SEVO® Systems Provider Remote Annunciator Designed with: CP-4410RA 3M™ Novec™ 1230 Fire Protection Fluid The CP-4410RA remote annunciator is designed to operate with the CPRP4410 releasing control panel. The unit mounts to a 4 gang box. There are 34 LED's to indicate a change in panel status. There is a buzzer on the annunciator that sounds for any trouble or supervisory condition. Pressing the LAMP TEST button illuminates all of the lamps. The release panel supervises and communicates with the annunciator via separate connections for the RS-485 communication and the 24VDC power requirements of the CP-4410RA. Seperate cables should be used for power and communication. Shielded cable must be used for the communication line. Up to four annunciators can be connected to one panel. A Rotary switch is provided on the panel to indicate how many annunciators are connected. Another rotary switch is on the annunciator to set the address. The annunciators must be addressed consecutively. Architecture/Engineering Specifications The Annunciator for the extinguishing agent release panel shall be a microprocessor based device. The unit shall require 24vdc operating voltage and a shielded RS-485 connection for communication; both supplied by the release panel. The annunciator shall have a rotary switch to set the address number of that annunciator to allow for supervision by the panel. The annunciator shall have indicators for Alarm, Trouble, and Supervisory per zone, Output circuits active, Output circuit troubles, AC power, Power trouble, Supervisory condition, Supervisory trouble, Abort, System trouble, Alarm silence, Ground fault, Abort, Pre-discharging/Discharged. In addition to the visual indicators there shall also be a buzzer that sounds on any trouble or supervisory condition, a button to silence the buzzer and test the indicators. • Up to 4 annunciators can be connected to one PFC4410RC • Rotary switches on panel and annunciator for supervisory purposes • Trouble/Supervisory buzzer • Separate LED's for: Alarm and Trouble per zone, Outputs activated or in trouble, Supervisory, Abort, Supervisory trouble, Power trouble, System trouble, Alarm silence, Ground fault, Discharging/Discharged • Lamp test silence switch • Slide in Zone & Output identification labels SEVSafe Environmental SYSTEMS Choice ® info@SEVOSystems.com • • • • • • • • UL, cUL, & CSFM Listed, FM Approved, MEA Accepted Dimensions: 8-1/4" W x 4-1/2" H x 1" D (Approximate) Enclosure: Stainless steel plate with clear plastic shield protecting zone and output identification labels. Mounts in 4 gang box. For surface mounting use back box stk# 3006401 Environmental Specifications: Indoor use only Temperature range 32°F to 120°F (0°C to 49°C) 93% Humidity Electrical Requirements: • 24VDC 10 ma standby 26ma max. (lamp test) • RS-485 Communication: (Two wire Shielded cable required). • Ground drain wire to S terminal on PFC-4410RC only. • Max. Distance: 2000 ft. using 22 ga. wire and 4000 ft. using 20 ga. wire. Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Remote Annunciator Designed with: 3M™ Novec™ 1230 Fire Protection Fluid PFC-4410RC Main Board 24 VDC RS-485 S CP-4410RA ANNUNCIATOR SELECTOR SWITCH SET FOR THE TOTAL NUMBER OF DEVICES INSTALLED ON THE RS-485 TERMINALS 120 OHM RESISTOR - REMOVE THE RESISTOR FROM THE PFC-4410RC AND INSTALL ON THE LAST DEVICE ONLY. CONNECT THE DRAIN WIRE OF THE SHIELDED CABLE TO THE S TERMINAL ON THE PFC-4410RC ONLY. DO NOT CONNECT THE DRAIN WIRE TO ANY ANNUNCIATOR. THE DRAIN WIRE MUST MAKE A CONTINUOUS PATH TO THE LAST ANNUNCIATOR WHERE IT IS CUT OFF AND INSULATED. RA-4410RC #1 NOTE: THE RESISTOR IS INSTALLED ONLY ON LAST DEVICE. S 24 VDC RS-485 ANNUNCIATOR ADDRESS SWITCH (FIRST DEVICE, ADDRESS 1) DO NOT CONNECT THE SHIELDED CABLE TO THE REMOTE ANNUNCIATOR RA-4410RC #2 CUT OFF AND TERMINATE THE DRAIN WIRE AT THE LAST DEVICE. DO NOT CONNECT THE SHIELDED CABLE TO THE REMOTE ANNUNCIATOR S 24 VDC RS-485 INSTALL THE RESISTOR ON THE LAST RA-4410RC ANNUNCIATOR ADDRESS SWITCH DWG# 1175-2 SEV SYSTEMS Safe Environmental Choice ® info@SEVOSystems.com Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Releasing Circuit Disable Switch Designed with: AS-55 3M™ Novec™ 1230 Fire Protection Fluid Description The device consists of a stainless steel faceplate and a modular switch assembly. It is designed to mount on a standard single gang electrical enclosure. Application The AS-55 complies with the requirements of NFPA 72, 2007, 6.12.5, 6.12.5.1, and 6.12.5.2: • Specifying a physical switch to disconnect the release circuit in place of a software controlled disconnect. • Creating a supervisory condition on the associated release panel. Installation and Operation 1. Connect the red and black leads to the 24 VDC auxiliary power terminals on the release panel. Be certain to observe polarity. RED BLACK YELLOW 2. Connect the yellow wires to the supervisory zone on the panel. YELLOW ORANGE ORANGE • • • • The connection for the supervisory circuit has 4 wires: 2 yellow and 2 grey. The 2 yellow wires are for connection to the supervisory circuit. The 2 grey wires are for connection to additional supervisory devices or the EOLR for the supervisory zone. SEVSafe Environmental SYSTEMS Choice ® info@SEVOSystems.com • • • • UL recognized components Dimensions: 2 3/4" W x 4-1/2" H x 2" D (Approximate) Mounts on single gang or handy box Contact Rating: Key operated