Description
Distribution Box
Floor Module
RevisionDate
10/15/1999
03/15/2002
Circuit Distributor
Cable Extender
Circuit Selector Unit
Drop Cable
Power Tee
Splitter Splice
Standard Selector Cable
Switching Tee
07/15/1997
07/15/1997
01/15/1996
07/15/1998
10/15/2001
07/15/1997
01/15/1996
01/15/1996
The Distribution Box is used as the interface between Reloc and hardwiring in access floor applications. The DB is located at the homerun location. From the DB, circuits are fed in different directions for service fittings or other access floor power devices.
• Pin-and-socket contacts
• Rated for use on 20-amp branch circuits
• All conductors are No. 12 AWG stranded copper with 90 o C thermoplastic insulation rated at 600V
• All components provide a fully-rated No. 12 AWG grounding conductor
• Available with up to twelve power ports.
• Up to three circuits per port, depending on system
• Safety-keying prevents accidental mismatching of components with different voltages
• Color-coding rapidly identifies system voltage
• Leads prestripped 5/8” for ease of wiring
• Isolated ground or two-circuit/two-neutral options available
• 1/2” trade-size knockouts on sides of box
• Additional labeling properly denotes type and position of each conductor
• UL listed; listed and labeled to comply with Canadian Standards
Catalog Number
Notes Type
DB
DB 120
Family
DB
Voltage
120 120V
Number of conductors
D Three
E Four
F Five
1 Distribution boxes requiring six to eight ports will be provided in an 8”x6”x4” box. More than eight ports will be provided in a 14” x 16” x 4.5” box.
2 Available only on the 14” x 16” x 4.5” box.
DB 120 D 6CD 32 2N
Number of ports
4 Four
6 Six
8 Eight 1
12 Twelve 1
Type of port
CD Circuit distributor
QC Quickflex connector
MR Modular regulator
Options
2N Two circuits, two neutrals
IG Isolated ground
(2N and IG not available on the same DB)
T B Terminal blocks 2
SL Standoff legs 2
Reloc
POW-100
DB
Dimensions are shown in inches.
# o f p o r t s W i d t h
1 6 6 "
7 8 6 "
9 1 4 * 1 4 "
*Standoff legs included on this version.
L e n g t h
6 "
8 "
1 6 "
H e i g h t
3 "
4 "
4 .
5 "
DB.P65 ©1990 Acuity Lighting Group, Inc., Rev. 10/99
Lithonia Lighting
Acuity Lighting Group, Inc.
Reloc Wiring Systems
One Lithonia Way, Decatur, GA 30035
Phone: 800-241-4750
In Canada: 1100 50th Ave., Lachine, Quebec H8T 2V3 www.lithonia.com
INTENDED USE
The Reloc Floor Module provides separate compartments for data, communication and power in an access floor. When prewired with a
RELOC interface, relocation of office work stations is as easy as moving partitions and floor panels.
ATTRIBUTES
Easy to install or relocate in any access floor.
Concealed service top of sturdy molded Lexan.
Wide access openings (two sizes).
Easy entry into access floor.
Hinged floor plate.
Interchangeable faceplates for flexibility.
16-gauge galvanized steel. Up to 135 cubic inches capacity.
Sturdy Lexan carpet/tile floor flange supports box on panel. Also acts as carpet flange.
Available with factory-installed electrical devices and Reloc interface for wiring ease and flexibility.
LISTING
UL listed only.
Catalog Number
Notes Type
FMI3
Choose the boldface catalog nomenclature that best suits your needs and write it on the appropriate line. Order accessories as separate catalog number.
Example: FMI3 P B RQ
Family 1
FM
Size
I1 5" X 6" (two compartments)
I3 10" X 6" X 5-1/4"
(Five compartments)
Power options
P One power panel for one duplex receptacle (receptacle not included)
P1 One prewired 20A duplex receptacle
(one circuit)
P2 One prewired 20A isolated ground duplex receptacle
(one circuit).
Y Custom design 2
Data/communications options
(blank) None provided
D Blank panels
Z Custom design 2
Color options
B Black
G Gray
Reloc wiring interface options
(blank) None
RQ Reloc interface custom design 2
NOTES:
1 120V only.
2 Consult factory for custom design options.
Sheet #: FMI3 POW-130
FMI3
DIMENSIONS SHOWN IN INCHES AND (MILLIMETERS)
A 16-gauge pre-galvanized steel body and panels.
B Two 1/2" K.O.s standard.
