480V 75hp
SED2-BT300-F-7
SED2 208V 50 to 60hp 480V 100 to 125hp
SED2-BT300-F-8
Description
Part No.
SED2
PC Kit.
SED2-PC-KIT
Gland Plates.
(included with NEMA Type 1)
• Frame A
SED2-GL-A
• Frame B
SED2-GL-B
• Frame C
SED2-GL-C
Protection Shield.
(included with NEMA Type 1)
SED2-PS-A
• Frame B
SED2-PS-B
• Frame C
SED2-PS-C
• Frame D, E
SED2-PS-DE
NEMA Type 1 and 3R Enclosed Reactors.
Contact Sales Partners
NEMA Type 3R Floor Mounting Kit.
• Frames A, B, C
994-809
BOP/AOP Door Mounting Kits.
• BOP/AOP Single Inverter
SED2-DOOR-KIT1
• AOP Multi-Inverter
SED2-DOOR-KIT2
Operator Panel.
• Basic Operator Panel (included with all SED2s)
SED2-BOP1
• Advanced Operator Panel (AOP)
SED2-AOP1
www.usa.siemens.com/hvac
C-39
Variable Frequency Drives
• Frame A
Accessories and Service Kits
Description
Part No.
SED2
Variable Frequency Drives
C-40
www.usa.siemens.com/hvac
LON Interface Option.
SED2-LONI/F
Modbus RTU Interface Module for SED2.
SED2-MODBUS2
SED2 Modbus Configuration Kit.
SED2-MODBUS2_KIT
Download