LED Magnum 8” Downlight

advertisement
LED Magnum 8” Downlight
Installation instructions for MAG8 Series
WARNING: These products may represent a possible shock or fire hazard if improperly installed or attached
in any way. Products should be installed in accordance with these instructions, and with current electrical
codes and/or the current National Electric Code (NEC). This light module is intended to be installed only by
qualified personnel.
WARNING: To avoid electric shock, disconnect power at source prior to installation.
Save these instructions.
Alteration of the fixture will void the warranty.
Do not make or alter any open holes in a wiring enclosure, nor in any electrical components during kit
installation! WARNING: Risk of fire or electric shock. Kit installation requires knowledge of recessed lighting
luminaires electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.
SUITABLE FOR USE IN DRY AND DAMP LOCATIONS; AND TYPE IC LOCATIONS.
Do not use these products in areas where elevated ambient temperatures exist. This fixture is suitable for
installation where ambient temperatures do not exceed 104˚F (40˚C) during anticipated hours of fixture
operation. This fixture is airtight certified. Not for use in dimming circuits.
WARNING: Risk of fire or electric shock. The electrical rating of this product is 120-277V AC. The installer must
determine that the supply is within the range of 120-277V AC at the luminaire before installation.
WARNING: To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON
FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
This product cannot be disassembled. The LEDs are not replaceable. If the LEDs become damaged, the fixture
should be disconnected and recycled. Failure to do so may result in electric shock, and become a fire hazard.
FUTURE LAMP REPLACEMENT: Model MAG8-XX-XX (8” MAGNUM LED Downlight) is available from American
Lighting, Inc. Contact 800-880-1180 or visit www.americanlighting.com to find a local distributor.
NEW CONSTRUCTION/REMODEL/RETROFIT: No rough-in can needed! Best practices include use of a laser to mark
fixture locations on floor for finish electrical; and removing any existing housings through cut-out hole or through
plenum as needed.
CAUTION: Always make sure power to the fixture is disconnected before beginning of removal of
existing lamp and/or trim, or beginning installation. Failure to do so can cause electric shock, which
can result in injury or death.
INSTALLATION
1. Using the cut-out template supplied with the fixture, mark and cut a 8.07 inch round hole in the ceiling
where the fixture is to be mounted. See Figure 1.
Four knockouts (two on opposing sides) for use with 1/2” conduit and
3/8” clamp connectors (not included with fixture).
Figure 1
Junction
Box
Cover
2.67 in
5.38 in
7.74 in
9.05 in
Figure 2
Knockouts
are located
on two
sides of
junction
box
8.07 in
Cut-out template = 8.07”
(205mm) diameter
2. Remove attached junction box cover and set aside. Punch out whichever knockout is best suited for
connection to supply wires. Knockouts are located on the sides of the junction box. See Figures 1 and 2.
(CONTINUED ON REVERSE)
Denver, CO 80231 • www.americanlighting.com
© 2014 American Lighting, Inc.
RV1411
Page 1 of 2
LED Magnum 8” Downlight
Installation instructions for MAG8 Series
INSTALLATION (CONTINUED FROM REVERSE)
3. Install 3/4” cable connnector to this open knockout and connect
fixture wires following National Electric Code and/or local building
code requirements. Use minimum 18AWG solid copper wires. AC
supply should be protected by circuit breaker or fuse.
4. Attach line voltage AC supply wires to fixture lead wires: Black to
Black/Hot, White to White/Neutral and Yellow/Green (Ground) to
Green or bare wire inside the fixture. Secure each connection using
UL Listed wire connectors. If your system has no ground wire, consult
a qualified electrician before proceeding with the installation. Note:
Electric shock, overheating, low or no light output and shortened
fixture life can result if proper grounding is not done. See Figure 3.
5. Connect support cable kit to both sides of junction box housing
using slots in junction box side straps. See Figure 4.
6. Tie off cable kit to a plenum rated support of the building.
Alternatively, run appropriately sized lengths of empty conduit
through side straps in lieu of tying off.
7. Pull spring brackets upward (see Figure 6), then place the Downlight
into the ceiling (see Figure 7). Spring brackets will hold Downlight
securely in place.
5- YEAR LIMITED PRODUCT WARRANTY
This product is warranted to be free from defects in material and
workmanship for a period of five years from the date of purchase.
Products that prove to be defective during this period will be
either repaired (i.e. replacement of defective electronics, defective
parts of the fixture housing, lens, wiring, switching or lamp
sockets; excluding the lamp) or replaced, at the discretion of
American Lighting, Inc. Claims for defective products must be
submitted to the retail location from which the product was
purchased within the warranty period. Upon submission of proper
return claim documentation and product to American Lighting,
Inc by the retailer, American Lighting, Inc reserves the right to
inspect the product for misuse or abuse. Claims for indirect or
consequential damages or for product that, in American Lighting
Inc's opinion has been misused will be denied. This is a warranty of
product reliability only and not a warranty of merchantability or
fitness for a particular purpose. American Lighting, Inc shall have
no liability whatsoever in any event for payment of incidental or
consequential damages, including, without limitations, installation
costs and damages for personal injury and property. These
products may represent a possible shock or fire hazard if
improperly installed or altered in any way. This warranty applies
only to product that has been properly installed in accordance
with instruction sheet and current local codes and/or the National
Electrical Code. Warranty does not apply to any product that has
been improperly installed or in situations where components have
been altered in any way.
Figure 3
Figure 4
Cable
kit
Side strap
with slot
Figure 5
Tie off to
plenum rated
building
support
Cable Kit
Ceiling
Figure 6
Figure 7
For questions / comments, technical assistance or repair parts –
Please call toll free at: 1-800-285-8051 (M-F 8am – 5pm, MST)
Ceiling
© 2014 American Lighting, Inc.
Denver, CO 80231 • www.americanlighting.com
RV1411
Page 2 of 2
Download