C Carpet tile / floor flange colors available in gray, black and brown.
NOTES:
Self-drilling screws provided to secure FMI in place.
Box will fit into 10 3/4" x 6 1/4" cutout in the floor panel.
Box dimensions with trim: 12 3/8" x 7" x 5 1/2"
Sheet #: FMI3
FMI3.P65 ©2002 Acuity Lighting Group, Inc., Rev. 03/02
Lithonia Lighting
Acuity Lighting Group, Inc.
Reloc Wiring Systems
One Lithonia Way, Decatur, GA 30035
Phone: 800-241-4750
In Canada: 1100 50th Ave., Lachine, Quebec H8T 2V3 www.lithonia.com
• Pin and socket contacts.
• Rated for use on 20 amp branch circuits.
• Installed through standard 1/2" trade-sized knockout.
• All conductors are No. 12 AWG copper with 90°C thermoplastic insulation rated at 600V.
• All components provide a fully rated No. 12 AWG grounding conductor.
• Safety-keying prevents accidental mismatching of components with different voltages.
• Color-coding rapidly identifies system voltage.
• Additional labeling properly denotes type and position of each conductor.
• 6" leads are prestripped 5/8" for ease of wiring.
• Extremely low-profile.
• UL listed.
• Listed and labeled to comply with Canadian Standards.
Catalog Number
Notes
The Circuit Distributor (CD) provides the interface between hardwiring and Reloc. Conventional wiring methods bring power from the panel to the homerun location where the CD is installed.
Type
CD
The following information details the construction of a typical catalog number. Consult your RELOC sales representative for any special product needs.
CD
Series Voltage
120
208 1
240 1
277
347
480 1
Number of Conductors
D Three
E Four
F Five
Options add only if required
2N Two circuits, two neutrals
IG Isolated ground
Notes:
1. For use with 208, 240, 480 volts, consult factory.
820-100
CD
DIMENSIONS SHOWN IN INCHES AND (MILLIMETERS)
A Die-cast zinc with zinc-plated CRS cover
B UL recognized connector body
C Tin-plated copper contacts
D Six-inch Leads prestripped 5/8"
E Threaded nipple with locknut for easy installation in 1/2" tradesize K.O.
CD.P65 ©1996 Acuity Lighting Group, Inc., Rev. 7/97
Lithonia Lighting
Acuity Lighting Group, Inc.
Reloc Wiring Systems
One Lithonia Way, Decatur, GA 30035
Phone: 800-241-4750
In Canada: 1100 50th Ave., Lachine, Quebec H8T 2V3 www.lithonia.com
• Pin and socket contacts.
• Rated for use on 20-amp branch circuits.
• All No. conductors are No. 12 AWG copper with 90°C thermoplastic insulation rated at 600V.
• All components provide a fully rated No. 12 AWG grounding conductor.
• Safety-keying prevents accidental mismatching of components with different voltages.
• Additional labeling properly denotes type and position of each conductor.
• Available in most lengths to suit job requirements.
• Auto-latching springs prevent accidental disengagement.
• UL listed.
• Listed and labeled to comply with Canadian Standards.
Catalog Number
Type .............................................................................................................................................................
Notes
Catalog number .........................................................................................................................................
CE
The Cable Extender is a male/female cable that provides additional length anywhere throughout the Reloc system. The CE provides power to the ST to introduce local switching. The CE also provides power to the RCA, RCR, PT, SSU and CSU.
The following information details the construction of a typical catalog number. Consult your RELOC sales representative for any special product needs.
CE U
Series Voltage
120
208 1
240 1
277
347
480 1
Number of Conductors
D Three
E Four
F Five
Factory Keying
CE 120 D U 3 2N
Cable Length
Available in lengths from 3 to 31 feet in two foot increments
Options add only if required
2N Two circuits, two neutrals
IG Isolated ground
Notes:
1. For use with 208, 240, 480 volts. Consult factory.
Reloc
820-110
CE
DIMENSIONS SHOWN IN INCHES AND (MILLIMETERS)
A Die-cast zinc with zinc-plated CRS cover
B UL recognized connector body
C Tin-plated copper contacts
1, 2 or 3 hot conductors in 120V and 277V as required. Rated for 20amp capacity.
Prefabricated Cable Extender carrying No. 12 AWG copper conductors rated at 600V, 90°C thermoplastic insulation and fully rated solid bare grounding conductor.
CE.P65 ©1996 Acuity Lighting Group, Inc., Rev. 7/97
Lithonia Lighting
Acuity Lighting Group, Inc.