switch with 2 N.O. contacts 2.5A/125VAC, 350 mA/125VDC Power Requirements: 24 VDC Environmental Specifications: Indoor use only Temperature range -22°F to 140°F (-30°C to 60°C) Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Abort Switch Designed with: CP-4410AS 3M™ Novec™ 1230 Fire Protection Fluid Description The Potter Abort Switch is designed to be wired to the abort terminals of the Potter PFC-4410-RC, PFC-4410A-RC and PFC4410RC (9th Edition) releasing panels. The device consists of a stainless steel faceplate and a modular switch assembly. It is designed to mount on a standard double gang electrical enclosure. EOLR FROM RELEASING PANEL DWG. #1136-1 • • • • • SEV SYSTEMS Safe Environmental Choice ® info@SEVOSystems.com UL Listed, and FM Approved Dimensions: 4-1/2" W x 4-1/2" H x 2" D (Approximate) Contact Rating: One N.O. momentary contact rated. 5 Amps @ 24 VDC (10 ma minimum) Environmental Specifications: Indoor use only Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Pull Station Designed with: AL-MR 3M™ Novec™ 1230 Fire Protection Fluid Description The Potter Pull Station Series offers a complete line of diecast pull stations for a variety of applications focusing mainly on fire alarm systems. The pull stations are available in single or dual action models. All of the pull stations have a 10-amp snap action switch and a dedicated terminal block for the ease of wire connections. All of the metal is completely coated to inhibit corrosion and provide for a uniform and quality finish. The standard models have a hex key reset. The models are available with shallow and deep surface mount back boxes, as well as a weatherproof version that is rated for NEMA 4. Operation The Potter single action series of pull stations operate by pulling the white operating handle straight down and the handle will lock into place. The dual action stations require the lifting of the front cover and then pulling the white operating handle straight down. The stations are reset by opening the front and placing the handle in the normal position. Engineering Specifications The contractor shall furnish and install the Potter series of pull stations as indicated. The pull station shall be die cast construction with a "T" type pull handle that is ADA compliant. Single action pull stations shall be the MS-NBG12. Dual action pull stations shall be the AL-MR. The contact shall be a single pole, single throw switch rated at 1 amp 30V DC/125V AC. The device shall have a terminal block for ease of wiring. Once activated, the pull station shall be reset by opening the front cover. Opening of the cover in a normal state shall initiate an alarm. Specifications Switch Rating: 1 Amp @ 30 VDC 1 Amp @ 125 VAC Pull Station Dimensions: 4-3/4" H x 3-1/4" W x 7/8" D Single Pull Color: Red with raised white letters, white pull bar with raised red letters Double Pull Color: Blue with raised white letters. SEVSafe Environmental SYSTEMS Choice ® info@SEVOSystems.com • • • • • • • • • • • UL and ULc Listed, FM Approved, CSFM Listed, MEA Approved, ADA Compliant Single or Dual Action Terminal connectors 10 Amp Snap Action Switch Gold plated SPST contacts Optional auxiliary contacts Mounts on standard single gangbox Surface backboxes available High-gloss red enamel finish Glass breakrod Made in the U.S.A. Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Indoor/Outdoor Horn Designed with: AL-H-IE 3M™ Novec™ 1230 Fire Protection Fluid The AL-H-IE Electronic Horn allows a number of applications on a single device. The horn settings include Temporal, NonTemporal, March Time and a Chime sound. The horn also has Low, Mid and High volume settings for each pattern and tone. The tones include 2400 Hz, Electro-Mechanical, Broadband and Chime. The voltage input can be either regulated DC or full wave rectified (FWR) 12 volt or 24 volt operation. The AL-H-IE utilizes a universal mounting plate that will mount on a single gang, double gang, octagon and 4” square electrical boxes. Outdoor installations must use either the BBK-1 4” square (weatherproof bell backbox) or the BBX-5 (weatherproof backbox). The back plate allows the installer to mount the plate and terminate the wire connections. The horn attaches in a hinge fashion from the top and is secured by a single mounting screw. The horn completely covers the mounting back plate, therefore it can be mounted before other trades work is completed and not affect the final look. Call for additional listings Note: Installation must comply in accordance with applicable standards. DWG# 8910006-1A • • • • • • • • • • • 33 sound output settings Horn or chime sound output Indoor/outdoor* listed Pre-wire back plate Universal back plate mounting (single gang, double gang, octagon, or 4” square) Single screw mounting Low current draw UL and cUL listed Patents pending Outdoor installation requires the BBK-1 #1500001, BBX5R #4270048, or BBX-5W #4270049 SEV SYSTEMS Safe Environmental Choice ® info@SEVOSystems.com OPTIONAL BBK-1 WEATHERPROOF BACKBOX A jumper plug is provided to test for correct wiring in the supervisory mode only. Do not pass alarm current through the jumper. Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Indoor/Outdoor Horn Designed with: AL-H-IE 3M™ Novec™ 1230 Fire Protection Fluid PFC-4410RC Main Board 24 VDC RS-485 S ANNUNCIATOR SELECTOR SWITCH SET FOR THE TOTAL NUMBER OF DEVICES INSTALLED ON THE RS-485 TERMINALS 120 OHM RESISTOR - REMOVE THE RESISTOR FROM THE PFC-4410RC AND INSTALL ON THE LAST DEVICE ONLY. CONNECT THE DRAIN WIRE OF THE SHIELDED CABLE TO THE S TERMINAL ON THE PFC-4410RC ONLY. DO NOT CONNECT THE DRAIN WIRE TO ANY ANNUNCIATOR. THE DRAIN WIRE MUST MAKE A CONTINUOUS PATH TO THE LAST ANNUNCIATOR WHERE IT IS CUT OFF AND INSULATED. RA-4410RC #1 NOTE: THE RESISTOR IS INSTALLED ONLY ON LAST DEVICE. S 24 VDC RS-485 ANNUNCIATOR ADDRESS SWITCH (FIRST DEVICE, ADDRESS 1) DO NOT CONNECT THE SHIELDED CABLE TO THE REMOTE ANNUNCIATOR RA-4410RC #2 CUT OFF AND TERMINATE THE DRAIN WIRE AT THE LAST DEVICE. DO NOT CONNECT THE SHIELDED CABLE TO THE REMOTE ANNUNCIATOR S 24 VDC RS-485 INSTALL THE RESISTOR ON THE LAST RA-4410RC ANNUNCIATOR ADDRESS SWITCH DWG# 1175-2 SEVSafe Environmental SYSTEMS Choice ® info@SEVOSystems.com Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Indoor/Outdoor Horn Designed with: AL-H-IE 3M™ Novec™ 1230 Fire Protection Fluid 6 7 8 Architecture/Engineering Specifications The installer shall provide and install the Potter AL-H-IE indoor/outdoor selectable horn. The horn shall have thirtythree (33) different settings. The horn shall be selectable for continuous (non-temporal), temporal (ANSI Code 3) and March Time patterns. The horns shall have a 2400 hertz, Electro-Mechanical, Broadband or a Chime tone. Each of the patterns and tones shall be selectable for a Low, Mid or High volume setting. The horn shall operate at 12 or 24 VDC regulated or full wave rectified. The horn shall have an operating range between 8 and 33 VDC. The horn shall utilize a mounting plate that allows the installer to pre-wire the mounting plate. The mounting plate shall be universal and mount on a single gang, double gang, octagon or 4 inch square box. If the horn is needed in a wet or outdoor installation, it shall be mounted on either a BBX-1 4” square back box or a BBK-5 outdoor matching back box. The horn shall have a gasket on the back plate that seals the electrical connection of the terminal connection. The mounting plate shall be completely covered by the horn and shall be secured by a single screw. Operating temperature range will be 32°F to 120°F (0°C to 49°C) for indoor model and -40°F to 151°F (-40°C to 66°C) for outdoor model. The horn shall be UL listed to standard 464, Audible Signaling Devices. In addition, the device shall be cUL listed to CANULC S525. 6 5/64 (154.4) 5 5 (127) 1 27/32 (47) Dipswitch Settings Pattern 1 ON - Non-temporal 1 OFF - Temporal 1 2 3 4 Both 2 = OFF 1 and 2 ON = March Time Tone 3 and 4 ON = 2400Hz 3 ON and 4 OFF = Electromechanical 3 and 4 OFF = Chime 3 OFF and 4 ON = Broadband Volume 5 and 6 ON = High 5 ON and 6 OFF = Mid 5 and 6 OFF = Low 7 and 8 ON = Horn/strobe on 2 wires 7 and 8 OFF = Horn and strobe on 4 wires DWG# 8910006-3 DWG# 8910006-2A Voltage Regulated 12 DC/ FWR Regulated 24 DC/FWR Operating Voltage Range 8 - 17.5V 16 - 33V Sync Modules NA Available Operating Temperature Range SEV SYSTEMS Safe Environmental Choice ® info@SEVOSystems.com 12/24V UL Designation Indoor: 32°F to 120°F (0°C to 49°C) Outdoor: -40°F to 151°F (-40°C to 66°C) Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Wall Mount Strobe/Horn Designed with: 3M™ Novec™ 1230 Fire Protection Fluid AL-HIS The AL-HIS Strobe/Horn Series provides a wide range of candela light output options in a single device. The candela settings include a 12 or 24 volt DC operation for the 15, 35 and 60 (75 on axis) candela settings and 24 volt DC operation for the 15, 35, 60, 75, 95 and 110 candela settings. The candela setting is displayed through the front window and is selectable using a drum wheel. The horn settings include Temporal, Non-Temporal, March Time and a Chime sound. The horn also has Low, Mid and High volume settings for each pattern and tone. The tones include 2400 Hz, Electro-Mechanical, Broadband and Chime. The voltage input can be either regulated DC or full wave rectified (FWR) 12 volt or 24 volt operation with an operating range from 8 to 33 V DC. The strobes can be synchronized using a control panel with the Potter (Amseco) sync protocol or a SMD10-3A sync module. The AL-HIS utilizes a universal mounting plate that will mount on a single gang, double gang, octagon and 4” square electrical boxes. The back plate allows the installer to mount the plate and connect the wire connections. The strobe attaches in a hinge fashion from the top and is secured by a single mounting screw. The strobe completely covers the mounting back plate, therefore it can be mounted before other trades work is completed and not affect the final look. • • • • • • • • • • • • • 12 VDC with 15, 35 or 60 cd setting 24 VDC with 15, 35, 60, 75, 95 or 110 cd settings 6 distinct candela settings Candela selection view window 15/75 ADA compliant on 60cd setting 33 sound output settings Horn or chime sound output Pre-wire back plate Universal back plate mounting (single gang, double gang, octagon, or 4” square) Single screw mounting Low current draw UL and cUL listed Patents pending SEVSafe Environmental SYSTEMS Choice ® info@SEVOSystems.com Note: Installation must comply in accordance with applicable standards. A jumper plug is provided to test for correct wiring in the supervisory mode only. Do not pass alarm current through the jumper. Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Wall Mount Strobe/Horn Designed with: AL-HIS 3M™ Novec™ 1230 Fire Protection Fluid Dimensions: inches (mm) 6 5/64 (154.4) Light output in percentage when measured from the following directions per UL 1971. 2 5/16 (59) 5 (127) High voltage may be present inside the light assembly even though power is not connected. If access to teh coponent board is required (removal or replacement), the capacitor must be discarged by touching a wire to both ends of the flashtube. DO NOT attempt to touch or move the assembly until the capacitor has been discharged. Specifications Strobe Current Light Output Max. RMS Operating Current (mA RMS) Reg. 12 VDC Reg. 12 FWR Reg. 24 VDC Reg. 24 FWR 15cd 116 152 62 99 35cd 209 267 102 152 60/75cd 254 258 131 190 75cd NA NA 146 208 95cd NA NA 177 243 110cd NA NA 196 268 Voltage 12/24V UL Designation Regulated 12 DC/FWR Regulated 24 DC/FWR Operating Voltage Range 8 - 17.5V 16 - 33V Flash Rate 60 times/min. Sync Module (SMD10-3A) Operating Temperature Range NA Available Indoor model: 32°F to 120°F (0°C to 49°C) Note: To determine total current draw, add desired strobe setting and horn selection. Refer to the installation instructions for further information. SEV SYSTEMS Safe Environmental Choice ® info@SEVOSystems.com ON Horn Dipswitch Pattern 1 ON - Non-temporal 1 2 3 4 1 OFF - Temporal Both 2 = OFF 1 and 2 ON = March Time Tone 3 and 4 ON = 2400Hz 3 ON and 4 OFF = Electromechanical 3 and 4 OFF = Chime 3 OFF and 4 ON = Broadband Volume 5 and 6 ON = High 5 ON and 6 OFF = Mid 5 and 6 OFF = Low 7 and 8 ON = Horn/strobe on 2 wires 7 and 8 OFF = Horn and strobe on 4 wires 5 6 7 8 Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Wall Mount Strobe/Horn Designed with: AL-HIS 3M™ Novec™ 1230 Fire Protection Fluid Non-Temporal Horn Current Pattern 2400 Hz Electro-Mechanical Broadband Chime Volume Max. RMS Current (mA RMS Current) dBA Reverberant Ratings per UL464 (dBA @ 10 ft.) dBA Anechoic Ratings per CAN/ULC S525 (dBA @ 10 ft.) Reg 12 VDC Reg 24 VDC Reg 12 VDC Reg 24 VDC Reg 12 VDC Reg 24 VDC High 119 87 87 87 99 100 Mid 44 28 82 82 94 96 Low 30 18 79 80 92 92 High 118 81 86 87 100 100 97 Mid 43 26 82 84 96 Low 27 16 79 80 93 93 High 146 78 86 86 101 102 Mid 41 26 81 82 96 98 Low 28 16 77 79 94 95 High 27 21 70 70 86 86 Mid 11 8 62 62 79 80 Low 9 7 58 57 75 75 Temporal Horn Current Pattern 2400 Hz Electro-Mechanical Broadband Chime Volume Max. RMS Current (mA RMS Current) dBA Reverberant Ratings per UL464 (dBA @ 10 ft.) dBA Anechoic Ratings per CAN/ULC S525 (dBA @ 10 ft.) Reg 12 VDC Reg 24 VDC Reg 12 VDC Reg 24 VDC Reg 12 VDC Reg 24 VDC High 124 87 82 82 100 100 Mid 46 30 77 79 95 96 Low 30 18 74 75 92 92 High 114 80 83 82 100 101 96 Mid 42 27 78 80 95 Low 28 16 75 76 93 93 High 151 80 82 82 101 102 Mid 45 26 77 78 97 98 Low 30 16 75 76 94 95 High 29 21 68 70 86 86 Mid 10 9 61 61 79 79 Low 9 8 55 55 75 76 March Time Horn Current Pattern 2400 Hz Electro-Mechanical Broadband SEVSafe Environmental SYSTEMS Choice ® info@SEVOSystems.com Volume Max. RMS Current (mA RMS Current) dBA Reverberant Ratings per UL464 (dBA @ 10 ft.) dBA Anechoic Ratings per CAN/ULC S525 (dBA @ 10 ft.) Reg 12 VDC Reg 24 VDC Reg 12 VDC Reg 24 VDC Reg 12 VDC Reg 24 VDC High 121 92 83 84 99 100 Mid 47 31 79 81 95 96 Low 36 19 76 77 92 92 High 114 86 83 83 100 100 96 Mid 42 27 80 81 95 Low 30 19 77 77 92 93 High 153 77 83 84 101 102 Mid 42 28 79 80 97 98 Low 29 16 76 77 94 95 Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Wall Mount Strobe/Horn Designed with: AL-HIS 3M™ Novec™ 1230 Fire Protection Fluid Wiring Diagram H H DWG# 8910004-1 Architecture/Engineering Specifications The installer shall provide and install the Potter AL-HIS selectable strobe/horn. The strobe shall have six (6) candela settings. The candela settings shall be selectable using a drum roller and shall display the candela setting on the front of the device. The horn shall have 33 selectable settings configurable by dip switches. The sounder shall be capable of ANSI Temporal Code 3, March Time and produce a chime output. The horn shall have three distinct volume levels. The strobe/horn shall operate at 12 or 24 VDC regulated or full wave rectified. The strobe/horn shall have an operating range between 8 and 33 VDC. the strobes an by synchronized using a SEV SYSTEMS Safe Environmental Choice ® info@SEVOSystems.com control panel with the Potter sync protocol or the SMD103A sync module. The strobe shall utilize a mounting plate that allows the installer to pre-wire the mounting plate. The mounting plate shall be universal and mount on a single gang, double gang, octagon or 4 inch square box. The mounting plate shall be completely covered by the strobe and shall be secured by a single screw. The strobe shall be UL listed to standard 1638, General Signaling, and standard 1971, Signaling Devices for the Hearing Impaired. In addition, the strobes shall be cUL listed to CAN-ULC S526. The horn shall be UL listed to standard 464, Audible Signaling Devices. Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Ionization Smoke Detector Designed with: SD-I-24 3M™ Novec™ 1230 Fire Protection Fluid The SD-I-24 can be used in all areas where Ionization Smoke Detectors are required. The responsive, yet highly stable operation allows the SD-I-24 to fit in a wide range of uses. The SD-I-24 can be used in areas where early warning of superheated or flaming combustibles is expected. SB Series style bases may be used with the SD-I-24. The only current compatible device is the SD-P-24 Photoelectric detector. Operation The SD-I-24 ionization smoke detector utilizes two bi-colored LED's for status indication purposes. In a normal standby condition the LED's flash green approximately once each second. When the detector senses smoke and goes into alarm the status LED's will latch on red. A single radioactive source of Americium-241 ionizes two chambers within the detector, a reference chamber and the smoke sensing chamber. The air is ionized by this source and a small DC current flows between the electrodes of each chamber. Smoke can freely enter the sensing chamber, while the inner chamber is virtually sealed to smoke. Smoke entering the sensing chamber causes a reduction in the DC current flow, the voltage imbalance between the two chambers is proportional to the smoke density. When the voltage difference becomes great enough it causes the detector to go into alarm. The two chamber design is utilized to compensate for changes in atmospheric and environmental conditions. • • • • • • • • • • • • Low profile, 1.8” high (with base) 2 or 4 wire base compatibility, relay bases available Highly stable operation, RF/Transient protection Low standby current, 40 µA at 24 VDC Two built-in power/alarm LED’s for 360° viewing Non-directional smoke chamber Vandal resistant security locking feature Built-in magnetic detector sensitivity test feature. Meets NFPA 72, Chapter 7, Inspection, Testing and Maintenance requirements Compatible with PS-24 photoelectric detectors Backwards compatible with Potter PS and IS smoke detectors. Compatible with Potter releasing controls SEVSafe Environmental SYSTEMS Choice ® info@SEVOSystems.com • • • • • • • • • • • UL , ULC, CSFM Listed, FM Approved Radioactive Source: AM-241 0.5 µCi Rated Voltage: 17.7 - 30.0 VDC Working Voltage: 15.0 - 33.0 VDC Maximum Voltage: 42 VDC Supervisory Current: 40 µA at 24 VDC Surge Current: 200 µA at 24 VDC Alarm Current: 150 mA at 24 VDC Ambient Temperature: 32°F to 120°F (0° C to 49°C) Sensitivity Test: Magnetically activated dual reed switch test Mounting: Refer to Potter SB Series Smoke Detector Base Series, bulletin no. 8840008 Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Ionization Smoke Detector Designed with: SD-I-24 3M™ Novec™ 1230 Fire Protection Fluid Architecture/Engineering Specifications SD-I-24 Sensitivity Test Feature The contractor shall furnish and install where indicated on the plans, Potter Model SD-I-24 ionization smoke detectors. The combination detector head and twist­-lock base shall be UL listed compatible with a UL listed fire alarm panel. The base shall permit direct interchange with Potter SDP-24 photoelectric type detector and PS-24H combination photoelectric/heat detector. The base shall be appropriate twist-lock base SB Series. In the event of partial or complete retrofit, the SD-I-24 may be used in conjunction with, or as a replacement for, Potter detectors (SD-P-24, PS-24H and the SD-I-24) on most SB base applications. The smoke detector shall have two flashing status LED's for visual supervision. When the detector is in standby condition the LED's will flash green. When the detector is actuated, the flashing LED's will latch on red. The detector may be reset by actuating the control panel reset switch. Test Procedure 1. With detector wired to appropriate initiating circuit or current limited power source and with normal applied power, place magnet as shown in Fig. 1. 2. Wait at least six seconds. Detector SHOULD NOT alarm and LED should not light. 3. Place magnet on detector as shown in Fig. 2 (opposite side). 4. Wait at least six seconds. Detector SHOULD alarm. 5. If detector does alarm when magnet is positioned as in Fig. 1 or does not produce an alarm when magnet is positioned as in Fig. 2, detector is not within specified sensitivity limits and may require service. The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the detector without the need of generating smoke. The test method shall simulate effects of products of combustion in the chamber to ensure testing of the detector electronics. To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be employed to minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated. The vandal-resistant, security locking feature shall be used in those areas indicated on the drawing. The locking feature shall be field removable when not required. Specifications subject to change without notice. INT T info@SEVOSystems.com PA INT T LED’S T SEV SYSTEMS Safe Environmental Choice ® OT ES T FIG. 1 Conduct testing only under Normal Standby conditions. Abnormal or Low Power conditions may affect sensitivity. Always reset power prior to testing of next unit. N DO PA DO OT ES N FIG. 2 DWG# 884306-4 Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Photoelectric Smoke Detector Designed with: SD-P-24 3M™ Novec™ 1230 Fire Protection Fluid The SD-P-24 can be used in all areas where Photoelectric Smoke Detectors are required. The wide range smoke chamber makes the SD-P-24 well suited for fires ranging from smoldering to flaming fires. SB Series Style bases may be used with the SD-P-24. Current interchangeable/compatible devices are the SD-I-24 ionization detector. Operation The SD-P-24 photoelectric smoke detector utilizes two bicolored LED’s for indication of status. In a normal standby condition the LED’s flash green every 3 seconds. When the detector