Product sheet AC9.48 Accessory Type HRH HRH Electronic Level Controllers HRH Level Controllers monitor fluid level in wells, tanks, pools and reservoirs. HRH level controllers can be used to monitor up to two tanks with single point switching (empty or full tank), or to monitor one tank for two levels. HRH works by means of two sensors,which measure resistance of fluid. For measuring signal is used intermittent voltage 5V/50Hz. Using the alternating signal increased oxidation of sensors is prevented , polarization and electrolysis of fluid. By DIP switch could be control two independent levels or use combined function for monitoring of one level. Relay is equipped by regulation of sensitivity to changing resistance of fluid. By setting sensitivity according to real condition it is possible eliminate misreadings (e.g.pollution of sensors, grounds, humidity etc.). For every sensor can be set up a delay in range 0.5-10s and by DIP switch the type of delay (at switch on and off relay, choice is made according to application requirement). Features • Single Switch with Double State Monitoring • Two independent switches with single state switching • Fill in or emptying control • Galvanically Separated Supply • Single Switch with Single State Monitoring Model Type Technical Data Model Description HRH-1 Level Controller, 230Vac Supply SHR-2 Level Sensor for HRH Power Supply 230Vac or 24Vac/dc, <4.5A Inputs 3 SHR Sensor Inputs, Maximu Level, Minimum Level, Common Measuring Circuit Hysteresis: 5kOhm .. 100 kOhm Voltage on Electrode: AC 5V Current via Sounders: AC <1mA Time Reaction: max. 400 ns Max Cable Capacity: 4 nF Length of cables: Max. 100m Time Delay tD: adjustable 0.5 .. 10s Time Delay tH: adjustable 0.5 .. 10s Accuracy +/-5% Output Number: 2 x changeover Rated Current: 16A / AC1 Breaking Capacity: 4000VA / AC1, 384W /DC Inrush Current: 30A / < 3s Switching Voltage: 250V AC1 / 24V DC Op Temperature -20..+55°C Storage Temperature -30..+70°C Protection Class IP40 Dimensions W52 x L90 x D65 mm Online store: www.syxthsense.com Enquiries: T: 0844 840 3100 F: 0844 840 3200 PS AC9.48 - 1/4 SyxthSense Ltd DESCRIPTION SETTINGS Description of Buttons Selection of delay type ofi Input H Selection of delay type ofi Input D Inversion off unction ofi nput D Function selection: double/single level relay Indication of supply voltage HRH-1 Un Output contact relay 1 Function 2x Input inverse OFF Delay type D ta Delay Type H ta 1x ON tb tb 4 Adjusting delay input H 6 2 H 8 0.5 10 tH [s] 30 50 20 Output contact relay 2 D ELK O 70 10 90 5 100 R [k ] 4 Adjusting delay input D 6 2 8 0.5 10 tD [s] Adjusting sensitivity of sounder according to liquid resistance FUNCTIONS HRH works by means of two sensors,which measure resistance of fluid. For measuring signal is used intermittent voltage 5V/50Hz. Using the alternating signal increased oxidation of sensors is prevented , polarization and electrolysis of fluid. By DIP switch could be control two independent levels or use combined function for monitoring of one level. Relay is equipped by regulation of sensitivity to changing resistance of fluid. By setting sensitivity according to real condition it is possible eliminate misreadings (e.g.pollution of sensors, grounds, humidity etc.). For every sensor can be set up a delay in range 0.5-10s and by DIP switch the type of delay (at switch on and off relay, choice is made according to application requirement). Function Diagram C D H C D H C D H C D H 2 independent single level switches. Relay closed when container is empty. A1-A2 Out1 (15-18) tA tB Re2 (25-28) tA DIP 3 = tA DIP 3 = tB DIP 1 = 1x DIP 2 = ON tB Input D is inverted when DIP 2 is in position OFF, relay is closed when the container is full. DIP2 = OFF. Function H is the same as in previous adjustment. DIP 4 = tA DIP 4 = tB tA Out1 (15-18) tB DIP 3 = tA DIP 3 = tB tA Out1 (15-18) tB DIP 3 = tA DIP 3 = tB Out2 (25-28) tB tA tB DIP 4 = tA DIP 4 = tB Out1 (15-18) tA Monitoring liquid in container. DIP 1 = 1x DIP 2 = ON Relay 1 closed when bottom sounder is disconnected (liquid is being pumped in). Relay 2 closed (break contact used), when upper sounder is connected (liquid is being pumped out). tB DIP 3 = tA DIP 3 = tB Out2 (25-26) Both sounders in one container. DIP 1 = 2x DIP 2 = ON Relay 1 - closed when container is full - opened when bottom sounder is discon. Relay 2 - closed when bottom sounder is discon. - opened when upper sounder is closed tA tB DIP 4 = tA DIP 4 = tB Online store: www.syxthsense.com Enquiries: T: 0844 840 3100 F: 0844 840 3200 Copyright © 2008 SyxthSense Ltd. All rights reserved - 03/2008 PS AC9.48 - 2/4 SyxthSense Ltd WIRING DETAILS Un A1 A2 C D H S Terminals description : A1, A2 - supply voltage C - wire for both sounders D - wire of bottom soundery H - wire of upper sounder S - earth terminal for possible screening of cable 15-16-18 output contact relay 1 25-26-28 output contact relay 2 16 15 18 28 25 26 Dimensions 90 67.5 45 19 21 65 56.5 52 Online store: www.syxthsense.com Enquiries: T: 0844 840 3100 F: 0844 840 3200 Copyright © 2008 SyxthSense Ltd. All rights reserved - 03/2008 PS AC9.48 - 3/4 SyxthSense Ltd Online store: www.syxthsense.com Enquiries: T: 0844 840 3100 F: 0844 840 3200 Copyright © 2008 SyxthSense Ltd. All rights reserved - 03/2008 PS AC9.48 - 4/4