Reloc Wiring Systems
One Lithonia Way, Decatur, GA 30035
Phone: 800-241-4750
In Canada: 1100 50th Ave., Lachine, Quebec H8T 2V3 www.lithonia.com
Pin and socket contacts.
Rated for use on 20-amp branch circuits.
Snaps into standard 1/2" trade-size knockoutno locknut required.
All conductors are No. 12 AWG copper with 90°C thermoplastic insulation rated at 600V.
All components provide a fully rated No. 12 AWG grounding conductor.
Safety-keying prevents accidental mismatching of components with different voltages.
Color-coding rapidly identifies system voltage.
Additional labeling properly denotes type and position of each conductor.
No. 12 AWG copper leads provided with poke-home connectors.
Auto-latching springs prevent accidental disengagement.
Male/female design allows removal without additional components.
Extremely low-profile.
UL listed, CSA Certified and IBEW union assembled.
The Circuit Selector Unit provides wiring of any device through a 1/2" trade-size knockout. The CSU used No. 12 AWG leads which allow for full circuit access.
Catalog Number
Notes Type
Catalog number .........................................................................................................................................
Circuit Selector Unit
CSU
The following information details the construction of a typical catalog number. Consult your
RELOC sales representative for any special product needs.
CSU F
Series Voltage
120
208
240
1
1
277
347
480 1
Number of Conductors
F Five
U
Factory Keying
Example: CSU 120 F U 2N
Options add only if required
2N Two circuits, two neutrals
IG Isolated ground
820-150
CSU
DIMENSIONS SHOWN IN INCHES AND (MILLIMETERS)
A Die-cast zinc with zinc plated CRS cover
B UL recognized connector body
C Tin-plated copper contacts
D Cast snap-in fitting 1/2" trade-size KO and provides gounding.
E No. 12 AWG copper wires with 600V, 90°C thermoplastic insulation
4-5/8" (117.5)
2-3/16"
(55.6)
1-7/16"
(36.5)
9/16"
(14.3)
1-1/16"
(27.0)
csu.pdf ©1996 Acuity Lighting Group, Inc., Rev. 01/96
Lithonia Lighting
Acuity Lighting Group, Inc.
Reloc Wiring Systems
One Lithonia Way, Decatur, GA 30035
Phone: 800-241-4750
In Canada: 1100 50th Ave., Lachine, Quebec H8T 2V3 www.lithonia.com
The Drop Cable allows any convenience power outlet, switch or other device (clock, miscellaneous fixture, etc.) to become part of the Reloc system. The use of conventional pipe and wire is not required in these applications to convey the wiring.
• Pin-and-socket contacts
• Rated for use on 20-amp branch circuits
• All conductors are No. 12 AWG copper with 90 o C thermoplastic insulation rated at 600V
• All components provide a fully-rated No. 12 AWG grounding conductor
• Prestripped solid-copper leads for easy installation into side, back or push-in type terminals
• Safety-keying prevents accidental mismatching of components with different voltages
• Color-coding rapidly identifies system voltage
• Additional labeling properly denotes type and position of each conductor
• Available in most lengths to suit job requirements
• Auto-latching springs prevent accidental disengagement
• Installs through standard 1/2" trade-size knockout
• UL listed; listed and labeled to comply with Canadian Standards
Catalog Number
Notes Type
DC
DC
Family
DC
Voltage
120 120V
208 208V *
240 240V *
277 277V
347 347V
480 480V *
Number of conductors
D Three
E Four
F Five
*For use with 208, 240 and 480 volts. Consult factory.
U
Factory keying
Cable length
Available in lengths up to 31’ in two-foot increments.
Options
2N Two circuits, two neutrals
IG Isolated ground
DC 120 D U 09
Reloc
820-170
DC
Dimensions are shown in inches (millimeters).
A 18-gauge, zinc-plated CRS cover
B UL-recognized connector body
C Tin-plated, copper contacts
D .015” spring steel latches
Prefabricated lighting drop cable assembly carrying No. 12 AWG standard copper conductors rated at 600V with 90 o
C thermoplastic insulation and fully rated insulated grounding conductor
D
Sheet #: DC DC.P65 ©1990 Acuity Lighting Group, Inc., Rev. 7/98
Lithonia Lighting
Acuity Lighting Group, Inc.