senses that its sensitivity has drifted outside the UL listed sensitivity window the LED’s will flash red every 3 seconds. When the detector senses smoke and goes into alarm the status LED’s will latch on red. The detector utilizes an infrared LED light source and silicon photo diode receiving element in the smoke chamber. In a normal standby condition, the receiving element receives no light from the pulsing LED light source. In the event of a fire, smoke enters the detector smoke chamber and light is reflected from the smoke particles to the receiving element. The light received is converted into an electronic signal. Signals are processed and compared to a reference level, and when two consecutive signals exceeding the reference level are received within a specified period of time, the time delay circuit triggers the SCR switch to activate the alarm signal. The status LED’s light continuously during the alarm period. • • • • • • • • • • • • • UL, ULC, and CSFM Listed, FM Approved Light Source: GaAIAs Infrared Emitting Diode Rated Voltage: 17.7 - 33.0 VDC Working Voltage: 15.0 - 33.0 VDC Maximum Voltage: 42 VDC Supervisory Current: 45 µA Max. at 24 VDC Surge Current: 160 µA Max. at 24 VDC Alarm Current: 150 mA Max. at 24 VDC Ambient Temperature: 32°F to 120°F (0°C to 49°C) Sensitivity Test Feature: Automatic Sensitivity window verification test. Mounting: Refer to Potter SB Series Smoke Detector Base series, bulletin no. 8840008. Low profile, 1.8” high (with base) 2 or 4 wire base compatibility, relay bases available SEVSafe Environmental SYSTEMS Choice ® info@SEVOSystems.com • • • • • • • • • • • Highly stable operation, RF/Transient protection Low standby current, 45 µA at 24 VDC Two built-in power/sensitivity supervision/alarm LED’s Non-directional smoke chamber Vandal resistant security locking feature Built-in magnetic go/no go detector test feature Removable smoke labyrinth for cleaning or replacement Automatic Sensitivity window verification function meets outlined requirements in NFPA 72, Chapter 7, Inspection, Testing and Maintenance. Compatible with IS-24 ionization detectors Backwards compatible with Potter PS and IS detectors. Compatible with Potter releasing controls Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Photoelectric Smoke Detector Designed with: 3M™ Novec™ 1230 Fire Protection Fluid SD-P-24 Architecture/Engineering Specifications The contractor shall furnish and install where indicated on the plans, Potter Model SD-P-24 photoelectric smoke detectors. The combination detector head and twist-lock base shall be UL listed compatible with a UL listed fire alarm panel. The base shall permit direct interchange with Potter, PS24H, combination photoelectric/heat detector and SD-I-24 ionization type smoke detector. The base shall be appropriate twist-lock base SB Series. In the event of partial or complete retrofit, the PS-24 may be used in conjunction with, or as a replacement for, Potter detectors (SD-P-24, PS-24H and the SD-I-24) the SB base applications. The smoke detector shall have two flashing status LED’s for visual supervision. When the detector is in standby condition the LED’s will flash green. When the detector is outside the UL listed sensitivity window the LED’s will flash red. When the detector is actuated, the flashing LED’s will latch on red. The detector may be reset by actuating the control panel reset switch. The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the detector without the need of generating smoke. The sensitivity of the detector shall be monitored automatically and continuously to verify that it is operating within the listed sensitivity range. To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be employed to minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field removable when not required. Specifications subject to change without notice. PS-24 Sensitivity Test Feature The SD-P-24 Photoelectric Smoke Detector has a built-in automatic sensitivity test feature. 1. In normal condition, both LED’s flash green. 2. When the sensitivity drifts outside of its sensitivity limits, both LED’s flash red. 3. In the alarm state both LED’s are red continuously. 4. When the sensitivity drifts outside of its sensitivity limits and both LED’s flash red, the device needs to be cleaned or returned to the factory for cleaning. SEV SYSTEMS Safe Environmental Choice ® info@SEVOSystems.com Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Releasing Control Panel Designed with: CPRP4410 3M™ Novec™ 1230 Fire Protection Fluid The Potter Model CPRP4410 is a flexible multi-hazard releasing control panel that is well suited for a number of applications. The CPRP4410 is listed for use with pre-action and deluge sprinkler suppression systems and agent based fire suppression systems. The panel utilizes a microprocessor-based system that has 19 Standard Programs, which covers a majority of installations. The simple to follow Menu Structure programs the entire system in a matter of minutes. In addition to the Standard Programs, the panel allows custom programming to accommodate any installation. The panel is Ninth Edition UL listed, ULC listed, Factory Mutual, California State Fire Marshal (CSFM) and New York Materials Equipment Acceptance (MEA) approved. The CPRP4410 is housed in a durable steel cabinet with removable door and key lock. The panel is available in either a red or