Quickstart Guide: P-CBI

advertisement
quickstart guide
P-CBI
1
Prodigy® Wireless Keypad
1Introduction
The Prodigy® P-CBI is an elegant yet robust in-wall keypad
providing simple direct control of lighting or devices, utilizing
mesh network technology of 802.15.4 affording reliable
communications and load control without the need to run
additional control system wiring.
2
Application
The following diagram illustrates a P-CBI in a system with
other Prodigy devices.
3
Assembly
The P-CBI is supplied partially assembled along with several
items as listed in the following table.
USE
ITEM
1. Make sure the light masks are correctly positioned. The light masks will not fall
out of their locations, but can easily be removed and/or relocated as necessary.
2. Attach the button strips to the housing assembly according to the way the unit is
programmed. The button strips are held in place by three mounting posts.
QTY
Rear housing with
switch circuitry and
light masks attached
Body of P-CBI
1
Bezel Assembly
Holds button caps in position on
rear housing
1
Screws, steel, flat
Phillips head, 4B x 3/4”
Attach the mounting plate to the
electrical box
2
Two-button cap strip
Provides two large-size buttons
2
Three-button cap strip
Provides three medium-size
buttons
2
Six-button cap strip
Provides six small-size buttons
2
Mounting plate
Mounts to electrical box and
provides mounting point for P-CBI
1
Screws, steel, Phillips,
pan head, 04-40 x 1/4”
Attach the assembled keypad to
the mounting plate
4
Removal
Assembly
Light
Masks
Small Flatblade
Screwdriver
Button Strip
Mounting
Posts
3-Button
Strip
6-Button
Strip
3. If the button strips need to be changed or replaced, insert a flat blade screwdriver into the notches provided and carefully pry the button strip up and off the
mounting posts.
4. Using the Phillips screwdriver, attach the mounting plate to the electrical box as
shown in the illustration below.
The following items are required for assembly and installation:
• Phillips screwdriver (not supplied)
• Flat blade screwdriver (not supplied)
NOTE: The mounting plate can be attached as shown, or can be rotated 90°
if necessary to accommodate the orientation of the electrical box.
Light masks are used to reduce the backlight intensity between
the buttons. The housing assembly is shipped with light masks
in place for two six-button cap strips.
UK-Style
Electrical Box
Mounting
Plate
Screws
4B X 3/4”
For Regulatory Compliance information, refer to the latest
version of Doc. 7073.
QUICKSTART DOC. 7072A (2028707) 07.10
www.crestron.com/prodigy
©2010 Specifications subject to
change without notice.
888.273.7876
201.767.3400
All brand names, product names, and trademarks
are the property of their respective owners.
P-CBI
When using two- or three-button cap strips, remove the extra
light masks. Use one light mask for two-button strips, two masks
for three-button strips, and five masks for six-button strips.
(Retain the extra light masks in case the keypad is
reprogrammed for a different configuration.) Refer to the
illustration in the following column.
1
Notch
quickstart guide
P-CBI
Prodigy® Wireless Keypad
1 1
6 Acquire the P-CBI
4
1 1
4 Hardware Hookup
Use the following procedure to connect the keypad to an electrical
circuit.
1. Turn AC power OFF.
WARNING: Turn off power at the circuit breaker. Installing with
power on can result in serious personal injury and damage to the
device.
!
NOTE: Refer to the following diagram when making
connections to the device.
No
Yes
Do Not Insert Wires Behind Screw Head. Insert Wires Into Wire Entry Holes.
2. Connect the AC power cable to the line, neutral, and ground
terminals on the keypad assembly following all local codes.
51
4
Installation
Use the following procedure to install the keypad in an electrical box.
1. Push the wires into the electrical box and attach the keypad
assembly to the mounting plate as shown in the following
illustration.
!
CAUTION: Excess wire pinched between the keypad and
electrical box could cause a short circuit. Make sure that all
excess wire is completely inside the electrical box and not
between the box and the keypad.
Mounting
Plate
Keypad
Assembly
Bezel
2. Attach the bezel by putting it in position over the button caps and
snapping it in place.
3. Turn AC power ON.
2
For Regulatory Compliance information, refer to the latest
version of Doc. 7073.
QUICKSTART DOC. 7072A (2028707) 07.10
7
Troubleshooting
Use the Prodigy Composer software to configure
your Prodigy system (refer to the online help for
detailed information).
The following table provides corrective action for possible trouble
situations. If further assistance is required, please contact a
Crestron customer service representative.
NOTE: The Prodigy Composer software is
available for download from
www.crestron.com/prodigycomposer.
Before a P-CBI can be used, it must first be
acquired by the P-MNETGW gateway that is
connected to a Prodigy system. When prompted by
the Prodigy Network Setup Wizard within Prodigy
Composer to physically put detected devices into
Acquire mode, it is recommended that you start
with the device that is closest to the gateway. As
each device is acquired by the gateway, the device
functions as a repeater to reinforce the network.
TROUBLE
The keypad
does not
function.
All LEDs blink
four times after
button press.
To place the P-CBI into Acquire mode:
1. With the keypad connected to AC power,
press and hold any two buttons for
approximately 10 seconds until the
bottom LED blinks, and then immediately
release both buttons.
2. Press and hold the top-left button for at
least five seconds until the top LED blinks,
and then immediately release the button.
Improper wireless ID
used.
Verify that the keypad’s wireless
ID matches the wireless ID in
the software program.
Keypad is not receiving
power.
Check circuit breaker.
Check AC connection.
Keypad is not
communicating with the
P-MNETGW.
Repeat the acquire procedures
given in section 6.
P-CBI is not acquired by
gateway.
Acquire the keypad to the
wireless network.
You can also log onto the online help section of the Crestron website
(www.crestron.com/onlinehelp) to ask questions about Crestron products.
First-time users will need to establish a user account to fully benefit from
all available features.
Future Updates
As Crestron improves functions, adds new features and extends the
capabilities of the P-CBI, additional information may be made available as
manual updates. These updates are solely electronic and serve as
intermediary supplements prior to the release of a complete technical
documentation revision.
Check the Crestron website periodically for manual update availability
and its relevance. Updates are identified as an “Addendum” in the
Download column.
Turns on
Device communicating with
P-MNETGW and control system
program
Blinks one time Device acquired but not
communicating with network
Device not joined to network
Stays off
888.273.7876
CORRECTIVE ACTION
If you cannot locate specific information or have questions after reviewing
this guide, please take advantage of Crestron's award winning customer
service team by calling Crestron at 1-888-CRESTRON [1-888-273-7876].
The keypad enters the Acquire mode. The
top-left LED will blink until the device is
acquired. When the device is acquired,
the top-left LED will stop blinking and the
second-to-bottom-left LED will light.
3. Press the top-left button to exit the Acquire
mode.
To check the communication status of the P-CBI,
perform step 1. The second-to-bottom left LED will
indicate communication status as described below.
LED
COMMUNICATION STATUS
www.crestron.com/prodigy
POSSIBLE CAUSE(S)
Further Inquiries
NOTE: Holding the button for more than
five seconds may exit the Acquire mode.
©2010 Specifications subject to
change without notice.
Problem Solving
201.767.3400
All brand names, product names, and trademarks
are the property of their respective owners.
P-CBI
Screws
4-40X1/4”
1
Download