Reloc Wiring Systems
One Lithonia Way, Decatur, GA 30035
Phone: 800-241-4750
In Canada: 1100 50th Ave., Lachine, Quebec H8T 2V3 www.lithonia.com
The Power Tee is a through-wired component that makes it possible to select which branch circuit conductor feeds a specific device. The PT also provides power to devices used on convenience power, access floor systems and commercial lighting.
• Pin-and-socket contacts.
• Rated for use on 20-amp branch circuits.
• Replaces conventional cord and plug.
•
All conductors are No. 12 AWG copper with 90 o C thermoplastic insulation rated at 600V.
• All components provide a fully-rated No. 12 AWG grounding conductor.
• Accommodates up to three hot conductors plus neutral and ground feed-through of branch circuits in a single component.
• Enables receptacle outlets or utilization equipment (e.g., exit signs) to become a part of the Reloc system.
•
Prestripped solid-copper leads for easy installation into side, back or push-in type terminals.
• Safety-keying prevents accidental mismatching of components with different voltages
• Color-coding rapidly identifies system voltage
• Additional labeling properly denotes type and position of each conductor
•
Male/female design allows removal of a device without additional components.
• Available in most lengths to suit job requirements
• Auto-latching springs prevent accidental disengagement
• Installs through standard 1/2" trade-size knockout
•
UL listed; CSA Certified and IBEW union assembled.
Catalog Number
Notes Type
PT
PT
Series Voltage
120 120V
277 277V
347 347V
Number of conductors
F Five
Tap position
1 Tap from position one
2 Tap from position two
3 Tap from position three
12 Tap from position one and two
13 Tap from position one and three
23 Tap from position two and three
123 Tap from position one, two and three
Type of drop
A Armored
PT 120 F 1 A 01 2N
Cable length
01 One foot
03 Three feet
09 Nine feet
Options
2N Two circuits, two neutrals
IG Isolated ground
*For use with 208, 240 and 480 volts. Consult factory.
Reloc
820-160
PT
Dimensions are shown in inches (millimeters).
A Die-cast zinc with zinc-plated, cold-rolled steel cover
B UL-recognized connector body
C Tin-plated, copper contacts
D No. 12 AWG wire with 600V, 90 o C thermoplastic insulation rated for 20-amp capacity
PT.P65 ©2001 Acuity Lighting Group, Inc., Rev. 10/01
Lithonia Lighting
Acuity Lighting Group, Inc.
Reloc Wiring Systems
One Lithonia Way, Decatur, GA 30035
Phone: 800-241-4750
In Canada: 1100 50th Ave., Lachine, Quebec H8T 2V3 www.lithonia.com
The Splitter Splice is used to split the branch circuit into two directions. The SS is a male/female component that allows it to be used anywhere throughout the Reloc system.
• Pin-and-socket contacts.
• Rated for use on 20-amp branch circuits.
• All conductors are No. 12 AWG copper with 90 o C thermoplastic insulation rated at 600V.
• All components provide a fully-rated No. 12 AWG grounding conductor.
• Capable of accommodating cable with up to three conductors.
• Safety-keying prevents accidental mismatching of components with different voltages.
• Additional labeling properly denotes type and position of each conductor.
• Listed and labeled to comply with Canadian Standards.
Catalog Number
Notes Type
SS
SS F
Family
SS
Voltage
120
208 *
240 *
277
347
480 *
# of conductors
F Five
* For use with 208V, 240V and 480V; consult factory.
U
Factory keying
U
Reloc
SS 120 F U
820-180
SS
Dimensions are inches (millimeters).
A
B
C
Die-cast zinc with zinc-plated CRS cover
UL-recognized connector body
Tin-plated copper contacts
Prefabricated splice module carrying No. 12 AWG copper conductors rated at 600V, 90°C thermoplastic insulation and fully rated grounding conductor.
SS.P65 ©1996 Acuity Lighting Group, Inc., Rev. 7/97
Lithonia Lighting
Acuity Lighting Group, Inc.
Reloc Wiring Systems
One Lithonia Way, Decatur, GA 30035
Phone: 800-241-4750
In Canada: 1100 50th Ave., Lachine, Quebec H8T 2V3 www.lithonia.com
Pin and socket contacts.
Rated for use on 20-amp branch circuits.
All conductors are No. 12 AWG copper with 90°C thermoplastic insulation rated at 600V.
All components provide a fully rated No. 12 AWG grounding conductor.
Fixture leads are No. 18 AWG solid copper, with poke-home terminals for easy connection to ballast leads. No wirenuts required.