white finish and an optional flush mount trim ring is available. The cabinet contains knockouts on the side, back and top of the cabinet to ease installation. In addition, the cabinet will house up to 18 amp-hour batteries that will provide in excess of 90 hours of standby power. • • • • • • • • • • • • • • Multi-Hazard Operation Four Class B Initiating Circuits Two Class B Supervisory Circuits ** Four Class B Output Circuits Programmable Cross Zoning Supervised Microprocessor 32 Character Alpha-Numeric LCD Display Custom Banner Message and Zone Description text Custom Zone Description Text On Board Menu Driven Programming Controls Releasing Circuits Protected From False Activation Continuous or Timed Discharge 40 Event History Buffer Walktest with Automatic Time-out Dimensions: 18 ¼" x 14 ½" x 4 ¾" • • Alarm, Trouble Supervisory, and Waterflow relays Optional Class A Initiating Zone and output module • 34 character LED supplemental display • 19 Standard Programs in Panel Memory • Password Protection for all Programming • 24 Hour Clock • Suitable for agent or waterbased extinguishing • Programmable pre-discharge timers* • One Class B Abort circuit* (Defaults to additional supervisory zone in water based mode.) • Three Abort modes* * Available in Chemical mode only ** One zone programmable as abort in chemical mode. UL and ULC Listed, FM Approved, NYMEA Accepted, and CSFM Approved SEVSafe Environmental SYSTEMS Choice ® info@SEVOSystems.com Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Releasing Control Panel Designed with: 3M™ Novec™ 1230 Fire Protection Fluid Architects/Engineers Specifications The control panel for the extinguishing agent releasing system shall be a microprocessor based control capable of protecting multiple hazards in one control panel. It shall be Underwriters Laboratories Inc. listed under Standard 864 Ninth Edition and Underwriters Laboratories of Canada for Local Control Units for Releasing Service. The control shall also be approved by Factory Mutual Research Corporation and be compiant with the requirements of NFPA-72 (Local: A, M, SS service types; DAC and NC signaling type) and NFPA12, NFPA12A, NFPA-13, NFPA15, NFPA-16, NFPA-17, NFPA-17A, NFPA-750, and NFPA-2001. The control shall be housed in an 18 gauge steel cabinet that has a hinged, removable door with a key lock. The finish shall be baked enamel and available in red or off-white with contrasting trim and logo. An optional matching bezel should be available for semi-flush mounting. The cabinet shall have adequate space to house 18 AH standby batteries capable of operating the system for at least 90 hours. The control shall include a fully supervised integral power supply/ battery charger capable of providing 200mA to the auxiliary power circuit. It shall also be capable of providing 2.5 Amps to all releasing and notification appliance circuits combined. All initiating, output and auxiliary power circuits shall be power limited. The control shall have a 32 character (16 characters, 2 lines) backlit LCD display and a 34 LED supplemental display. All diagnostic and alarm event information shall be viewable in text form on this display. A field programmable custom banner message with the current date and time shall be displayed when no current alarm or diagnostic information exists. All operational features of the control panel shall be field programmable using menu driven selections on the alphanumeric display and on board controls. No special programmer will be required and jumpers or switches to configure operational features shall not be permitted. Alarm and trouble indications shall resound when required. The control panel shall be equipped with 19 programs built into the panel memory, 13 for water based extinguishing and 6 for agent extinguishing. In addition, the panel shall have the ability to add custom programs. All programming functions shall be password protected. The control shall have four fully supervised Class B (Style B) initiating circuits capable of supporting the operation of 25 compatible 2-wire smoke detectors on each circuit. The individual circuits shall be selectable through the programming sequence to operate in one of the following modes: Conventional, Waterflow, Linear Heat Detection (up to 10,000 feet per zone), Manual Release, Low Air Alarm, Supervisory, Tamper, Low Air or High Air. SEV SYSTEMS Safe Environmental Choice ® info@SEVOSystems.com CPRP4410 Optional Class A modules, CA2Z, may be added for Class A operation. The panel shall have a Low Air Zone that creates a supervisory condition and map to an output. UL and ULC Listed, FM Approved, NYMEA Accepted, CSFM Approved The control shall have two fully supervised Class B (Style B) supervisory circuits. These circuits shall be selectable through the programming sequence to operate in one of the following modes: Supervisory, Tamper, Low Air or High Air. The control shall have one fully supervised class B (style B) Abort circuit with 3 different operating modes, ULI, IRI, and NYC. The control shall have four fully supervised Class B (Style Y) output circuits. These circuits shall be selectable through the programming sequence to operate as one of the following: Alarm Notification Appliance, Supervisory Notification Appliance, Trouble Notification Appliance or Releasing. The optional CAM module may be added to convert the outputs to Class A. The panel shall have an RS-485 output and auxiliary power outputs for connection and supervision of up to 4 remote annunciators. The releasing circuits shall be supervised for short circuit conditions and shall be programmable for cross zoning operation when required. The discharge timer for these releasing circuits shall be programmable for times of 7, 8, 9, 10, 20 minutes or continuous. All initiating and output circuits shall be capable of being individually disabled or enabled. In addition, when in the agent extinguishing mode there shall be a pre-discharge timer adjustable from 0-60 seconds from an alarm zone or 0-30 seconds from a manual release zone. The control shall have a test mode that will automatically disable all releasing circuits. The test mode shall operate in such a manner as to automatically reset the initiating circuit and indicating circuits after detecting each alarm condition initiated by the test. All testing shall be recorded in the 40 event history buffer. The test mode will automatically terminate after twenty minutes of inactivity. The control shall have four integral relay contacts rated 3 Amps at 30 VDC for connection to external auxiliary equipment. One relay shall operate when an alarm condition occurs, another when a trouble signal occurs, the third when a supervisory condition occurs, and the fourth during a waterflow condition. UL and ULC Listed, FM Approved, NYMEA Accepted, CSFM Approved. Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Bells Designed with: 3M™ Novec™ 1230 Fire Protection Fluid AL-B6 AL-B8 AL-B10 These vibrating type bells are designed for use as fire, burglar or general signaling devices. They have low power consumption and high decibel ratings. The unit mounts on a standard 4” (101mm) square electrical box for indoor use or on a model BBK-1 weatherproof backbox or AL-BBD deep weatherproof backbox for outdoor applications. Weatherproof backbox model AL-BB, Stock No. 1500001. UL, ULC, and FM Approved Sizes Available: 6” (150mm), 8” (200mm) and 10” (250mm) Voltages Available: 24VAC 120VAC 12VDC (10.2 to 15.6) Polarized 24VDC (20.4 to 31.2) Polarized Service Use: Fire Alarm General Signaling Burglar Alarm Environment: Indoor or outdoor use (See Note 1) -40° to 150°F (-40° to 66°C) (Outdoor use requires weatherproof backbox.) Termination: AC Bells - 4 No. 18 AWG stranded wires DC Bells - Terminal strip Finish: Red powder coating Optional: Model AL-BB weatherproof backbox Model AL-BBD deep weatherproof backbox Size inches (mm) Voltage Model Number Stock Number 6 (150) 12VDC MBA126 1750070 .12A 85 76 8 (200) 12VDC MBA128 1750080 .12A 90 77 10 (250) 12VDC 1750060 .12A 92 78 6 (150) 24VDC MBA246 1750100 .06A 87 77 8 (200) 24VDC MBA248 1750110 .06A 91 79 10 (250) 24VDC 1750090 .06A 94 80 6 (150) 24VAC PBA246 1806024* .17A 91 78 8 (200) 24VAC PBA248 1808024* .17A 94 77 10 (250) 24VAC PBA2410 1810024* .17A 94 78 PBA1206 1806120* .05A 92 83 6 (150) Current Typical dB (Max.) at 10 ft. (3m) (2) All DC bells are polarized and have built-in transient protection. * Does not have ULC listing. SEVSafe Environmental SYSTEMS Choice ® info@SEVOSystems.com * Minimum dB at 10 ft. (3m) (1) Notes: 1. Minimum dB ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as specified in UL Standard 464. UL temperature range is -30° to 150°F (-34° to 66°C). 2. Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of output levels in an actual installation. 3. ULC only applies to MBA DC bells. In outdoor or wet installations, bell must be mounted with weatherproof backbox, AL-BB or AL-BBD. Standard electrical boxes will not provide a weatherproof enclosure. If the bell and/or assembly is exposed to moisture, it may fail or create an electrical hazard. Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com SEVO® Systems Provider Bells Designed with: AL-B6 AL-B8 AL-B10 3M™ Novec™ 1230 Fire Protection Fluid Wiring (rear view) Fig. 3 Bells Dimensions Inches (mm) Fig. 1 A.C. BELLS WHITE (IN) 10” (250) 8” (200) WHITE (OUT) FROM CONTROL PANEL OR PRECEDING BELL 6” (150) BLACK (OUT) BLACK (IN) CAUTION: WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN. 2 11/16” (68) NOTES: DWG# 776-1 1. WHEN USING AC BELLS, TERMINATE EACH EXTRA WIRE SEPARATELY AFTER LAST BELL. 2. END-OF-LINE RESISTOR IS NOT REQUIRED ON AC BELLS. DWG# 776-3 Weatherproof Backbox Dimensions Inches (mm) Fig. 2 FACP Box has one threaded 1/2" conduit entrance 3 3/8” (86) 5 3/4” (146) 3 3/8” (86) 1 5/8” (41) 4 1/4” (108) 4 1/4” (108) 3 3/8” (85.9) DWG# 776-2 2” AL-BBD 5” (127) _ + To Next Device or End-of-Line Resistor Installation 1. The bell shall be installed in accordance with NFPA 13, 72, or local AHJ. The top of the device shall be no less than 90" AFF and not less than 6" below the ceiling. 2. Remove the gong. 3. Connect wiring (see Fig. 3). 4. Mount bell mechanism to backbox (bell mechanism must be mounted with the striker pointing down). 5. Reinstall the gong (be sure that the gong positioning pin, in the mechanism housing, is in the hole in the gong). 6. Test all bells for proper operation and observe that they can be heard where required (bells must be heard in all areas as designated by the authority having jurisdiction). ) (51 Failure to install striker down will prevent bell from operating. SEV SYSTEMS Safe Environmental Choice ® info@SEVOSystems.com Phone +1.913.677.1112 Fax +1.913.384.5935 14824 West 107th St. Lenexa, KS 66215 USA www.SEVOSystems.com