Safety-keying prevents accidental mismatching of components with different voltages.
Color-coding rapidly identifies system voltage.
Additional labeling properly denotes type and position of each conductor.
Snaps into standard 1/2" trade-size knockoutno locknut required.
Designed with auto-grounding (fixture) mechanism standard.
Available in varying lengths to suit most common fixture spacing requirements.
UL listed, CSA Certified and IBEW union-assembled.
The Standard Selector Cable is a male/female cable that provides power from fixture to fixture. The SSC attaches directly into the access plate or through any 1/2" trade-size knockout.
Standard Selector Cable
SSC
The following information details the construction of a typical catalog number. Consult your
RELOC sales representative for any special product needs.
SSC
Series Voltage
120
277
347
Number of
Conductors
D Three
E Four
F Five
U
Factory Keying Cable Length
Available in lengths from 3 to 31 feet in two foot increments
Example: SSC 120 D U 2N
Options add only if required
2N Two circuits, two neutrals
G Ground leads with lug terminal
FP Factory pack selector cable equipped with prestripped leads to be wired into fixture by
O.E.M. (length of cable limited to
13 feet)
820 - 120
SSC
DIMENSIONS SHOWN IN INCHES AND (MILLIMETERS)
DIMENSIONS
A UL recognized connector body
B Die-cast zinc with zinc-plated CRS cover
C Tin plated copper contacts
D Cast snap-in fitting fits 1/2" trade-size K.O. and provides grounding
E No. 18 AWG solid copper wires rated at 600V, 90°C thermoplastic insulation with UL recognized poke-home terminals
1, 2 or 3 hot conductors in 120V and 277V as required.
Prefabricated Standard Selector Cable carrying No. 12 AWG copper conductors. 600V, 90°C thermoplastic insulation and fully rated solid bare grounding conductor. Rated for 20-amp capacity.
NOTE: Standard Selector Cable provides auto-grounding to fixture unless specified otherwise. Lengths of 19 feet or longer provide a ground drop as standard.
ssc.pdf ©1996 Acuity Lighting Group, Inc., Rev. 1/96
Lithonia Lighting
Acuity Lighting Group, Inc.
Reloc Wiring Systems
One Lithonia Way, Decatur, GA 30035
Phone: 800-241-4750
In Canada: 1100 50th Ave., Lachine, Quebec H8T 2V3 www.lithonia.com
Pin and socket contacts.
Rated for use on 20-amp branch circuits.
All conductors are No. 12 AWG copper with 90°C thermoplastic insulation rated at 600V.
All components provide a fully-rated No. 12 AWG grounding conductor.
Enables switches to be completely wired into the Reloc system.
Provides switched and unswitched power at every switch location.
Located directly over switch.
Prestripped, solid copper leads for easy installation into side, back or push-in type terminals on switches.
Safety-keying prevents accidental mismatching of components with different voltages.
Additional labeling properly denotes type and position of each conductor.
Color-coding rapidly identifies system voltage.
UL listed, CSA Certified and IBEW union-assembled.
The Switching Tee, located above the primary switch location, introduces local switching to Reloc systems. It provides local switched power and unswitched power to be used as needed for subsequent fixtures.
Catalog Number
Type .............................................................................................................................................................
Notes Type
Catalog number .........................................................................................................................................
ST
The following information details the construction of a typical catalog number. Consult your
RELOC sales representative for any special product needs.
ST
Series
P
Drop Type
P Protected
Voltage
120
277
347
Number of
Conductors
D Three
E Four
F Not applicable
Switching
Function
1 Single level switching
2 Two level switching
3 Three-way switching
(primary only)
4 Four-way switching
ST 120 D 1 P U 06 N
U
Factory
Keying
Cable
Length
06 Six feet
08 Eight feet
15 Fifteen feet
Options add only if required
N Neutral provided in drop
2N Two circuits, two neutrals
820-140
ST
DIMENSIONS SHOWN IN INCHES AND (MILLIMETERS) WIRING SCHEMATICS
ST____D2PU06
A UL recognized connector body
B Tin plated copper contacts
C No. 12 AWG wire rated at 600V 90°C thermoplastic insulation
D Die-cast zinc with zinc-plated CRS cover
Rated for 20-amp capacity
ST____E2PU06
st.pdf ©1996 Acuity Lighting Group, Inc., Rev. 1/96
Lithonia Lighting
Acuity Lighting Group, Inc.
Reloc Wiring Systems
One Lithonia Way, Decatur, GA 30035